Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Allen-Bradley, DriveExplorer, DriveExecutive, DPI, SCANPort, PowerFlex, Rockwell Software, Ro ckwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
Updated the description for parameter 465 [Fan Control] to indicate that the
default value has been changed to 1 “Enabled.”
Updated parameter 212 [Drive Alarm 2] to include new bit 8 “Fan Cooling.”39
Updated parameter 238 [Fault Config 1] to include new bit 14 “Fan Cooling.”42
Added a note to the description for the “IGBT OverTemp” fault (F9) to specify that
the “IGBT Overtemp” fault is equivalent to the Drive Overload (Software), and is
not adjustable.
Added a note to the “System Fault” (F10) to specify that the fault subcodes are
only available in revision 4.001 or later.
Update the description for the “OverCurrent” fault (F12) to specify that the drive
output current has instantaneously exceeded 360% of the HD rating.
Added a note to the description for the “IGBT Temp HW” fault (F31) to specify
that the “IGBT Temp HW” fault is equivalent to the Drive Instantaneous Overload
(Hardware), and is not adjustable.
Updated the description for the “Fan Cooling” fault (F32) to include information
on configuring a “Fan Cooling” alarm.
32
64
65
65
66
66
Rockwell Automation Publication 20C-PM001F-EN-P - March 20123
Summary of Changes
Notes:
4Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
6Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Preface
The purpose of this manual is to provide you with the basic information needed
to start-up, program and troubleshoot the PowerFlex 700H adjustable frequency
AC drive.
For information on…See page…
Who Should Use this ManualBelow
What Is Not in this ManualBelow
Additional Resources8
General Precautions8
Who Should Use this Manual
What Is Not in this Manual
This manual is intended for qualified personnel. You must be able to program
and operate Adjustable Frequency AC drives and related devices. In addition, you
must have an understanding of the parameter settings and functions.
The PowerFlex 700H Programming Manual does not provide installation
instructions or maintenance and repair information.
For installation information, refer to:
• PowerFlex 700S/700H Adjustable Frequency AC Drives, Frames 9…14
Installation Instructions, publication PFLEX-IN006
• PowerFlex 700S/700H IP00 Open Power Structure, Frames 10…14
Installation Instructions, publication PFLEX-IN020
For maintenance and repair information, refer to:
• PowerFlex 700H and 700S Hardware Service Manual, Frame 9, PFLEX-
TG001
• PowerFlex 700H and 700S Hardware Service Manual, Frame 10, PFLEX-
TG002
• PowerFlex 700H and 700S Hardware Service Manual, Frame 11, PFLEX-
TG003
• PowerFlex 700H and 700S Hardware Service Manual, Frame 12, PFLEX-
TG004
• PowerFlex 700H and 700S Hardware Service Manual, Frame 13, PFLEX-
TG005
• PowerFlex 700H and 700S Hardware Service Manual, Frame 14, PFLEX-
TG006
.
.
For detailed drive application information refer to:
Rockwell Automation Publication 20C-PM001F-EN-P - March 20127
.
Preface
Additional Resources
General Precautions
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Preventive Maintenance of Industrial Control and Drive
System Equipment, publication DRIVES-TD001
Safety Guidelines for the Application, Installation and
Maintenance of Solid State Control, publication SGI-1.1
A Global Reference Guide for Reading Schematic Diagrams,
publication 100-2.10
Product Certifications website, http://www.ab.comProvides declarations of conformity, certificates, and
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides a checklist that can be used as a guide in
performing preventive maintenance of industrial
control and drive system equipment.
Provides general guidelines for the application,
installation, and maintenance of solid-state control.
wiring diagram symbols used throughout various parts
of the world.
other certification details.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
7
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component
damage or a reduction in product life. Wiring or application errors, such as,
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus voltage
at the Power Terminal Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC terminal and
the chassis. The voltage must be zero for all three measurements.
ATTENTION: Risk of injury or equipment damage exists. DPI host products must
not be directly connected together via 1202 cables. Unpredictable behavior can
result if two or more devices are connected in this manner.
8Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Preface
ATTENTION: The sheet metal cover and mounting screws on the ASIC Board
located on the power structure are energized at (-) DC bus potential high
voltage. Risk of electrical shock, injury, or death exists if someone comes in
contact with the assembly.
ATTENTION: The “adjust freq” portion of the bus regulator function is extremely
useful for preventing nuisance overvoltage faults resulting from aggressive
decelerations, overhauling loads, and eccentric loads. It forces the output
frequency to be greater than commanded frequency while the drive's bus
voltage is increasing towards levels that would otherwise cause a fault.
However, it can also cause either of the following two conditions to occur.
• Fast positive changes in input voltage (more than a 10% increase within 6
minutes) can cause uncommanded positive speed changes. However an
“OverSpeed Limit” fault will occur if the speed reaches [Max Speed] +
[Overspeed Limit]. If this condition is unacceptable, action should be taken to 1)
limit supply voltages within the specification of the drive and, 2) limit fast
positive input voltage changes to less than 10%. Without taking such actions, if
this operation is unacceptable, the “adjust freq” portion of the bus regulator
function must be disabled (see parameters 161 and 162).
• Actual deceleration times can be longer than commanded deceleration times.
However, a “Decel Inhibit” fault is generated if the drive stops decelerating
altogether. If this condition is unacceptable, the “adjust freq” portion of the bus
regulator must be disabled (see parameters 161 and 162). In addition, installing
a properly sized dynamic brake resistor will provide equal or better performance
in most cases.
Important: These faults are not instantaneous. Test results have shown that they
can take between 2…12 seconds to occur.
Rockwell Automation Publication 20C-PM001F-EN-P - March 20129
Preface
Notes:
10Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 1
Drive Start-Up
This chapter describes how you start up the PowerFlex 700H drive. Refer to
Appendix
For Information on…See page…
Prepare For Drive Start-UpBelow
Start-Up the Drive12
A for a brief description of the LCD Human Interface Module (HIM).
ATTENTION: Power must be applied to the drive to perform the following startup procedure. Some of the voltages present are at incoming line potential. To
avoid electric shock hazard or damage to equipment, only qualified service
personnel should perform the following procedure. Thoroughly read and
understand the procedure before beginning. If an event does not occur while
performing this procedure, Do Not Proceed. Remove Power including user
supplied control voltages. User supplied voltages may exist even when main AC
power is not applied to then drive. Correct the malfunction before continuing.
Prepare For Drive Start-Up
Before Applying Power to the Drive
❏1. Confirm that all inputs are connected to the correct terminals and are
secure.
❏2. Verify that AC line power at the disconnect device is within the rated value
of the drive.
❏3. Verify that control power voltage is correct.
The remainder of this procedure requires that a HIM be installed. If an
operator interface is not available, remote devices should be used to start
up the drive.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201211
Chapter 1Drive Start-Up
Apply Power to the Drive
❏4. Apply AC power and control voltages to the drive.
Start-Up the Drive
• If the STS (status) LED is NOT flashing green, refer to Drive Status
page 62 for more information.
• If any of the six digital inputs are configured for “Stop – CF” (CF =
Clear Fault) or “Enable,” verify that signals are present or reconfigure
[Digital Inx Sel].
• If an I/O option is not installed (no I/O terminal block is present),
verify that [Digital Inx Sel] is not configured to “Stop – CF” or
“Enable.” If this is not done, the drive will not start. Refer to Fault and
Alarm Descriptions on page 64 for a list of potential digital input
conflicts.
• If a fault code appears, refer to Chapter
❏5. Proceed to “Start-Up the Drive”.
The PowerFlex 700H drive is designed so that start up is simple and efficient. If
you have an LCD HIM, two start-up methods are provided, allowing you to
select the desired level needed for the application.
• S.M.A.R.T. Start
This routine allows you to quickly set up the drive by programming values
for the most commonly used functions. See Running S.M.A.R.T. Start
page 13.
3.
on
on
•Assisted Start Up
This routine prompts you for information that is needed to start up a drive
for most applications, such as line and motor data, commonly adjusted
parameters and I/O. See Running an Assisted Start Up
IMPORTANT
Power must be applied to the drive when viewing or changing parameters.
Previous programming may affect the drive status and operation when power
is applied.
on page 13.
12Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Drive Start-UpChapter 1
/
Running S.M.A.R.T. Start
During a Start Up, the majority of applications require changes to only a few
parameters. The LCD HIM on a PowerFlex 700H drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these parameters,
you can set the following functions:
S - Start Source and Stop Mode
M - Minimum and Maximum Speed
A - Accel Time 1 and Decel Time 1
R - Reference Source
T - Thermal Motor Overload
To run a S.M.A.R.T. start routine, follow these instructions:
StepKey(s)Example LCD Displays
1. Press ALT and then Esc (S.M.A.R.T). The S.M.A.R.T. star t
screen appears.
2. View and change parameter values as desired. For HIM
information, see Appendix
A.
3. Press Esc to exit the S.M.A.R.T. star t.
ALT
Esc
Esc
F-> StoppedAuto
0.0
SMART List:
Main Menu:
Digital In2 Sel
Diagnostics
Stop Mode A
Parameter
Minimum Speed
Hz
Running an Assisted Start Up
IMPORTANT
The Assisted start-up routine asks simple yes or no questions and prompts you to
input required information. Access Assisted Start Up by selecting “Start Up”
from the Main Menu.
Figure 1 - PowerFlex 700H Start Up Menu
Main Menu:
Start-Up
Input Voltage
Select
Sets Input
Voltage
To perform an Assisted Start-Up, follow these instructions:
StepKey(s)Example LCD Displays
1. In the Main Menu, press the Up Arrow or Down Arrow to
scroll to “Start Up”.
2. Press Enter.
This start-up routine requires an LCD HIM.
Motor Data and
Ramp Times
Enter Motor NP
Data, Stop Mode,
Accel/Decel
Ramp Times
Motor Tests
Optimize Torque
and
Verify Direction
Speed Limits
Set Min/Max
Speed and
Direction Control
Speed/Torque
Control
Configure
Source, Value
and Scale for
Speed References
Digital Inputs/Outputs
F-> StoppedAuto
0.0
Main Menu:
Memory Storage
Start Up
Preferences
Start/Stop/I/O
Configure
Control Method
(2 Wire/3 Wire), I/O,
and Analog Outputs
Hz
Done
Exit
Rockwell Automation Publication 20C-PM001F-EN-P - March 201213
Chapter 1Drive Start-Up
Notes:
14Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 2
Programming and Parameters
This chapter provides a complete list and description of the PowerFlex 700H
parameters. The parameters can be programmed (viewed/edited) using an LCD
Human Interface Module (HIM). As an alternative, programming can also be
performed using DriveExplorer™ or DriveExecutive™ software and a personal
computer. Refer to HIM Overview
HIM.
For Information on…See page…
About ParametersBelow
How Parameters are Organized17
Monitor File20
Motor Control File21
Speed Command File24
Dynamic Control File30
Utility File35
Communication File45
Inputs/Outputs File49
Param eter Li st by Na me56
Parameter List by Number58
on page 81 for a brief description of the LCD
About Parameters
To configure a drive to operate in a specific way, drive parameters may have to be
changed to values different than the default setting. Three types of parameters
exist:
•ENUM Parameters
ENUM parameters allow a selection from a list of items. The LCD HIM
will display a text message for each item.
•Bit Parameters
Bit parameters have individual bits associated with features or conditions.
If the bit is 0, the feature is off or the condition is false. If the bit is 1, the
feature is on or the condition is true.
•Numeric Parameters
These parameters have a single numerical value (i.e. 0.1 Volts).
Rockwell Automation Publication 20C-PM001F-EN-P - March 201215
Chapter 2Programming and Parameters
This table is an example of how each parameter type is presented in this manual.
Each numbered column is described in the table following this example.
123 456
File
Parameter Name & DescriptionValues
Group
No.
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values
from a selected user set location in drive
Drive . . .
nonvolatile memory to active drive memory.
216 [Dig In Status]
Default:
Options:00
“Ready”
“Ready”
“User Set 1”
1
“User Set 2”
2
“User Set 3”
3
Read Only361
Status of the digital inputs.
UTILITY
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In6
Digital In5
Digital In4
Digital In3
Diagnostics
044 [Motor NP RPM]
32
MOTOR . . .
Motor Data
Column
Description
Defaultxxxxxxxxxx000000
Bit1514131211109876543210
Set to the motor nameplate rated RPM.
Default:
Min/Max:
Units:
1750.0 RPM
60.0/19200.0 RPM
1.0 RPM
Digital In2
No.
1File – Lists the major parameter file category.
2Group – Lists the parameter group within a file.
3No. – Parameter number. = Parameter value cannot be changed until drive is stopped.
32
= 32 bit parameter.
4Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief description of
the parameters function. Parameters names appear within square brackets [] throughout this manual.
5Values – Defines the various operating characteristics of the parameter. Three types exist.
ENUMDefault:
Options:
Lists the default value assigned at the factory. “Read Only” = no default.
Displays the optional programming selections available.
BitBit:Lists the bit name, default setting and place holder for each bit.
Numeric Default:
Min/Max:
Units:
Lists the default value assigned at the factory. “Read Only” = no default.
The range (lowest and highest setting) possible for the parameter.
Unit of measure and resolution as shown on the LCD HIM.
Important: Some parameters will have two unit values:
• Analog inputs can be set for current or voltage with parameter 320 [Anlg In Config].
• Setting parameter 79 [Speed Units] selects “Hz” or “RPM.”
Important: When sending values through DPI ports, simply remove the decimal point to arrive
at the correct value (i.e. to send “5.00 Hz,” use “500”).
6Related – Lists parameters (if any) that interact with the selected parameter. The symbol “” indicates
that additional parameter configuration information is available in Appendix
B.
Related
199
thru
366
Digital In1
16Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
How Parameters are
Organized
The LCD HIM displays parameters in a File-Group-Parameter or Numbered
List view order. To switch display mode, access the Main Menu, press ALT, then
Sel while the cursor is on the parameter selection. In addition, using [Param
Access Lvl], you can display only the commonly used parameters or all
parameters.
File-Group-Parameter Order View
This view simplifies programming by grouping parameters that are used for
similar functions. The parameters are organized into six files in Basic Parameter
view or seven files in Advanced Parameter view. Each file is divided into groups,
and each parameter is an element in a group. By default, the LCD HIM displays
parameters by File-Group-Parameter view.
Numbered List View
In this view, all parameters are listed in ascending numerical order.
Basic Parameter View
Parameter 196 [Param Access Lvl] set to option 0 “Basic.”
Faul t 1 Su bCod e54 3
Faul t 2 Su bCod e54 5
Faul t 3 Su bCod e54 7
Faul t 4 Su bCod e54 9
Faul t 5 Su bCod e55 1
Faul t 6 Su bCod e55 3
Faul t 7 Su bCod e55 5
Faul t 8 Su bCod e55 7
Alarm7 Code268
Alarm8 Code269
DPI Port Value275
Reference Owner292
Accel Owner293
Decel Owner294
Fault Clr Owner295
MOP Owner296
Local Own er297
Data Out C1314
Data Out C2315
Data Out D1316
Data Out D2317
Analog In1 Loss324
Analog In2 Loss327
Anlg Out1 Scal354
Anlg Out2 Scal355
Anlg1 Out Setpt377
Anlg2 Out Setpt378
20C-DG1 Remove358
20C-DG1 Status359
Dig Out3 OnTime390
Dig Out3 OffTime391
Dig Out Setpt379
Rockwell Automation Publication 20C-PM001F-EN-P - March 201219
Chapter 2Programming and Parameters
Monitor File
File
Parameter Name & DescriptionValues
Group
No.
001 [Outp ut Freq]
Output frequency present at U/T1, V/T2 & W/T3.
002 [Commanded Speed]
32
Value of the active Speed/Frequency Reference.
Displayed in Hz or RPM, depending on value of
[Speed Units].
003 [Output Current]
The total output current present at U/T1, V/T2 &
W/T3.
004 [Torque Current]
Based on the motor, the amount of current that is
in phase with the fundamental voltage
component.
005 [Flux Current]
Amount of current that is out of phase with the
fundamental voltage component.
006 [Outp ut Voltag e]
Output voltage present at terminals U/T1, V/T2 &
W/T3.
007 [Output Power]
Output power present at U/T1, V/T2 & W/T3.
008 [Outp ut Powr Fctr]
Output power factor.
009 [Elapsed MWh]
Metering
MONITOR
32
Accumulated output energy of the drive.
010 [Elapsed Run Time]
32
Accumulated time drive is outputting power.
011 [MOP Reference]
32
Value of the signal at MOP (Motor Operated
Potentiometer).
012 [DC Bus Voltage]
Present DC bus voltage level.
013 [DC Bus Memory]
Approximate full load DC bus voltage level.
016
[Analog In1 Value]
017
[Analog In2 Value]
Value of the signal at the analog inputs.
022 [Ramped Speed]
32
Value of commanded speed after Accel/Decel, and
S-Curve are applied.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+ [Maximum Freq]
0.1 Hz
Read Only
–/+ [Maximum Speed]
0.1 Hz
0.1 RPM
Read Only
0.0/Drive Rated Amps x 2
0.1 Amps
Read Only
Drive Rating x –2/+2
0.1 Amps
Read Only
Drive Rating x –2/+2
0.1 Amps
Read Only
0.0/Drive Rated Volts
0.1 VAC
Read Only
0.0/Drive Rated kW x 2
0.1 kW
Read Only
0.00/1.00
0.01
Read Only
0.0/429496729.5 MWh
0.1 MWh
Read Only
0.0/214748364.0 Hrs
0.1 Hrs
Read Only
–/+ [Maximum Speed]
0.1 Hz
0.1 RPM
Read Only
0.0/Based on Drive Rating
0.1 VDC
Read Only
0.0/Based on Drive Rating
0.1 VDC
Read Only
0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Related
079
079
079
20Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
023 [Speed Reference]
32
Summed value of ramped speed, process PI and
droop.
024 [Commanded Torque]
Final torque refe rence value after limits and
filtering are applied. Percent of motor rated
Metering
torque.
Note: Added for firmware revision 4.001.
025 [Speed Feedback]
This parameter displays the estimated value of
actual motor speed.
MONITOR
026 [Rated kW]
32
Drive power rating.
027 [Rated Volts]
The drive input voltage class (208, 240, 400 etc.).
028 [Rated Amps]
Drive Data
The drive rated output current.
029 [Control SW Ver]
Main Control Board software revision.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Read Only
–/+800.0%
0.1%
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Read Only
0.00/3000.00 kW
0.01 kW
Read Only
0.0/690.0 VAC
0.1 VAC
Read Only
0.0/6553.5 Amps
0.1 Amps
Read Only
0.000/255.255
0.001
Related
079
053
Motor Control File
File
Parameter Name & DescriptionValues
Group
No.
040 [Motor Type]
Set to match the type of motor connected.
041 [Motor NP Volts]
Set to the motor nameplate rated volts.
042 [Motor NP FLA]
Set to the motor nameplate rated full load amps.
043 [Motor NP Hertz]
Set to the motor nameplate rated frequency.
Motor Data
MOTOR CONTROL
044 [Motor NP RPM]
Set to the motor nameplate rated RPM.
32
045 [Motor NP Power]
Set to the motor nameplate rated power.
32
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Induction”
“Induction”
Based on Drive Rating
0.0/[Rated Volts]
0.1 VAC
Based on Drive Rating
0.0/[Rated Amps] × 2
0.1 Amps
Based on Drive Rating
5.0/320.0 Hz
0.1 Hz
Based on Drive Rating
60.0/19200.0 RPM
1.0 RPM
Based on Drive Rating
0.00/5000.00
0.01 kW/HP
See [Mtr NP Pwr Units]
Related
053
047
048
046
Rockwell Automation Publication 20C-PM001F-EN-P - March 201221
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
046 [Mtr NP Pwr Units]
Selects the motor power units to be used.
“Convert H P” = converts all power units to
Horsepower.
“Convert kW” = converts al l power units to
kilowatts.
Note: This parameter does not get changed with a
“Reset to Defaults”.
047 [Motor OL Hertz]
Selects the output frequency below which the
motor operating current is derated. The motor
thermal overload will generate a fault at lower
levels of current below this output frequency.
048 [Motor OL Factor]
Sets the operating level for the motor overload.
Motor
FLAOLFactor
049 [Motor Poles]
Motor Data
Defines the number of poles in the motor.
Note: Maximum value changed from 12 to 18 for
firmware revision 4.001.
050 [Motor OL Mode]
“Pwr Cyc Ret” - If “0”, the value of parameter 220 [Motor OL Count] is reset to zero by a drive reset
or power cycle. If “1”, the value of parameter 220 [Motor OL Count] is maintained. A “1” to “0”
transition resets parameter 220 [Motor OL Count] to zero.
Note: Added for firmware revision 3.001.
1 = Enabled
0 = Disabled
Related
Default:
Options:–0
Default:
Min/Max:
Units:
Default:
Min/Max:
x
Level
Operating
=
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
“Horsepower”
“kiloWatts”
1
“Convert HP”
2
“Convert kW”
3
Motor NP Hz/3
0.0/Motor NP Hz
0.1 Hz
1.00
0.20/2.00
0.01
4
2/18
1 Pole
042
220
042
220
220
MOTOR CONTROL
053 [Motor Cntl Sel]
Sets the method of motor control used in the
drive.
055 [Maximum Freq]
Sets the highest frequency the drive will output.
Refer to parameter 083 [Overspeed Limit].
056 [Compensation]
“Mtr Lead Rev” - If “1”, reverses the phase rotation of the applied voltage, effectively reversing
the motor leads.
Notes: Not retained when the parameters are reset to defaults. Added for firmware revision
3.001.
Torq Attributes
1 = Enabled
0 = Disabled
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Pwr Cyc Ret
Defaultxxxxxxxxxxxxxxx0
Bit1514131211109876543210
Default:
Options:00
Default:
Min/Max:
Units:
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Defaultxxxxxxxxxx0xxxxx
Bit1514131211109876543210
“Sensrls Vect”
“Sensrls Vect”
1
“SV Economize”
2
“Custom V/Hz”
3
“Fan/Pmp V/Hz”
Based on Drive Rating
5.0/320.0 Hz
0.1 Hz
Reserved
Mtr Lead Rev
Reserved
Reserved
Reserved
Reserved
Reserved
083
22Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Group
No.
057 [Flux Up Mode]
058 [Flux Up Time]
059 [SV Boost Filter]
061 [Autotune]
Torq Attributes
MOTOR CONTROL
Parameter Name & DescriptionValues
Flux is established for [Flux Up Time] before
Default:
Options:00
“Manual”
“Manual”
acceleration.
Sets the amount of time the drive will use to try
and achieve full motor stator flux. When a Start
Default:
Min/Max:
Units:
0.2 Secs
0.0/5.0 Secs
0.1 Secs
command is issued, DC current at current limit
level is used to build stator flux before
accelerating. This will occur unless [Rated Amps]
is less than [Motor NP FLA], then only 81% of
drive rated current is used.
55
0/32767
1
“Calcul ate”
“Ready”
“Static Tune”
1
“Rotate Tune”
2
“Calcul ate”
3
Sets the amount of filtering used to boost voltage
during Sensorless Vector operation.
Provides a manual or automatic method for
setting [IR Voltage Drop], and [Flux Current Ref].
Note: Program parameter 053 [Motor Cntl Sel]
prior to running an autotune.
Default:
Min/Max:
Units:
Default:
Options:30
“Ready” (0) = Parameter returns to this setting following a “Static Tune” or “Rotate Tune.” It also
permits manually setting [IR Voltage Drop], [Ixo Voltage Drop] and [Flux Current Ref].
“Static Tune” (1) = A temporary command that initiates a non-rotational motor stator resistance
test for the best possible automatic setting of [IR Voltage Drop], [Break Voltage] and [Break
Frequency] in all modes. A start command is required within 20 seconds following initiation of
this setting. The parameter returns to “Ready” (0) following the test, at which time another start
transition is required to operate the drive in normal mode. Used when motor cannot be rotated.
“Rotate Tune” (2) = A temporary command that initiates a “Static Tune” followed by a rotational
test for the best possible automatic setting of [Flux Current Ref] and [Start Boost]. A start
command is required following initiation of this setting. The parameter returns to “Ready” (0)
following the test, at which time another start transition is required to operate the drive in
normal mode. Important: Used when motor is uncoupled from the load. Results may not be
valid if a load is coupled to the motor during this procedure.
Related
053
058
053
058
053
062
ATT EN TI ON : Rotation of the motor in an undesired direction can occur during
this procedure. To guard against possible injury and/or equipment damage, it
is recommended that the motor be disconnected from the load before
proceeding.
“Calculate” (3) = This setting uses motor nameplate data to automatically set [IR Voltage Drop],
[Flux Current Ref] and [Slip RPM @ FLA].
062 [IR Voltage Drop]
Value of voltage drop across the resistance of the
motor stator at rated motor current.
063 [Flux Current Ref]
32
Value of amps for full motor flux.
069 [Start Boost]
Sets the voltage boost level for starting and
acceleration. Refer to parameter 083 [Overspeed
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Motor NP Volts]×0.50
0.1 VAC
Based on Drive Rating
0.00/[Motor NP FLA]
0.01 Amps
Based on Drive Rating
0.0/[Motor NP Volts] × 0.25
0.1 VAC
Limit].
071 [Break Voltage]
Sets the voltage the drive will output at [Break
Frequency]. Refer to parameter 083 [Overspeed
Volts p er Hertz
Limit].
072 [Break Frequency]
Sets the frequency the drive will output at [Break
Voltage]. Refer to parameter 083.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Motor NP Volts]
0.1 VAC
Based on Drive Rating
0.0/[Maximum Freq]
0.1 Hz
053
061
053
061
053
053
072
053
071
Rockwell Automation Publication 20C-PM001F-EN-P - March 201223
Chapter 2Programming and Parameters
Speed Command File
File
Parameter Name & DescriptionValues
Group
No.
079 [Speed Units]
Selects the units to be used for all speed related
parameters. Options 0 & 1 indicate status only.
Options 2 & 3 will convert/configure the drive for
that selection.
“Convert Hz” (2) - converts all speed based
parameters to Hz, and changes the value
proportionately (i.e. 1800 RPM = 60 Hz).
“Convert RPM” (3) - converts all speed based
parameters to RPM, and changes the value
proportionately.
Note: This parameter does not get changed with a
“Reset to Defaults”.
080 [Feedback Select]
Selects the source for motor speed feedback.
“Open Loop” (0) - no encoder is present, and slip
compensation is not needed.
“Slip Comp” (1) - tight speed control is needed,
and encoder is not present.
081 [Minimum Speed]
Sets the low limit for speed reference after scaling
32
is applied. Refer to parameter 083 [Overspeed
Limit].
082 [Maximum Speed]
Sets the high limit for speed reference after
32
scaling is applied. Refer to parameter 083
[Overspeed Limit].
083 [Overspeed Limit]
Sets the incremental amount of the output
Spd Mode/Limits
SPEED COMMAND
32
frequency (above [Maximum Speed]) allowable
for functions such as slip compensation.
[Maximum Speed] + [Overspeed Limit] must be
≤[Maximum Freq]
Motor Volts
Voltage
Break Volts
Start Boost
Allowable Output Frequency Range
Bus Regulation or Current Limit
Allowable Output Frequency Range
Normal Operation
Allowable Reference Frequency Range
Frequency Trim due to
Speed Control Mode
Default:
Options:00
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Overspeed
Limit
“Hz”
“Hz”
1
“RPM”
2
“Convert Hz”
3
“Convert RPM”
“Open Loop”
“Open Loop”
1
“Slip Comp”
0.0
0.0/[Maximum Speed]
0.1 Hz
0.1 RPM
50.0 or 60.0 Hz (volt class)
[Motor NP RPM]
5.0/320.0 Hz
75.0/19200.0 RPM
0.1 Hz
0.1 RPM
10.0 Hz
300.0 RPM
0.0/20.0 Hz
0.0/600.0 RPM
0.1 Hz
0.1 RPM
Related
152
079
083
092
095
055
079
083
091
094
055
079
082
0Min
Speed
084
[Skip Frequency 1]
085
[Skip Frequency 2]
086
[Skip Frequency 3]
32
Sets a frequency at which the drive will not
Break
Frequency
operate. [Skip Frequency x] and [Skip Frequency
Band] must not equal 0.
087 [Skip Freq Band]
32
Determines the bandwidth around a skip
frequency. [Skip Freq Band] is split, applying 1/2
above and 1/2 below the actual skip frequency.
The same bandwidth applies to all skip
frequencies.
24Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Motor
Hz
Frequency
Default:
Default:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Max
Output
Speed
Freq Limit
Based on Drive Rating
0.0 Hz
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
0.0 Hz
0.0/30.0 Hz
0.1 Hz
Max
Freq
087
084
085
086
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
088 [Speed/Torque Mod]
Selec ts the torque reference source.
“Speed Reg” (1) - drive operates as a speed
regulato r.
454 [Rev Speed Limit]
32
Sets a limit on speed in the negative direction.
Spd Mode/Limits
Used in bipolar mode only. A value of zero
disables this parameter and uses [Min Speed] for
minimum speed.
090 [Speed Ref A Sel]
Selects the source of the speed reference to the
drive unless [Speed Ref B Sel] or [Preset Speed 17] is selected.
(1)
See Installation Manual for DPI port locations.
SPEED COMMAND
091 [Speed Ref A Hi]
32
Scales the upper value of the [Speed Ref A Sel]
Speed References
selection when the source is an analog input.
092 [Speed Ref A Lo]
32
Scales the lower value of the [Speed Ref A Sel]
selection when the source is an analog input.
093 [Speed Ref B Sel]
See [Speed Ref A Sel]
094 [Speed Ref B Hi]
32
Scales the upper value of the [Speed Ref B Sel]
selection when the source is an analog input.
095 [Speed Ref B Lo]
32
Scales the lower value of the [Speed Ref B Sel]
selection when the source is an analog input.
Related
Default:
Options:11
Default:
Min/Max:
“Speed Reg”
“Speed Reg”
0.0 RPM
–[Max Speed]/0.0 Hz
053
–[Max Speed]/0.0 RPM
Units:
0.0 Hz
0.0 RPM
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Analog In 2”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
002
091
thru
093
101
thru
107
117
thru
120
192
thru
194
(1)
(1)
(1)
(1)
(1)
213
272
273
320
361
thru
Default:
Options:21
366
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
.
Options:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
11“Preset Spd1”
See [Speed Ref A Sel]
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
082
079
081
090
079
093
079
090
093
Rockwell Automation Publication 20C-PM001F-EN-P - March 201225
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
096 [TB Man Ref Sel]
Sets the manual speed reference source when a
digital input is configured for “Auto/Manual.”
Note: Options 18…20 were added for firmware
revision 5.002.
(1)
Speed References
097 [TB Man Ref Hi]
32
Scales the upper value of the [TB Man Ref Sel]
selection when the source is an analog input.
098 [TB Man Ref Lo]
32
Scales the lower value of the [TB Man Ref Sel]
selection when the source is an analog input.
100 [Jog Speed 1]
Sets the output frequency when Jog Speed 1 is
selected.
SPEED COMMAND
[Preset Speed 1]
101
[Preset Speed 2]
102
[Preset Speed 3]
103
[Preset Speed 4]
104
[Preset Speed 5]
105
[Preset Speed 6]
106
[Preset Speed 7]
107
Discrete Speeds
32
Provides an internal fixed speed command value.
In bipolar mode direction is commanded by the
sign of the referen ce.
108 [Jog Speed 2]
32
Sets the output frequency when Jog Speed 2 is
selected.
116 [Trim % Setpoint]
Adds or subtracts a percentage of the speed
reference or maximum speed. Dependent on the
setting of parameter 118 [Trim Out Select].
Speed Trim
Note: Added for firmware revision 3.001.
“Analog In 2” is not a valid selection if it was
selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep Wake Ref]
Default:
Options:11
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Analog In 1”
“Analog In 1”
“Analog In 2”
2
3…8
“Reserved”
9
“MOP Level”
18
“DPI Port1”
19
“DPI Port2”
20
“DPI Port3”
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
1 RPM
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
0.0%
–/+200%
0.1%
Related
097
098
(1)
079
096
079
096
079
079
090
093
118
26Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
117 [Trim In Select]
Specifies which analog input signal is being used
as a trim input.
(1)
118 [Trim Out Select]
Specifies which speed references are to be trimmed and allows you to trim the speed reference
based on a percentage or the frequency of the input signal.
Note: Added bit 2 “Add or %” for firmware revision 3.001.
Speed Trim
See Installation Manual for DPI port locations.
ValueBit 2Bit 1, 0
1 =%Trimmed
0 =AddNot Trimmed
Default:
Options:20
1
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Analog In 2”
“Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
Related
090
093
(1)
(1)
(1)
(1)
(1)
117
119
120
SPEED COMMAND
119 [Trim Hi]
32
120 [Trim Lo]
32
121 [Slip RPM @ FLA]
Slip Comp
123 [Slip RPM Meter]
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Add or %
Tri m Re f B
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
1 RPM
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
1 RPM
Scales the upper value of the [Trim In Select]
selection when the source is an analog input.
Scales the lower value of the [Trim In Select]
selection when the source is an analog input.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Important: Parameters in the Slip Comp Group are used to enable and tune the Slip
Compensation Regulator. In order to allow the Slip Compensation Regulator to control drive
operation, parameter 080 [Feedback Select] must be set to 1 “Slip Comp”.
Based on [Motor NP RPM]
0.0/1200.0 RPM
0.1 RPM
Read Only
–/+300.0 RPM
0.1 RPM
Sets the amount of compensation to drive output
at motor FLA.
Displays the present amount of adjustment being
applied as slip compensation.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Tri m Re f A
079
082
117
0791
17
061
080
123
080
121
Rockwell Automation Publication 20C-PM001F-EN-P - March 201227
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
124 [PI Configuration]
Sets configuration of the PI regulator.
Note: Added bit 9 “% of Ref” for firmware revision 3.001.
1 = Enabled
0 = Disabled
Defaultxxxxxx0x00000000
Bit1514131211109876543210
125 [PI Control]
Controls the PI regulator.
1 = Enabled
0 = Disabled
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
126 [PI Reference Sel]
Selects the source of the PI reference.
Process PI
SPEED COMMAND
127 [PI Setpoint]
Provides an internal fixed value for process
setpoint when [PI Reference Sel] is set to “PI
Setpoint.”
128 [PI Feedback Sel]
Selects the source of the PI feedback.
129 [PI Integral Time]
Time required for the integral component to reach
100% of [PI Error Meter]. Not functional when the
PI Hold bit of [PI Control] = “1” (enabled).
130 [PI Prop Gain]
Sets the value for the PI proportional component.
PI Error x PI Prop Gain = PI Output
131 [PI Lower Limit]
Sets the lower limit of the PI output.
132 [PI Upper Limit]
Sets the upper limit of the PI output.
Name
Name
Related
124
thru
138
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
% of Ref
Reserved
Anti-Wind Up
Stop Mode
Feedbak Sqrt
Zero Clamp
Ramp Ref
Preload Mode
Invert Error
Excl Mode
080
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PI Reset
PI Hold
PI Enable
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Options:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“PI Setpoint”
“PI Setpoint”
“Analog In 1”
1
“Analog In 2”
2
“Reserved”
3-8
“MOP Level”
9
“Master Ref ”
10
“Preset Spd1-7”
11-17
“DPI Port 1-5”
18-22
50.0%
–/+100.0% of Maximum
Process Value
0.1%
2“Analog In 2”
See [PI Reference Sel]
2.0 Secs
0.00/100.00 Secs
0.01 Secs
1.0
0.00/100.00
0.01
–[Maximum Freq]
100%
–/+800.0%
0.1%
+[Maximum Freq]
100%
–/+800.0%
0.1%
124
thru
138
124
thru
138
124
thru
.
138
124
thru
138
124
thru
138
079
124
thru
138
079
124
thru
138
28Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
133 [PI Preload]
Sets the value used to preload the integral
component on start or enable.
134 [PI Status]
Status of the Process PI regulator.
1 = Condition True
0 = Condition False
Defaultxxxxxxxxxxxx0000
Bit1514131211109876543210
135 [PI Ref Meter]
Pres ent va lue of the PI reference signal.
136 [PI Fdback Meter]
Pres ent va lue of the PI feedback signal.
137 [PI Error Meter]
Present value of the PI error.
Process PI
SPEED COMMAND
138 [PI Output Meter]
Present value of the PI output.
460 [PI Reference Hi]
Scales the upper value of [PI Reference Sel] of the
source.
461 [PI Reference Lo]
Scales the lower value of [PI Reference Sel] of the
source.
462 [PI Feedback Hi]
Scales the upper value of [PI Feedback] of the
source.
463 [PI Feedback Lo]
Scales the lower value of [PI Feedback] of the
source.
464 [PI Output Gain]
Sets the gain factor for [PI Output Meter].
Note: Added for firmware revision 3.001.
Name
Related
Default:
Min/Max:
Units:
0.0 Hz
100%
–/+800.0%
0.1%
079
124
thru
138
Read Only124
thru
138
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PI InLimit
PI Reset
PI Hold
PI Enabled
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0 Hz
–/+100.0%
0.1 Hz
124
thru
138
124
thru
138
124
thru
138
124
thru
138
0.1%
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
–100.0%
–/+100.0%
0.1%
100.0%
–/+100.0%
0.1%
0.0%
–/+100.0%
0.1%
1.000
–/+8.000
0.001
138
Rockwell Automation Publication 20C-PM001F-EN-P - March 201229
Chapter 2Programming and Parameters
Dynamic Control File
File
Parameter Name & DescriptionValues
Group
No.
140
[Accel Time 1]
141
[Accel Time 2]
Sets rate of accel for all speed increases.
Max Speed
Accel Time
142
[Decel Time 1]
143
[Decel Time 2]
Sets rate of decel for all speed decreases.
Ramp Rates
Max Speed
Decel Time
146 [S Curve %]
Sets the percentage of accel or decel time that is
applied to the ramp as S Curve. Time is added, 1/2
at the beginning and 1/2 at the end of the ramp.
147 [Current Lmt Sel]
Selects the source for the adjustment of current
limit (i.e. parameter, analog input, etc.).
148 [Current Lmt Val]
Defines the current limit value when [Current Lmt
Sel] = “Cur Lim Val.”
149 [Current Lmt Gain]
Sets the responsiveness of the current limit.
150 [Drive OL Mode]
DYNAMIC CONTROL
Selects drive response to increasing drive
temperature.
Load Limits
151 [PWM Frequency]
Sets the carrier frequency for the PWM output.
Drive derating may occur at higher carrier
frequencies.
152 [Droop RPM @ FLA]
Selects amount of droop that the speed reference
is reduced when at full load torque. Zero disables
the droop function.
=
=
Accel Rate
Decel Rate
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:30
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
0%
0/100%
1%
“Cur Lim Val”
“Cur Lim Val”
“Analog In 1”
1
“Analog In 2”
2
Based on Drive Rating
Based on Drive Rating
0.1 Amps
10000
0/32767
1
“Both-PWM 1st”
“Reserved”
“Reduce Clim”
1
“Reserved”
2
“Both-PWM 1st”
3
1.5 kHz or 2 kHz based on Drive
Rating
1/Based on Drive Rating
1 kHz
0.0 RPM
0.0/200.0 RPM
0.1 RPM
Related
142
143
146
361
thru
366
140
141
146
361
thru
366
140
thru
143
146
149
147
149
147
148
Important: Selecting “Slip Comp” with
parameter 080 in conjunction with parameter
152, may produce undesirable results.
145 [DB While Stopped]
Enables/disables dynamic brake operation when
drive is stopped. DB may operate if input voltage
becomes too high.
• Disa bled = DB will not
operate when the drive
is stopped.
• Enabled = DB may operate whenever drive is
Stop/Brake Modes
energized.
Notes: This parameter is used for frame 9 drives
only. Added for firmware revision 3.001.
30Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Default:
Options:00
“Disabled”
“Disabled”
“Enabled”
1
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
155
[Stop/Brk Mode A]
156
[Stop/Brk Mode B]
Active stop mode. [Stop Mode A] is active unless
[Stop Mode B] is selec ted by inputs.
(1)
information.
(2)
Attention statements at [DC Brake Level].
157 [DC Brake Lvl Sel]
Selects the source for [DC Brake Level].
158 [DC Brake Level]
Defines the DC brake current level injected into
the motor when “DC Brake” is selected as a stop
mode.
The DC braking voltage used in this function is
created by a PWM algorithm and may not
generate the smooth holding force needed for
some applications.
Refer to Stop Modes on page 101 for important
When using options 1 or 2, refer to the
ATT EN TI ON : If a hazard of injury due to movement of equipment or material
exists, an auxiliary mechanical braking device must be used.
ATT EN TI ON : This feature should not be used with synchronous or permanent
magnet motors. Motors may be demagnetized during braking.
Default:
Default:
Options:
Default:
Options:00
Default:
Min/Max:
Units:
“Ramp”
1
0
0
1
2
3
(1)
“Coast”
(1)
“Coast”
(2)
“Ramp”
“Ramp to Hold”
“DC Brake”
“DC Brake Lvl”
“DC Brake Lvl”
1
“Analog In 1”
2
“Analog In 2”
Based on the Drive Rating
0/[Rated Amps]
0.1 Amps
Related
157
158
159
(2)
155
156
158
159
159 [DC Brake Time]
Stop/Brake Modes
DYNAMIC CONTROL
160 [Bus Reg Ki]
161
162
Sets the amount of time DC brake current is
“injected” into the motor.
Sets the responsiveness of the bus regulator.
[Bus Reg Mode A]
[Bus Reg Mode B]
Sets the method and sequence of the DC bus
voltage regulator. Choices are dynamic brake,
frequency adjust or both. Options 2 & 3 only
appear when a dynamic brake is installed in the
drive.
Dynamic Brake Setup:
If a dynamic brake resistor is connected to the
drive, both of these parameter s must be set to
either option 2 or 3.
Refer to the Attention statement on page 8
for
important information on bus regulation.
ATT EN TI ON : The drive does not offer protection for externall y mounted brake
resistors. A risk of fire exists if external braking resistors are not protected.
External resistor packages must be self-protected from over temperature or
the protective circuit shown in Figure 3 on page 87
supplied.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:
0.0 Secs
0.0/90.0 Secs
0.1 Secs
Based on Drive Rating
0/5000
1
“Ad ju st Fre q”
1
“Disabled”
0
“Disabled”
0
“Ad ju st Fre q”
1
“Dynamic Brak”
2
“Both-DB 1st”
3
(or equivalent) must be
155
thru
158
161
162
160
163
163 [DB Resistor Type]
Selects whether an external DB resistor will be
used.
Default:
Options:00
1
“None”
“None”
“External Res”
161
162
Note: Used for frame 9 drives only.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201231
Chapter 2Programming and Parameters
File
DYNAMIC CONTROL
Parameter Name & DescriptionValues
Group
No.
164 [Bus Reg Kp]
Proportional gain for the bus regulator. Used to
adjust regulator response.
165 [Bus Reg Kd]
Derivative gain for the bus regulator. Used to
control regulator overshoot.
465 [Fan Control]
Enables/Disables the drive cooling fan control.
“Disabled” = Drive cooling fan control off - fan(s)
always runs
Stop/Brake Modes
“Enabled” = Drive cooling fan control on - the
cooling fan(s) stops if the drive is stopped and the
heatsink temperature is below 55° C for 60
seconds
Note: Added for firmware revision 4.001. Changed
the default value to 1 “Enabled” for firmware
revision 6.001.
167 [Powerup Delay]
Defines the programmed delay time, in seconds,
before a start command is accepted after a power
up.
168 [Start At PowerUp]
Enables/disables a feature to issue a Start or Run
command and automatically resume running at
commanded speed after drive input power is
restored. Requires a digital input configured for
Run or Start and a valid start contact.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:10
Default:
Min/Max:
Units:
Default:
Options:00
Based on Drive Rating
0/10000
1
122
0/10000
1
“Enabled”
“Disabled”
1
“Enabled”
0.0 Secs
0.0/30.0 Secs
0.1 Secs
“Disabled”
“Disabled”
1
“Enabled”
Related
ATT EN TI ON : Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national and international codes,
standards, regulations or industry guidelines.
169 [Flying Start En]
Enables/disables the function which reconnects
Restart Modes
to a spinning motor at actual RPM when a start
command is issued.
174 [Auto Rstrt Tries]
Sets the maximum number of times the drive
attempts to reset a fault and restart.
ATT EN TI ON : Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national and international codes,
standards, regulations or industry guidelines.
175 [Auto Rstrt Delay]
Sets the time between restart attempts when
[Auto Rstrt Tries] is set to a value other than zero.
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Disabled”
“Disabled”
“Enabled”
1
0
0/9
1
1.0 Secs
0.5/30.0 Secs
0.1 Secs
175
174
32Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
178 [Sleep Wake Mode]
Enables/disables the Sleep/Wake function.
Important: When enabled, the following
conditions must be met:
• A proper minimum value must be
• A speed reference must be selected in [Speed
• At least one of the following must be
Note: Option 2 was added for firmware revision
2.001.
Conditions Required to Start Drive
InputAfter Power-Up After a Drive FaultAfter a Stop Command
StopStop Closed
EnableEnable Closed
Run
Run For.
Run Rev.
Restart Modes
DYNAMIC CONTROL
(1)
(2)
(3)
(4)
(5)
(6)
179 [Sleep Wake Ref]
Selects the source of the input controlling the
Sleep Wake function.
180 [Wake Level]
Defines the analog input level that will start the
drive.
181 [Wake Time]
Defines the amount of time at or above [Wake
Level] before a Start is issued.
182 [Sleep Level]
Defines the analog input level that will stop the
drive.
183 [Sleep Time]
Defines the amount of time at or below [Sleep
Level] before a Stop is issued.
ATT EN TI ON : Enabling the Sleep Wake function can cause unexpected machine
operation during the Wake mode. Equipment damage and/or personal injury
can result if this parameter is used in an inappropriate application. Do Not use
this function without considering the table below and applicable local, national
& international codes, standards, regulations or industry guidelines.
(1)(2)(3)
Reset by Stop-CF,
HIM or TB
Wake Sign al
Wake Sign al
Run Closed
Wake Sign al
When power is cycled, if all conditions are present after power is restored, restart will occur.
The drive only starts after Sleep Wake Mode is “enabled” and a valid signal is received.
The active speed reference is determined as explained in “Reference Control” in the Installation Ma nual. The Sleep/
Wake function and the speed reference may be assigned to the same in put.
Command must be issued from HIM, TB or network.
Run Command must be cycled.
Signal does not need to be greater than wake level.
Stop Closed
Wake Sig nal
New Start or Run Cmd.
Enable Closed
(4)
Wake Sig nal
New Start or Run Cmd.
New Run Cmd.
Wake Sig nal
(5)
Reset by Clear
Faults (TB)
Stop Closed
Wake Sign al
(4)
Enable Closed
Wake Sign al
(4)
Run Closed
Wake Sign al
Default:
Options:21
Default:
Min/Max:
HIM or TB
Stop Closed
Analog Sig. > Sleep Level
New Start or R un Cmd.
Enable Closed
Analog Sig. > Sleep Level
New Start or R un Cmd.
New Run Cmd.
Wake Sign al
(5)
“Analog In 2”
“Analog In 1”
“Analog In 2”
2
“Reserved”
3-6
6.000 mA, 6.000 Volts
[Sleep Level]/20.000 mA 10.000
Vol ts
Units:
0.001 mA
0.001 Volts
Default:
Min/Max:
Units:
Default:
Min/Max:
0.0 Secs
0.0/1000.0 Secs
0.1 Secs
5.000 mA, 5.000 Volts
4.000 mA/[Wake Level]
0.000 Volts/[Wake Level]
Units:
0.001 mA
0.001 Volts
Default:
Min/Max:
Units:
0.0 Secs
0.0/1000.0 Secs
0.1 Secs
Related
168
(6)
(4)
(6)
(4)
181
180
183
182
Rockwell Automation Publication 20C-PM001F-EN-P - March 201233
Chapter 2Programming and Parameters
File
DYNAMIC CONTRO
Parameter Name & DescriptionValues
Group
No.
184 [Power Loss Mode]
Sets the reaction to a loss of input power. Power
loss is recognized when:
• DC bus voltage is ≤73% of [DC Bus Memory]
• DC bus voltage is ≤82% of [DC Bus Memory]
185 [Power Loss Time]
Sets the time that the drive will remain in power
loss mode before a fault is issued.
186 [Power Loss Volts]
Sets the level at which the [Power Loss Mode]
selection will occur.
The drive can use the percentages referenced in [Power Loss Mode] or a trigger point can be set
at [Power Loss Volts]. A digital input (programmed to “29, Pwr Loss Lvl”) is used to toggle
Power Loss
between fixed percentages and the [Power Loss Volts] level.
189 [Shear Pin Time]
Sets the time that the drive is at or above current
limit before a fault occurs. Zero disables this
feature.
Note: Added for firmware revision 3.001.
and [Power Loss Mode] is set to “Coast”.
and [Power Loss Mode] is set to “Decel”.
ATTENTION: Drive damage can occur if proper input impedance is not
provided as explained below. If the value for [Power Loss Volts] is less than
82% of the nominal DC bus voltage, the user must provide a minimum line
impedance to limit inrush current when the power line recovers. The input
impedance should be equal to or greater than the equivalent of a 5%
transformer with a VA rating 5 times the drives input VA rating.
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Coast”
“Coast”
“Decel”
1
“Continue”
2
0.5 Secs
0.0/60.0 Secs
0.1 Secs
Based on Drive Rated Volts
170.0/780.0 VDC
0.1 VDC
0.0 Secs
0.0/30.0 Secs
0.1 Secs
Related
013
185
184
238
34Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Utility File
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
190 [Direction Mode]
Selects the method for changing drive direction.
ModeDirection Change
UnipolarDrive Logic
BipolarSign of Reference
Direction Config
Reverse DisNot Changeable
192 [Save HIM Ref]
• Bit 0 “S ave HIM Ref” enables a feature to save the present frequency reference value issued by
• Bit 1 “ Manual Mode” enables the HIM to control the Speed Reference only or the Speed
Note: Bit 1 “Manual Mode” was added for firmware revision 4.001.
Save HIM Ref
1 = Enabled
0 = Disabled
Manual Mode
1 = HIM controls Reference, Start, and Jog
0 = HIM controls only the Reference
HIM Ref Config
Defaultxxxxxxxxxxxxxx01
Bit1514131211109876543210
193 [Man Ref Preload]
Enables/disables a feature to automatically load
UTILITY
the present “Auto” frequency reference value into
the HIM when “Manual” is selected. Allows
smooth speed transition from “Auto” to “Manual.”
194 [Save MOP Ref]
Enables/disables the feature that saves the present MOP frequency reference at power down or
at stop.
1 = Save at power down
0 = Do not save
Default:
Options:00
1
2
“Unipolar”
“Unipolar”
“Bipolar”
“Reverse Dis”
the HIM to Drive memory on power loss. Value is restored to the HIM on power up.
Reference, Start and Jog in Manual mode, including two-wire control.
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Default:
Options:00
“Disabled”
“Disabled”
“Enabled”
1
Related
320
thru
327
361
thru
366
Reserved
Manual Mode
Save HIM Ref
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
At Stop
At Powr Down
Defaultxxxxxxxxxxxxxx00
MOP Config
Bit1514131211109876543210
195 [MOP Rate]
32
Sets rate of change of the MOP reference in
response to a digital input.
Default:
Min/Max:
1.0 Hz/s
30.0 RPM/s
0.2/[Maximum Speed]
6.0/[Maximum Speed]
Units:
0.1 Hz/s
0.1 RPM/s
196 [Param Access Lvl]
Selects the parameter display level viewable on
the HIM.
Basic = Reduced parameter set
Drive Memory
Advance d = Full parame ter set
Default:
Options:00
1
2
“Basic”
“Basic”
“Advanced”
“Reserved”
Rockwell Automation Publication 20C-PM001F-EN-P - March 201235
Chapter 2Programming and Parameters
File
UTILITY
Parameter Name & DescriptionValues
Group
No.
197 [Reset To Defalts]
Resets parameters to the factory defaults except
parameters [Mtr NP Pwr Units], [Speed Units],
[Language], and [Param Access Lvl] (parameters
46, 79, 196 and 201).
Important: The drive will reset after a reset to
defaults.
• 1 “Ready” - resets all affected parameters to
• 2 “Low Voltage” and 3 “High Voltage” will set
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values
from a selected user set location in drive
nonvolatile memory to active drive memory.
199 [Save To User Set]
Saves the parameter values in active drive
memory to a user set in drive nonvolatile
memory.
Drive Memory
200 [Reset Meters]
Resets selected meters to zero.
201 [Language]
Selects the display language when using an LCD
HIM. This parameter is not functional with an LED
HIM.
Options 6, 8 and 9 are “Reserved.”
202 [Voltage Class]
Displays the last “Reset to Defaults” operation.
203 [Drive Checksum]
Provides a checksum value that indicates whether
or not a change in drive programming has
occurred.
36Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
204 [Dyn UsrSet Cnfg]
Enables/Disables dynamic selection of user parameter sets.
Important: In dynamic mode, changes to the parameters are not saved to nonvolatile storage.
Switching user sets restores the values last saved before enabling dynamic mode.
Note: Added for firmware revision 4.001.
Dynamic Mode
1 = Enabled
0 = Disabled
Contro l Source
1 = [Dyn UserSet Sel]
0 = Digital Inputs
205 [Dyn UsrSet Sel]
Selects user set if [Dyn UsrSet Cnfg] = 0000000000000011.
Important: All digital input selections (parameters 361…366) must be identical in all three
user sets for proper Dynamic User Set operation (even if only two sets are used).
Note: Added for firmware revision 4.001.
1 = Enabled
0 = Disabled
UTILITY
Drive Memory
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Ctrl Source
Dynamic Mode
Defaultxxxxxxxxxxxxxx00
Bit1514131211109876543210
UserSet Sel2 UserSet Sel1 User Set Active
00User Set 1
01User Set 2
10User Set 3
11User Set 4
Related
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
UserSet Sel2
UserSet Sel1
Defaultxxxxxxxxxxxxxx00
Bit1514131211109876543210
206 [Dyn UserSet Actv]
Indicates the active user set and if the operation is dynamic or normal.
Note: Added for firmware revision 4.001.
1 = Condition True
0 = Condition False
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
User Set 3
User Set 2
User Set 1
Dynamic Mode
Defaultxxxxxxxxxxxx0000
Bit1514131211109876543210
Rockwell Automation Publication 20C-PM001F-EN-P - March 201237
Chapter 2Programming and Parameters
File
Group
No.
209 [Drive Status 1]
210 [Drive Status 2]
UTILITY
Diagnostics
Parameter Name & DescriptionValues
Read Only210
Present operating condition of the drive.
1 = Condition True
0 = Condition False
(2)
(2)
(2)
(2)
(1)
(1)
(1)
Spd Ref ID 3
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Local ID 2
Local ID 1
Local ID 0
At Speed
Faul ted
Alarm
Decelerating
Accelerat ing
Actual Dir
Comma nd Dir
Active
Default0000000000000000
Bit1514131211109876543210
(2)
Bits
Description
Ref A Auto
0
0
0
0
0
0
0
0
0
0
1
0
1
0
1
0
1
0
0
1
0
1
0
1
0
1
1
1
1
1
1
1
1
1
Ref B Auto
1
0
Preset 2 Auto
0
1
Preset 3 Auto
1
1
Preset 4 Auto
0
0
Preset 5 Auto
1
0
Preset 6 Auto
0
1
Preset 7 Auto
1
1
TB Manual
0
0
Port 1 Manu al
1
0
Port 2 Manu al
0
1
Port 3 Manu al
1
1
Port 4 Manu al
0
0
Port 5 Manu al
1
0
Port 6 Manu al
0
1
Jog Ref
1
1
Bits
0
0
0
0
1
1
1
1
(1)
Description15 14 13 1211 10 9
Port 0 (TB)
0
0
Port 1
1
0
Port 2
0
1
Port 3
1
1
Port 4
0
0
Port 5
1
0
Port 6
0
1
No Local Control
1
1
Read Only209
Present operating condition of the drive.
1 = Condition True
0 = Condition False
Related
Ready
Name
Reserved
Reserved
DPI at 500 k
Motor Overld
Bus Freq Reg
Curr Limit
AutoRst Act
AutoRst Ctdn
Reserved
AutoTuning
DC Braking
Stopping
Jogging
Defaultxx000000x0000000
Bit1514131211109876543210
211 [Drive Alarm 1]
Read Only212
Alarm conditions that currently exist in the drive.
Notes: Bit 15 was added for firmware revision 2.001. Bits 7, 8,
and 14 were changed to “Reserved” for firmware revision
38Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
212 [Drive Alarm 2]
Alarm conditions that currently exist in the drive.
Notes: Bits 14 and 15 were added for firmware revision 2.001.
Bits 8, 9 and 11 were changed to “Reserved” for firmware
revision 3.001. Bit 0 was changed from “DigIn Test” to “DigIn
CflctA” and bit 11 “UserSetCflct” was added for firmware
revision 4.001. Bit 8 “Fan Cooling” was added for firmware
revision 6.001.
1 = Condition True
0 = Condition False
Default000000x000000000
Bit1514131211109876543210
213 [Speed Ref Source]
Displays the source of the speed reference to the
drive.
UTILITY
Diagnostics
214 [Start Inhibits]
Displays the inputs currently preventing the drive from
starting.
Notes: Bit 15 was added for firmware revision 2.001. Bit 14 was
changed to “Reserved” for firmware revision 3.001.
1 = Inhibit True
0 = Inhibit False
“PI Output”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Jog Speed 1”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
““Reserved”
“Au to Tune”
“Jog Speed 2”
090
093
096
101
Read Only
Name
Gate Disable
Reserved
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Reserved
Startup Actv
Param s Reset
Stop Assertd
DC Bus Pchrg
Enable
Tye p 2 A lar m
Faul t
Default0x000000x0000000
Bit1514131211109876543210
Rockwell Automation Publication 20C-PM001F-EN-P - March 201239
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
215 [Last Stop Source]
Displays the source that initiated the most recent
stop sequence. It will be cleared (set to 0) during
the next start sequence.
216 [Dig In Status]
Status of the digital inputs.
1 = Input Present
0 = Input Not Present
Defaultxxxxxxxxxx000000
Bit1514131211109876543210
Name
Related
Default:
Options:0
1
2
3
4
5
6
7
8
9
10
11
12
13
Read Only
“Pwr Removed”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
“Reserved”
“Digital In”
“Fault”
“Not Enabled”
“Sleep”
“Jo g ”
“Au t ot u n e”
“Precharge”
361
362
363
364
365
366
Read Only361
thru
366
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In6
Digital In5
Digital In4
Digital In3
Digital In2
Digital In1
217 [Dig Out Status]
Status of the digital outputs.
UTILITY
1 = Output Energized
Diagnostics
0 = Output De-energized
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
218 [Drive Temp]
Present operating temperature of the drive power
section.
220 [Motor OL Count]
Accumulated percentage of motor overload.
Continuously operating the motor over 100% of
the motor overload setting will increase this value
to 100% and cause a drive fault.
224 [Fault Frequency]
Captures and displays the output speed of the
drive at the time of the last fault.
225 [Fault Amps]
Captures and displays motor amps at the time of
the last fault.
226 [Fault Bus Volts]
Captures and displays the DC bus voltage of the
drive at the time of the last fault.
Name
Read Only380
384
388
thru
380
384
388
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital Out3
Digital Out2
Digital Out1
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
0.0/100.0%
0.1%
Read Only
0.0/100.0%
0.1%
Read Only
0.0/+[Maximum Freq]
0.1 Hz
Read Only
0.0/[Rated Amps] × 2
0.1 Amps
Read Only
0.0/Max Bus Volts
0.1 VDC
047
048
079
225
thru
230
224
thru
230
224
thru
230
40Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
227 [Status 1 @ Fault]
Captures and displays [Drive Status 1] bit pattern at the time of
the last fault.
1 = Condition True
0 = Condition False
228 [Status 2 @ Fault]
Captures and displays [Drive Status 2] bit pattern at the time of
the last fault.
1 = Condition True
0 = Condition False
Read Only209
Name
Spd Ref ID 3
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Local ID 2
Local ID 1
Local ID 0
At Speed
Faul ted
Alarm
Decelerating
Accelerating
Actual Dir
Command Dir
Active
Ready
Default0000000000000000
Bit1514131211109876543210
Read Only210
Name
Reserved
Reserved
DPI at 500 k
Motor Overld
Bus Freq Reg
Curr Limit
AutoRst Act
AutoRst Ctdn
Reserved
AutoTuning
DC Braking
Stopping
Jogging
Running
Active
Ready
Defaultxx000000x0000000
Bit1514131211109876543210
Related
224
thru
230
224
thru
230
229 [Alarm 1 @ Fault]
Captures and displays [Drive Alarm 1] at the time of the last
UTILITY
fault.
Diagnostics
Notes: Bit 15 was added for firmware revision 2.001. Bits 7, 8,
and 14 were changed to “Reserved” for firmware revision
Captures and displays [Drive Alarm 2] at the time of the last
fault.
Note: Bits 14 and 15 were added for firmware revision 2.001.
1 = Condition True
0 = Condition False
Read Only211
Name
Gate Disable
Reserved
Load Loss
Phase Loss
Motor Therm
Waki ng
Decel Inhibt
Reserved
Reserved
Heatsink Temp
IntDBRes OH
Anlg in Loss
Str At PwrUp
Power L oss
UnderVoltage
Prechrg Actv
Default0x00000xx0000000
Bit1514131211109876543210
Read Only212
Name
HDW OverTemp
PTC Cflct
TB Ref Cflct
Sleep Config
UserSet Cflct
SpdRef Cflct
Reserved
Reserved
VHz NegSlope
MaxFrq Cflct
NP Hz Cflct
MtrTyp Cflct
Bipolr Cflct
DigIn CflctC
DigIn CflctB
DigIn CflctA
Default000000xx00000000
Bit1514131211109876543210
224
thru
230
224
thru
230
Rockwell Automation Publication 20C-PM001F-EN-P - March 201241
Chapter 2Programming and Parameters
File
Group
No.
234
236
235
Diagnostics
237
238 [Fault Config 1]
UTILITY
Parameter Name & DescriptionValues
[Testpoint 1 Sel]
[Testpoint 2 Sel]
Selects the function whose value is displayed in
Default:
Min/Max:
Units:
499
0/65535
1
[Testpoint x Data]. These are internal values that
are not accessible through parameters.
Note: These parameters were added for future use
in firmware revision 4.001.
[Testpoint 1 Data]
[Testpoint 2 Data]
The present value of the function
Default:
Min/Max:
Units:
Read Only
-/+32767
1
selected in [Testpoint x Sel].
Note: These parameters were added for future use
in firmware revision 4.001.
Enables/disables annunciation of the listed faults.
Setting bit 14 “Fan Cooling” to 1 configures the drive for a “Non-Resettable” fault (F32 “Fan
Cooling”). In this case, the drive must be powered-down and the cause of the fault must be
corrected before the fault can be cleared. Setting bit 14 to “0” will configure the drive for a “NonConfigurable” alarm. In this case the drive will continue to run.
Notes: Bit 9 “Load Loss” should not be changed from “0”. Bit 10 was added for firmware revision
2.001. Bits 2 “Motor Stall” and 11 “Shear PNO Ac” were added for firmware revision 3.001. Bit 14
“Fan Cooling” was added for firmware revision 6.001.
1 = Enabled
0 = Disabled
Related
Name
Reserved
Fan Cooling
Reserved
Reserved
Shear PNO Ac
Gate Disable
Load Loss
Phase Loss
Motor Therm
Decel Inhib
AutRst Tries
Shear Pin
Defaultx1xx000100001110
Bit1514131211109876543210
Faul ts
1
2
1
“Ready”
“Ready”
“Clear Faul ts”
“Clr Flt Q ue”
“Enabled”
“Disabled”
“Enabled”
240 [Fault Clear]
Resets a fault and clears the fault queue.
241 [Fault Clear Mode]
Enables/disables a fault reset (clear faults)
attempt from any source. This does not apply to
Default:
Options:00
Default:
Options:10
fault codes which are cleared indirectly via other
actions.
242 [Power Up Marker]
32
Elapsed hours since initial drive power up. This
value will rollover to 0 after the drive has been
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295 Hr
0.1 Hr
powered on for more than the max value shown.
For relevance to most recent power up see [Fault x
Time].
Motor Overld
Motor Stall
UnderVoltage
Power L oss
244
246
248
250
252
254
256
258
42Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
[Fault 1 Code]
243
[Fault 2 Code]
245
[Fault 3 Code]
247
[Fault 4 Code]
249
[Fault 5 Code]
251
[Fault 6 Code]
253
[Fault 7 Code]
255
[Fault 8 Code]
257
Default:
Min/Max:
Units:
Related
Read Only
0/65535
0
A code that represents the fault that tripped the
drive. The codes will appear in these parameters
in the order they occur ([Fault 1 Code] = the most
recent fault). See Fault and Alarm Descriptions
on
page 64 for a list of fault and alarm codes and the
corresponding descriptions and possible actions.
244
[Fault 1 Time]
246
[Fault 2 Time]
248
[Fault 3 Time]
250
[Fault 4 Time]
252
[Fault 5 Time]
254
[Fault 6 Time]
256
[Fault 7 Time]
258
[Fault 8 Time]
Faul ts
32
UTILITY
The time between initial drive power up and the
Default:
Min/Max:
Units:
Read Only
0.0000/429496.7295 Hr
0.0001 Hr
242
occurrence of the associated trip fault. Can be
compared to [Power Up Marker] for the time from
the most recent power up.
[Fault x Time] – [Power Up Marker] = Time
difference to the most recent power up. A
negative value indicates fault occurred before
most recent power up. A positive value indicate s
fault occurred after most recent power up.
[Fault 1 Subcode]
543
[Fault 2 Subcode]
545
[Fault 3 Subcode]
547
[Fault 4 Subcode]
549
[Fault 5 Subcode]
551
[Fault 6 Subcode]
553
[Fault 7 Subcode]
555
[Fault 8 Subcode]
557
Default:
Min/Max:
Units:
Read Only
0/65535
1
Fault subcode. Provides additional information for
certain faults. Refer to Fault and Alarm
Descriptions on page 64.
Note: Added for firmware revision 4.001.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201243
Chapter 2Programming and Parameters
File
Group
No.
259 [Alarm Config 1]
261 [Alarm Clear]
Alarms
UTILITY
262
263
264
265
266
267
268
269
Parameter Name & DescriptionValues
Enables/disables alarm conditions that will initiate an active drive alarm.
Note: Bits 14 and 15 were added for firmware revision 2.001.
1 = Condition True/Enabled
0 = Condition False/Disabled
A code that represents a drive alarm. The codes
will appear in the order they occur (first 4 alarms
in – first 4 out alarm queue). A time stamp is not
available with alarms.
Related
Prechrg Actv
262
263
264
265
266
267
268
269
261
44Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Communication File
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
271 [Drive Logic Rslt]
The final logic command resulting from the combination of all
DPI and discrete inputs. This parameter has the same structure
as the product-specific logic command received via DPI and is
used in peer to peer communications.
1 = Condition True
0 = Condition False
Bits
0
0
0
Comm Control
COMMUNICATION
0
1
1
1
1
272 [Drive Ref Rslt]
Present frequency reference scaled as a DPI
reference for peer to peer communications. The
value shown is the value prior to the accel/decel
ramp and the corrections supplied by slip comp,
PI, etc.
273 [Drive Ramp Rslt]
Present frequency reference scaled as a DPI
reference for peer to peer communications. The
value shown is the value after the accel/decel
ramp, but prior to any corrections supplied by slip
comp, PI, etc.
Read Only
(1)
(1)
(1)
Name
MOP Dec
Spd Ref ID 2
Spd Ref ID 1
Spd Ref ID 0
Decel 2
Decel 1
Accel 2
Accel 1
MOP Inc
Local Cont rl
Reverse
Forward
Clear Fault
Jog
Start
Stop
Default0000000000000000
Bit1514131211109876543210
(1)
Description14 13 12
No Command - Man. Mode
0
0
Ref A Auto
1
0
Ref B Auto
0
1
Preset 3 Auto
1
1
Preset 4 Auto
0
0
Preset 5 Auto
1
0
Preset 6 Auto
0
1
Preset 7 Auto
1
1
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+32767
1
Read Only
–/+32767
1
Related
Rockwell Automation Publication 20C-PM001F-EN-P - March 201245
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
274 [DPI Port Sel]
Selects which DPI port reference value will appear
in [DPI Port Value].
Comm Control
275 [DPI Port Value]
Value of the DPI reference selected in [DPI Port
Sel].
276 [Logic Mask]
Determines which adapters can control the drive. If the bit for an adapter is set to “0,” the
adapter will have no control functions except for stop.
1 = Control Permitted
0 = Control Masked
277 [Start Mask]
Controls which adapters can issue star t
commands.
278 [Jog Mask]
Controls which adapters can issue jog commands.
279 [Direction Mask]
COMMUNICATION
Controls which adapters can issue for ward/
reverse direction commands.
280 [Reference Mask]
Controls which adapters can select an alternate
Masks/Owners
reference; [Speed Ref A Sel], [Speed Ref B Sel] or
[Preset Speed x].
281 [Accel Mask]
Controls which adapters can select [Accel Time 1]
or [Accel Time 2].
282 [Decel Mask]
Controls which adapters can select [D ecel Time 1]
or [Decel Time 2].
283 [Fault Clr Mask]
Controls which adapters can clear a fault.
284 [MOP Mask]
Controls which adapters can issue MOP
commands to the drive.
285 [Local Mask]
Controls which adapters are allowed to take
exclusive control of drive logic commands (except
stop). Exclusive “local” control can only be taken
while the drive is stopped.
Default:
Options:1
Default:
Min/Max:
Units:
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Defaultxxxxxxxxx0111111
Bit1514131211109876543210
“DPI Port 1”
“DPI Port 1”
“DPI Port 2”
2
“DPI Port 3”
3
“DPI Port 4”
4
“DPI Port 5”
5
Read Only
–/+32767
1
DPI Port 6
DPI Port 5
DPI Port 4
See [Logic Mask]
DPI Port 3
DPI Port 2
DPI Port 1
.288
Digital In
See [Logic Mask].288
See [Logic Mask]
See [Logic Mask]
See [Logic Mask]
See [Logic Mask]
.288
.288
.288
.288
See [Logic Mask].288
See [Logic Mask]
See [Logic Mask]
.288
.288
Related
288
thru
297
thru
297
thru
297
thru
297
thru
297
thru
297
thru
297
thru
297
thru
297
thru
297
46Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
288 [Stop Owner]
Adapters that are presently issuing a valid stop command.
1 = Issuing Command
0 = No Command
Defaultxxxxxxxxx0000000
Bit1514131211109876543210
289 [Start Owner]
Adapters that are presently issuing a valid start
command.
290 [Jog Owner]
Adapters that are presently issuing a valid jog
command.
291 [Direction Owner]
Adapter that currently has exclusive control of
direction changes.
292 [Reference Owner]
Adapter that has the exclusive control of the
command frequency source selection.
Masks/Owners
293 [Accel Owner]
Adapter that has exclusive control of selecting
[Accel Time 1, 2].
294 [Decel Owner]
COMMUNICATION
Adapter that has exclusive control of selecting
[Decel Time 1, 2].
295 [Fault Clr Owner]
Adapter that is presently clearing a fault.
296 [MOP Owner]
Adapters that are currently issuing increases or
decreases in MOP command frequency.
297 [Local Owner]
Adapter that ha s requested exclusive control o f all
drive logic functions. If an adapter is in local
lockout, all other functions (except stop) on all
other adapters are locked out and non-functional.
Local control can only be obtained when the drive
is not running.
300
[Data In A1] - Link A Word 1
301
[Data In A2] - Link A Word 2
Parameter number whose value will be written
from a communications device data table.
Value will not be updated until drive is stopped.
Refer to your communications option manual for
Datalinks
datalink information.
302
[Data In B1] - Link B Word 1
303
[Data In B2] - Link B Word 2
Name
Related
Read Only276
thru
285
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
See [Stop Owner]
.276
thru
285
See [Stop Owner]
.276
thru
285
See [Stop Owner]
.276
thru
285
See [Stop Owner]
.276
thru
285
See [Stop Owner]
.140
276
thru
285
See [Stop Owner]
.142
276
thru
285
See [Stop Owner].276
thru
285
See [Stop Owner].276
thru
285
See [Stop Owner].276
thru
285
Default:
Min/Max:
Units:
See [Data In A1] -
0 (0 = “Disabled”)
0/486
1
Link A Word 1 [Data In A2]
- Link A Word 2.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201247
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
304
[Data In C1] - Link C Word 1
305
[Data In C2] - Link C Word 2
306
[Data In D1] - Link D Word 1
307
[Data In D2] - Link D Word 2
310
[Data Out A1] - Link A Word 1
311
[Data Out A2] - Link A Word 2
Parameter number whose value will be written to
Datalinks
a communications device data table.
312
[Data Out B1] - Link B Word 1
313
[Data Out B2] - Link B Word 2
314
[Data Out C1] - Link C Word 1
315
[Data Out C2] - Link C Word 2
316
[Data Out D1] - Link D Word 1
317
[Data Out D2] - Link D Word 2
595 [Port Mask Ac t]
Bits 0…6 indicate status for DPI port communication. Bit 15
indicates when security software is controlling the parameter.
Note: Added for firmware revision 4.001
1 = Active
0 = Not Active
COMMUNICATIONS
See [Data In A1] - Link A Word 1 [Data In A2]
- Link A Word 2.
See [Data In A1] -
Link A Word 1 [Data In A2]
- Link A Word 2.
Default:
Min/Max:
Units:
See [Data Out A1] -
0 (0 = “Disabled”)
0/544
1
Link A Word 1 [Data Out
A2] - Link A Word 2.
See [Data Out A1] -
Link A Word 1 [Data Out
A2] - Link A Word 2.
See [Data Out A1] - Link A Word 1 [Data Out
A2] - Link A Word 2.
Read Only
Name
Security
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Host
Default0xxxxxxxx0000000
Bit1514131211109876543210
Related
596 [Write Mask Cfg]
Security
Enables/disables write access (parameters, links, etc.) for DPI ports. Changes to this parameter
only become effective when power is cycled, the drive is reset or bit 15 of parameter 597 [Write
Mask Act], transitions from “1” to “0.”
Note: Added for firmware revision 4.001.
1 = Write Permitted
0 = Read Only
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
Defaultxxxxxxxxx1111110
Bit1514131211109876543210
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
48Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
597 [Write Mask Act]
Status of write access for DPI ports. When bit 15 is set, network
security is controlling the write mask instead of parameter 596
[Write Mask Cfg].
Note: Added for firmware revision 4.001.
1 = Write Permitted
0 = Read Only
Default0xxxxxxxx0000000
Bit1514131211109876543210
598 [Logic Mask Act]
Security
COMMUNICATIONS
Indicates status of the logic mask for DPI ports. When bit 15 is
set, network security is controlling the logic mask instead of
parameter 276 [Logic Mask].
Note: Added for firmware revision 4.001.
1 = Control Permitted
0 = Control Masked
Default0xxxxxxxx0000000
Bit1514131211109876543210
Name
Name
Related
Read Only
Security
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Host
Read Only
Security
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Inputs/Outputs File
File
Group
No.
320 [Anlg In Config]
Analog Inputs
INPUTS/OUTPUTS
Parameter Name & DescriptionValues
Selects the mode for the analog inputs.
1 = Current
0 = Voltage
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
An2 0=V 1=mA
Defaultxxxxxxxxxxxxxx00
Bit1514131211109876543210
Related
322
325
323
326
An1 0=V 1=mA
Rockwell Automation Publication 20C-PM001F-EN-P - March 201249
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
321 [Anlg In Sqr Root]
Enables/disables the square root function for each input.
1 = Enable
0 = Disable
Defaultxxxxxxxxxxxxxx00
Bit1514131211109876543210
322
[Analog In1 Hi]
325
[Analog In2 Hi]
Sets the highest input value to the analog input x
scaling block.
[Anlg In Config], parameter 320 defines if this
input will be –/+10V or 0-20 mA.
Note: The Min. value was changed from 4.000mA
to 0.000mA for firmware revision 3.001.
Analog Inputs
323
[Analog In1 Lo]
326
[Analog In2 Lo]
Sets the lowest input value to the analog input x
scaling block.
[Anlg In Config], parameter 320 defines if this
input will be –/+10V or 0-20 mA.
INPUTS/OUTPUTS
Note: The Min. value was changed from 4.000mA
to 0.000mA for firmware revision 3.001.
324
[Analog In1 Loss]
327
[Analog In2 Loss]
Selects drive action when an analog signal loss is
detected. Signal loss is defined as an analog
signal less than 1V or 2mA. The signal loss event
ends and normal operation resumes when the
input signal level is greater than or equal to 1.5V
or 3mA.
340 [Anlg Out Config]
Selects the mode for the analog output s.
1 = Current
0 = Voltage
50Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
An2 0=V 1=mA
An1 0=V 1=mA
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
341 [Anlg Out Absolut]
Selects whether the signed value or absolute value of a parameter is used before being scaled to
drive the analog output.
1 = Absolute
0 = Signed
Defaultxxxxxxxxxxxxxx11
Bit1514131211109876543210
342
[Analog Out1 Sel]
345
[Analog Out2 Sel]
Selects the source of the value that drives the
analog output.
Options
0
1
2
3
4
5
6
7
8
9
10
11
12
13…15
16
17…23
24
Analog Outputs
INPUTS/OUTPUTS
343
[Analog Out1 Hi]
346
[Analog Out2 Hi]
Sets the analog output value when the source
value is at maximum.
Note: The Min. value was changed from
4.000 mA…0.000 mA for firmware revision
3.001.
344
[Analog Out1 Lo]
347
[Analog Out2 Lo]
Sets the analog output value when the source
value is at minimum.
Note: The Min. value was changed from
4.000 mA…0.000 mA for firmware revision
3.001.
354
[Anlg Out1 Scale]
355
[Anlg Out2 Scale]
32
Sets the high value for the range of analog output
scale. Entering 0.0 will disabl e this scale and max
scale will be used. Example: If [Analog Outx Sel]
= “Commanded Freq,” a value of 150 = 150%
scale in place of the default 200%.
377
[Anlg1 Out Setpt]
378
[Anlg2 Out Setpt]
Sets the analog output value from a
communication device. Example: Set [Data In Ax]
to “377” (value from communication device).
Then set [Analog Outx Sel] to “Param Cntl.”
Rockwell Automation Publication 20C-PM001F-EN-P - March 201251
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
358 [20C-DG1 Remove]
Clears an F10 "System Fault" issued when the
drive has recognized that the 20C-DG1 option
board has been removed for service and has not
been re-installed. The drive is designed to
generate a non-resettable fault, F10 "System
Fault", if the option board is removed from the
drive's control. You must manually set this
parameter to 1"Remove" and then back to 0
"Ready" to clear and acknowledge the fault. Once
maintenance or service is completed and the 20CDG1 option card has been reinstalled, the drive
will recognize the option card on power-up.
Note: This parameter was added for firmware
revision 2.001. Please refer to the PowerFlex 700H
and 700S Drives Installation Manual (Frame
9…14), publication PFLEX-IN006
information on the 20C-DG1 option board.
359 [20C-DG1 Status]
Displays the status of the Gate Disable option board (20C-DG1) functions.
Bit 0 = Gate Disable active
Bit 1 = Thermistor input active
Bit 2 = Unexpected problem in Gate Disable circuitry / inputs
Bit 3 = No Gate Enable input on channel 1
Bit 4 = No Gate Enable input on channel 2
INPUTS/OUTPUTS
Bit 6 = The test pulse detected a problem in the thermistor input
Bit 5 = Thermistor short circuit detected
Digital Inputs
Bit 7 = +5V overvoltage detected on the 20C-DG1 option board
Bit 8 = +5V undervoltage detected on the 20C-DG1 option board
Bit 9 = The test pulse detected a problem in the Gate Disable inputs
Bit 10 = ASIC trip input ETR not set, even if the Gate Disable inputs are active
Bit 11 = +5V or REF voltage problem detected on the 20C-DG1 option board
Bit 12 = The 20C-DG1 option board has been removed
Bit 13 = The 20C-DG1 option board has an EEPROM error
Bit 14 = The 20C-DG1 option board has been found by identification software
Bit 15 = A system fault (unexpected hardware problem) has been generated and cannot be
cleared
Note: This parameter was added for firmware revision 2.001.
1 = True
0 = False
for more
Default:
Options:00
Related
“Ready”
359
“Ready”
“Remove”
1
358
Name
Unexp HW Pro
20C-DG1 ID O
20C-DG1 EEPR
20C-DG1 Remo
+5V Ref Prob
ASIC Trip In
Default0000000000000000
Bit1514131211109876543210
52Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Input Pulse
+5V Undervol
+5V Overvolt
Therm Pulse
Therm Shor t
NoEnable CH2
NoEnable CH1
Unexp In Pro
Therm Activ
Gate Disable
Programming and ParametersChapter 2
File
INPUTS/OUTPUTS
Parameter Name & DescriptionValues
Group
No.
[Digital In1 Sel]
361
[Digital In2 Sel]
362
[Digital In3 Sel]
363
[Digital In4 Sel]
364
[Digital In5 Sel]
365
[Digital In6 Sel]
366
(9)
Selects the function for the digital inputs.
Notes: Options 36…42 are “Reserved”. Added
options 43 and 46 for firmware revision 3.001.
Added options 41, 42, 44 and 45 for firmware
revision 4.001. Added option 68 for firmware
revision 5.002.
(1)
Speed Select Inputs.
321Auto Reference Source
Reference A
0
0
0
0
0
0
1
1
1
1
To access Preset Speed 1, set [Speed Ref x Sel] to
“Preset Speed 1”.
Type 2 Alarms - Some digital input programming
may cause conflicts that will result in a Type 2
alarm. Example: [Digital In1 Sel] set to “5, Start” in
3-wire c ontrol and [Di gital In2 S el] set to 7 “R un”
in 2-wire.
Digital Inputs
Refer to Table 1 on page 64
resolving this type of conflict.
(2)
When [Digital Inx Sel] is set to option 2 “Clear
Faults” the Stop button cannot be used to clear a
fault condition.
(3)
Typical 3-Wire Inputs - Requires that only 3-wire
functions are chosen. Including 2-wire selections
will cause a type 2 alarm.
(4)
Typical 2-Wire Inputs - Requires that only 2-wire
functions are chosen. Including 3-wire selections
will cause a type 2 alarm. See Table 1 on page 64
for conflicts.
(5)
Auto/Manual - Refer to the Installation Manual for
details.
(6)
Opening an “Enable” input will cause the motor to
coast-to-stop, i gnoring any programmed Stop
modes.
(7)
A “Dig In ConflictB” alarm will occur if a “Start ” input is programmed without a “Stop” input.
(8)
Refer to the Sleep Wake Mode Attention statement on page 33.
(9)
A dedicated hardware enable input is available via a jumper selection. Refer to Installation Manual for
further information.
(10)
Refer to [Dyn UsrSet Sel] on page 37 for selection information.
(11)
Refer to Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel] on page 55.
(12)
The function of this value is similar to 18 “Auto/Manual”, except the polarity is opposite.
“Jo g 1 ”
“Jo g For war d”
“Jo g R eve rs e”
“Stop Mode B”
“Bus Reg Md B”
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Au to / Ma nu al”
“Local”
“Acc2 & Dec2”
“Accel 2”
“Decel 2”
“MOP Inc”
“MOP Dec”
“Excl Link”
Rockwell Automation Publication 20C-PM001F-EN-P - March 201253
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
379 [Dig Out Setpt]
Sets the digital output value from a communication device.
Example:
Set [Data In B1] to “379.” The first three bits of this value will determine the setting of [Digital
Outx Sel] which should be set to value 30 “Param Cntl.”
1 = Output Energized
0 = Output De-energized
380
[Digital Out1 Sel]
384
[Digital Out2 Sel]
388
[Digital Out3 Sel]
Selects the drive status that will energize a (CRx)
output relay.
(1 )
Digital Outputs
INPUTS/OUTPUTS
(2)
(3)
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Net DigOut3
Net DigOut2
Net DigOut1
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
Default:
Options:
Any relay programmed as Fault or Alarm will
energize (pick up) when power is applied to drive
and deenergize (drop out) when a fault or alarm
exists. Relays selected for other functions will
energize only when that condition exists and will
deenergize when condition is removed.
Activation level is defined in [Dig Outx Level] below.
At SpeedRelay changes state when drive has reached commanded speed.380 384 388
Excl LinkLinks digital input to a digital output if the output is set to “Input 1…6
Link.” This does not need to be selected in the Vector option.
Input 1-6 Link When Digital Output 1 is set to one of these (i.e. Input 3 Link) in
MOP DecDecrements speed reference as long as input is closed.361…366
MOP IncIncre ments speed re ference as lon g as input is closed.361…366
Param Cntl (A.O.)Parameter controlled analog output allows PLC to control analog
Param Cntl (D.O.)Parameter controlled digital output allows PLC to control digital outputs
PI ReferenceReference for PI block (see Process PI on page 93).342 345
Run Level
RunFwd Level
RunRev Level
Run w/CommAllows the Comms start bit to operate like a run with the run input on
Digital Outputs
[Dig Out1 Level]
381
[Dig Out2 Level]
385
[Dig Out3 Level]
389
Sets the relay activation level for options 10…15
in [Digital Outx Sel]. Units are assumed to match
the above selection (i.e. “At Freq” = Hz, “At
Tor que ” = Am ps ).
[Dig Out1 OnTime]
382
[Dig Out2 OnTime]
386
[Dig Out3 OnTime]
390
Sets the “ON Delay” time for the digital outputs.
This is the time between the occurrence of a
condition and activation of the relay.
[Dig Out1 OffTime]
383
[Dig Out2 OffTime]
387
[Dig Out3 OffTime]
391
Sets the “OFF Delay” time for the digital outputs.
This is the time between the disappearance of a
condition and de-activation of the relay.
conjunction with Digital Input 3 set to “Excl Link,” the Digital Input 3
state (on/off) is echoed in the Digital Output 1.
outputs through data links. Set in [Anlgx Out Setpt], par. 377…378.
through data links. Set in [Dig Out Setpt], parameter 379.
Provides a run level input. A run level input doe s not require a transition
for enable or fault, but does require a transition for a stop.
the terminal block. Ownership rules apply.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
0.0
0.0
0.0
0.0/1500.0
0.1
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
Related
361…366
380 384 388
342 345
380 384 388
361…366
361…366
380
384
388
380
384
388
380
384
388
Rockwell Automation Publication 20C-PM001F-EN-P - March 201255
Chapter 2Programming and Parameters
Parameter List by Name
Parameter NameNumber GroupPage
20C-DG1 Remove358Digital Inputs2-52
20C-DG1 Status359Digital Inputs2-52
Accel Mask281Masks/Owners2-46
Accel Owner293Masks/Owners2-47
Accel Time X140, 141 Ramp Rates2-30
Alarm Clear261Alarms2-44
Alarm Config 1259Al arms2-44
Alarm X @ Fault229, 230 Diagnostics2-41
Alarm X Code262-269 Alarms2-44
Analog In X Hi322, 325 Analog Inputs2-50
Analog In X Lo323, 326 Analog Inputs2-50
Analog In X Loss324, 327 Analog Inputs2-50
Analog In1 Value016Metering2-20
Analog In2 Value017Metering2-20
Analog OutX Hi343, 346 Analog Outputs2-51
Analog OutX Lo344, 347 Analog Outputs2-51
Analog OutX Sel342, 345 Analog Outputs2-51
Anlg In Config320Analog Inputs2-49
Anlg In Sqr Root321Analog Inputs2-50
Anlg Out Absolut341Analog Outputs2-51
Anlg Out Config340Analog Outputs2-50
Anlg OutX Scale354, 355 Analog Outputs2-51
Anlg OutX Setpt377, 378 Analog Outputs2-51
Auto Rstrt De lay17 5Restart Mod es2-32
Auto Rstrt Tries174Restart Modes2-32
Autotune061Torq Attributes2-23
Break Frequency072Volts per Hertz2-23
Break Voltage071Volts per Hertz2-23
Bus Reg Kd165Stop/Brake Modes2-32
Bus Reg Ki160Stop/Brake Modes2-31
Bus Reg Kp164Stop/Brake Modes2-32
Bus Reg Mode X161, 162 Stop/Brake Modes2-31
Commanded Speed002Metering2-20
Command ed Torque024Metering2-21
Compensation056Torq Attributes2-22
Control SW Ver029D rive Data2-21
Current Lmt Gain149Load Limits2-30
Current Lmt Sel147Load Limits2-30
Current Lmt Val148Load Limits2-30
Data In XX300-307 Datalinks2-47
Data Out XX310-317 Datalinks2-48
DB Resistor Type163Stop/Brake Modes2-31
DB While Stopped145Ramp Rates2-30
DC Brake Level158Stop/Brake Modes2-31
DC Brake Time159Stop/Brake Modes2-31
DC Brk Lvl Sel157Stop/Brake Modes2-31
DC Bus Memory013Metering2-20
DC Bus Voltage012Metering2-20
Decel Mask282Masks/Owners2-46
Decel Owner294Masks/Owners2-47
Decel Time X142, 143 Ramp Rates2-30
Dig In Status21 6Diagnostics2-40
Dig Out Setpt379Digital Outputs2-54
Dig Out Status217Diagnostics2-40
Dig OutX Level381, 385,
Dig OutX OffTime383, 387,
Dig OutX OnTime382, 386,
Digital InX Sel361-366 Digital Inputs2-53
Digital OutX Sel380, 384,
Direction Mask279Masks/Owners2-46
Direction Mode190Direction Config2-35
Direction Owner291M asks/Owners2-47
DPI Port Sel274Comm Control2-46
DPI Port Value275Comm Control2-46
Drive Alarm X211, 212 Diagnostics2-38
Drive Checksum203Drive Memory2-36
Drive Logic Rslt271Comm Control2-45
56Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
Parameter NameNumber GroupPage
Motor NP FLA042Motor Data2-21
Motor NP Hert z043Mo tor Data2-21
Motor NP Power0 45Motor Data2-21
Motor NP RPM044Motor Data2-21
Motor NP Volts041Motor Data2-21
Motor OL Count220Diagnostics2-40
Motor OL Factor048Motor D ata2-22
Motor OL Hert z047Motor Data2-22
Motor OL Mode050Motor Data2-22
Motor Poles049Motor Data2-22
Motor Type0 40Motor Data2-21
Mtr NP Pwr Units046Motor Data2-22
Output Current003Metering2-20
Output Freq001Metering2-20
Output Power007M etering2-20
Output Powr Fctr008Metering2-20
Output Voltage006Metering2-20
Overspeed Limit083Spd Mode/Limits2-24
Param Access Lvl196D rive Memory2-35
PI Configuration124Process PI2-28
PI Control125Process PI2-28
PI Error Meter1 37Process PI2-29
PI Fdback Meter136Process PI2-29
PI Feedback Hi462Process PI2-29
PI Feedback Lo463Process PI2-29
PI Feedback Sel128Process PI2-28
PI Integral Time129Process PI2-28
PI Lower Limit131Process PI2-28
PI Output Meter138Process PI2-29
PI Preload133Process PI2-29
PI Prop Gain130Process PI2-28
PI Ref Meter135Process PI2-29
PI Reference Hi460Process PI2-29
PI Reference Lo46 1Process PI2-29
PI Reference Sel126Process PI2-28
PI Setpoint127Process PI2-28
PI Status134Process PI2-29
PI Output Gain4 64Process PI2-29
PI Upper Limit132Process PI2-28
Port Mask Act595Security2-48
Power Loss Vo lts186Power Loss2-34
Power Loss Mode184Power Loss2-34
Power Loss Time185Power Loss2-34
Power Up Marker242Faults2-42
Powerup Delay167Restar t Modes2-32
Preset Speed X101-107 Discrete Speeds2-26
PWM Frequency151Load Limits2-30
Ramped Speed022Metering2-20
Rated Amps028Drive Data2-21
Rated kW026Drive Data2-21
Rated Volts027Drive Data2-21
Reference Mask280Masks/Owners2-46
Reference Owner292Masks/Owners2-47
Reset Meters2 00Drive Memory2-36
Reset To Defalts197Drive Memory2-36
Rev Speed Limit454Speed Regulator2-25
S Curve %146Ramp Rates2-30
Save HIM Ref192HIM Ref Config2-35
Save MOP Ref194MOP Config2-35
Save To User Set199Drive Memory2-36
Shear Pin Time189Power Loss2-34
Skip Freq Band087Spd Mode/Limits2-24
Skip Frequency X084-086 Spd Mode/Limits2-24
Sleep Level182Restart Modes2-33
Sleep Time183Restart Modes2-33
Sleep Wake Mode178Restart Modes2-33
Sleep Wake Ref179Restart Modes2-33
Slip RPM @ FLA121Slip Comp2-27
Slip RPM Meter123Slip Comp2-27
Speed Feedback025Metering2-21
Speed Ref Source213Diagnostics2-39
Parameter NameNumber GroupPage
Speed Ref X Hi091, 094 Speed Re ference2-25
Speed Ref X Lo092, 095 Speed Reference2-25
Speed Ref X Sel090, 093 Speed Reference2-25
Speed Reference023Metering2-21
Speed Units079Spd Mode/Limits2-24
Speed/Torque Mod088Spd Mode/Limits2-25
Start At PowerUp168Restart Modes2-32
Start Inhibits214Diagnostics2-39
Start Mask277Masks/Owners2-46
Start Owner289Masks/Owners2-47
Start/Acc Boost069Volts per Hertz2-23
Status X @ Fault227, 228 Diagnostics2-41
Stop Owner288Masks/Owners2-47
Stop/Brk Mode X155, 156 Stop/Brake Modes2-31
SV Boost Filter059Torq Attributes2-23
TB Man Ref Hi097Speed Reference2-26
TB Man Ref Lo098Speed Reference2-26
TB Man Ref Sel096Speed Reference2-26
Testpoint 1 Data235Diagnostics2-42
Testpoint 2 Data237Diagnostics2-42
Testpoint 1 Sel234Diagnostics2-42
Testpoint 2 Sel236Diagnostics2-42
Torque Current004Metering2-20
Trim % Setpoint116Sp eed Trim2-26
Trim Hi119Speed Trim2-27
Tri m In S ele ct1 17Spe ed Tr im2-27
Tri m Lo12 0S pee d Tri m2-27
Tri m Out Sel ect11 8S pee d Tri m2-27
Wake Level180Restart Modes2-33
Wake Time181Restart Modes2-33
Write Mask Act597S ecurity2-49
Write Mask Cfg596Securit y2-48
Voltage Class202Drive Memor y2-36
Rockwell Automation Publication 20C-PM001F-EN-P - March 201257
Rockwell Automation Publication 20C-PM001F-EN-P - March 201259
Chapter 2Programming and Parameters
Notes:
60Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 3
Troubleshooting
This chapter provides information to guide you in troubleshooting the
PowerFlex 700H drive. Included is a listing and description of drive faults and
alarms (with possible solutions, when applicable).
For Information on…See page…
Drive Status62
Faults and Alarms63
Manually Clear Faults63
Fault and Alarm Descriptions64
Fault Subcodes71
Clear Alarms77
Common Drive Symptoms and Corrective Actions77
Technical Support Options79
Rockwell Automation Publication 20C-PM001F-EN-P - March 201261
Chapter 3Troubleshooting
Drive Status
The condition or state of your drive is constantly monitored. Any changes will be
indicated through the LEDs and/or the HIM (if present).
Front Panel LED Indications
1
2
#NameColorStateDescription
1PWR (Power)GreenSteadyIlluminates when power is applied to the drive.
2PORT
(1) Refer to the appropriate Communication Option User Manual for details.
MOD
NET A
NET B
(1)
(1)
(1)
(1)
Green–Status of DPI port internal communications (if present).
Yellow–Status of communications module (when installed).
Red–Status of network (if connected).
Red–Status of secondary network (if connected).
HIM Indications
The LCD HIM also provides visual notification of a fault or alarm condition.
ConditionDisplay
Drive is indicating a fault.
The LCD HIM immediately repor ts the fault condition by
displaying the following.
• “Faulted” appears in the status line
• Fa ult n umber
• Fa ult n ame
• Time that has passed since fault occurred
Press Esc to regain HIM control.
Drive is indicating an alarm.
The LCD HIM immediately reports the alarm condition by
displaying the following.
• Alarm name (Type 2 alarms only)
• Alarm bell graphic
62Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
F-> FaultedAuto
Hz
0.0
— Fault — F5
Main Menu:
OverVoltage
Diagnostics
Time Since Fault
Parameter
0000:23:52
F-> Power LossAuto
Hz
0.0
Main Menu:
Diagnostics
Parameter
Device Select
TroubleshootingChapter 3
Faults and Alarms
Manually Clear Faults
A fault is a condition that stops the drive. There are three fault types.
TypeFault Description
1Auto-Reset RunWhen this type of fault occurs, and [Auto Rstrt Tries] (see page 32
greater than “0,” a user-configurable timer, [Auto Rstrt Delay] (see page 32) begins.
When the timer reaches zero, the drive attempts to automatically reset the fault. If
the condition that caused the fault is no longer present, the fault will be reset and the
drive will be restarted.
2Non-ResettableThis type of fault normally requires drive or motor repair. The cause of the fault must
be corrected before the fault can be cleared. The fault will be reset on power up after
repair.
3User ConfigurableThese faults can be enabled/disabled to annunciate or ignore a fault condition.
) is set to a value
An alarm is a condition that, if not addressed, may stop the drive. There are two
alarm types.
TypeAlarm Description
1User ConfigurableThese alarms can be enabled or disabled through [Alarm Config 1] on page 44
2Non-ConfigurableThese alarms are always enabled.
See Fault and Alarm Descriptions
StepKey(s)
1. Press Esc to acknowledge the fault. The fault information will be
removed so that you can use the HIM.
on page 64.
Esc
.
2. Address the condition that caused the fault.
The cause must be corrected before the fault can be cleared.
3. After corrective action has been taken, clear the fault by one
methods.
– Press Stop
– Cycle drive power
– Set parameter 240 [Fault Clear] to “1.”
– “Clear Faults” on the HIM Diagnostic menu.
of these
Rockwell Automation Publication 20C-PM001F-EN-P - March 201263
Chapter 3Troubleshooting
Fault and Alarm Descriptions
Table 1 - Fault/Alarm Types, Descriptions and Actions
No. Name
1PrechargeActv1 The drive received a start command
2Auxiliary In1The auxiliary input interlock is
3Power Loss1,31 The DC bus voltage remained below
4UnderVoltage1,31 The DC bus voltage fell below the
while in the DC bus precharge state.
See Tab le 3 , “
(F1) Subcodes,” o n p ag e 7 1 for
more information on this fault.
open.
the value set in parameter 186
[Power Loss Volts] for longer than
the time specified in parameter 185
[Power Loss Time]. You can enable/
disable this fault with parameter
238 [Fault Config 1] (page 42
minimum value of 333V for 400/
480V drives and 461V for 600/ 690V
drives. You can enable/disable this
fault with parameter 238 [Fault
Config 1] ( page 2-42
See Tab le 4 , “Under Voltage Fault
(F4) Subcodes,” o n p ag e 7 1 for
more information on this fault.
maximum value.
See Tab le 5 , “Over Voltage Fault
(F5) Subcodes,” o n p ag e 7 1 for
more information on this fault.
current and low frequency and is
not accelerating.
See Tab le 6 , “
Subcode,” on page 71 for more
information on this fault.
You can enable/disable this fault
with parameter 238 [Fault Config 1]
(page 42
exceeded the maximum allowable
value.
85 degrees C = Alarm
90 degrees C = Fault
See Tab le 7 , “
Temperature Fault (F8) Subcodes,”
on page 71 for more information on
this fault.
exceeded their maximum operating
temperature due to an excessive
load.
Note: IGBT Overtemp = Drive
Overload (Software), not
adjustable.
See Tab le 8 , “IGBT Over
Temperature Fault (F9) Subcode,”
on page 72 for more information on
this fault.
Precharge Active Fault
).
).
Motor Stall Fault (F6)
).
Heatsink Over
–
Check all remote wiring.
Monitor the incoming AC line for low voltage
or line power interruption.
Monitor the incoming AC line for low voltage
or power interruption.
Monitor the AC line for high line voltage or
transient conditions. Bus overvoltage can
also be caused by motor regeneration.
Extend the decel time or install a dynamic
brake option.
1. Run an Autotune.
2. Reduce the Load.
1. Run an Autotune.
2. Verify the settings of parameters 48
[Motor OL Factor] and 47 [Motor OL
Hertz].
3. Reduce the load so that the drive output
current does not exceed the current set
by the value in parameter 42 [Motor NP
FLA].
1. Verify that the maximum ambient
temperature has not been exceeded.
2. Check the fans (including the ASIC board
on frame 10 and higher drives).
3. Check for an excess load.
4. Check the carrier frequency.
1. Verify that the maximum ambient
temperature has not been exceeded.
2. Check the fan(s).
3. Check for an excess load.
64Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
TroubleshootingChapter 3
No. Name
10System Fault2One of the following has occurred:
12OverCurrent1The drive output current has
13Ground Fault1A current path to earth ground
14InverterFault2A hardware problem exists in the
15Load Loss3 1 Do not use this fault in PowerFlex
16Motor Therm3 1 The option board thermistor input
17Input Phase3 1 One input line phase is missing.
19Unbalanced2An imbalance between the power
21OutPhasMissng2There is zero current in one of the
22NP Hz Cnflct2 The “fan/pump” mode is selected in [Motor Cntl Sel] and the ratio of parameter 43
DescriptionAction (if applicable)
Fault
Alarm
• A hardware problem exists in
the power structure.
See Tab le 9 , “System Fault (F10)
Subcodes,” o n p ag e 7 2 for more
information on this fault.
Note: Subcodes are only
available in revision 4.001 or
later.
• The 20C-DG1 option board has
been removed.
See Tab le 9 , “System Fault (F10)
Subcodes,” o n p ag e 7 2 for more
information on this fault.
Note: Subcodes are only
available in revision 4.001 or
later.
instantaneously exceeded 360% of
the HD rating.
See Tab le 1 0, “ Over Current Fault
(F12) Subcodes,” on page 73 for
more information on this fault.
exists that is greater than 50% of
the drive's heavy duty rating. The
current must appear for 800ms
before the drive will fault.
See Tab le 1 1, “
Subcode,” on page 73 for more
information on this fault.
power structure.
700H applications.
See Tab le 1 2, “Load Loss Fault ( F15)
Subcode,” on page 73 for more
information on this fault.
is greater than the limit.
See Tab le 1 3, “
(F17) Subcodes,” on page 73 for
more information on this fault.
modules exists (paralleled units frames 12 & 14 only).
output motor phases.
See Tab le 1 4, “
Missing Fault (F21) Subcode,” on
page 74 for more information on
this fault.
[Motor NP Hertz] to 55 [Maximum Freq] is greater than 26.
Ground Fault (F13)
Input Phase Fault
Output Phase
1. Cycle the power.
2. Verify the fiber optic connections.
3. Contact Technical Support. See Te ch n ic al
Support Options on page 79 for more
information. If the problem persists,
replace the drive.
Set parameter 358 [20C-DG1 Remove] to
1"Remove” and then back to 0 “Ready” to
clear and acknowledge the fault. Once
maintenance or service is completed and the
20C-DG1 option card has been reinstalled,
the drive will recognize the option card on
power-up.
Check programming for an excess load,
improper DC boost setting, DC brake voltage
set too high or other causes of excess
current. Check for shorted motor leads or a
shorted motor.
Check the motor and external wiring to the
drive output terminals for a grounded
condition.
1. Cycle the power.
2. Contact Technical Support. See Te ch n ic al
Support Options on page 79 for more
information.
3. If the problem persists, replace the drive.
Parameter 238 [Fault Config 1] / bit 0
“Power Loss” and parameter 259 [Alarm
Config 1] / bit 13 “Load Loss” are set to zero.
1. Check to ensure that the motor is cooling
properly.
2. Check for an excess load.
3. Verify the thermistor connection. If the
thermistor connection on the option
board is not used, it must be shorted.
1. Check all user-supplied fuses
2. Check the AC input line voltage.
1. Check for DC voltage imbalance between
the power modules.
2. Check for current output imbalance
between the power modules.
1. Check the motor wiring.
2. Check the motor for an open phase.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201265
Chapter 3Troubleshooting
No. Name
23MaxFreqCnflct2 The sum of parameters 82 [Maximum Speed] and 83 [Overspeed Limit] exceeds
24Decel Inhibit3 1 The drive cannot follow the
25OverSpd Limit1Functions such as Slip
26VHz Neg Slope2 Parameter 53 [Motor Cntl Sel] = “Custom V/Hz” & the V/Hz slope is negative.
27SpdRef Cnflct2 [Speed Ref x Sel] or [PI Reference Sel] is set to “Reserved”.
28BrakResMissing2No brake resistor has been
29Anlg In Loss1,31 An analog input is configured to
55 [Maximum Freq]. Raise [Maximum Freq] or lower [Maximum Speed] and/or
[Overspeed Limit] so that the sum is less than or equal to [Maximum Freq].
commanded decel due to bus
limiting.
Compensation or Bus Regulation
have attempted to add an output
frequency adjustment greater than
the value programmed in
parameter 83 [Overspeed Limit].
detected.
See Tab le 1 5, “
Missing Fault (F28) Subcodes,” on
page 74 for more information on
this fault.
fault on a signal loss. A signal loss
has occurred. Configure this fault
with [Anlg In x Loss] (page 50
timeout has occurred.
See Tab le 1 6, “
Watchdog Fault (F30) Subcode,” o n
page 74 for more information on
Hardware Fault (F31) Subcodes,” o n
page 74 for more information on
this fault.
command.
See Tab le 1 8, “ Fan Co olin g Fault
(F32) Subcodes,” on page 74 for
more information on this fault.
You can configure this fault to be an
alarm by setting bit 14 “Fan
Cooling” of parameter 238 [Fault
Config 1] to 1 (page 42
to reset a fault and resumed
running for the programmed
number of [Auto Rstrt Tries]. You
can enable/disable this fault with
parameter 238 [Fault Config 1]
(page 42
Brake Resistor
Microprocessor
).
).
1. Verify that the input voltage is within the
specified limits.
2. Verify that the system ground impedance
follows the proper grounding
techniques.
3. Disable bus regulation and/or add a
dynamic brake resistor and/or extend the
deceleration time. Refer to the Attention
statement regarding the “adjust freq”
setting for bus regulation on page 8 for
more information.
Remove the excessive load or overhauling
conditions or increase the value in
[Overspeed Limit].
1. Program [Bus Reg Mode x] to not use the
brake option.
2. Install a brake resistor and set parameter
163 [DB Resistor Type] to 1 “External Res”
(frame 9 drives only).
1. Check parameter settings.
2. Check for broken/loose connections at
the inputs.
).
1. Cycle the power.
2. Replace the Main Control board.
1. Check for an excess load.
2. Raise the value set in either [Accel Time
x] parameters.
3. Parameter 53 [Motor Cntl Sel] may need
to be set to “Custom V/Hz”.
4. Verify the values set in parameters 62 [IR
Voltage Drop] and 63 [Flux Current Ref].
5. Contact Technical Support. See Te ch n ic al
Support Options on page 3-79 for more
information.
1. Check for flashing LEDs on the fan
inverter board(s).
2. Check the fan motor bearings.
3. Check the fan motor windings resistance.
4. Check the fan inverter fuses.
5. Check the 7 μF fan capacitor(s).
Note: See the “PowerFlex 700S and 700H
Drives Hardware Service Manual” for the
applicable frame size for component
locations.
Correct the cause and manually clear the
fault.
66Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
TroubleshootingChapter 3
No. Name
34CAN Bus Flt2A sent message was not
37HeatsinkUndTp1The ambient temperature is too
44Device Change2The new power unit or option
45Device Add2A new option board was added.
47NvsReadChksum2There was an error reading
48ParamsDefault2The drive was commanded to write
54Zero Divide2This event occurred because a
59Gate Disable3 1 Both of the digital gate disable
60Hrdwr Therm3 1 The thermistor input is activated
63Shear Pin3The value programmed in
65I/O Removed2An I/O option board has been
DescriptionAction (if applicable)
Fault
Alarm
acknowledged.
See Tab le 1 9, “
Fault (F34) Subcode,” o n p ag e 7 4
for more information on this fault.
low.
See Tab le 2 0, “ Heatsink Under
Temperature Fault (F37) Subcodes,”
on page 75 for more information on
this fault.
board installed is a different type.
See Table 21, “
Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” o n
page 75 for more information on
this fault.
See Table 21, “Device Change (F44),
Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” o n
page 75 for more information on
this fault.
parameters 9 [Elapsed MWh] and
10 [Elapsed Run Time] from
EEPROM.
See Tab le 2 2, “
Fault (F47) Subcode,” o n p ag e 7 6
for more information on this fault.
default values to EEPROM.
mathematical function had a
dividend of zero.
inputs (SD-1 and SD-2) are not
enabled on the 20C-DG1 option
board.
(>4 kΩ) on the 20C-DG1 option
board.
parameter 148 [Current Lmt Val]
has been exceeded. You can
enable/disable this fault with
parameter 238 [Fault Config 1]
(page 42
removed.
Communication Bus
Device Change (F44),
NVS Read Checksum
).
1. Cycle the power.
2. Replace the Main Control board.
Raise the ambient temperature.
Clear the fault and reset the drive to the
factory defaults.
Clear the fault.
1. Cycle the power.
2. Replace the Main Control board.
1. Clear the fault or cycle power to the
drive.
2. Program the drive parameters as needed.
1. Cycle the power.
2. Replace the main Control board.
1. Check the motor.
2. Verify that the option board is properly
wired.
3. Replace the option board. See Appendix
E - “Instructions for ATEX Approved
PowerFlex 700H Drives in Group II
Category (2) Applications with ATEX
Approved Motors” in the PowerFlex 700H
and 700S Drives Installation Manual,
publication PFLEX-IN006, for information
on installing this option board.
1. Check the motor.
2. The resistance of the thermistor input
must go below 2 kΩ before the drive can
be reset.
Check the load requirements and the value
in [Current Lmt Val].
Clear the fault.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201267
Chapter 3Troubleshooting
No. Name
70Power Unit2One or more of the output
71Periph Loss2The communications card has a
81Port DPI Loss2The DPI port has stopped
94Hardware EnblAn enable signal is missing from
95AutoT Rs Stat2The Autotune Rs Static Test has
96AutoT Lm Rot2The Autotune Lm rotate test has
97AutoT MagRot2The Autotune magnet izing current
98AutoT Saturat2The Autotune saturation cu rve test
99UserSet Timer2A User Set load or save was not
100 Param Chksum2The checksum read from the Main
104 PwrBrd Chksum2The checksum read from the
DescriptionAction (if applicable)
Fault
Alarm
transistors were operating in the
active region instead of
desaturation. This can be caused by
excessive transistor current or
insufficient base drive voltage.
See Tab le 2 4, “
(F70) Subcodes,” on page 76 for
more information on this fault.
fault on the network side.
communicatin g.
A SCANport device was connected
to a drive operating DPI devices at
500k baud.
the control terminal block.
See Tab le 2 5, “
Fault (F94) Subcode,” o n p ag e 7 6
for more information on this fault.
failed.
failed.
rotate test has failed.
has failed.
completed in less than 5 seconds.
Control board does not match the
checksum calculated.
See Tabl e 2 6, “
Fault (F100) Subcodes,” o n p ag e 7 6
for more information on this fault.
EEPROM does not match the
checksum calculated from the
EEPROM data.
See Table 21, “
Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” o n
page 75 for more information on
this fault.
Power Unit Fault
Hardware Enable
Parameter Checksum
Device Change (F44),
Clear the fault.
Check the DPI device event queue and
corresponding fault information for the
device.
1. If the adapter was not intentionally
disconnected, check the wiring to the
port. Replace the wiring, port expander,
adapters, Main control board or complete
drive as required.
2. Check the HIM connection.
3. If an adapter was intentionally
disconnected and the [Logic Mask] bit for
that adapter is set to “1”, this fault will
occur. To disable this fault, set the bit in
parameter 276 [Logic Mask] for the
adapter to “0”.
1. Check the control wiring.
2. Check the position of the hardware
enable jumper.
3. Check the digital input programming.
1. Verify that the motor is not rotating
when autotune is enabled.
2. Check the motor connections.
1. Check the motor nameplate data.
2. Check the motor connections.
3. Verify that the Accel Time < (Base
Speed/40) x 33 sec. Note: 33 sec. = time
limit to bring motor to 40 Hz.
1. Check the motor nameplate data.
2. Check the motor connections.
3. Verify that the Accel Time < (Base
Speed/40) x 33 sec. (see above).
1. Check the motor nameplate data.
2. Check the motor connections.
Attempt to save the User Set again.
If this error occurs again, replace the Main
Control board.
1. Restore the drive to the factory defaults.
2. Cycle the power.
3. Reload User Set if used.
1. Cycle the power.
2. Contact Technical Support. See Te ch n ic al
Support Options on page 79 for more
information.
3. If the problem persists, replace the drive.
68Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
TroubleshootingChapter 3
No. Name
106 MCB-PB Config2The drive rating information stored
107 New IO Option2A New option board was added to
113 Fatal App2A Fatal Application error has
114 AutoT Enable2Autotune is enabled but has not
120 I/O Change2An option board has been replaced.
121 I/O Comm Loss2An I/O Board lost communications
133 DigIn CnflctA2 Digital input functions are in conflict. Combinations marked with a “ ” will cause
134 DigIn CnflctB2 A digital Start input has been configured without a Stop input or other functions
DescriptionAction (if applicable)
Fault
Alarm
1. Reset the fault or cycle the power.
on the power board is incompatible
with the Main Control board.
See Tab le 2 7, “
Power Board Configuration Fault
(F106) Subcode,” on page 76 for
more information on this fault.
the Main Control board.
See Table 21, “
Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” o n
page 75 for more information on
this fault.
occurred.
started.
See Table 21, “
Device Added (F45), I/O Option
Board Removed (F65), Power Board
Checksum (F104), New I/O Option
Board (F107) and I/O Option Board
Change (F120) Fault Subcodes,” o n
page 75 for more information on
this fault.
with the Main Control board.
an alarm.
* Jog 1 and Jog 2
Acc2 / Dec2
Accel 2
Decel 2
Jog *
Jog Fwd
Jog Rev
Fwd/Re v
are in conflict. Combinations that conflict are marked with a “ ” and will cause
an alarm.
* Jog 1 and Jog 2
Start
Stop-CF
Run
Run Fwd
Run Rev
Jog*
Jog Fwd
Jog Rev
Fwd/Rev
Main Control Board -
Device Change (F44),
Device Change (F44),
Acc2/
Accel 2 Decel 2 Jog* Jog Fwd Jog Rev Fwd/Rev
Dec2
Start Stop-CFRun Run
2. Replace the Main Control board.
1. Restore the drive to the factory defaults.
2. Reprogram parameters as necessary.
Replace the Main Control board.
Press the Start key within 20 seconds of
enabling autotune.
Reset the fault.
1. Check the connector.
2. Check for induced noise.
3. Replace I/O board or Main Control board.
Run
Rev
Jog* Jog
Fwd
Fwd
Jog Rev Fwd/
Rev
Rockwell Automation Publication 20C-PM001F-EN-P - March 201269
Chapter 3Troubleshooting
No. Name
135 DigIn CnflctC2 More than one physical input has been configured to the same input function.
136 BipolarCnflct2 Parameter 190 [Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or
139 UserSetCflct2 Not all digital inputs and datalinks in the user set you are saving are the same. All
143 TB Man Conflict2 Parameter 96 [TB Man Ref Sel] is
147 Start AtPwrUp1 Parameter 168 [Start At PowerUp] is enabled. The drive may star t at any time
148 IntDB OvrHeat1 The drive has temporarily disabled the DB regulator because the resistor
149 Waking1 The Wake timer is counting toward a value that will start the drive.
150 Sleep Config2 Sleep/Wake configuration error. With parameter 178 [Sleep Wake Mode] =
DescriptionAction (if applicable)
Fault
Alarm
Multiple configurations are not allowed for the following input functions.
Fwd/RevRun ReverseB us Reg Md B UserSet Sel2
Speed Sel 1Jog ForwardAcc2 & Dec2Run Level
Speed Sel 2Jog ReverseAccel 2RunFwd Level
Speed Sel 3RunDecel 2RunRev Level
Run ForwardStop Mode BUserSet Sel1Run w/Comm
more of the following digital input functions is configured: “Fwd/Reverse,” “Run
Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”
user sets must be saved with the same settings for parameters 361-366, 300-307
and 310-317.
using an analog input that is
programmed for another function.
within 10 seconds of drive powerup.
temperature has exceeded a predetermined value.
“Direct,” possible causes include: drive is stopped and parameter 180 [Wake Level]
< parameter 182 [Sleep Level].“Stop=CF,” “Run,” “Run Forward,” or “Run
Reverse” is not configured in [Digital Inx Sel].
Check the parameter settings to avoid
problem.
Table 2 - Fault/Alarm Cross Reference
NameNo.
Faul t
Alarm
Anlg In Loss29MaxFreqCnflct23
AutoReset Lim33MCB-PB Config106
AutoT Enable114 MicroWatchdog30
AutoT Lm Rot96Motor Stall6
AutoT MagRot97Motor Therm16
AutoT Rs Stat95MotorCalcData50
AutoT Saturat98MotorOverload7
Auxiliary In2New IO Option107
BipolarCnflct136NP Hz Cnflct22
BrakResMissng28NvsReadChksum47
CAN Bus Flt34OutPhasMissng21
Decel Inhibit24OverCurrent12
Device Add45OverSpd Limit25
Device Change44OverVoltage5
DigIn CnflctA133Param Chksum100
DigIn CnflctB134ParamsDefault48
DigIn CnflctC135Periph Loss71
Fan Cooli ng32Port DPI Loss81
Fatal App113 Power Loss3
Gate Disable59Powe r Unit70
Ground Fault13PrechargeActv1
Hardware Enbl94PwrBrd Chksum104
HeatsinkOvrTp8Shear Pin63
HeatsinkUndTp37Sleep Config150
Hrdwr Therm60SpdRef Cnflct27
I/O Change120
I/O Comm Loss121 Sys tem Fault10
I/O Removed65TB Man Conflict143
Start AtPwrUp147
NameNo.
Faul t
Alarm
70Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Fault Subcodes can be viewed in parameters 543, 545, 547, 549, 551, 553, 555,
and 557 [Fault x Subcode]. Each of these parameters corresponds with
parameters 243, 245, 247, 249, 251, 253, 255, and 257 [Fault x Code],
respectively. For example, if parameter 243 [Fault 1 Code] displays “5” and
parameter 543 [Fault 1 Subcode] displays “273”, an over voltage fault (F5) has
occurred in the power unit of the drive.
Table 3 - Precharge Active Fault (F1) Subcodes
SubcodeDescription
273The precharge circuit in the power unit is active.
289The precharge circuit in power unit 1 is active.
305The precharge circuit in power unit 2 is active.
Table 4 - Under Voltage Fault (F4) Subcodes
SubcodeDescription
273The DC Bus voltage in the power unit is too low while the drive is in a run state.
529The DC Bus voltage in the power unit is too low while the drive is in a run state.
545The DC Bus voltage in power unit 1 is too low while the drive is in a run state.
561The DC Bus voltage in power unit 2 is too low while the drive is in a run state.
785The DC Bus voltage in the power unit fell too low during a fast stop.
Table 5 - Over Voltage Fault (F5) Subcodes
SubcodeDescription
273There is an over voltage in the power unit.
289There is an over voltage in power unit 1.
276There is an over voltage in power unit 2.
277There is an over voltage in the power unit.
Table 6 - Motor Stall Fault (F6) Subcode
SubcodeDescription
400The motor is operating at high current and low frequency and is not accelerating.
Table 7 - Heatsink Over Temperature Fault (F8) Subcodes
SubcodeDescription
272, 273There is a heatsink over temperature in the power unit.
274There is a heatsink over temperature on the Power board of the power unit.
275There is a heatsink over temperature in the U phase of the power unit (typically frame 11 and 13 drives).
276There is a heatsink over temperature in the V phase of the power unit (typically frame 11 and 13 drives).
277There is a heatsink over temperature in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289There is a heatsink over temperature in power unit 1 (typically frame 12 and 14 drives).
290There is a heatsink over temperature on the Power board of power unit 1 (typically frame 12 and 14 drives).
291There is a heatsink over temperature in the U phase of power unit 1 (typically frame 12 and 14 drives).
292There is a heatsink over temperature in the V phase of power unit 1 (typically frame 12 and 14 drives).
Rockwell Automation Publication 20C-PM001F-EN-P - March 201271
Chapter 3Troubleshooting
SubcodeDescription
293There is a heatsink over temperature in the W phase of power unit 1 (typically frame 12 and 14 drives).
304, 305There is a heatsink over temperature in power unit 2 (typically frame 12 and 14 drives).
306There is a heatsink over temperature on the Power board of power unit 2 (typically frame 12 and 14 drives).
307There is a heatsink over temperature in the U phase of power unit 2 (typically frame 12 and 14 drives).
308There is a heatsink over temperature in the V phase of power unit 2 (typically frame 12 and 14 drives).
309There is a heatsink over temperature in the W phase of power unit 2 (typically frame 12 and 14 drives).
530There is a Thermistor over temperature on the Power board (typically frame 12 and 14 drives).
Table 8 - IGBT Over Temperature Fault (F9) Subcode
SubcodeDescription
273The output transistors have exceeded their maximum operating temperature due to an excessive load.
Table 9 - System Fault (F10) Subcodes
SubcodeDescriptionAction
273There is an output phase feedback fault from the motor cables.
275There is an output phase feedback fault from the U phase motor cable (typically frame 11 and 13 drives).
276There is an output phase feedback fault from the V phase motor cable (typically frame 11 and 13 drives).
277There is an output phase feedback fault from the W phase motor cable (typically frame 11 and 13 drives).
1042There is a disturbance at the ASIC fault-input of the Power board - ribbon cable/software.
1058There is a disturbance at the ASIC fault-input of the Power board in power unit 1 - ribbon cable/software (typically frame 12 and 14 drives).
1074There is a disturbance at the ASIC fault-input of the Power board in power unit 2 - ribbon cable/software (typically frame 12 and 14 drives).
1090There is a disturbance at the ASIC fault-input of the Control board - application software.
1298There is too much disturbance in system bus traffic on the Power board.
1314There is too much disturbance in system bus traffic on the Power board in power unit 1 (typically frame 12 and 14 drives).
1330There is too much disturbance in system bus traffic on the Power board in power unit 2 (typically frame 12 and 14 drives).
1553The charging relay feedback is not working.
1810The charging relay control is not set on the Power board.
1826The charging relay control is not set on the Power board on power unit 1 (typically frame 12 and 14 drives).
1827The charging relay control is not set configured on the Power board on power unit 2 (typically frame 12 and 14 drives).
2065The Gate Driver board is without auxiliar y voltage (Power ASIC-TRIN).
2067The Gate Driver board for the U phase is without auxiliary voltage (typically frame 11 and 13 drives).
2068The Gate Driver board for the V phase is without auxiliary voltage (typically frame 11 and 13 drives).
2069The Gate Driver board for the W phase is without auxiliary voltage (typically frame 11 and 13 drives).
2080The Gate Driver board in power unit 1 is without auxiliary voltage. (typically frame 11 and 13 drives).
2081The Gate Driver board in power unit 1 is without auxiliary voltage (t ypically frame 12 and 14 drives).
2083The Gate Driver board for the U phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).
2084The Gate Driver board for the V phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).
2085The Gate Driver board for the W phase in power unit 1 is without auxiliary voltage (typically frame 14 drives).
2097The Gate Driver board in power unit 2 is without auxiliary voltage (t ypically frame 12 and 14 drives).
2099The Gate Driver board for the U phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).
2100The Gate Driver board for the V phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).
2101The Gate Driver board for the W phase in power unit 2 is without auxiliary voltage (typically frame 14 drives).
2370The TX fiber optic cable connected to H6 on the 700H Control board is broken.
2594The fiber optic cable connec ted to TRIP on the Star Coupler board for power unit 1 is broken (typically frame 12 and 14 drives).
2610The fiber optic cable connec ted to TRIP on the Star Coupler board for power unit 2 is broken (typically frame 12 and 14 drives).
2834The fiber optic cable connected to H5 on the ASIC board is broken.
7767The safe disable inputs on the 20C-DG1 option board have been in a different
state for more than 5 seconds.
8023A thermistor short circuit has been detected on the 20C-DG1 option board.• Verify the thermistor connections and correct if necessary.
8279The 20C-DG1 option board has been removed.Set parameter 359 [20C-DG1 Status] to 1"Remove" and then back to 0 "Ready".
8535There is an EEPROM error on the 20C-DG1 option board.Replace the 20C-DG1 option board.
8791A supply voltage hardware problem has been detected on the 20C-DG1 option
board.
• Verify all connections to the 20C-DG01 option board.
• If this fault and subcode occurs again, replace the 20C-DG1 option board.
• Verify that the jumper at X10 is in the correct position.
Replace the 20C-DG1 option board.
72Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
SubcodeDescriptionAction
9047A supply voltage hardware problem has been detected on the 20C-DG1 option
board.
9303A supply voltage hardware problem has been detected on the 20C-DG1 option
board.
9559A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
9815A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
10071A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
10327A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
10583A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
10839A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
11096A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
11351A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
11607A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
11863A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
12119The 20C-DG1 option board has been mounted in an incompatible Main Control
board that is not equipped with the Safe Disable function.
12376Parameter expander board, slot B, Therm Trip is set to OFF even if the jumper X12 is not cut.
Replace the 20C-DG1 option board.
Replace the 20C-DG1 option board.
Replace the 20C-DG1 option board.
If this fault occurs again, replace the Main Control board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the 20C-DG1 option board.
Replace the 20C-DG1 option board.
Replace the 20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
Replace the Main Control board.
TroubleshootingChapter 3
Table 10 - Over Current Fault (F12) Subcodes
SubcodeDescription
272, 273There is an over current in the power unit.
275There is an over current in the U phase of the power unit (typically frame 11 and 13 drives).
276There is an over current in the V phase of the power unit (typically frame 11 and 13 drives).
277There is an over current in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289There is an over current in power unit 1 (typically frame 12 drives).
291There is an over current in the U phase of power unit 1 (typically frame 14 drives).
292There is an over current in the V phase of power unit 1 (typically frame 14 drives).
293There is an over current in the W phase of power unit 1 (typically frame 14 drives).
304, 305There is an over current in power unit 2 (typically frame 12 drives).
307There is an over current in the U phase of power unit 2 (typically frame 14 drives).
308There is an over current in the V phase of power unit 2 (typically frame 14 drives).
309There is an over current in the W phase of power unit 2 (typically frame 14 drives).
Table 11 - Ground Fault (F13) Subcode
SubcodeDescription
273There is a ground fault in the power unit.
Table 12 - Load Loss Fault (F15) Subcode
SubcodeDescription
400The motor underload protection has tripped.
Table 13 - Input Phase Fault (F17) Subcodes
SubcodeDescription
273One input line phase in the power unit is missing.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201273
Chapter 3Troubleshooting
SubcodeDescription
289One input line phase in power unit 1 is missing.
305One input line phase in power unit 2 is missing.
529One input line phase in a regenerative power unit is missing.
322A microprocessor watchdog timeout has occurred on the Control board.
Table 17 - IGBT Temperature Hardware Fault (F31) Subcodes
SubcodeDescription
272, 273The output current has exceeded the instantaneous current limit in the power unit.
275The output c urrent has exceeded t he instantaneous current limit in the U phase of the power unit (typically
frame 11 and 13 drives).
276The output current has exceeded the instantaneous current limit in t he V phase of the power unit (typically
frame 11 and 13 drives).
277The output current has exceeded the instantaneous current limit in the W phase of the power unit
(typically frame 11 and 13 drives).
288, 289The output current has exceeded the instantaneous current limit in power unit 1 (typically frame 12 and 14
drives).
291The output current has exceeded the instantaneous current limit in the U phase of power unit 1 (typically
frame 14 drives).
292The output current has exceeded the instantaneous current limit in the V phase of power unit 1 (typically
frame 14 drives).
293The output current has exceeded the instantaneous current limit in the W phase of power unit 1 (typically
frame 14 drives).
304, 305The output current has exceeded the instantaneous current limit in power unit 2 (typically frame 12 and 14
drives).
307The output current has exceeded the instantaneous current limit in the U phase of power unit 2 (typically
frame 14 drives).
308The output current has exceeded the instantaneous current limit in the V phase of power unit 2 (typically
frame 14 drives).
309The output current has exceeded the instantaneous current limit in the W phase of power unit 2 (typically
frame 14 drives).
Table 18 - Fan Cooling Fault (F32) Subcodes
SubcodeDescription
273The fan(s) in the power unit does not work according to feedback information.
289The fans in power unit 1 does not work according to feedback information (typically frame 12 and 14
305The fans in power unit 2 does not work according to feedback information (typically frame 12 and 14
drives).
drives).
Table 19 - Communication Bus Fault (F34) Subcode
SubcodeDescription
338A sent message was not acknowledged.
74Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
TroubleshootingChapter 3
Table 20 - Heatsink Under Temperature Fault (F37) Subcodes
SubcodeDescription
272, 273There is a heatsink under temperature in the power unit.
275There is a heatsink under temperature in the U phase of the power unit (typically frame 11 and 13 drives).
276There is a heatsink under temperature in the V phase of the power unit (typically frame 11 and 13 drives).
277There is a heatsink under temperature in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289There is a heatsink under temperature in power unit 1 (typically frame 12 and 14 drives).
291There is a heatsink under temperature in the U phase of power unit 1 (typically frame 14 drives).
292There is a heatsink under temperature in the V phase of power unit 1 (typically frame 14 drives).
293There is a heatsink under temperature in the W phase of power unit 1 (typically frame 14 drives).
304, 305There is a heatsink under temperature in power unit 2 (typically frame 12 and 14 drives).
307There is a heatsink under temperature in the U phase of power unit 2 (typically frame 14 drives).
308There is a heatsink under temperature in the V phase of power unit 2 (typically frame 14 drives).
309There is a heatsink under temperature in the W phase of power unit 2 (typically frame 14 drives).
273The power unit has been changed, added, removed, has experienced a checksum error, or is new and the
274The Power board has been changed, added, removed, has experienced a checksum error, or is new and the
278The circuit board in Slot A of the control unit has been changed, added, removed, has experienced a
279The circuit board in Slot B of the control unit has been changed, added, removed, has experienced a
282The circuit board in Slot E of the control unit has been changed, added, removed, has experienced a
289A device or circuit board in power unit 1 has been changed, adde d, removed, has experienced a checksum
290The Power board in power unit 1 has been changed, added, removed, has experienced a checksum error, or
294The circuit board in Slot A of the control unit has been changed, added, removed, has experienced a
295The circuit board in Slot B of the control unit has been changed, added, removed, has experienced a
298The circuit board in Slot E of the control unit has been changed, added, removed, has experienced a
305A device or circuit board in power unit 2 has been changed, adde d, removed, has experienced a checksum
321A device or circuit board has been changed, added, removed, has experienced a checksum error, or is new
322The Control board has been changed, added, removed, has experienced a checksum error, or is ne w and the
326The circuit board in Slot A of the control unit has been changed, added, removed, has experienced a
327The circuit board in Slot B of the control unit has been changed, added, removed, has experienced a
330The circuit board in Slot E of the control unit has been changed, added, removed, has experienced a
369The Star Coupler board on the control unit has been changed, added, removed, has experienced a
parameters for the device/board remain unchanged.
parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
error, or is new and the parameters for the device/board remain unchanged (typically frame 12 and 14
drives).
is new and the parameters for the device/board remain unchanged (typically frame 12 and 14 drives).
checksum error, or is new and the parameters for the device/board remain unchanged (typically frame 12
and 14 drives).
checksum error, or is new and the parameters for the device/board remain unchanged (typically frame 12
and 14 drives).
checksum error, or is new and the parameters for the device/board remain unchanged (typically frame 12
and 14 drives).
error, or is new and the parameters for the device/board remain unchanged.
and the parameters for the device/board remain unch anged.
parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged.
checksum error, or is new and the parameters for the device/board remain unchanged (typically frame 12
and 14 drives).
Rockwell Automation Publication 20C-PM001F-EN-P - March 201275
Chapter 3Troubleshooting
SubcodeDescription
370The Star Coupler board has been changed, added, removed, has experienced a checksum error, or is new
and the parameters for the device/board remain unchanged (typically frame 12 and 14 drives).
528The power level in power unit 2 is not equal to the power level in power unit 1 after a microprocessor reset
(typically frame 12 and 14 drives).
561The power level in power unit 2 is not equal to the power level in power unit 1 after a microprocessor reset
(typically frame 12 and 14 drives).
Table 22 - NVS Read Checksum Fault (F47) Subcode
SubcodeDescription
322An operating time or energy counter checksum error has occurred on the Control board.
Table 23 - Motor Over Temperature Fault (F16) Subcode
SubcodeDescription
400The motor is operating at high current and low frequency and is not accelerating.
Table 24 - Power Unit Fault (F70) Subcodes
SubcodeDescription
272, 273There is saturation in the power unit.
275There is saturation in the U phase of the power unit (typically frame 11 and 13 drives).
276There is saturation in the V phase of the power unit (typically frame 11 and 13 drives).
277There is saturation in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289There is saturation in power unit 1 (typically frame 12 and 14 drives).
291There is saturation in the U phase of power unit 1 (typically frame 14 drives).
292There is saturation in the V phase of power unit 1 (typically frame 14 drives).
293There is saturation in the W phase of power unit 1 (typically frame 14 drives).
304, 305There is saturation in power unit 2 (typically frame 12 and 14 drives).
307There is saturation in the U phase of power unit 2 (typically frame 14 drives).
308There is saturation in the V phase of power unit 2 (typically frame 14 drives).
309There is saturation in the W phase of power unit 2 (typically frame 14 drives).
Table 25 - Hardware Enable Fault (F94) Subcode
SubcodeDescription
338An hardware enable signal is missing from the control terminal block.
322A firmware interface power down variable checksum error has occurred on the Control board.
578A firmware interface variable checksum error has occurred on the Control board.
834A system powerdown variable checksum error (panel menu index, fault history pointer) has occurred on
1090A system parameter checksum error (multimonitor, panel default pages) has occurred on the Control
1346An application defined powerdown, variable checksum error has occurred on the Control board.
1602An application defined powerdown, variable checksum error has occurred on the Control board.
2626A system parameter checksum error (fault history entries, device valid, system menu parameters) has
the Control board.
board.
occurred on the Control board.
Table 27 - Main Control Board - Power Board Configuration Fault (F106) Subcode
SubcodeDescription
385The software and the power unit are incompatible.
76Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
TroubleshootingChapter 3
Clear Alarms
Common Drive Symptoms
and Corrective Actions
Alarms are automatically cleared when the condition that caused the alarm is no
longer present.
Drive does not Start from Start or Run Inputs Wired to the Terminal
Block
Cause(s)IndicationCorrective Action
Drive is FaultedFlashing red status lightClear fault.
• Press Stop
• Cy cle p ower
)
Incorrect input wiring. See pages Installation
Manual for wiring examples.
• 2 wire contro l requires Run, Run Forward,
Run Reverse or Jog input.
• 3 wire control requires Start and Stop inputs.
• Jumper from terminal 17 to 20 is required
when using the 24V DC internal supply.
Incorrect digital input programming.
• Mutually exclusive choices have been made
(i.e., Jog and Jog Forward).
• 2 wire and 3 wire programming may be
conflicting.
• Exclusive functions (i.e, direction control)
may have multiple inputs configured.
• Stop is fac tory default and is not wired.
• Set [Fault Clear] to 1 (see page 42
• “Clear Faults” on the HIM Diagnostic
menu.
NoneWire inputs correctly and/or install
NoneProgram [Digital Inx Sel] for correct
Flashing yellow status light
and “DigIn CflctB”
indication on LCD HIM.
[Drive Status 2] shows type
2 alarm(s).
jumper.
inputs (see page 53
Start or Run programming may be
missing.
Program [Digital Inx Sel] to resolve
conflicts (see page 53).
Remove multiple selections for the same
function.
Install stop button to apply a signal at
stop terminal.
).
Drive does not Start from HIM
Cause(s)IndicationCorrective Action
Drive is programmed for 2 wire control. HIM
Start button is disabled for 2 wire control.
NoneI f 2 wire control is requ ired, no acti on
needed.
If 3 wire contro l is required, p rogram
[Digital Inx Sel] for correct inputs (see
).
page 53
Rockwell Automation Publication 20C-PM001F-EN-P - March 201277
Chapter 3Troubleshooting
Drive does not Respond to Changes in Speed Command
Cause(s)IndicationCorrective Action
No value is coming from the source of the
command.
Incorre ct reference s ource has been
programmed.
Incorrect reference source is being selected
via remote device or digital inputs.
LCD HIM Status Line
indicates “At Speed” and
output is 0 Hz.
None3. Check [Speed Ref Source] for the source of
None5. Check [Drive Status 1], (see page 38
1. If the source is an analog input, check
wiring and use a meter to check for
presence of signal.
2. Check [Commanded Speed] for correct
source (see page 20
the speed reference (see page 39
4. Reprogram [Speed Ref A Sel] for correct
source (see page 25).
12 and 13 for unexpected source selections.
6. Check [Dig In Status], (see page 40) to see if
inputs are selecting an alternate source.
7. Reprogram digital inputs to correct “Speed
Sel x” option (see page 53).
).
Motor and/or Drive will not Accelerate to Commanded Speed
Cause(s)IndicationCorrective Action
Acceleration time is excessive.NoneReprogram [Accel Time x] (see page30
Excess load or a short acceleration time
forces the drive into current limit, slow, or
no acceleration.
Speed command source or value is not as
expected.
Programming is preventing the drive output
from exceeding limiting values.
NoneCheck [Drive Status 2], bit 10 to see if the drive is in
NoneCheck for the proper Speed Command using the steps
NoneCheck [Maximum Speed] (see page 24
Current Limit (see page 38
Remove excess load or reprogram [Accel Time x] (see
page 30).
outlined in “Drive does not Respond to Changes in
Speed Command” above.
Freq] (see page 22) to assure that speed is not limited
by programming.
).
).
) and [Maximum
).
), bits
Motor Operation is Unstable
Cause(s)IndicationCorrective Action
Motor data was incorrectly entered or
Autotune was not performed.
None1. Correctly enter motor nameplate data.
2. Perform “Static” or “Rotate” Autotune procedure
(see page 23
3. Set gain parameters to default values.
Drive will not Reverse Motor Direction
Cause(s)IndicationCorrective Action
Digital input is not selected for reversing
control.
Digital input is incorrectly wired.NoneCheck input wiring.
Direction mode parameter is incorrectly
programmed.
Motor wiring is improperly phased for
reverse.
A bipolar analog speed command input is
incorrectly wired or signal is absent.
NoneCheck [Digital Inx Sel], (see page 53
input and program for reversing mode.
NoneReprogram [Direction Mode], (see page 35
“Bipolar” or digital “Unipolar” control.
NoneCheck for single phasing on the output of the drive.
None1. Use meter to check that an analog input voltage is
present.
2. Check wiring.
Positive vol tage commands forward direc tion. Negative
voltage commands reverse direc tion.
).
). Choose correct
) for analog
78Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Stopping the Drive Results in a Decel Inhibit Fault
Cause(s)IndicationCorrective Action
The bus regulation feature is enabled and
is halting deceleration due to excessive
bus voltage. Excess bus voltage is
normally due to excessive regenerated
energy or unstable AC line input voltages.
Internal timer has halted drive operation.
Decel Inhibit fault
screen.
LCD Status Line
indicates “Faulted”.
1. See Attention statement on page page 8
2. Reprogram parameters 161/162 to eliminate any
“Ad ju st Fre q” s el ec ti on.
3. Disable bus regulation (parameters 161 & 162) and
add a dynamic brake.
4. Correct AC input line instability or add an isolation
transformer.
5. Reset drive.
TroubleshootingChapter 3
.
Technical Support Options
Technical Support Wizards
If you are connected to a drive via DriveExplorer™ or DriveExecutive™, you can
run a Tech Support wizard to gather information that will help diagnose
problems with your drive and/or peripheral device. The information gathered by
the wizard is saved as a text file and can be emailed to your remote technical
support contact. (See W ha t You Ne ed Wh en Yo u C al l Te ch Su pp or t
for more information.)
To run a Tech Support wizard in DriveExplorer, select Wizards from the Actions
menu. In DriveExecutive, select Wizards from the To o l s menu. Or, click the
button. Follow the prompts to complete the wizard.
on page 80
Rockwell Automation Publication 20C-PM001F-EN-P - March 201279
Chapter 3Troubleshooting
What You Need When You Call Tech Support
When you contact Technical Support, please be prepared to provide the
following information:
• Order number
• Product catalog number and drives series number (if applicable)
• Product serial number
• Firmware revision level
• Most recent fault code
• Your application
The data contained in the following parameters will help in initial
troubleshooting of a faulted drive. You can use the table below to record the data
provided in each parameter listed.
Parameter(s) NameDescriptionParameter Data
224Fault FrequencyCaptures and displays the output speed of drive at time of last fault.
225Fault AmpsCaptures and displays motor amps at time of last fault.
226Fault Bus VoltsCaptures and displays the DC bus voltage of drive at time of last fault.
227Status 1 @ FaultCaptures and displays [Drive Status 1] bit pattern at time of last fault.
228Status 2 @ FaultCaptures and displays [Drive Status 2] bit pattern at time of last fault.
229Alarm 1 @ FaultCaptures and displays [Drive Alarm 1] bit pattern at time of last fault.
230Alarm 2 @ FaultCaptures and displays [Drive Alarm 2] bit pattern at time of last fault.
243Fault 1 CodeA code that represents the fault that tripped the drive.
245Fault 2 Code
247Fault 3 Code
249Fault 4 Code
251Fault 5 Code
253Fault 6 Code
255Fault 7 Code
257Fault 8 Code
244Fault 1 TimeTime stamp of the fault occurrence.
246Fault 2 Time
248Fault 3 Time
250Fault 4 Time
252Fault 5 Time
254Fault 6 Time
256Fault 7 Time
258Fault 8 Time
543Fault 1 SubcodeThe subcode for the corresponding fault identified in [Fault x Code]
545Fault 2 Subcode
547Fault 3 Subcode
549Fault 4 Subcode
551Fault 5 Subcode
553Fault 6 Subcode
555Fault 7 Subcode
557Fault 8 Subcode
262…269Alarm Code 1-8A code that represents a drive alarm. No time stamp available.
80Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
HIM Overview
For Information on…See page…
External and Internal ConnectionsBelow
LCD Di spla y Ele ment s82
ALT Func tions82
Menu Structure83
View and Edit Parameters85
Remove and Install the HIM86
Appendix A
External and Internal
Connections
The PowerFlex 700H drive provides the following cable connection points:
1
X2
X1
To Drive Control
(DPI Interface Board)
2
No. ConnectorDescription
1DPI Port 1HIM connection when installed in drive.
2DPI Port 2Cable connection for handheld and remote options.
3DPI Port 3 or 2Splitter cable connected to DPI Port 2 provides additional port.
4DPI Port 4Not available.
5DPI Port 5Cable connection for communications adapter.
The HIM panel opens to allow access to the DPI interface. To open the panel,
3
remove the screws on left side of the HIM panel and swing the panel open.
5
Rockwell Automation Publication 20C-PM001F-EN-P - March 201281
Appendix AHIM Overview
LCD Display Elements
ALT Functions
DisplayDescription
F-> Power LossAuto
Hz
0.0
Main Menu:
Diagnostics
Parameter
Device Select
Direction⎥ Drive Status⎥ Alarm⎥ Auto/Man⎥ Information
Commanded or Output Frequency
Programming / Monitoring / Troubleshooting
To use an ALT function, press the ALT key, release it, then press the
programming key associated with one of the following functions:
Table 28 - ALT Key Functions
ALT Key and then …Performs this function …
S.M.A.R.T.Displays the S.M.A.R.T. screen.
Esc
ViewAllows the se lection of how parameters will be viewed or
Sel
LangDisplays the language selection screen.
Auto / ManSwitches between Auto and Manual Modes.
detailed information about a parameter or component.
ALT
RemoveAllows HIM removal without causing a fault if the HIM is not
ExpAllows value to be entered as an exponent.
..
Param #Allows entr y of a parameter number for viewing/editing.
+/–
the last controlling device and does not have Manual control
of the drive.
(Not available on PowerFlex 700.)
82Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
HIM OverviewAppendix A
Menu Structure
Figure 2 - HIM Menu Structure
Diagnostics
Parameter
Device Select
Alarms
Faults
Status Info
Device Items
Device Version
HIM Version
View selected through
Param Access Lvl
File-Group-Par
Numbered List
Changed Params
PowerFlex 700H
Connected DPI Devices
User
Display
Esc Sel
View Alarm Queue
Clr Alarm Queue
PowerFlex 700H
Product Data
Control Board
Power Board Slot A-E
LCD HIM Product Data
LCD HIM Control Board
Keyboard – Numeric
ALT
FGP: File
File 1 Name
File 2 Name
File 3 Name
Sel
Drive Status 1
Drive Status 2
Drive Alarm 1
Drive Alarm 2
Speed Ref Source
Start Inhibits
Last Stop Source
Dig In Status
Dig Out Status
Drive Temp
Motor OL Count
FGP: Parameter
Parameter Name
Parameter Name
Parameter Name
Value Screen
Memory Storage
Start-Up
Preferences
Him CopyCat
Device User Sets
Reset To Defaults
Continue
Start Over
Only available if power
cycled during startup
Device Identity
Change Password
User Dspy Lines
User Dspy Time
User Dspy Video
Reset User Dspy
Contrast
Drive User Set:
Save To User Set
Device <- HIM
Delete HIM Set
Load Frm Usr Set
Active Name Set
Device -> HIM
Introduction
Complete Steps:
1. Input Voltage
2. Motor Dat/Ramp
3. Motor Tests
4. Speed Limits
5. Speed Control
6. Strt/Stop/I/O
7. Done/Exit
Press
Press
Press
Pressto select how to view parameters
ALT
to move between menu items
to select a menu item
Esc
to move 1 level back in the menu structure
Sel
Make a selection:
Abort
Esc
Backup
Resume
Start-Up Menu
Rockwell Automation Publication 20C-PM001F-EN-P - March 201283
Appendix AHIM Overview
Diagnostics Menu
When a fault trips the drive, use this menu to access detailed data about the drive:
OptionDescription
FaultsView fault queue or fault information, clear faults or reset drive.
Status InfoView parameters that display status information about the drive.
Device VersionView the firmware revision and hardware series of components.
HIM VersionView the firmware revision and hardware series of the HIM.
Parameter Menu
See View and Edit Parameters on page 85.
Device Select Menu
Use this menu to access parameters in connected peripheral devices.
Memory Storage Menu
Drive data can be saved to, or recalled from, User and HIM sets.
Use r set s are files stored in permanent nonvolatile drive memory.
HIM sets are files stored in permanent nonvolatile HIM memory.
OptionDescription
HIM Copycat
Device -> HIM
Device <- HIM
Device User SetsSave data to a User set, load data from a User set to active drive
Reset To DefaultsRestore the drive to its factory-default settings.
Save data to a HIM set, load data from a HIM set to active drive memory
or delete a HIM set.
memory or name a User set.
Start Up Menu
See Chapter 1.
Preferences Menu
The HIM and drive have features that you can customize.
OptionDescription
Drive IdentityAdd text to identify the drive.
Change PasswordEnable/disable or modify the password.
User Dspy LinesSelect the display, parameter, scale and text for the user display. The user display is two lines
User Dspy TimeSet the wait time for the user display or enable/disable it.
User Dspy VideoSelect Reverse or Normal video for the Frequency and user display lines.
Reset User DspyReturn all the options for the user display to factory default values.
of user-defined data that appears when the HIM is not being used for programming.
84Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
HIM OverviewAppendix A
The PowerFlex 700H drive is initially set to Basic Parameter View. To view all
parameters, set parameter 196 [Param Access Lvl] to option 1 “Advanced”.
View and Edit Parameters
LCD HIM
To view and edit a parameter using the LCD HIM, follow these instructions:
StepKey(s)Example Displays
1. In the Main Menu, press the Up Arrow or Down
Arrow to scroll to “Parameter.”
2. Press Enter.
“FGP: File” displays on the top line and the first
three files display below it.
3. Press the Up Arrow or Down Arrow to scroll
through the files.
4. Press Enter to select a file.
The groups display below the File name.
5. Repeat steps 3 and 4 to select a group and then a
parameter.
The parameter value screen displays.
6. Press Enter to edit the selected parameter.
or
FGP: File
Monitor
Motor Control
Speed Reference
or
FGP: Group
Motor Data
Torq Attributes
Vol t s pe r Hertz
FGP: Parameter
Maximum Voltage
Maximum Freq
Compensation
7. Press the Up Arrow or Down Arrow to change the
value. If desired, press Sel to move from digit to
digit, letter to letter, or bit to bit. The digit or bit
that you can change will be highlighted.
8. Press Enter to save the value. If you want to cancel
a change, press Esc.
9. Press the Up Arrow or Down Arrow to scroll
through the parameters in the group, or press Esc
to return to the group list.
or
Sel
or
Esc
FGP:Par 55
Maximum Freq
60.00 Hz
25 <> 400.00
FGP:
Maximum Freq
90.00
Hz
25 <> 400.00
Par 55
Numeric Keypad Shortcut
If using a HIM with a numeric keypad, press the ALT key and the +/– key to
access the parameter by typing its number.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201285
Appendix AHIM Overview
Remove and Install the HIM
The HIM can be removed or installed while the drive is powered.
IMPORTANT
HIM removal is only permissible in Auto mode. If the HIM is removed while in
Manual mode or the HIM is the only remaining control device, a fault will occur.
StepKey(s)Example Displays
To remove the HIM . . .
1. Press ALT and then Enter (Remove). The Remove
HIM confirmation screen appears.
2. Press Enter to confirm that you want to remove
the HIM.
3. Remove the HIM from the drive.
To install HIM . . .
1. Insert into drive or connect cable.
ALT
+
- Remove HIM Do you wish to
continue?
Press Enter
86Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Appendix B
Application Notes
For Information on…See page…For Information on…See page…
External Brake ResistorBelowProcess PI93
Minimum SpeedBelowReverse Speed Limit96
Motor Control Technology 88Skip Frequency97
Motor Overload89Sleep Wake Mode99
Overspeed91Start At Power Up101
Power Loss Ride Th rough91Stop Modes101
External Brake Resistor
Figure 3 - External Brake Resistor Circuitry
Three-Phase
AC Input
(Input Contactor) M
Power Off
Power SourceDB Resistor Thermostat
R (L1)
S (L2)
T (L3)
Power On
M
M
Minimum Speed
See Reverse Speed Limit on page 96
Rockwell Automation Publication 20C-PM001F-EN-P - March 201287
Appendix BApplication Notes
Motor Control Technology
Within the PowerFlex family there are several motor control technologies:
• To r q u e P r o du ce rs
• Torque Controllers
• Speed Regulators
Torque Producers
Volts /Her tz
This technology follows a specific pattern of voltage and frequency output to the
motor, regardless of the motor being used. The shape of the V/Hz curve can be
controlled a limited amount, but once the shape is determined, the drive output
is fixed to those values. Given the fixed values, each motor will react based on its
own speed/torque characteristics.
This technology is good for basic centrifugal fan/pump operation and for most
multi-motor applications. Torque production is generally good.
Sensorless Vector
This technology combines the basic Volts/Hertz concept with known motor
parameters such as Rated FLA, HP, Voltage, stator resistance and flux producing
current. Knowledge of the individual motor attached to the drive allows the drive
to adjust the output pattern to the motor and load conditions. By identifying
motor parameters, the drive can maximize the torque produced in the motor and
extend the speed range at which that torque can be produced.
This technology is excellent for applications that require a wider speed range and
applications that need maximum possible torque for breakaway, acceleration or
overload. Centrifuges, extruders, conveyors and others are candidates.
Speed Regulators
Any of the PowerFlex drives, regardless of their motor control technology (Volts/
Hz, Sensorless Vector or Vector) can be set up to regulate speed. Speed regulation
and torque regulation must be separated to understand drive operation.
The PowerFlex 70/700 with Standard Control and the PowerFlex 700H can be
programmed to regulate speed using the slip compensation feature. Slip
compensation reacts to load changes by adjusting the drive output frequency to
maintain motor speed
produces speed regulation of about 0.5% of base speed over a specified speed
range (40:1 for V/Hz and 80:1 for Sensorless Vector). These drives do not have
the capability to extend the speed range or tighten the speed regulation below
0.5% because they do not have connections for a feedback device.
. Torque production operates independently. This feature
88Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Application NotesAppendix B
Motor Overload
For single motor applications the drive can be programmed to protect the motor
2
from overload conditions. An electronic thermal overload I
a thermal overload relay. This operation is based on three parameters; [Motor NP
FLA], [Motor OL Factor] and [Motor OL Hertz] (parameters 042, 048 and 047,
respectively).
[Motor NP FLA] is multiplied by [Motor OL Factor] to allow the user to define
the continuous level of current allowed by the motor thermal overload. [Motor
OL Hertz] is used to allow the user to adjust the frequency below which the
motor overload is derated.
The motor can operate up to 102% of FLA continuously. If the drive had just
been activated, it will run at 150% of FLA for 180 seconds. If the motor had been
operating at 100% for over 30 minutes, the drive will run at 150% of FLA for 60
seconds. These values assume the drive is operating above [Motor OL Hertz],
and that [Motor OL Factor] is set to 1.00.
Operation below 100% current causes the temperature calculation to account for
motor cooling.
T function emulates
Motor Overload Curve
100000
Cold
Hot
10000
1000
Trip Time (Sec)
100
10
100125150175200225250
Full Load Amps (%)
[Motor OL Hertz] defines the frequency where motor overload capacity derate
should begin. The motor overload capacity is reduced when operating below
Rockwell Automation Publication 20C-PM001F-EN-P - March 201289
Appendix BApplication Notes
[Motor OL Hertz]. For all settings of [Motor OL Hertz] other than zero, the
overload capacity is reduced to 70% at an output frequency of zero.
120
Changing Overload Hz
OL Hz = 10
100
80
OL Hz = 25
OL Hz = 50
60
40
Continuous Rating
20
0
0102030405060708090100
% of Base Speed
[Motor NP FLA] is multiplied by [Motor OL Factor] to select the rated current
for the motor thermal overload. This can be used to raise or lower the level of
current that will cause the motor thermal overload to trip. The effective overload
factor is a combination of [Motor OL Hertz] and [Motor OL Factor].
Changing Overload Factor
140
OL % = 1.20
120
100
OL % = 1.00
OL % = 0.80
80
60
40
Continuous Rating
20
0
0102030405060708090100
% of Base Speed
Note: This graph represents a motor with a speed range of 2:1.
90Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Application NotesAppendix B
Overspeed
Overspeed Limit is a user programmable value that allows operation at maximum
speed, but also provides an “overspeed band” that will allow a speed regulator
such as slip compensation to increase the output frequency above maximum
speed in order to maintain maximum motor speed.
The figure below illustrates a typical Custom V/Hz profile. Minimum Speed is
entered in Hertz and determines the lower speed reference limit during normal
operation. Maximum Speed is entered in Hertz and determines the upper speed
reference limit. The two “Speed” parameters only limit the speed reference and
not the output frequency.
The actual output frequency at maximum speed reference is the sum of the speed
reference plus “speed adder” components from functions such as slip
compensation.
The Overspeed Limit is entered in Hertz and added to Maximum Speed and the
sum of the two (Speed Limit) limit the output frequency. This sum (Speed
Limit) must is compared to Maximum Frequency and an alarm is initiated which
prevents operation if the Speed Limit exceeds Maximum Frequency.
Allowable Output Frequency Range
Bus Regulation or Current Limit
Allowable Output Frequency Range
Normal Operation
Allowable Reference Frequency Range
Motor Volts
Voltage
Break Volts
Start Boost
Frequency Trim due to
Speed Control Mode
Overspeed
Limit
Power Loss Ride Through
0Min
Speed
Break
Frequency
Motor
Hz
Frequency
Max
Speed
Output
Freq Limit
Max
Freq
When AC input power is lost, energy is being supplied to the motor from the
DC bus capacitors. The energy from the capacitors is not being replaced (via the
AC line), thus, the DC bus voltage will fall rapidly. The drive must detect this fall
and react according to the way it is programmed.
There are three possible methods of dealing with low bus voltages:
1. “Coast” – Disable the transistors and allow the motor to coast.
2. “Decel” – Decelerate the motor at just the correct rate so that the energy
absorbed from the mechanical load balances the losses.
3. “Continue” – Allow the drive to power the motor down to the
undervoltage trip level.
Two parameters display DC bus voltage:
Rockwell Automation Publication 20C-PM001F-EN-P - March 201291
Appendix BApplication Notes
• [DC Bus Voltage] – displays the instantaneous value.
• [DC Bus Memory] – displays an estimate of the full-load DC bus voltage.
All drive reactions to power loss are based on either a fixed percentage of [DC
Bus Memory], a fixed DC bus voltage, or a user-programmable DC bus voltage.
The selected power loss mode determines which trigger levels are available, and
the choice of voltage levels is made by “toggling” a digital input programmed to
“Pwr Loss Lvl.”
If “Continue” is selected, the drive will ignore a loss of DC bus voltage and
continue to run the motor until the drive trips on an Undervoltage Fault (F004).
If “Decel” is selected, there is a choice of two levels for recognizing a power loss. If
a digital input is programmed for “Pwr Loss Lvl” but is not energized, or no input
is programmed, the drive will recognize a power loss at 80% of [DC Bus
Memory]. If a digital input is programmed for “Pwr Loss Lvl” and the input is
energized, a power loss will be recognized at the value of [Power Loss Volts].
If “Coast” is selected, there is a choice of two levels for recognizing a power loss. If
a digital input is programmed for “Pwr Loss Lvl” but is not energized, or no input
is programmed, the drive will recognize a power loss at 73% of [DC Bus
Memory]. If a digital input is programmed for “Power Loss Lvl” and the input is
energized, a power loss will be recognized at the value of [Power Loss Volts].
Figure 4 - Power Loss Mode = Coast
Bus Voltage
Motor Speed
Power Loss
Output Enable
Figure 5 - Power Loss Mode = Decel
Bus Voltage
Motor Speed
Nominal
73%
Nominal
80%
Power Loss
Output Enable
92Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Application NotesAppendix B
Process PI
*(PI Ref Sel)
*(PI Fbk Sel)
PI_Status
.Enabled
Spd Ref
PI_Config
.Torq Trim
A
Vector Control Option
(currently not available for
PowerFlex 700H drives)
The internal PI function of the PowerFlex 700H provides closed loop process
control with proportional and integral control action. The function is designed
for use in applications that require simple control of a process without external
control devices. The PI function allows the microprocessor of the drive to follow
a single process control loop.
PI Kp
*
+
+
PI_Status
.Enabled
PI Neg Limit
PI Pos Limit
+
+
-1
z
to A (below)
PI Output
In Limit
PI Ref
0
PI_Config
.Sqrt
PI_Config
.SpdReg
PI_Config
.RampCmd
&
Linear
Ramp
PI_Status
.Enabled
Linear Ramp
& S-Curve
Torq Ref A
Torq Ref B
PI Cmd
PI Fbk
Spd Ramp
0
+
+
PI ExcessErr
PI Error
Spd Cmd
0
0
0
0
PI XS Error
PI Ki
PI_Config
.Exclusive
Preload Value
Spd Cmd
PI_Config
.PreloadCmd
Spd Cmd
Zclamped
Torq Cmd
*
PI_Status
.Hold
Current Limit
or Volt Limit
abs
-
+
-
PI_Config
.Invert
PI_Config
.ZeroClamp
+
+
+
+
0
+32K
-32K
+32K
-32K
+800
-800
+800
-800
The PI function reads a process variable input to the drive and compares it to a
desired setpoint stored in the drive. The algorithm will then adjust the output of
the PI regulator, changing drive output frequency to try and make the process
variable equal the setpoint.
It can operate as trim mode by summing the PI loop output with a master speed
reference.
Or, it can operate as control mode by supplying the entire speed reference. This
method is identified as “exclusive mode”
Rockwell Automation Publication 20C-PM001F-EN-P - March 201293
Appendix BApplication Notes
Slip Adder
Spd Ref
PI Ref
PI Fbk
Slip Adder
Spd Ref
PI Ref
PI Fbk
Process PI
Controller
Process PI
Controller
PI Enabled
PI Enabled
Linear Ramp
& S-Curve
Linear Ramp
& S-Curve
+
+
+
+
+
+
Slip
Comp
Open
Loop
Process
PI
Speed Control
Slip
Comp
Open
Loop
Process
PI
Speed Control
Spd Cmd
Spd Cmd
Drive
Running
PI Enable
The output of the PI loop can be turned on (enabled) or turned off (disabled).
This control allows the user to determine when the PI loop is providing part or
all of the commanded speed. The logic for enabling the PI loop is shown below.
Drive
Ramping
to Stop
Bit 0Bit 6
[PI Configuration]
Drive
Jogging
A Digital Input
is Configured
to PI Enable
The drive must be running for the PI loop to be enabled. The loop will be
disabled when the drive is ramping to a stop (unless “Stop Mode” is configured in
[PI Configuration]), jogging or the signal loss protection for the analog input(s)
is sensing a loss of signal.
If a digital input has been configured to “PI Enable,” two events are required to
enable the loop: the digital input must be closed AND bit 0 of the PI Control
parameter must be = 1.
Bit 0 of
[PI Control] = 1
(enabled)
The Configured
Signal Loss
Digital Input
is Closed
The PI Loop
is Enabled
"Enabled" Status
Digital Input
is Reflected
in [PI Status]
Bit 0 = 1
94Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Application NotesAppendix B
If no digital input is configured to “PI Enable,” then only the Bit 0 = 1 condition
must be met. If the bit is permanently set to a “1”, then the loop will become
enabled as soon as the drive goes into “run”.
PI Pre-load Value
PI Pre-load Value = 0PI Pre-load Value > 0
PI Enabled
Start at Spd Cmd
PI Output
Spd Cmd
Pre-load to Command Speed
100.0
75.0
50.0
25.0
0.0
-25.0
-50.0
-75.0
Normalized SQRT(Feedback)
-100.0
-100.0-75.0-50.0-25.00.025.050.075.0100.0
Normalized Feedback
Rockwell Automation Publication 20C-PM001F-EN-P - March 201295
Appendix BApplication Notes
Reverse Speed Limit
Figure 6 - [Rev Speed Limit], parameter 454 set to zero
10V
[Maximum
Speed]
Reverse
Speed
[Maximum
Reverse
Speed
Speed]
Minimum
Speed 0
–10V
10V
Minimum
Speed 0
Minimum
Speed = 0
[Maximum
Speed]
[Maximum
Speed]
Forward
Speed
Forward
Speed
–10V
Figure 7 - [Rev Speed Limit], parameter 454 set to a non-zero Value
10V
Note: Minimum speed is not used when
Reverse Speed Limit is set to a non-zero
value.
Reverse
Speed
Reverse
Speed
Limit
Forward
Speed
Maximum
Speed
–10V
96Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Application NotesAppendix B
Skip Frequency
Figure 8 - Skip Frequency
Frequency
Skip + 1/2 Band
Skip Frequency
Skip – 1/2 Band
Command
Frequency
Drive Output
Frequency
Time
(A)
(B)
(A)
35 Hz
30 Hz
25 Hz
(B)
Some machinery may have a resonant operating frequency that must be avoided
to minimize the risk of equipment damage. To assure that the motor cannot
continuously operate at one or more of the points, skip frequencies are used.
Parameters 084 [Skip Frequency 1] … 086, [Skip Frequency 3] are available to set
the frequencies to be avoided.
The value programmed into the skip frequency parameters sets the center point
for an entire “skip band” of frequencies. The width of the band (range of
frequency around the center point) is determined by parameter 87, [Skip Freq
Band]. The range is split, half above and half below the skip frequency parameter.
If the commanded frequency of the drive is greater than or equal to the skip
(center) frequency and less than or equal to the high value of the band (skip plus
1/2 band), the drive will set the output frequency to the high value of the band.
See (A) in Figure 8
.
If the commanded frequency is less than the skip (center) frequency and greater
than or equal to the low value of the band (skip minus 1/2 band), the drive will
set the output frequency to the low value of the band. See (B) in Figure 8
.
Acceleration and deceleration are not affected by the skip frequencies. Normal
accel/decel will proceed through the band once the commanded frequency is
greater than the skip frequency. See (A) & (B) in Figure 8
. This function affects
only continuous operation within the band.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201297
Appendix BApplication Notes
Skip Frequency Examples
The skip frequency will have hysteresis
so the output does not toggle between
high and low values. Three distinct
bands can be programmed. If none of
the skip bands touch or overlap, each
band has its own high/low limit.
Max. Frequency
Skip Frequency 1
Skip Band 1
If skip bands overlap or touch, the
center frequency is recalculated based
on the highest and lowest band values.
If a skip band(s) extend beyond the max
frequency limits, the highest band
value will be clamped at the max
frequency limit. The center frequency is
recalculated based on the highest and
lowest band values.
If the band is outside the limits, the skip
band is inactive.
Skip Frequency 2
0 Hz
320 Hz.
Skip Frequency 1
Skip Frequency 2
0 Hz
320 Hz.
Max.Frequency
Skip
0 Hz
320 Hz.
Skip Band 2
Adjusted
Skip Band
w/Recalculated
Skip Frequency
Adjusted
Skip Band
w/Recalculated
Skip Frequency
Skip Frequency 1
60 Hz. Max.
Frequency
0 Hz
98Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Inactive
Skip Band
Application NotesAppendix B
Sleep Wake Mode
This function stops (sleep) and starts (wake) the drive based on separately
configurable analog input levels rather than discrete start and stop signals. by
default, this function is disabled. The following Sleep/Wake modes are available:
• 1 “Direct” - In this mode, the drive will start (wake) when the analog input
signal is greater than or equal to the value set in [Wake Level] and the drive
will stop (sleep) when the analog input signal is less than or equal to the
value in [Sleep Level].
• 2 “Invert” - In this mode, the analog input signal used by the [Wake Level]
and [Sleep Level] parameters is inverted. In this mode, the drive will start
(wake) when the analog input signal is less than or equal to the value set in
[Wake Level] and the drive will stop (sleep) when the analog input signal is
greater than or equal to the value in [Sleep Level].
Definitions:
• Wake - A start command generated when the analog input value remains
above [Wake Level] for a time greater than [Wake Time].
• Sleep - A Stop command generated when the analog input value remains
below [Sleep Level] for a time greater than [Sleep Time].
• Speed Reference – The active speed command to the drive as selected by
drive logic and [Speed Ref x Sel].
• Start Command - A command generated by pressing the Start button on
the HIM, closing a digital input programmed for Start, Run, Run Forward
or Run Reverse.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201299
Appendix BApplication Notes
Is Sleep-Wake
Working?
No
Have these conditions been met?
1. [Sleep-Wake Ref] must be set to the analog input that will control
"Start/Stop" functions.
2. [Sleep-Wake Mode] must = "1, Direct" (Enable) or "2, Invert (Enable)."
3. [Sleep Level] must be less than [Wake Level] in Direct mode (or
greater than [Wake Level] in "Invert" mode).
4. [Speed Ref x Sel] must be set to a speed reference source that will
control the drive. If [Sleep-Wake Ref] = [Speed Ref x Sel], the same
analog signal will control start/stop and speed reference.
5. At least one of the following must be programmed for [Digital Inx Sel]:
"Stop," "Enable," "Start," "Run," "Run Forward," "Run Reverse."
Ye s
No
Meet all Conditions!
Decrease Analog Input
Signal and wait for a time
period greater than or
equal to [Wake Time].
Reset Fault
Run, Run Forward
or Run Reverse
Open & Close Input
No
Is Analog Signal Less
than or equal to [Wake Level]?
and for time period greater than
or equal to [Wake Time]
Ye sYe s
Ye s
Did a Drive
Fault Occur?
No
Is Required Input Closed?
No
(Stop, Enable, Run)
Ye s
Which Mode is Selected?
DirectInvert
"Invert" or "Direct"
Is Analog Signal Greater
than or equal to [Wake Level]?
and for time period greater than
or equal to [Wake Time]
Was a Stop Issued?
Which Required Input
was Chosen?
or
Power Cycled?
Ye s
Issue a Start Command
(HIM, Network or TB)
Close Input
No
No
Stop or Enable
Increase Analog Input
Signal and wait for a time
period greater than or
equal to [Wake Time].
Consult Factory
Drive Running?
No
100Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Consult Factory
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.