Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Allen-Bradley, DriveExplorer, DriveExecutive, DPI, SCANPort, PowerFlex, Rockwell Software, Ro ckwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
Updated the description for parameter 465 [Fan Control] to indicate that the
default value has been changed to 1 “Enabled.”
Updated parameter 212 [Drive Alarm 2] to include new bit 8 “Fan Cooling.”39
Updated parameter 238 [Fault Config 1] to include new bit 14 “Fan Cooling.”42
Added a note to the description for the “IGBT OverTemp” fault (F9) to specify that
the “IGBT Overtemp” fault is equivalent to the Drive Overload (Software), and is
not adjustable.
Added a note to the “System Fault” (F10) to specify that the fault subcodes are
only available in revision 4.001 or later.
Update the description for the “OverCurrent” fault (F12) to specify that the drive
output current has instantaneously exceeded 360% of the HD rating.
Added a note to the description for the “IGBT Temp HW” fault (F31) to specify
that the “IGBT Temp HW” fault is equivalent to the Drive Instantaneous Overload
(Hardware), and is not adjustable.
Updated the description for the “Fan Cooling” fault (F32) to include information
on configuring a “Fan Cooling” alarm.
32
64
65
65
66
66
Rockwell Automation Publication 20C-PM001F-EN-P - March 20123
Summary of Changes
Notes:
4Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
6Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Preface
The purpose of this manual is to provide you with the basic information needed
to start-up, program and troubleshoot the PowerFlex 700H adjustable frequency
AC drive.
For information on…See page…
Who Should Use this ManualBelow
What Is Not in this ManualBelow
Additional Resources8
General Precautions8
Who Should Use this Manual
What Is Not in this Manual
This manual is intended for qualified personnel. You must be able to program
and operate Adjustable Frequency AC drives and related devices. In addition, you
must have an understanding of the parameter settings and functions.
The PowerFlex 700H Programming Manual does not provide installation
instructions or maintenance and repair information.
For installation information, refer to:
• PowerFlex 700S/700H Adjustable Frequency AC Drives, Frames 9…14
Installation Instructions, publication PFLEX-IN006
• PowerFlex 700S/700H IP00 Open Power Structure, Frames 10…14
Installation Instructions, publication PFLEX-IN020
For maintenance and repair information, refer to:
• PowerFlex 700H and 700S Hardware Service Manual, Frame 9, PFLEX-
TG001
• PowerFlex 700H and 700S Hardware Service Manual, Frame 10, PFLEX-
TG002
• PowerFlex 700H and 700S Hardware Service Manual, Frame 11, PFLEX-
TG003
• PowerFlex 700H and 700S Hardware Service Manual, Frame 12, PFLEX-
TG004
• PowerFlex 700H and 700S Hardware Service Manual, Frame 13, PFLEX-
TG005
• PowerFlex 700H and 700S Hardware Service Manual, Frame 14, PFLEX-
TG006
.
.
For detailed drive application information refer to:
Rockwell Automation Publication 20C-PM001F-EN-P - March 20127
.
Preface
Additional Resources
General Precautions
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Preventive Maintenance of Industrial Control and Drive
System Equipment, publication DRIVES-TD001
Safety Guidelines for the Application, Installation and
Maintenance of Solid State Control, publication SGI-1.1
A Global Reference Guide for Reading Schematic Diagrams,
publication 100-2.10
Product Certifications website, http://www.ab.comProvides declarations of conformity, certificates, and
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides a checklist that can be used as a guide in
performing preventive maintenance of industrial
control and drive system equipment.
Provides general guidelines for the application,
installation, and maintenance of solid-state control.
wiring diagram symbols used throughout various parts
of the world.
other certification details.
You can view or download publications at
http:/www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
7
ATTENTION: This drive contains ESD (Electrostatic Discharge) sensitive parts and
assemblies. Static control precautions are required when installing, testing,
servicing or repairing this assembly. Component damage may result if ESD
control procedures are not followed. If you are not familiar with static control
procedures, reference A-B publication 8000-4.5.2, “Guarding Against
Electrostatic Damage” or any other applicable ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can result in component
damage or a reduction in product life. Wiring or application errors, such as,
undersizing the motor, incorrect or inadequate AC supply, or excessive ambient
temperatures may result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable frequency AC
drives and associated machinery should plan or implement the installation,
start-up and subsequent maintenance of the system. Failure to comply may
result in personal injury and/or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the voltage on the bus
capacitors has discharged completely before servicing. Check the DC bus voltage
at the Power Terminal Block by measuring between the +DC and -DC terminals,
between the +DC terminal and the chassis, and between the -DC terminal and
the chassis. The voltage must be zero for all three measurements.
ATTENTION: Risk of injury or equipment damage exists. DPI host products must
not be directly connected together via 1202 cables. Unpredictable behavior can
result if two or more devices are connected in this manner.
8Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Preface
ATTENTION: The sheet metal cover and mounting screws on the ASIC Board
located on the power structure are energized at (-) DC bus potential high
voltage. Risk of electrical shock, injury, or death exists if someone comes in
contact with the assembly.
ATTENTION: The “adjust freq” portion of the bus regulator function is extremely
useful for preventing nuisance overvoltage faults resulting from aggressive
decelerations, overhauling loads, and eccentric loads. It forces the output
frequency to be greater than commanded frequency while the drive's bus
voltage is increasing towards levels that would otherwise cause a fault.
However, it can also cause either of the following two conditions to occur.
• Fast positive changes in input voltage (more than a 10% increase within 6
minutes) can cause uncommanded positive speed changes. However an
“OverSpeed Limit” fault will occur if the speed reaches [Max Speed] +
[Overspeed Limit]. If this condition is unacceptable, action should be taken to 1)
limit supply voltages within the specification of the drive and, 2) limit fast
positive input voltage changes to less than 10%. Without taking such actions, if
this operation is unacceptable, the “adjust freq” portion of the bus regulator
function must be disabled (see parameters 161 and 162).
• Actual deceleration times can be longer than commanded deceleration times.
However, a “Decel Inhibit” fault is generated if the drive stops decelerating
altogether. If this condition is unacceptable, the “adjust freq” portion of the bus
regulator must be disabled (see parameters 161 and 162). In addition, installing
a properly sized dynamic brake resistor will provide equal or better performance
in most cases.
Important: These faults are not instantaneous. Test results have shown that they
can take between 2…12 seconds to occur.
Rockwell Automation Publication 20C-PM001F-EN-P - March 20129
Preface
Notes:
10Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 1
Drive Start-Up
This chapter describes how you start up the PowerFlex 700H drive. Refer to
Appendix
For Information on…See page…
Prepare For Drive Start-UpBelow
Start-Up the Drive12
A for a brief description of the LCD Human Interface Module (HIM).
ATTENTION: Power must be applied to the drive to perform the following startup procedure. Some of the voltages present are at incoming line potential. To
avoid electric shock hazard or damage to equipment, only qualified service
personnel should perform the following procedure. Thoroughly read and
understand the procedure before beginning. If an event does not occur while
performing this procedure, Do Not Proceed. Remove Power including user
supplied control voltages. User supplied voltages may exist even when main AC
power is not applied to then drive. Correct the malfunction before continuing.
Prepare For Drive Start-Up
Before Applying Power to the Drive
❏1. Confirm that all inputs are connected to the correct terminals and are
secure.
❏2. Verify that AC line power at the disconnect device is within the rated value
of the drive.
❏3. Verify that control power voltage is correct.
The remainder of this procedure requires that a HIM be installed. If an
operator interface is not available, remote devices should be used to start
up the drive.
Rockwell Automation Publication 20C-PM001F-EN-P - March 201211
Chapter 1Drive Start-Up
Apply Power to the Drive
❏4. Apply AC power and control voltages to the drive.
Start-Up the Drive
• If the STS (status) LED is NOT flashing green, refer to Drive Status
page 62 for more information.
• If any of the six digital inputs are configured for “Stop – CF” (CF =
Clear Fault) or “Enable,” verify that signals are present or reconfigure
[Digital Inx Sel].
• If an I/O option is not installed (no I/O terminal block is present),
verify that [Digital Inx Sel] is not configured to “Stop – CF” or
“Enable.” If this is not done, the drive will not start. Refer to Fault and
Alarm Descriptions on page 64 for a list of potential digital input
conflicts.
• If a fault code appears, refer to Chapter
❏5. Proceed to “Start-Up the Drive”.
The PowerFlex 700H drive is designed so that start up is simple and efficient. If
you have an LCD HIM, two start-up methods are provided, allowing you to
select the desired level needed for the application.
• S.M.A.R.T. Start
This routine allows you to quickly set up the drive by programming values
for the most commonly used functions. See Running S.M.A.R.T. Start
page 13.
3.
on
on
•Assisted Start Up
This routine prompts you for information that is needed to start up a drive
for most applications, such as line and motor data, commonly adjusted
parameters and I/O. See Running an Assisted Start Up
IMPORTANT
Power must be applied to the drive when viewing or changing parameters.
Previous programming may affect the drive status and operation when power
is applied.
on page 13.
12Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Drive Start-UpChapter 1
/
Running S.M.A.R.T. Start
During a Start Up, the majority of applications require changes to only a few
parameters. The LCD HIM on a PowerFlex 700H drive offers S.M.A.R.T. start,
which displays the most commonly changed parameters. With these parameters,
you can set the following functions:
S - Start Source and Stop Mode
M - Minimum and Maximum Speed
A - Accel Time 1 and Decel Time 1
R - Reference Source
T - Thermal Motor Overload
To run a S.M.A.R.T. start routine, follow these instructions:
StepKey(s)Example LCD Displays
1. Press ALT and then Esc (S.M.A.R.T). The S.M.A.R.T. star t
screen appears.
2. View and change parameter values as desired. For HIM
information, see Appendix
A.
3. Press Esc to exit the S.M.A.R.T. star t.
ALT
Esc
Esc
F-> StoppedAuto
0.0
SMART List:
Main Menu:
Digital In2 Sel
Diagnostics
Stop Mode A
Parameter
Minimum Speed
Hz
Running an Assisted Start Up
IMPORTANT
The Assisted start-up routine asks simple yes or no questions and prompts you to
input required information. Access Assisted Start Up by selecting “Start Up”
from the Main Menu.
Figure 1 - PowerFlex 700H Start Up Menu
Main Menu:
Start-Up
Input Voltage
Select
Sets Input
Voltage
To perform an Assisted Start-Up, follow these instructions:
StepKey(s)Example LCD Displays
1. In the Main Menu, press the Up Arrow or Down Arrow to
scroll to “Start Up”.
2. Press Enter.
This start-up routine requires an LCD HIM.
Motor Data and
Ramp Times
Enter Motor NP
Data, Stop Mode,
Accel/Decel
Ramp Times
Motor Tests
Optimize Torque
and
Verify Direction
Speed Limits
Set Min/Max
Speed and
Direction Control
Speed/Torque
Control
Configure
Source, Value
and Scale for
Speed References
Digital Inputs/Outputs
F-> StoppedAuto
0.0
Main Menu:
Memory Storage
Start Up
Preferences
Start/Stop/I/O
Configure
Control Method
(2 Wire/3 Wire), I/O,
and Analog Outputs
Hz
Done
Exit
Rockwell Automation Publication 20C-PM001F-EN-P - March 201213
Chapter 1Drive Start-Up
Notes:
14Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 2
Programming and Parameters
This chapter provides a complete list and description of the PowerFlex 700H
parameters. The parameters can be programmed (viewed/edited) using an LCD
Human Interface Module (HIM). As an alternative, programming can also be
performed using DriveExplorer™ or DriveExecutive™ software and a personal
computer. Refer to HIM Overview
HIM.
For Information on…See page…
About ParametersBelow
How Parameters are Organized17
Monitor File20
Motor Control File21
Speed Command File24
Dynamic Control File30
Utility File35
Communication File45
Inputs/Outputs File49
Param eter Li st by Na me56
Parameter List by Number58
on page 81 for a brief description of the LCD
About Parameters
To configure a drive to operate in a specific way, drive parameters may have to be
changed to values different than the default setting. Three types of parameters
exist:
•ENUM Parameters
ENUM parameters allow a selection from a list of items. The LCD HIM
will display a text message for each item.
•Bit Parameters
Bit parameters have individual bits associated with features or conditions.
If the bit is 0, the feature is off or the condition is false. If the bit is 1, the
feature is on or the condition is true.
•Numeric Parameters
These parameters have a single numerical value (i.e. 0.1 Volts).
Rockwell Automation Publication 20C-PM001F-EN-P - March 201215
Chapter 2Programming and Parameters
This table is an example of how each parameter type is presented in this manual.
Each numbered column is described in the table following this example.
123 456
File
Parameter Name & DescriptionValues
Group
No.
198 [Load Frm Usr Set]
Loads a previously saved set of parameter values
from a selected user set location in drive
Drive . . .
nonvolatile memory to active drive memory.
216 [Dig In Status]
Default:
Options:00
“Ready”
“Ready”
“User Set 1”
1
“User Set 2”
2
“User Set 3”
3
Read Only361
Status of the digital inputs.
UTILITY
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Digital In6
Digital In5
Digital In4
Digital In3
Diagnostics
044 [Motor NP RPM]
32
MOTOR . . .
Motor Data
Column
Description
Defaultxxxxxxxxxx000000
Bit1514131211109876543210
Set to the motor nameplate rated RPM.
Default:
Min/Max:
Units:
1750.0 RPM
60.0/19200.0 RPM
1.0 RPM
Digital In2
No.
1File – Lists the major parameter file category.
2Group – Lists the parameter group within a file.
3No. – Parameter number. = Parameter value cannot be changed until drive is stopped.
32
= 32 bit parameter.
4Parameter Name & Description – Parameter name as it appears on an LCD HIM, with a brief description of
the parameters function. Parameters names appear within square brackets [] throughout this manual.
5Values – Defines the various operating characteristics of the parameter. Three types exist.
ENUMDefault:
Options:
Lists the default value assigned at the factory. “Read Only” = no default.
Displays the optional programming selections available.
BitBit:Lists the bit name, default setting and place holder for each bit.
Numeric Default:
Min/Max:
Units:
Lists the default value assigned at the factory. “Read Only” = no default.
The range (lowest and highest setting) possible for the parameter.
Unit of measure and resolution as shown on the LCD HIM.
Important: Some parameters will have two unit values:
• Analog inputs can be set for current or voltage with parameter 320 [Anlg In Config].
• Setting parameter 79 [Speed Units] selects “Hz” or “RPM.”
Important: When sending values through DPI ports, simply remove the decimal point to arrive
at the correct value (i.e. to send “5.00 Hz,” use “500”).
6Related – Lists parameters (if any) that interact with the selected parameter. The symbol “” indicates
that additional parameter configuration information is available in Appendix
B.
Related
199
thru
366
Digital In1
16Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
How Parameters are
Organized
The LCD HIM displays parameters in a File-Group-Parameter or Numbered
List view order. To switch display mode, access the Main Menu, press ALT, then
Sel while the cursor is on the parameter selection. In addition, using [Param
Access Lvl], you can display only the commonly used parameters or all
parameters.
File-Group-Parameter Order View
This view simplifies programming by grouping parameters that are used for
similar functions. The parameters are organized into six files in Basic Parameter
view or seven files in Advanced Parameter view. Each file is divided into groups,
and each parameter is an element in a group. By default, the LCD HIM displays
parameters by File-Group-Parameter view.
Numbered List View
In this view, all parameters are listed in ascending numerical order.
Basic Parameter View
Parameter 196 [Param Access Lvl] set to option 0 “Basic.”
Faul t 1 Su bCod e54 3
Faul t 2 Su bCod e54 5
Faul t 3 Su bCod e54 7
Faul t 4 Su bCod e54 9
Faul t 5 Su bCod e55 1
Faul t 6 Su bCod e55 3
Faul t 7 Su bCod e55 5
Faul t 8 Su bCod e55 7
Alarm7 Code268
Alarm8 Code269
DPI Port Value275
Reference Owner292
Accel Owner293
Decel Owner294
Fault Clr Owner295
MOP Owner296
Local Own er297
Data Out C1314
Data Out C2315
Data Out D1316
Data Out D2317
Analog In1 Loss324
Analog In2 Loss327
Anlg Out1 Scal354
Anlg Out2 Scal355
Anlg1 Out Setpt377
Anlg2 Out Setpt378
20C-DG1 Remove358
20C-DG1 Status359
Dig Out3 OnTime390
Dig Out3 OffTime391
Dig Out Setpt379
Rockwell Automation Publication 20C-PM001F-EN-P - March 201219
Chapter 2Programming and Parameters
Monitor File
File
Parameter Name & DescriptionValues
Group
No.
001 [Outp ut Freq]
Output frequency present at U/T1, V/T2 & W/T3.
002 [Commanded Speed]
32
Value of the active Speed/Frequency Reference.
Displayed in Hz or RPM, depending on value of
[Speed Units].
003 [Output Current]
The total output current present at U/T1, V/T2 &
W/T3.
004 [Torque Current]
Based on the motor, the amount of current that is
in phase with the fundamental voltage
component.
005 [Flux Current]
Amount of current that is out of phase with the
fundamental voltage component.
006 [Outp ut Voltag e]
Output voltage present at terminals U/T1, V/T2 &
W/T3.
007 [Output Power]
Output power present at U/T1, V/T2 & W/T3.
008 [Outp ut Powr Fctr]
Output power factor.
009 [Elapsed MWh]
Metering
MONITOR
32
Accumulated output energy of the drive.
010 [Elapsed Run Time]
32
Accumulated time drive is outputting power.
011 [MOP Reference]
32
Value of the signal at MOP (Motor Operated
Potentiometer).
012 [DC Bus Voltage]
Present DC bus voltage level.
013 [DC Bus Memory]
Approximate full load DC bus voltage level.
016
[Analog In1 Value]
017
[Analog In2 Value]
Value of the signal at the analog inputs.
022 [Ramped Speed]
32
Value of commanded speed after Accel/Decel, and
S-Curve are applied.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+ [Maximum Freq]
0.1 Hz
Read Only
–/+ [Maximum Speed]
0.1 Hz
0.1 RPM
Read Only
0.0/Drive Rated Amps x 2
0.1 Amps
Read Only
Drive Rating x –2/+2
0.1 Amps
Read Only
Drive Rating x –2/+2
0.1 Amps
Read Only
0.0/Drive Rated Volts
0.1 VAC
Read Only
0.0/Drive Rated kW x 2
0.1 kW
Read Only
0.00/1.00
0.01
Read Only
0.0/429496729.5 MWh
0.1 MWh
Read Only
0.0/214748364.0 Hrs
0.1 Hrs
Read Only
–/+ [Maximum Speed]
0.1 Hz
0.1 RPM
Read Only
0.0/Based on Drive Rating
0.1 VDC
Read Only
0.0/Based on Drive Rating
0.1 VDC
Read Only
0.000/20.000 mA
–/+10.000V
0.001 mA
0.001 Volt
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Related
079
079
079
20Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
023 [Speed Reference]
32
Summed value of ramped speed, process PI and
droop.
024 [Commanded Torque]
Final torque refe rence value after limits and
filtering are applied. Percent of motor rated
Metering
torque.
Note: Added for firmware revision 4.001.
025 [Speed Feedback]
This parameter displays the estimated value of
actual motor speed.
MONITOR
026 [Rated kW]
32
Drive power rating.
027 [Rated Volts]
The drive input voltage class (208, 240, 400 etc.).
028 [Rated Amps]
Drive Data
The drive rated output current.
029 [Control SW Ver]
Main Control Board software revision.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Read Only
–/+800.0%
0.1%
Read Only
–/+320.0 Hz
–/+19200.0 RPM
0.1 Hz
0.1 RPM
Read Only
0.00/3000.00 kW
0.01 kW
Read Only
0.0/690.0 VAC
0.1 VAC
Read Only
0.0/6553.5 Amps
0.1 Amps
Read Only
0.000/255.255
0.001
Related
079
053
Motor Control File
File
Parameter Name & DescriptionValues
Group
No.
040 [Motor Type]
Set to match the type of motor connected.
041 [Motor NP Volts]
Set to the motor nameplate rated volts.
042 [Motor NP FLA]
Set to the motor nameplate rated full load amps.
043 [Motor NP Hertz]
Set to the motor nameplate rated frequency.
Motor Data
MOTOR CONTROL
044 [Motor NP RPM]
Set to the motor nameplate rated RPM.
32
045 [Motor NP Power]
Set to the motor nameplate rated power.
32
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Induction”
“Induction”
Based on Drive Rating
0.0/[Rated Volts]
0.1 VAC
Based on Drive Rating
0.0/[Rated Amps] × 2
0.1 Amps
Based on Drive Rating
5.0/320.0 Hz
0.1 Hz
Based on Drive Rating
60.0/19200.0 RPM
1.0 RPM
Based on Drive Rating
0.00/5000.00
0.01 kW/HP
See [Mtr NP Pwr Units]
Related
053
047
048
046
Rockwell Automation Publication 20C-PM001F-EN-P - March 201221
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
046 [Mtr NP Pwr Units]
Selects the motor power units to be used.
“Convert H P” = converts all power units to
Horsepower.
“Convert kW” = converts al l power units to
kilowatts.
Note: This parameter does not get changed with a
“Reset to Defaults”.
047 [Motor OL Hertz]
Selects the output frequency below which the
motor operating current is derated. The motor
thermal overload will generate a fault at lower
levels of current below this output frequency.
048 [Motor OL Factor]
Sets the operating level for the motor overload.
Motor
FLAOLFactor
049 [Motor Poles]
Motor Data
Defines the number of poles in the motor.
Note: Maximum value changed from 12 to 18 for
firmware revision 4.001.
050 [Motor OL Mode]
“Pwr Cyc Ret” - If “0”, the value of parameter 220 [Motor OL Count] is reset to zero by a drive reset
or power cycle. If “1”, the value of parameter 220 [Motor OL Count] is maintained. A “1” to “0”
transition resets parameter 220 [Motor OL Count] to zero.
Note: Added for firmware revision 3.001.
1 = Enabled
0 = Disabled
Related
Default:
Options:–0
Default:
Min/Max:
Units:
Default:
Min/Max:
x
Level
Operating
=
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
“Horsepower”
“kiloWatts”
1
“Convert HP”
2
“Convert kW”
3
Motor NP Hz/3
0.0/Motor NP Hz
0.1 Hz
1.00
0.20/2.00
0.01
4
2/18
1 Pole
042
220
042
220
220
MOTOR CONTROL
053 [Motor Cntl Sel]
Sets the method of motor control used in the
drive.
055 [Maximum Freq]
Sets the highest frequency the drive will output.
Refer to parameter 083 [Overspeed Limit].
056 [Compensation]
“Mtr Lead Rev” - If “1”, reverses the phase rotation of the applied voltage, effectively reversing
the motor leads.
Notes: Not retained when the parameters are reset to defaults. Added for firmware revision
3.001.
Torq Attributes
1 = Enabled
0 = Disabled
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Pwr Cyc Ret
Defaultxxxxxxxxxxxxxxx0
Bit1514131211109876543210
Default:
Options:00
Default:
Min/Max:
Units:
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Defaultxxxxxxxxxx0xxxxx
Bit1514131211109876543210
“Sensrls Vect”
“Sensrls Vect”
1
“SV Economize”
2
“Custom V/Hz”
3
“Fan/Pmp V/Hz”
Based on Drive Rating
5.0/320.0 Hz
0.1 Hz
Reserved
Mtr Lead Rev
Reserved
Reserved
Reserved
Reserved
Reserved
083
22Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Group
No.
057 [Flux Up Mode]
058 [Flux Up Time]
059 [SV Boost Filter]
061 [Autotune]
Torq Attributes
MOTOR CONTROL
Parameter Name & DescriptionValues
Flux is established for [Flux Up Time] before
Default:
Options:00
“Manual”
“Manual”
acceleration.
Sets the amount of time the drive will use to try
and achieve full motor stator flux. When a Start
Default:
Min/Max:
Units:
0.2 Secs
0.0/5.0 Secs
0.1 Secs
command is issued, DC current at current limit
level is used to build stator flux before
accelerating. This will occur unless [Rated Amps]
is less than [Motor NP FLA], then only 81% of
drive rated current is used.
55
0/32767
1
“Calcul ate”
“Ready”
“Static Tune”
1
“Rotate Tune”
2
“Calcul ate”
3
Sets the amount of filtering used to boost voltage
during Sensorless Vector operation.
Provides a manual or automatic method for
setting [IR Voltage Drop], and [Flux Current Ref].
Note: Program parameter 053 [Motor Cntl Sel]
prior to running an autotune.
Default:
Min/Max:
Units:
Default:
Options:30
“Ready” (0) = Parameter returns to this setting following a “Static Tune” or “Rotate Tune.” It also
permits manually setting [IR Voltage Drop], [Ixo Voltage Drop] and [Flux Current Ref].
“Static Tune” (1) = A temporary command that initiates a non-rotational motor stator resistance
test for the best possible automatic setting of [IR Voltage Drop], [Break Voltage] and [Break
Frequency] in all modes. A start command is required within 20 seconds following initiation of
this setting. The parameter returns to “Ready” (0) following the test, at which time another start
transition is required to operate the drive in normal mode. Used when motor cannot be rotated.
“Rotate Tune” (2) = A temporary command that initiates a “Static Tune” followed by a rotational
test for the best possible automatic setting of [Flux Current Ref] and [Start Boost]. A start
command is required following initiation of this setting. The parameter returns to “Ready” (0)
following the test, at which time another start transition is required to operate the drive in
normal mode. Important: Used when motor is uncoupled from the load. Results may not be
valid if a load is coupled to the motor during this procedure.
Related
053
058
053
058
053
062
ATT EN TI ON : Rotation of the motor in an undesired direction can occur during
this procedure. To guard against possible injury and/or equipment damage, it
is recommended that the motor be disconnected from the load before
proceeding.
“Calculate” (3) = This setting uses motor nameplate data to automatically set [IR Voltage Drop],
[Flux Current Ref] and [Slip RPM @ FLA].
062 [IR Voltage Drop]
Value of voltage drop across the resistance of the
motor stator at rated motor current.
063 [Flux Current Ref]
32
Value of amps for full motor flux.
069 [Start Boost]
Sets the voltage boost level for starting and
acceleration. Refer to parameter 083 [Overspeed
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Motor NP Volts]×0.50
0.1 VAC
Based on Drive Rating
0.00/[Motor NP FLA]
0.01 Amps
Based on Drive Rating
0.0/[Motor NP Volts] × 0.25
0.1 VAC
Limit].
071 [Break Voltage]
Sets the voltage the drive will output at [Break
Frequency]. Refer to parameter 083 [Overspeed
Volts p er Hertz
Limit].
072 [Break Frequency]
Sets the frequency the drive will output at [Break
Voltage]. Refer to parameter 083.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
0.0/[Motor NP Volts]
0.1 VAC
Based on Drive Rating
0.0/[Maximum Freq]
0.1 Hz
053
061
053
061
053
053
072
053
071
Rockwell Automation Publication 20C-PM001F-EN-P - March 201223
Chapter 2Programming and Parameters
Speed Command File
File
Parameter Name & DescriptionValues
Group
No.
079 [Speed Units]
Selects the units to be used for all speed related
parameters. Options 0 & 1 indicate status only.
Options 2 & 3 will convert/configure the drive for
that selection.
“Convert Hz” (2) - converts all speed based
parameters to Hz, and changes the value
proportionately (i.e. 1800 RPM = 60 Hz).
“Convert RPM” (3) - converts all speed based
parameters to RPM, and changes the value
proportionately.
Note: This parameter does not get changed with a
“Reset to Defaults”.
080 [Feedback Select]
Selects the source for motor speed feedback.
“Open Loop” (0) - no encoder is present, and slip
compensation is not needed.
“Slip Comp” (1) - tight speed control is needed,
and encoder is not present.
081 [Minimum Speed]
Sets the low limit for speed reference after scaling
32
is applied. Refer to parameter 083 [Overspeed
Limit].
082 [Maximum Speed]
Sets the high limit for speed reference after
32
scaling is applied. Refer to parameter 083
[Overspeed Limit].
083 [Overspeed Limit]
Sets the incremental amount of the output
Spd Mode/Limits
SPEED COMMAND
32
frequency (above [Maximum Speed]) allowable
for functions such as slip compensation.
[Maximum Speed] + [Overspeed Limit] must be
≤[Maximum Freq]
Motor Volts
Voltage
Break Volts
Start Boost
Allowable Output Frequency Range
Bus Regulation or Current Limit
Allowable Output Frequency Range
Normal Operation
Allowable Reference Frequency Range
Frequency Trim due to
Speed Control Mode
Default:
Options:00
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Overspeed
Limit
“Hz”
“Hz”
1
“RPM”
2
“Convert Hz”
3
“Convert RPM”
“Open Loop”
“Open Loop”
1
“Slip Comp”
0.0
0.0/[Maximum Speed]
0.1 Hz
0.1 RPM
50.0 or 60.0 Hz (volt class)
[Motor NP RPM]
5.0/320.0 Hz
75.0/19200.0 RPM
0.1 Hz
0.1 RPM
10.0 Hz
300.0 RPM
0.0/20.0 Hz
0.0/600.0 RPM
0.1 Hz
0.1 RPM
Related
152
079
083
092
095
055
079
083
091
094
055
079
082
0Min
Speed
084
[Skip Frequency 1]
085
[Skip Frequency 2]
086
[Skip Frequency 3]
32
Sets a frequency at which the drive will not
Break
Frequency
operate. [Skip Frequency x] and [Skip Frequency
Band] must not equal 0.
087 [Skip Freq Band]
32
Determines the bandwidth around a skip
frequency. [Skip Freq Band] is split, applying 1/2
above and 1/2 below the actual skip frequency.
The same bandwidth applies to all skip
frequencies.
24Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Motor
Hz
Frequency
Default:
Default:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Max
Output
Speed
Freq Limit
Based on Drive Rating
0.0 Hz
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
0.0 Hz
0.0/30.0 Hz
0.1 Hz
Max
Freq
087
084
085
086
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
088 [Speed/Torque Mod]
Selec ts the torque reference source.
“Speed Reg” (1) - drive operates as a speed
regulato r.
454 [Rev Speed Limit]
32
Sets a limit on speed in the negative direction.
Spd Mode/Limits
Used in bipolar mode only. A value of zero
disables this parameter and uses [Min Speed] for
minimum speed.
090 [Speed Ref A Sel]
Selects the source of the speed reference to the
drive unless [Speed Ref B Sel] or [Preset Speed 17] is selected.
(1)
See Installation Manual for DPI port locations.
SPEED COMMAND
091 [Speed Ref A Hi]
32
Scales the upper value of the [Speed Ref A Sel]
Speed References
selection when the source is an analog input.
092 [Speed Ref A Lo]
32
Scales the lower value of the [Speed Ref A Sel]
selection when the source is an analog input.
093 [Speed Ref B Sel]
See [Speed Ref A Sel]
094 [Speed Ref B Hi]
32
Scales the upper value of the [Speed Ref B Sel]
selection when the source is an analog input.
095 [Speed Ref B Lo]
32
Scales the lower value of the [Speed Ref B Sel]
selection when the source is an analog input.
Related
Default:
Options:11
Default:
Min/Max:
“Speed Reg”
“Speed Reg”
0.0 RPM
–[Max Speed]/0.0 Hz
053
–[Max Speed]/0.0 RPM
Units:
0.0 Hz
0.0 RPM
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Analog In 2”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
002
091
thru
093
101
thru
107
117
thru
120
192
thru
194
(1)
(1)
(1)
(1)
(1)
213
272
273
320
361
thru
Default:
Options:21
366
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
.
Options:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
11“Preset Spd1”
See [Speed Ref A Sel]
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
082
079
081
090
079
093
079
090
093
Rockwell Automation Publication 20C-PM001F-EN-P - March 201225
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
096 [TB Man Ref Sel]
Sets the manual speed reference source when a
digital input is configured for “Auto/Manual.”
Note: Options 18…20 were added for firmware
revision 5.002.
(1)
Speed References
097 [TB Man Ref Hi]
32
Scales the upper value of the [TB Man Ref Sel]
selection when the source is an analog input.
098 [TB Man Ref Lo]
32
Scales the lower value of the [TB Man Ref Sel]
selection when the source is an analog input.
100 [Jog Speed 1]
Sets the output frequency when Jog Speed 1 is
selected.
SPEED COMMAND
[Preset Speed 1]
101
[Preset Speed 2]
102
[Preset Speed 3]
103
[Preset Speed 4]
104
[Preset Speed 5]
105
[Preset Speed 6]
106
[Preset Speed 7]
107
Discrete Speeds
32
Provides an internal fixed speed command value.
In bipolar mode direction is commanded by the
sign of the referen ce.
108 [Jog Speed 2]
32
Sets the output frequency when Jog Speed 2 is
selected.
116 [Trim % Setpoint]
Adds or subtracts a percentage of the speed
reference or maximum speed. Dependent on the
setting of parameter 118 [Trim Out Select].
Speed Trim
Note: Added for firmware revision 3.001.
“Analog In 2” is not a valid selection if it was
selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep Wake Ref]
Default:
Options:11
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“Analog In 1”
“Analog In 1”
“Analog In 2”
2
3…8
“Reserved”
9
“MOP Level”
18
“DPI Port1”
19
“DPI Port2”
20
“DPI Port3”
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
1 RPM
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
0.0%
–/+200%
0.1%
Related
097
098
(1)
079
096
079
096
079
079
090
093
118
26Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
117 [Trim In Select]
Specifies which analog input signal is being used
as a trim input.
(1)
118 [Trim Out Select]
Specifies which speed references are to be trimmed and allows you to trim the speed reference
based on a percentage or the frequency of the input signal.
Note: Added bit 2 “Add or %” for firmware revision 3.001.
Speed Trim
See Installation Manual for DPI port locations.
ValueBit 2Bit 1, 0
1 =%Trimmed
0 =AddNot Trimmed
Default:
Options:20
1
2
3-8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
“Analog In 2”
“Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Reserved”
“Preset Spd1”
“Preset Spd2”
“Preset Spd3”
“Preset Spd4”
“Preset Spd5”
“Preset Spd6”
“Preset Spd7”
“DPI Port 1”
“DPI Port 2”
“DPI Port 3”
“DPI Port 4”
“DPI Port 5”
Related
090
093
(1)
(1)
(1)
(1)
(1)
117
119
120
SPEED COMMAND
119 [Trim Hi]
32
120 [Trim Lo]
32
121 [Slip RPM @ FLA]
Slip Comp
123 [Slip RPM Meter]
Name
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Add or %
Tri m Re f B
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
1 RPM
0.0 Hz
–/+[Maximum Speed]
0.1 Hz
1 RPM
Scales the upper value of the [Trim In Select]
selection when the source is an analog input.
Scales the lower value of the [Trim In Select]
selection when the source is an analog input.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Important: Parameters in the Slip Comp Group are used to enable and tune the Slip
Compensation Regulator. In order to allow the Slip Compensation Regulator to control drive
operation, parameter 080 [Feedback Select] must be set to 1 “Slip Comp”.
Based on [Motor NP RPM]
0.0/1200.0 RPM
0.1 RPM
Read Only
–/+300.0 RPM
0.1 RPM
Sets the amount of compensation to drive output
at motor FLA.
Displays the present amount of adjustment being
applied as slip compensation.
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Tri m Re f A
079
082
117
0791
17
061
080
123
080
121
Rockwell Automation Publication 20C-PM001F-EN-P - March 201227
Chapter 2Programming and Parameters
File
Parameter Name & DescriptionValues
Group
No.
124 [PI Configuration]
Sets configuration of the PI regulator.
Note: Added bit 9 “% of Ref” for firmware revision 3.001.
1 = Enabled
0 = Disabled
Defaultxxxxxx0x00000000
Bit1514131211109876543210
125 [PI Control]
Controls the PI regulator.
1 = Enabled
0 = Disabled
Defaultxxxxxxxxxxxxx000
Bit1514131211109876543210
126 [PI Reference Sel]
Selects the source of the PI reference.
Process PI
SPEED COMMAND
127 [PI Setpoint]
Provides an internal fixed value for process
setpoint when [PI Reference Sel] is set to “PI
Setpoint.”
128 [PI Feedback Sel]
Selects the source of the PI feedback.
129 [PI Integral Time]
Time required for the integral component to reach
100% of [PI Error Meter]. Not functional when the
PI Hold bit of [PI Control] = “1” (enabled).
130 [PI Prop Gain]
Sets the value for the PI proportional component.
PI Error x PI Prop Gain = PI Output
131 [PI Lower Limit]
Sets the lower limit of the PI output.
132 [PI Upper Limit]
Sets the upper limit of the PI output.
Name
Name
Related
124
thru
138
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
% of Ref
Reserved
Anti-Wind Up
Stop Mode
Feedbak Sqrt
Zero Clamp
Ramp Ref
Preload Mode
Invert Error
Excl Mode
080
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PI Reset
PI Hold
PI Enable
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Options:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
“PI Setpoint”
“PI Setpoint”
“Analog In 1”
1
“Analog In 2”
2
“Reserved”
3-8
“MOP Level”
9
“Master Ref ”
10
“Preset Spd1-7”
11-17
“DPI Port 1-5”
18-22
50.0%
–/+100.0% of Maximum
Process Value
0.1%
2“Analog In 2”
See [PI Reference Sel]
2.0 Secs
0.00/100.00 Secs
0.01 Secs
1.0
0.00/100.00
0.01
–[Maximum Freq]
100%
–/+800.0%
0.1%
+[Maximum Freq]
100%
–/+800.0%
0.1%
124
thru
138
124
thru
138
124
thru
.
138
124
thru
138
124
thru
138
079
124
thru
138
079
124
thru
138
28Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Programming and ParametersChapter 2
File
Parameter Name & DescriptionValues
Group
No.
133 [PI Preload]
Sets the value used to preload the integral
component on start or enable.
134 [PI Status]
Status of the Process PI regulator.
1 = Condition True
0 = Condition False
Defaultxxxxxxxxxxxx0000
Bit1514131211109876543210
135 [PI Ref Meter]
Pres ent va lue of the PI reference signal.
136 [PI Fdback Meter]
Pres ent va lue of the PI feedback signal.
137 [PI Error Meter]
Present value of the PI error.
Process PI
SPEED COMMAND
138 [PI Output Meter]
Present value of the PI output.
460 [PI Reference Hi]
Scales the upper value of [PI Reference Sel] of the
source.
461 [PI Reference Lo]
Scales the lower value of [PI Reference Sel] of the
source.
462 [PI Feedback Hi]
Scales the upper value of [PI Feedback] of the
source.
463 [PI Feedback Lo]
Scales the lower value of [PI Feedback] of the
source.
464 [PI Output Gain]
Sets the gain factor for [PI Output Meter].
Note: Added for firmware revision 3.001.
Name
Related
Default:
Min/Max:
Units:
0.0 Hz
100%
–/+800.0%
0.1%
079
124
thru
138
Read Only124
thru
138
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
PI InLimit
PI Reset
PI Hold
PI Enabled
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0%
0.1%
Read Only
–/+100.0 Hz
–/+100.0%
0.1 Hz
124
thru
138
124
thru
138
124
thru
138
124
thru
138
0.1%
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
–100.0%
–/+100.0%
0.1%
100.0%
–/+100.0%
0.1%
0.0%
–/+100.0%
0.1%
1.000
–/+8.000
0.001
138
Rockwell Automation Publication 20C-PM001F-EN-P - March 201229
Chapter 2Programming and Parameters
Dynamic Control File
File
Parameter Name & DescriptionValues
Group
No.
140
[Accel Time 1]
141
[Accel Time 2]
Sets rate of accel for all speed increases.
Max Speed
Accel Time
142
[Decel Time 1]
143
[Decel Time 2]
Sets rate of decel for all speed decreases.
Ramp Rates
Max Speed
Decel Time
146 [S Curve %]
Sets the percentage of accel or decel time that is
applied to the ramp as S Curve. Time is added, 1/2
at the beginning and 1/2 at the end of the ramp.
147 [Current Lmt Sel]
Selects the source for the adjustment of current
limit (i.e. parameter, analog input, etc.).
148 [Current Lmt Val]
Defines the current limit value when [Current Lmt
Sel] = “Cur Lim Val.”
149 [Current Lmt Gain]
Sets the responsiveness of the current limit.
150 [Drive OL Mode]
DYNAMIC CONTROL
Selects drive response to increasing drive
temperature.
Load Limits
151 [PWM Frequency]
Sets the carrier frequency for the PWM output.
Drive derating may occur at higher carrier
frequencies.
152 [Droop RPM @ FLA]
Selects amount of droop that the speed reference
is reduced when at full load torque. Zero disables
the droop function.
=
=
Accel Rate
Decel Rate
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:00
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
Default:
Options:30
Default:
Min/Max:
Units:
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
0%
0/100%
1%
“Cur Lim Val”
“Cur Lim Val”
“Analog In 1”
1
“Analog In 2”
2
Based on Drive Rating
Based on Drive Rating
0.1 Amps
10000
0/32767
1
“Both-PWM 1st”
“Reserved”
“Reduce Clim”
1
“Reserved”
2
“Both-PWM 1st”
3
1.5 kHz or 2 kHz based on Drive
Rating
1/Based on Drive Rating
1 kHz
0.0 RPM
0.0/200.0 RPM
0.1 RPM
Related
142
143
146
361
thru
366
140
141
146
361
thru
366
140
thru
143
146
149
147
149
147
148
Important: Selecting “Slip Comp” with
parameter 080 in conjunction with parameter
152, may produce undesirable results.
145 [DB While Stopped]
Enables/disables dynamic brake operation when
drive is stopped. DB may operate if input voltage
becomes too high.
• Disa bled = DB will not
operate when the drive
is stopped.
• Enabled = DB may operate whenever drive is
Stop/Brake Modes
energized.
Notes: This parameter is used for frame 9 drives
only. Added for firmware revision 3.001.
30Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Default:
Options:00
“Disabled”
“Disabled”
“Enabled”
1
Loading...
+ 86 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.