These records can be printed to provide a written record of parameter changes made to a PowerFlex 70 or PowerFlex 700 drive.
PFLEX-IN002A-EN-P
Last Reveision 1/21/02
Some manpulation of the spreadsheets may be necessary based on you selection of a printer.
Identity
S.M.A.R.T. Start
Parameter Setup
Customer Name ____________________
Plant ____________________
Machine # ____________________
Process Number ____________________
Other Data ____________________
Date Programmed ____________________
SW Version ____________________
Drive Cat # ____________________
Drive Ser # ____________________
ParParameter NameFactory DefaultProgrammed Value
40Motor TypeInduction
41Motor NP VoltsBased on Drive Rating
42Motor NP FLABased on Drive Rating
43Motor NP HertzBased on Drive Cat. No.
44Motor NP RPM1750 RPM
45Motor NP PowerBased on Drive Rating
46Mtr NP Pwr UnitsBased on Drive Rating
47Motor OL HertzMotor NP Hz/3
48Motor OL Factor1.00
53Torque Perf ModeSensrls Vect
61AutotuneCalculate
62IR Voltage DropBased on Drive Rating
63Flux Current RefBased on Drive Rating
81Minimum Speed0.0 Hz
82Maximum Speed50.0 or 60.0 Hz
83Overspeed Limit10.0 Hz
90Speed Ref A SelAnalog In 2
91Speed Ref A Hi[Maximum Speed]
92Speed Ref A Lo0.0 Hz
140Accel Time 110.0 Secs
142Decel Time 110.0 Secs
201LanguageNot Selected
320Anlg In Config0
321Anlg In Sqr Root0
322Analog In 1 Hi10.0 Volt
323Analog In 1 Lo0.0 Volt
324Analog In 1 LossDisabled
361Digital In1 SelStop - CF
362Digital In2 SelStart
ParParameter NameFactory DefaultProgrammed ValueParParameter NameFactory DefaultProgrammed Value
288 Stop OwnerRead Only1Output FreqRead Only
289 Start OwnerRead Only2Commanded FreqRead Only
290 Jog OwnerRead Only3Output CurrentRead Only
291 Direction OwnerRead Only4Torque CurrentRead Only
292 Reference OwnerRead Only5Flux CurrentRead Only
293 Accel OwnerRead Only6Output VoltageRead Only
294 Decel OwnerRead Only7Output PowerRead Only
295 Fault Clr OwnerRead Only8Output Powr FctrRead Only
296 MOP OwnerRead Only9Elapsed MWhRead Only
297 Local OwnerRead Only10Elapsed Run TimeRead Only
300 Data In A1011MOP FrequencyRead Only
301 Data In A2012DC Bus VoltageRead Only
302 Data In B1013DC Bus MemoryRead Only
303 Data In B2016Analog In1 ValueRead Only
304 Data In C1017Analog In2 ValueRead Only
305 Data In C2026Rated kWRead Only
306 Data In D1027Rated VoltsRead Only
307 Data In D2028Rated AmpsRead Only
310 Data Out A1029Control SW VerRead Only
311 Data Out A2040Motor TypeInduction
312 Data Out B1041Motor NP VoltsBased on Drive Rating
313 Data Out B2042Motor NP FLABased on Drive Rating
314 Data Out C1043Motor NP HertzBased on Drive Cat. No.
315 Data Out C2044Motor NP RPM1750 RPM
316 Data Out D1045Motor NP PowerBased on Drive Rating
317 Data Out D2046Mtr NP Pwr UnitsBased on Drive Rating
320 Anlg In Config047Motor OL HertzMotor NP Hz/3
321 Anlg In Sqr Root048Motor OL Factor1.00
322 Analog In 1 Hi10.0 Volt53Torque Perf ModeSensrls Vect
323 Analog In 1 Lo0.0 Volt54Maximum VoltageDrive Rated Volts
324 Analog In 1 LossDisabled55Maximum Freq110.0 or 130.0 Hz
325 Analog In 2 Hi10.0 Volt56Compensationxxxxxxxxxxxxxx11
326 Analog In 2 Lo0.0 Volt57Flux Up ModeManual
327 Analog In 2 LossDisabled58Flux Up Time0.00 secs
341 Anlg Out Absolutxxxxxxxxxxxxxxx161AutotuneCalculate
342 Analog Out1 SelOutput Freq62IR Voltage DropBased on Drive Rating
343 Analog Out1 Hi10.00 Volt63Flux Current RefBased on Drive Rating
344 Analog Out1 Lo0.00 Volt69Start/Acc BoostBased on Drive Rating
361 Digital In1 SelStop - CF70Run BoostBased on Drive Rating
362 Digital In2 SelStart71Break Voltage[Motor NP Volts] x 0.25
363 Digital In3 SelAuto/Manual72Break Frequency[Motor NP Freq] x 0.25
364 Digital In4 SelSpeed Sel 180Speed ModeOpen Loop
365 Digital In5 SelSpeed Sel 281Minimum Speed0.0 Hz
366 Digital In6 SelSpeed Set 382Maximum Speed
380 Digital Out1 SelFault83Overspeed Limit10.0 Hz
381 Dig Out1 Level0.084Skip Frequency 10.0 Hz
382 Dig Out1 OnTime0.00 Secs85Skip Frequency 20.0 Hz
383 Dig Out1 OffTime0.00 Secs86Skip Frequency 30.0 Hz
384 Digital Out2 SelRun87Skip Freq Band0.0 Hz
385 Dig Out2 Level0.090Speed Ref A SelAnalog In 2
386 Dig Out2 OnTime0.00 Secs91Speed Ref A Hi[Maximum Speed]
387 Dig Out2 OffTime0.00 Secs92Speed Ref A Lo0.0 Hz
93Speed Ref B SelPreset Spd1
94Speed Ref B Hi[Maximum Speed]
95Speed Ref B Lo0.0 Hz
96TB Man Ref SelAnalog In 1
97TB Man Ref Hi[Maximum Speed]
98TB Man Ref Lo0.0 Hz
100Jog Speed10.0 Hz
50.0 or 60.0 Hz
(Dep. on voltage class)
ParParameter NameFactory DefaultProgrammed ValueParParameter NameFactory DefaultProgrammed Value
101 Preset Speed 15.0 Hz195MOP Rate1.0 Hz/s
102 Preset Speed 210.0 Hz196Param Access LvlBasic
103 Preset Speed 320.0 Hz197Reset To DefaltsReady
104 Preset Speed 430.0 Hz198Load Frm Usr SetReady
105 Preset Speed 540.0 Hz199Save To User SetReady
106 Preset Speed 650.0 Hz200Reset MetersReady
107 Preset Speed 760.0 Hz201LanguageNot Selected
117 Trim In SelectAnalog In 2202Voltage ClassBased on Drive Cat. No.
118 Trim Out Selectxxxxxxxxxxxxxx00203Drive ChecksumRead Only
119 Trim Hi60.0 Hz209Drive Status 1Read Only
120 Trim Lo0.0 Hz210Drive Status 2Read Only
121 Slip RPM @ FLA
122 Slip Comp Gain40.0212Drive Alarm 2Read Only
123 Slip RPM MeterRead Only213Speed Ref SourceRead Only
124 PI Configurationxxxxxxxxxx000000214Start InhibitsRead Only
125 PI Controlxxxxxxxxxxxxx000215Last Stop SourceRead Only
126 PI Reference SelPI Setpoint216Dig In StatusRead Only
127 PI Setpoint50.00%217Dig Out StatusRead Only
128 PI Feedback SelAnalog In 2218Drive TempRead Only
129 PI Integral Time2.00 Secs219Drive OL CountRead Only
130 PI Prop Gain1.00220Motor OL CountRead Only
131 PI Lower Limit-[Maximum Freq]224Fault FrequencyRead Only
132 PI Upper Limit+[Maximum Freq]225Fault AmpsRead Only
133 PI Preload0.0 Hz226Fault Bus VoltsRead Only
134 PI StatusRead Only227Status 1 @ FaultRead Only
135 PI Ref MeterRead Only228Status 2 @ FaultRead Only
136 PI Fdback MeterRead Only229Alarm 1 @ FaultRead Only
137 PI Error MeterRead Only230Alarm 2 @ FaultRead Only
138 PI Output MeterRead Only234Testpoint 1 Sel499
140 Accel Time 110.0 Secs235Testpoint 1 DataRead Only
141 Accel Time 210.0 Secs236Testpoint 2 Sel499
142 Decel Time 110.0 Secs237Testpoint 2 DataRead Only
143 Decel Time 210.0 Secs238Fault Config 1xxxxxxxxx1001x10
146 S-Curve %0%240Fault ClearReady
147 Current Lmt SelCur Lim Val241Fault Clear ModeEnabled
148 Current Lmt Val[Rated Amps] x 1.5242Power Up MarkerRead Only
149 Current Lmt Gain250243Fault 1 CodeRead Only
150 Drive OL ModeBoth-PWM 1st244Fault 1 TimeRead Only
151 PWM Frequency4 kHz245Fault 2 CodeRead Only
155 Stop Mode ARamp246Fault 2 TimeRead Only
156 Stop Mode BCoast247Fault 3 CodeRead Only
157 DC Brk Lvl SelDC Brake Lvl248Fault 3 TimeRead Only
158 DC Brake Level[Rated Amps]249Fault 4 CodeRead Only
159 DC Brake Time0.0 sec250Fault 4 TimeRead Only
160 Bus Reg Ki450259Alarm Config 1xxxxxx111x111111
161 Bus Reg Mode AAdjust Freq270DPI Baud Rate125 kbps
162 Bus Reg Mode BBoth-Frq 1st271Drive Logic RsltRead Only
163 DB Resistor TypeInternal Res272Drive Ref RsltRead Only
168 Start At PowerUpDisabled273Drive Ramp RsltRead Only
169 Flying Start EnDisabled276Logic Maskxxxxxxxxxx1x1111
170 Flying StartGain4000277Start Maskxxxxxxxxxx1x1111
174 Auto Rstrt Tries0278Jog Maskxxxxxxxxxx1x1111
175 Auto Rstrt Delay1.0 Secs279Direction Maskxxxxxxxxxx1x1111
184 Power Loss ModeCoast280Reference Maskxxxxxxxxxx1x1111
185 Power Loss Time0.5 Secs281Accel Maskxxxxxxxxxx1x1111
190 Direction ModeUnipolar282Decel Maskxxxxxxxxxx1x1111
192 Save HIM Refxxxxxxxxxxxxxxx1283Fault Clr Maskxxxxxxxxxx1x1111
193 Man Ref PreloadDisabled284MOP Maskxxxxxxxxxx1x1111
194 Save MOP Refxxxxxxxxxxxxxx00285Local Maskxxxxxxxxxx1x1111
Based on
[Motor NP RPM]211Drive Alarm 1Read Only
PowerFlex 70
Parameter Record
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
Drive Rated Amps x 2
Read Only
Drive Rating x -2
Drive Rating x +2
Read Only
Drive Rating x -2
Drive Rating x +2
Read Only
Drive Rated Volts
Read Only
Elapsed MWh
0.0 MWh
429496729.5 MWh
Read Only
Elapsed Run Time
0.0 Hrs
429496729.5 Hrs
Read Only
Based on Drive Rating
Read Only
Based on Drive Rating
Based on Drive Rating
Read Only
16
Analog In1 Value
-10.000V
+10.000V
Read Only
17
Analog In2 Value
-10.000V
+10.000V
Read Only
0.0 VAC
[Rated Volts]
Based on Drive Rating
0.0 Amps
[Rated Amps] x 2
Based on Drive Rating
5.0 Hz
400.0 Hz
110.0 or 130.0 Hz
[Maximum Speed]
0.0 Hz
5.0 Hz
400.0 Hz
on voltage class)
87
Skip Freq Band
0.0 Hz
30.0 Hz
0.0 Hz
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
1Output Freq- [Maximum Freq]+ [Maximum Freq]Read Only
2Commanded Freq- [Maximum Speed]+ [Maximum Speed]Read Only
3Output Current0.0 Amps
4Torque Current
5Flux Current
6Output Voltage0.0 VAC
7Output Power0.0 kWDrive Rated kW x 2Read Only
8Output Powr Fctr0.001.00Read Only
9
10
11MOP Frequency- [Maximum Frequency]+ [Maximum Frequency]Read Only
12DC Bus VoltageBased on Drive Rating
13DC Bus Memory
0.000 mA
20.000 mA
0.000 mA
20.000 mA
26Rated kW0.37 kW15.0 kWRead Only
27Rated VoltsBased on Drive RatingBased on Drive RatingRead Only
28Rated Amps1.1 Amps32.2 AmpsRead Only
29Control SW Ver0.00065.256Read Only
40Motor TypeInductionInduction
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
214Start InhibitsFaulted1
Type 2 Alarm0
Enable0
DC Bus Pchrg0
Stop Assertd1
Params Reset0
Startup Actv0
UnusedX
Digital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
UnusedX
UnusedX
215Last Stop SourcePwr RemovedRead Only
DPI Port 1
DPI Port 2
DPI Port 3
Reserved
DPI Port 5
Reserved
Digital In
Fault
Not Enabled
Sleep
Jog
216Dig In StatusDigital In10
Digital In20
Digital In30
Digital In40
Digital In50
Digital In60
217Dig Out StatusDigital Out10
Digital Out20
218Drive Temp
219Drive OL Count
220Motor OL Count
224Fault Frequency0.0+[Maximum Freq]Read Only
225Fault Amps0.0 Amps[Rated Amps] x 2Read Only
226Fault Bus Volts0.0 VDCMax Bus VoltsRead Only
227Status 1 @ FaultReady0
Active0
Command Dir1
Actual Dir1
Accelerating0
Decelerating0
Alarm0
Faulted1
At Speed0
Local ID 01
Local ID 11
Local ID 21
Spd Ref ID 00
Spd Ref ID 10
Spd Ref ID 20
8 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
Prechrg Actv
1
UnderVoltage
1
PowerLoss
1
Str At PwrUp
1
Anlg In Loss
1
IntDBRes OH
1
Unused
X
Drv OL Lvl 1
1
Drv OL Lvl 2
1
Decel Inhibt
1
278
Jog Mask
Digital In
1
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
228Status 2 @ FaultReady0
Active0
Running1
Jogging1
Stopping0
DC Braking0
AutoTuning0
UnusedX
AutoRst Ctdn0
Auto Rst Act1
Curr Limit1
Bus Freq Reg1
Motor Overld0
DPI at 500 k0
UnusedX
UnusedX
229Alarm 1 @ FaultPrechrg Actv0
UnderVoltage0
Power Loss0
Str At PwrUp0
Anlg In Loss0
IntDBRes OH0
UnusedX
Drv OL Lvl 10
Drv OL Lvl 20
Decel Inhibt0
230Alarm 2 @ FaultDigIn CflctA0
DigIn CflctB0
DigIn CflctC0
Bipolr Cflct0
MtrTyp Cflct0
NP Hz Cflct0
MaxFrq Cflct0
VHz NegSlope0
IR Vlts Rang0
FlxAmps Rang0
SpdRef Cflct0
UnusedX
UnusedX
UnusedX
UnusedX
UnusedX
234Testpoint 1 Sel0999499
235Testpoint 1 Data065535Read Only
236Testpoint 2 Sel0999499
237Testpoint 2 Data065535Read Only
238Fault Config 1Power Loss0
Decel 21
Spd Ref ID 00
Spd Ref ID 10
Spd Ref ID 20
MOP Dec0
272Drive Ref Rslt032767Read Only
273Drive Ramp Rslt032767Read Only
276Logic MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
277Start MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
9 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
DPI Port 5
1
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
279Direction MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
10 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
DPI Port 5
0
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
280Reference MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
281Accel MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
282Decel MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
283Fault Clr MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
284MOP MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
285Local MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
288Stop OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
289Start OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
290Jog OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
291Direction OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
292Reference OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
293Accel OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
11 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
4.000 mA
20.000 mA
10.0 Volt
-10.0 V
+10.0 V
0.0V
10.0 V
4.000 mA
20.000 mA
0.0 Volt
-10.0V
+10.0V
0.0V
10.0V
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
294Decel OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
295Fault Clr OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
296MOP OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
297Local OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
300Data In A103870
301Data In A203870
302Data In B103870
303Data In B203870
304Data In C103870
305Data In C203870
306Data In D103870
307Data In D203870
310Data Out A103870
311Data Out A203870
312Data Out B103870
313Data Out B203870
314Data Out C103870
315Data Out C203870
316Data Out D103870
317Data Out D203870
320Anlg In ConfigAnalog In 10
Analog In 20
321Anlg In Sqr RootAnalog In 10
Analog In 20
322Analog In 1 Hi
323Analog In 1 Lo
12 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Goto Preset1
Hold OutFreq
4.000 mA
20.000 mA
10.0 Volt
-10.0 V
+10.0 V
0.0
10.0 V
4.000 mA
20.000 mA
0.0 Volt
-10.0V
+10.0V
0.0V
10.0V
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Goto Preset1
Hold OutFreq
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
324Analog In 1 Loss
325Analog In 2 Hi
326Analog In 2 Lo
327Analog In 2 Loss
341Anlg Out AbsolutAnalog Out11
342Analog Out1 SelOutput FreqOutput Freq
Command Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Outout
%Motor OL
%Drive OL
343Analog Out1 Hi0.00 Volt10.00 Volt10.00 Volt
344Analog Out1 Lo0.00 Volt10.00 Volt0.00 Volt
361Digital In1 SelNot UsedStop - CF
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
13 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
362Digital In2 SelNot UsedStart
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
363Digital In3 SelNot UsedAuto/Manual
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
14 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
364Digital In4 SelNot UsedSpeed Sel 1
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
365Digital In5 SelNot UsedSpeed Sel 2
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
15 of 17
PowerFlex 70 Parameter Record
Date programmed
Drive Serial #
383
Dig Out1 OffTime
0.00 Secs
600.00 Secs
0.00 Secs
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
366Digital In6 SelNot UsedSpeed Set 3
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
380Digital Out1 SelFaultFault
Alarm
Ready
Run
Forward Run
Reverse Run
Auto Restart
Powerup Run
At Speed
At Freq
At Current
At Torque
At Temp
At Bus Volts
At PI Error
DC Braking
Curr Limit
Economize
Motor Overld
Power Loss
Input 1 Link
Input 2 Link
Input 3 Link
Input 4 Link
Input 5 Link
Input 6 Link
40Motor TypeInduction
41Motor NP VoltsBased on Drive Rating
42Motor NP FLABased on Drive Rating
43Motor NP HertzBased on Drive Cat. No.
44Motor NP RPM1750 RPM
45Motor NP PowerBased on Drive Rating
46Mtr NP Pwr UnitsBased on Drive Rating
47Motor OL HertzMotor NP Hz/3
48Motor OL Factor1.00
53Torque Perf ModeSensrls Vect
61AutotuneCalculate
62IR Voltage DropBased on Drive Rating
63Flux Current RefBased on Drive Rating
81Minimum Speed0.0 Hz
82Maximum Speed50.0 or 60.0 Hz
83Overspeed Limit10.0 Hz
90Speed Ref A SelAnalog In 2
91Speed Ref A Hi[Maximum Speed]
92Speed Ref A Lo0.0 Hz
140Accel Time 110.0 Secs
142Decel Time 110.0 Secs
201LanguageNot Selected
320Anlg In Config0
321Anlg In Sqr Root0
322Analog In 1 Hi10.0 Volt
323Analog In 1 Lo0.0 Volt
324Analog In 1 LossDisabled
361Digital In1 SelStop - CF
362Digital In2 SelStart
ParParameter NameFactory DefaultProgrammed ValueParParameter NameFactory DefaultProgrammed Value
273 Drive Ramp RsltRead Only1Output FreqRead Only
276 Logic Mask12Commanded FreqRead Only
277 Start Mask13Output CurrentRead Only
278 Jog Mask14Torque CurrentRead Only
279 Direction Mask15Flux CurrentRead Only
280 Reference Mask16Output VoltageRead Only
281 Accel Mask17Output PowerRead Only
282 Decel Mask18Output Powr FctrRead Only
283 Fault Clr Mask19Elapsed MWhRead Only
284 MOP Mask110Elapsed Run TimeRead Only
285 Local Mask111MOP FrequencyRead Only
288 Stop Owner112DC Bus VoltageRead Only
289 Start Owner113DC Bus MemoryRead Only
290 Jog Owner116Analog In1 ValueRead Only
291 Direction Owner117Analog In2 ValueRead Only
292 Reference Owner126Rated kWRead Only
293 Accel Owner127Rated VoltsRead Only
294 Decel Owner128Rated AmpsRead Only
295 Fault Clr Owner129Control SW VerRead Only
296 MOP Owner140Motor TypeInduction
297 Local Owner141Motor NP VoltsBased on Drive Rating
300 Data In A1042Motor NP FLABased on Drive Rating
301 Data In A2043Motor NP HertzBased on Drive Cat. No.
302 Data In B1044Motor NP RPM1750 RPM
303 Data In B2045Motor NP PowerBased on Drive Rating
304 Data In C1046Mtr NP Pwr UnitsBased on Drive Rating
305 Data In C2047Motor OL HertzMotor NP Hz/3
306 Data In D1048Motor OL Factor1.00
307 Data In D2053Torque Perf ModeSensris Vect
310 Data Out A1054Maximum VoltageDrive Rated Volts
311 Data Out A2055Maximum Freq110.0 or 130.0 Hz
312 Data Out B1056Compensation1
313 Data Out B2057Flux Up ModeManual
314 Data Out C1058Flux Up Time0.00 secs
315 Data Out C2059SV Boost Filter500
316 Data Out D1061AutotuneCalculate
317 Data Out D2062IR Voltage DropBased on Drive Rating
320 Anlg In Config063Flux Current RefBased on Drive Rating
321 Anlg In Sqr Root064Ixo Voltage DropBased on Drive Rating
322 Analog In 1 Hi10.0 Volt69Start/Acc BoostBased on Drive Rating
323 Analog In 1 Lo0.0 Volt70Run BoostBased on Drive Rating
324 Analog In 1 LossDisabled71Break Voltage[Motor NP Volts] x 0.25
325 Analog In 2 Hi10.0 Volt72Break Frequency[Motor NP Freq] x 0.25
326 Analog In 2 Lo0.0 Volt80Speed ModeOpen Loop
327 Analog In 2 LossDisabled81Minimum Speed0.0 Hz
340 Anlg Out Config182Maximum Speed50.0 or 60.0 Hz (Depend on voltage class)
341 Anlg Out Absolut183Overspeed Limit10.0 Hz
342 Analog Out1 SelOutput Freq84Skip Frequency 10.0 Hz
343 Analog Out1 Hi10.00 Volt85Skip Frequency 20.0 Hz
344 Analog Out1 Lo0.00 Volt86Skip Frequency 30.0 Hz
361 Digital In1 SelStop - CF87Skip Freq Band0.0 Hz
362 Digital In2 SelStart90Speed Ref A SelAnalog In 2
363 Digital In3 SelAuto/Manual91Speed Ref A Hi[Maximum Speed]
364 Digital In4 SelSpeed Sel 192Speed Ref A Lo0.0 Hz
365 Digital In5 SelSpeed Sel 293Speed Ref B SelPreset Spd1
366 Digital In6 SelSpeed Set 394Speed Ref B Hi[Maximum Speed]
380 Digital Out1 SelFault95Speed Ref B Lo0.0 Hz
381 Dig Out1 Level0.096TB Man Ref SelAnalog In 1
382 Dig Out1 OnTime0.00 Secs97TB Man Ref Hi[Maximum Speed]
383 Dig Out1 OffTime0.00 Secs98TB Man Ref Lo0.0 Hz
384 Digital Out2 SelRun100Jog Speed10.0 Hz
385 Dig Out2 Level0.0101Preset Speed 15.0 Hz
386 Dig Out2 OnTime0.00 Secs102Preset Speed 210.0 Hz
387 Dig Out2 OffTime0.00 Secs103Preset Speed 320.0 Hz
ParParameter NameFactory DefaultProgrammed ValueParParameter NameFactory DefaultProgrammed Value
104 Preset Speed 430.0 Hz195MOP Rate1.0 Hz/s
105 Preset Speed 540.0 Hz196Param Access LvlBasic
106 Preset Speed 650.0 Hz197Reset To DefaltsReady
107 Preset Speed 760.0 Hz198Load Frm Usr SetReady
117 Trim In SelectAnalog In 2199Save To User SetReady
118 Trim Out Select0200Reset MetersReady
119 Trim Hi60.0 Hz201LanguageNot Selected
120 Trim Lo0.0 Hz202Voltage ClassBased on Drive Cat. No.
121 Slip RPM @ FLABased on [Motor NP RPM]203Drive ChecksumRead Only
122 Slip Comp Gain40.0209Drive Status 10
123 Slip RPM MeterRead Only210Drive Status 20
124 PI Configuration0211Drive Alarm 10
125 PI Control0212Drive Alarm 20
126 PI Reference SelPI Setpoint213Speed Ref SourceRead Only
127 PI Setpoint50.00%214Start Inhibits1
128 PI Feedback SelAnalog In 2215Last Stop SourceRead Only
129 PI Integral Time2.00 Secs216Dig In Status0
130 PI Prop Gain1.00217Dig Out Status0
131 PI Lower Limit-[Maximum Freq]218Drive TempRead Only
132 PI Upper Limit+[Maximum Freq]219Drive OL CountRead Only
133 PI Preload0.0 Hz220Motor OL CountRead Only
134 PI Status0224Fault FrequencyRead Only
135 PI Ref MeterRead Only225Fault AmpsRead Only
136 PI Fdback MeterRead Only226Fault Bus VoltsRead Only
137 PI Error MeterRead Only227Status 1 @ Fault0
138 PI Output MeterRead Only228Status 2 @ Fault0
140 Accel Time 110.0 Secs229Alarm 1 @ Fault0
141 Accel Time 210.0 Secs230Alarm 2 @ Fault0
142 Decel Time 110.0 Secs234Testpoint 1 Sel499
143 Decel Time 210.0 Secs235Testpoint 1 DataRead Only
146 S-Curve %0%236Testpoint 2 Sel499
147 Current Lmt SelCur Lim Val237Testpoint 2 DataRead Only
148 Current Lmt Val[Rated Amps] x 1.5238Fault Config 10
149 Current Lmt Gain250240Fault ClearReady
150 Drive OL ModeBoth-PWM 1st241Fault Clear ModeEnabled
151 PWM Frequency4 kHz242Power Up MarkerRead Only
155 Stop Mode ARamp243Fault 1 CodeRead Only
156 Stop Mode BCoast244Fault 1 TimeRead Only
157 DC Brk Lvl SelDC Brake Lvl245Fault 2 CodeRead Only
158 DC Brake Level[Rated Amps]246Fault 2 TimeRead Only
159 DC Brake Time0.0 sec247Fault 3 CodeRead Only
160 Bus Reg Ki450248Fault 3 TimeRead Only
161 Bus Reg Mode AAdjust Freq249Fault 4 CodeRead Only
162 Bus Reg Mode BBoth-Frq 1st250Fault 4 TimeRead Only
163 DB Resistor TypeInternal Res251Fault 5 CodeRead Only
164 Bus Reg Kp500252Fault 5 TimeRead Only
165 Bus Reg Kd1000253Fault 6 CodeRead Only
168 Start At PowerUpDisabled254Fault 6 TimeRead Only
169 Flying Start EnDisabled255Fault 7 CodeRead Only
170 Flying StartGain4000256Fault 7 TimeRead Only
174 Auto Rstrt Tries0257Fault 8 CodeRead Only
175 Auto Rstrt Delay1.0 Secs258Fault 8 TimeRead Only
178 Sleep-Wake ModeDisabled259Alarm Config 11
179 Sleep-Wake RefAnalog In 2261Alarm ClearReady
180 Wake Level6.000 mA, 6.000 Volts262Alarm 1 CodeRead Only
181 Wake Time1.0 Secs263Alarm 2 CodeRead Only
182 Sleep Level5.000 mA, 5.000 Volts264Alarm 3 CodeRead Only
183 Sleep Time1.0 Secs265Alarm 4 CodeRead Only
184 Power Loss ModeCoast266Alarm 5 CodeRead Only
185 Power Loss Time0.5 Secs267Alarm 6 CodeRead Only
186 Power Loss LevelDrive Rated Volts268Alarm 7 CodeRead Only
190 Direction ModeUnipolar269Alarm 8 CodeRead Only
192 Save HIM Ref1270DPI Baud Rate125 kbps
193 Man Ref PreloadDisabled271Drive Logic Rslt0
194 Save MOP Ref0272Drive Ref RsltRead Only
PowerFlex 700
Parameter Record
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
Drive Rated Amps x 2
Read Only
Drive Rating x -2
Drive Rating x +2
Read Only
Drive Rating x -2
Drive Rating x +2
Read Only
Drive Rated Volts
Read Only
Elapsed MWh
0.0 MWh
429496729.5 MWh
Read Only
Elapsed Run Time
0.0 Hrs
429496729.5 Hrs
Read Only
Based on Drive Rating
Read Only
Based on Drive Rating
Based on Drive Rating
Read Only
16
Analog In1 Value
-10.000V
+10.000V
Read Only
17
Analog In2 Value
-10.000V
+10.000V
Read Only
0.0 VAC
[Rated Volts]
Based on Drive Rating
0.0 Amps
[Rated Amps] x 2
Based on Drive Rating
5.0 Hz
400.0 Hz
110.0 or 130.0 Hz
[Maximum Speed]
0.0 Hz
5.0 Hz
400.0 Hz
on voltage class)
87
Skip Freq Band
0.0 Hz
30.0 Hz
0.0 Hz
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
1Output Freq- [Maximum Freq]+ [Maximum Freq]Read Only
2Commanded Freq- [Maximum Speed]+ [Maximum Speed]Read Only
3Output Current0.0 Amps
4Torque Current
5Flux Current
6Output Voltage0.0 VAC
7Output Power0.0 kWDrive Rated kW x 2Read Only
8Output Powr Fctr0.001.00Read Only
9
10
11MOP Frequency- [Maximum Frequency]+ [Maximum Frequency]Read Only
12DC Bus VoltageBased on Drive Rating
13DC Bus Memory
0.000 mA
20.000 mA
0.000 mA
20.000 mA
26Rated kW0.37 kW15.0 kWRead Only
27Rated VoltsBased on Drive RatingBased on Drive RatingRead Only
28Rated Amps1.1 Amps32.2 AmpsRead Only
29Control SW Ver0.00065.256Read Only
40Motor TypeInductionInduction
DPI Port 1
DPI Port 2
DPI Port 3
DPI Port 4
DPI Port 5
118 Trim Out SelectTrim Ref A0
Trim Ref B0
119 Trim Hi
120 Trim Lo
121 Slip RPM @ FLA0.0 RPM1200.0 RPM
122 Slip Comp Gain1.0100.040.0
123 Slip RPM Meter0.0 RPM300.0 RPMRead Only
124 PI ConfigurationExcl Mode0
DPI Port 5
129 PI Integral Time0.00 Secs100.00 Secs2.00 Secs
130 PI Prop Gain0.00100.001.00
131 PI Lower Limit
132 PI Upper Limit
133 PI Preload
134 PI StatusPI Enabled0
PI Hold0
PI Reset0
PI InLimit0
135 PI Ref Meter-100.00 %+100.00 %Read Only
136 PI Fdback Meter-100.00 %+100.00 %Read Only
137 PI Error Meter-100.00 %+100.00 %Read Only
138 PI Output Meter-[Maximum Freq]+[Maximum Freq]Read Only
140 Accel Time 10.1 Secs3600.0 Secs10.0 Secs
141 Accel Time 20.1 Secs3600.0 Secs10.0 Secs
142 Decel Time 10.1 Secs3600.0 Secs10.0 Secs
143 Decel Time 20.1 Secs3600.0 Secs10.0 Secs
146 S-Curve %0%100%0%
147 Current Lmt SelCur Lim ValCur Lim Val
Analog In 1
Analog In 2
148 Current Lmt Val
149 Current Lmt Gain05000250
150 Drive OL ModeDisabledBoth-PWM 1st
Reduce CLim
Reduce PWM
Both-PWM 1st
151 PWM Frequency
155 Stop Mode ACoastRamp
Ramp
Ramp to Hold
4 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
0.0 Amps
[Rated Amps] x 1.5
[Rated Amps]
Based on Drive Cat. No.
203
Drive Checksum
0
65535
Read Only
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
156 Stop Mode BCoastCoast
Ramp
Ramp to Hold
DC Brake
157 DC Brk Lvl SelDC Brake LvlDC Brake Lvl
Analog In 1
Analog In 2
158 DC Brake Level
159 DC Brake Time0.0 sec90.0 sec0.0 sec
160 Bus Reg Ki05000450
161 Bus Reg Mode ADisabledAdjust Freq
Adjust Freq
Dynamic Brak
Both-DB 1st
Both-Frq 1st
162 Bus Reg Mode BDisabledBoth-Frq 1st
Adjust Freq
Dynamic Brak
Both-DB 1st
Both-Frq 1st
163 DB Resistor TypeInternal ResInternal Res
External Res
None
168 Start At PowerUpDisabledDisabled
Enabled
169 Flying Start EnDisabledDisabled
Enabled
170 Flying StartGain20327674000
174 Auto Rstrt Tries090
175 Auto Rstrt Delay0.5 Secs30.0 Secs1.0 Secs
184 Power Loss ModeCoastCoast
Decel
185 Power Loss Time0.0 Secs60.0 Secs0.5 Secs
190 Direction ModeUnipolarUnipolar
Bipolar
Reverse Dis
192 Save HIM RefAt Powr Down1
193 Man Ref PreloadDisabledDisabled
Digital In20
Digital In30
Digital In40
Digital In50
Digital In60
217 Dig Out StatusDigital Out10
Digital Out20
218 Drive Temp
219 Drive OL Count
220 Motor OL Count
224 Fault Frequency0.0+[Maximum Freq]Read Only
225 Fault Amps0.0 Amps[Rated Amps] x 2Read Only
7 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
Decel Inhibt
0
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
227 Status 1 @ FaultReady0
Active0
Command Dir1
Actual Dir1
Accelerating0
Decelerating0
Alarm0
Faulted1
At Speed0
Local ID 01
Local ID 11
Local ID 21
Spd Ref ID 00
Spd Ref ID 10
Spd Ref ID 20
Spd Ref ID 30
228 Status 2 @ FaultReady0
Active0
Running1
Jogging1
Stopping0
DC Braking0
AutoTuning0
UnusedX
AutoRst Ctdn0
Auto Rst Act1
Curr Limit1
Bus Freq Reg1
Motor Overld0
DPI at 500 k0
UnusedX
UnusedX
229 Alarm 1 @ FaultPrechrg Actv0
UnderVoltage0
Power Loss0
Str At PwrUp0
Anlg In Loss0
IntDBRes OH0
UnusedX
Drv OL Lvl 10
Drv OL Lvl 20
8 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
9999
Read Only
429496.7295 Hr.
Read Only
Prechrg Actv
1
UnderVoltage
1
PowerLoss
1
Str At PwrUp
1
Anlg In Loss
1
IntDBRes OH
1
Unused
X
Drv OL Lvl 1
1
Drv OL Lvl 2
1
Decel Inhibt
1
DPI Port 2
1
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
Decel 21
Spd Ref ID 00
Spd Ref ID 10
Spd Ref ID 20
MOP Dec0
272 Drive Ref Rslt032767Read Only
273 Drive Ramp Rslt032767Read Only
276 Logic MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
277 Start MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
278 Jog MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
279 Direction MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
280 Reference MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
281 Accel MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
282 Decel MaskDigital In1
DPI Port 11
9 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
DPI Port 5
1
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
DPI Port 31
UnusedX
DPI Port 51
283 Fault Clr MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
284 MOP MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
10 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
4.000 mA
20.000 mA
10.0 Volt
-10.0 V
+10.0 V
0.0V
10.0 V
4.000 mA
20.000 mA
0.0 Volt
-10.0V
+10.0V
0.0V
10.0V
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Goto Preset1
Hold OutFreq
4.000 mA
20.000 mA
10.0 Volt
-10.0 V
+10.0 V
0.0
10.0 V
4.000 mA
20.000 mA
0.0 Volt
-10.0V
+10.0V
0.0V
10.0V
Disabled
Disabled
Fault
Hold Input
Set Input Lo
Set Input Hi
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
285 Local MaskDigital In1
DPI Port 11
DPI Port 21
DPI Port 31
UnusedX
DPI Port 51
288 Stop OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
289 Start OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
290 Jog OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
291 Direction OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
292 Reference OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
293 Accel OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
294 Decel OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
295 Fault Clr OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
296 MOP OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
297 Local OwnerDigital In1
DPI Port 10
DPI Port 20
DPI Port 30
UnusedX
DPI Port 50
300 Data In A103870
301 Data In A203870
302 Data In B103870
303 Data In B203870
304 Data In C103870
305 Data In C203870
306 Data In D103870
307 Data In D203870
310 Data Out A103870
311 Data Out A203870
312 Data Out B103870
313 Data Out B203870
314 Data Out C103870
315 Data Out C203870
316 Data Out D103870
317 Data Out D203870
320 Anlg In ConfigAnalog In 10
Analog In 20
321 Anlg In Sqr RootAnalog In 10
Analog In 20
322 Analog In 1 Hi
323 Analog In 1 Lo
324 Analog In 1 Loss
325 Analog In 2 Hi
326 Analog In 2 Lo
327 Analog In 2 Loss
11 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
Goto Preset1
Hold OutFreq
341
Anlg Out Absolut
Analog Out1
1
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
12 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
PI Reset
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
342 Analog Out1 SelOutput FreqOutput Freq
Command Freq
Output Amps
Torque Amps
Flux Amps
Output Power
Output Volts
DC Bus Volts
PI Reference
PI Feedback
PI Error
PI Outout
%Motor OL
%Drive OL
343 Analog Out1 Hi0.00 Volt10.00 Volt10.00 Volt
344 Analog Out1 Lo0.00 Volt10.00 Volt0.00 Volt
361 Digital In1 SelNot UsedStop - CF
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
362 Digital In2 SelNot UsedStart
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
13 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
363 Digital In3 SelNot UsedAuto/Manual
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
14 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
PI Reset
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
364 Digital In4 SelNot UsedSpeed Sel 1
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
365 Digital In5 SelNot UsedSpeed Sel 2
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
15 of 17
PowerFlex 700 Parameter Record
Date programmed
Drive Serial #
383
Dig Out1 OffTime
0.00 Secs
600.00 Secs
0.00 Secs
Machine #
ParParameter NameMinimum ValueMaximum ValueFactory DefaultProgrammed Value
366 Digital In6 SelNot UsedSpeed Set 3
Enable
Clear Faults
Aux Fault
Stop - CF
Start
Fwd/Reverse
Run
Run Forward
Run Reverse
Jog
Jog Forward
Jog Reverse
Stop Mode B
Bus Reg MD B
Speed Sel 1
Speed Sel 2
Speed Sel 3
Auto/Manual
Local
Acc2 & Dec2
Accel 2
Decel 2
MOP Inc
MOP Dec
Excl Link
PI Enable
PI Hold
PI Reset
380 Digital Out1 SelFaultFault
Alarm
Ready
Run
Forward Run
Reverse Run
Auto Restart
Powerup Run
At Speed
At Freq
At Current
At Torque
At Temp
At Bus Volts
At PI Error
DC Braking
Curr Limit
Economize
Motor Overld
Power Loss
Input 1 Link
Input 2 Link
Input 3 Link
Input 4 Link
Input 5 Link
Input 6 Link