Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
available from
) describes some
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the
consequence
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that
surfaces may reach dangerous temperatures.
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Software, Rockwell Automation, Micro800, Micro850, Connected Components Workbench, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides
information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• supporting information for Micro800™
Who Should Use this
Manual
Purpose of this Manual
Additional Resources
Use this manual if you are responsible for designing, installing, programming, or
troubleshooting control systems that use Micro800 controllers.
You should have a basic understanding of electrical circuitry and familiarity with
relay logic. If you do not, obtain the proper training before using this product.
This manual is a reference guide for Micro800 expansion I/O modules. It
describes the procedures you use to install, wire, and troubleshoot your expansion
I/O. This manual:
• gives you an overview of expansion I/O features and configuration
parameter
• gives you an overview of the Micro800 controller system
Refer to the Online Help provided with Connected Components Workbench™
software for more information about programming.
These documents contain additional information concerning related Rockwell
Automation products.
viiiRockwell Automation Publication 2080-UM003A-EN-E - March 2013
Hardware Features
Chapter
1
Micro800 Expansion I/O
Modules
Micro850 controllers support a range of discrete and analog expansion I/O
modules. You can attach up to four expansion I/O modules, in any combination,
to a Micro850 controller, as long as the total number of embedded, plug-in, and
expansion discrete I/O points is less than or equal to 132.
The following expansion I/O modules are compatible with Micro850
controllers:
2085-OV16Discrete16-point, 12/24V DC Sink Transistor Output
2085-OB16Discrete16-point, 12/24V DC Source Transistor Output
2085-OW8Discrete8-point, AC/DC Relay Output
2085-OW16Discrete16-point, AC/DC Relay Output
2085-IF4Analog4-channel, 14-bit isolated
2085-IF8Analog8-channel, 14-bit isolated
(1)
voltage/current input
(1)
voltage/current input
Rockwell Automation Publication 2080-UM003A-EN-E - March 20131
Chapter 1 Hardware Features
1
1
45308
8
Front view
Right top view
45307
1
2085-OW8 shown
2
5
5
3
3
3
6
4
7
6
Micro800 Expansion I/O Modules
CatalogTypeDescription
2085-OF4Analog4-channel, 12-bit isolated
2085-IRT4Analog4-channel, 16-bit isolated
2085-ECRTerminator2085 bus terminator
(1) Refers to isolation from field side wiring to controller, not channel-to-channel isolation.
(1)
voltage/current output
(1)
RTD and Thermocouple input module
The bus terminator, 2085-ECR, serves as an end cap and terminates the end of
the serial communication bus. It is required whenever an expansion I/O module
is connected to the controller and should be connected to the last expansion I/O
module in the system.
Hardware Features
Micro850 expansion I/O modules come as a single-width (87 x 28 x 90 mm,
HxWxD) or double-width (87 x 46 x 90 mm, HxWxD) form factor. See
specifications for Expansion I/O on page 240
dimensions.
Single-width Expansion I/O
for information on module
2Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Double-width Expansion I/O
1
1
45297
8
Front view
Right top view
45296
1
2085-OW16 shown
2
9
5
3
3
3
4
6
7
6
2
1
6
8
7
6
3
1
2
4
5
3
9
45927
Right top view
Front view
Module Description
Hardware Features Chapter 1
(1) The removable terminal block has slots for mechanical keying, to prevent inadvertently making the wrong
wire connections to your module. Expansion I/O modules are shipped with keys.
Rockwell Automation Publication 2080-UM003A-EN-E - March 20133
Chapter 1 Hardware Features
2085-IQ32T Hardware Components
DescriptionDescription
1Mounting screw hole / mounting foot6bus connector (male and female)
2Connector7latch hooks
3Connector retaining arm8I/O status LEDs
4Cable grip9DIN rail mounting latch
5Module interconnecting latch
Summary
This chapter included a brief introduction to the different analog and discrete
Micro800 expansion I/O modules and their hardware features.
4Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Chapter
2
Discrete and Analog Expansion I/O Features
Overview
Discrete Expansion I/O
Features
This section includes a brief description of the different features and
configuration parameters for the analog and discrete Micro800 expansion I/O
modules. It covers the following topics.
TopicPage
Discrete Expansion I/O Features5
Discrete Input5
Discrete Output6
Analog Expansion I/O Features6
Analog Input and Output7
Specialty Module 2085-IRT4 Temperature Input Module11
Micro800 discrete expansion I/O modules are input/output modules that
provide On/Off detection and actuation.
Module Information
The Connected Components Workbench programming software makes it easy
to configure the modules as most module features can be enabled or disabled
through the device configuration portion of the software. You can also use the
software to check any expansion I/O module in the system to retrieve:
• hardware revision information
• vendor ID
• module information
Channel Status Indicator Information
The discrete expansion I/O modules have yellow status indicators for each input/
output point which indicates the On/Off state of the point.
Discrete Input
Discrete input modules interface to sensing devices and detect whether they are
On or Off. These modules convert AC or DC On/Off signals from user devices
to appropriate logic level for use within the processor.
Rockwell Automation Publication 2080-UM003A-EN-E - March 20135
Chapter 2 Discrete and Analog Expansion I/O Features
TIP
IMPORTANT
The 2085-IA8, 2085-IM8, 2085-IQ16 and 2085-IQ32T modules update the
controller with new data whenever an input point transitions from On to Off and
Off to On.
On to Off and Off to On filter times can be adjusted through the Connected
Components Workbench software. These filters improve noise immunity within
a signal. A larger filter value affects the length of delay times for signals from these
modules.
You can select from a series of operational ranges for each channel. The range
designates the minimum and maximum signals that are detectable by the module.
Discrete Output
Output modules may be used to drive a variety of output devices. Typical output
devices compatible with the outputs include:
• motor starters
• solenoids
• indicators
Analog Expansion I/O
Features
Follow these guidelines when designing a system.
• Make sure that the outputs can supply the necessary surge and continuous
current for proper operation. (See Specifications
on page 45 for more
information.)
• Make sure that the surge and continuous current are not exceeded. Damage
to the module could result. When sizing output loads, check the
documentation supplied with the output device for the surge and
continuous current needed to operate the device. The Micro800 standard
digital outputs are capable of directly driving the Micro800 standard
digital inputs.
User-configurable options are not available in Connected Components
Workbench for discrete output modules.
On controller minor and major fault, all output channels are de-energized.
This section pertains to the following Micro800 analog expansion I/O modules:
Micro800 Expansion I/O Modules
CatalogTypeDescription
2085-IF4Analog4-channel, 14-bit isolated
2085-IF8Analog8-channel, 14-bit isolated
(1)
voltage/current input
(1)
voltage/current input
6Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Discrete and Analog Expansion I/O Features Chapter 2
Micro800 Expansion I/O Modules
CatalogTypeDescription
2085-OF4Analog4-channel, 12-bit isolated
2085-IRT4Analog4-channel, 16-bit isolated
2085-ECRTerminator2085 bus terminator
(1) Refers to isolation from field side wiring to controller, not channel-to-channel isolation.
(1)
voltage/current output
(1)
RTD and Thermocouple input module
Analog expansion I/O modules are interface modules that convert analog signals
to digital values for inputs and convert digital values to analog signals for outputs.
Controllers can then use these signals for control purposes.
Analog Input and Output
Input/Output Types and Ranges
The 2085-IF4 and 2085-IF8 modules support four and eight input channels,
respectively, while the 2085-OF4 supports four output channels. Each of the
channels can be configured as current or voltage input/output, with current
mode as default configuration.
Input/Output Type/Range for 2085-IF4, 2085-IF8, and 2085-OF4
ModuleInput/Output Type/Range
2085-IF40…20 mA
2085-IF8
2085-OF4
4…20 mA (default)
-10…10 V
0…10 V
To use an input or output as a current or voltage device, you must:
• wire the input/output connector for the correct input/output type (see
Input/Output Wiring
on page 15)
• configure the input/output as current or voltage through Connected
Components Workbench (see Configure Your Expansion I/O Module
page 29)
Data formats
This parameter configures each channel to present analog data in any of the
following formats:
• Raw/Proportional Data –The value presented to the controller is
proportional to the selected input and scaled into the maximum data range
allowed by the bit resolution of the A/D converter. For example, the data
value range for a ±10V DC user input is -32,768…32,767, which covers
the full-scale range of -10.5…10.5V. See Valid Range of the Data Formats
for 2085-IF4, 2085-IF8, and 2085-OF4 on page 8.
on
Rockwell Automation Publication 2080-UM003A-EN-E - March 20137
Chapter 2 Discrete and Analog Expansion I/O Features
Valid Range of the Data Formats for 2085-IF4, 2085-IF8, and 2085-OF4
The valid range of each Data Format corresponds to the full range of each Type/
Range (or normal range). For example, the full range of 0…20 mA is 0…21 mA.
Valid Range of the 2085-IF4 and 2085-IF8 Data Formats
Data FormatType/Range
Raw/Proportional Data
Engineering Units
Percent Range
• Engineering Units – The module scales the analog input data to the actual
current or voltage values for the selected input range. The resolution of the
engineering units is 0.001V or 0.001 mA per count.
• Percent Range – The input data is presented as a percentage of the normal
operating range. For example, 0V…10V DC equals 0…100%. The amount
over and under the normal operating range (the full-scale range) is also
supported.
0…20 mA
(1)
(2)
(3)
0…210003200…21000-10500…10500-500…10500
0…10500-500…10625Not supported-500…10500
(4)
4…20 mA
(4)
-10…10V
-32768…32767
(4)
0…10 V
(4)
(1) See Convert Analog Value to Data Format Value on page 9.
(2) The resolution is 0.001V or 0.001 mA per count. For example, 9999 here means 9.999V or 9.999 mA
(or 9999 x 0.001).
(3) The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%). See Convert
Analog Value to Data Format Value on page 9
(4) The full range value of:
a. 0…20 mA is 0…21 mA
b. 4 to 20 mA is 3.2…21 mA
c. -10…10V is -10.5…10.5V
d. 0…10V is -0.5…10.5V
Valid Range of the 2085-OF4 Data Formats
Data FormatType/Range
0…20 mA
Raw/Proportional
(1)
Data
Engineering Units
Percent Range
(1) See Convert Analog Value to Data Format Value on page 9.
(2) The resolution is 0.001V or 0.001 mA per count. For example, 9999 here means 9.999V or 9.999 mA (or 9999 x
0.001.
(3) The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%). See Convert
Analog Value to Data Format Value on page 9.
(4) The full range value of:
a. 0…20 mA is 0…21 mA
b. 4…20 mA is 3.2…21 mA
c. -10…10V is -10.5…10.5V
d. 0…10V is 0…10.5V
(2)
0…210003200…21000-10500…105000…10500
(3)
0…10500-500…10625Not supported0…10500
(4)
4…20 mA
(4)
-10…10V
-32768…32767
(4)
0…10V
(4)
8Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Discrete and Analog Expansion I/O Features Chapter 2
Convert Analog Value to Data Format Value
The formula for converting an analog value x to a data format value y (or
conversely, deriving data format value y to analog value x) is as follows:
Y = ((X - Minimum Value of X Range)*(Range of Y)/(Range of X)) +
(Minimum Value of Y Range)
Example 1:
Find the analog value Y of Type/Range 4…20 mA when the Raw/Proportional
Data X is -20000.
Given:
X = -20000
Minimum value of X Range = -32768
Range of X = 32767 - (-32768) = 65535
Range of Y = 21- 3.2 = 17.8
Minimum value of Y Range = 3.2
Using the conversion formula:
Y = (-20000 - (-32768))*17.8/65535 + (3.2) = 6.668 mA
Example 2:
Find the Raw/Proportional value (Y) of 10 mA (X) for type/range 4…20 mA.
Given:
X = 10 mA
Minimum Value of X Range = 3.2 mA (Minimum value of 4…20 mA)
Range of X = 21 - 3.2 = 17.8 mA (Range of 4…20 mA)
Range of Y = 32767 - (-32768) = 65535 (Range of Raw/Proportional
Data)
Minimum Value of Y Range = -32768. (Min value of Raw/Proportional
Data)
Using the conversion formula:
Y = -7732.15 (decimals are not displayed)
Input Filter
For the input modules, 2085-IF4 and 2085-IF8, the input filter parameter lets
you specify the frequency filter type for each channel. Frequency filter type
affects noise rejection, as explained below. Select a frequency filter type
considering acceptable noise and response time.
Through the Connected Components Workbench software, you can configure
input filter as:
• 50/60Hz Rejection (default)
• No Filter
• 2-Point Moving Average
Rockwell Automation Publication 2080-UM003A-EN-E - March 20139
Chapter 2 Discrete and Analog Expansion I/O Features
Noise Rejection
The input modules use a digital filter that provides noise rejection for the input
signals.
The moving average filter reduces the high frequencies and random white noise
while keeping an optimal step response. (See specifications for Analog Expansion
I/O on page 50 for minimum and maximum response times.)
Normal Mode Rejection is better than 40 dB, while Common Mode Rejection is
better than 60 dB @ 50/60 Hz, with the 50/60 Hz rejection filters selected. The
modules perform well in the presence of common mode noise as long as the
signals applied to the user plus and minus input terminals do not exceed the
common mode voltage rating (±10 V) of the modules. Improper earth ground
may be a source of common mode noise.
• 4-Point Moving Average
• 8-Point Moving Average
Process Level Alarms
Process level alarms alert you when the module has exceeded configured high and
low limits for each channel (for input modules, it provides additional high-high
and low-low alarms). When the channel input or output goes below a low alarm
or above a high alarm, a bit is set in the status words. All Alarm Status bits can be
read individually or read through the Channel Status Byte.
For the output module, 2085-OF4, it is possible to latch the alarm status bit
when the latch configuration is enabled.
You can configure each channel alarm individually.
Clamping Limits and Alarm
For the output module, 2085-OF4, clamping limits the output from the analog
module to remain within a range configured by the controller, even when the
controller commands an output outside that range. This safety feature sets a high
clamp and a low clamp. Once clamps are determined for a module, any data
received from the controller that exceeds those clamps transitions the output to
that limit but not beyond the clamp value. It also sets the alarm status bit when
the alarm is enabled. It is also possible to latch the alarm status bit when the latch
configuration is enabled.
For example, an application may set the high clamp on a module for 8V and the
low clamp for -8V. If a controller sends a value corresponding to 9V to the
module, the module will only apply 8V to its screw terminals.
You can configure the clamp limit (high/low clamp), the associated alarm, and its
latching configuration on a per channel basis.
10Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Discrete and Analog Expansion I/O Features Chapter 2
The following table shows the default values of the High/Low Clamps (in the
order of low clamp value followed by the high clamp value) for the respective
type/range when they are first enabled. You can change these values (within their
full range) according to your application.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201311
Chapter 2 Discrete and Analog Expansion I/O Features
Supported RTD Types and Ohms Range
Sensor RangeRange
100 Ω Nickel 618-60…250 °C(-76…482 °F)
200 Ω Nickel 618-60…200 °C(-76…392 °F)
120 Ω Nickel 672-80…260 °C(-112…500 °F)
10 Ω Copper 427-200…260 °C(-328…500 °F)
Ohms0…500 Ohms
Data format
You can configure the following data formats for channels 0…3 through the
Connected Components Workbench software.
• Engineering Units x 1 – If you select engineering units x 1 as the data
format for a Thermocouple and RTD input, the module scales input data
to the actual temperature values for the selected Thermocouple/RTD type
per Thermocouple/RTD standard. It expresses temperatures in 0.1 °C/° F
units. For resistance inputs, the module expresses resistance in 0.1 ohm per
count. For mV inputs, the module expresses it in 0.01 mV per count.
• Engineering Units x 10 – For a Thermocouple or RTD input, the module
scales input data to the actual temperature values for the selected
Thermocouple/RTD type per Thermocouple/RTD standard. With this
format, the module expresses temperatures in 1 °C/° F units. For resistance
inputs, the module expresses resistance in 1 ohm per count. For mV inputs,
the module expresses it in 0.1 mV per count.
• Raw/Proportional Data Format – The value presented to the controller is
proportional to the selected input and scaled into the maximum data range
allowed by the bit resolution of the A/D converter. For example, the full
data value range for a thermocouple type B 300...1800 °C is mapped to
-32768...32767. See Convert Analog Value to Data Format Value
on
page 13 for the conversion method.
• Percent Range – The input data is presented as a percentage of the normal
operating range. For example, 0…100 mV equals 0…100% or 300..1800 °C
equals 0...100% for thermocouple type B sensor. See Convert Analog Value
to Data Format Value on page 13 for the conversion method.
Valid Range of the Data Formats for 2085-IRT4
The following table shows the valid range of the Data Format versus the Data
Type/Range for channels 0…3.
12Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Discrete and Analog Expansion I/O Features Chapter 2
Valid Range of the 2085-IRT4 Data Formats
Data FormatSensor Type – Temperature
Raw/Proportional Data
Engineering Units x 1Temperature Value
Engineering Units x 10Temperature Value
Percent Range
(1) See Convert Analog Value to Data Format Value on page 13.
(2) The resolution is 0.01% per count. For example, 9999 here means 99.99% (or 9999 x 0.01%). See Convert
Analog Value to Data Format Value on page 13 for the conversion method.
(3) The resolution is 0.1 °C/°F per count. For example, 999 here means 99.9 °C/°F (or 999 x 0.1 °C/°F). The range
depends on the selected sensor type.
(4) The resolution is 1 °C/°F per count. For example, 999 here means 999 °C/°F (or 999 x 1 °C/°F). The range
depends on the selected sensor type.
(5) The resolution is 0.01 mV per count. For example, 9999 here means 99.99 mV (or 9999 x 0.01 mV).
(6) The resolution is 0.1 mV per count. For example, 999 here means 99.9 mV (or 999 x 0.1 mV).
(7) The resolution is 0.1 ohm per count. For example, 4999 here means 499.9 ohm (or 4999 x 0.1 ohm).
(8) The resolution is 1 ohm per count. For example, 499 here means 499 ohm (or 499 x 1 ohm).
(2)
(10 Thermocouples, 8 RTDs)
(1)
(3)
(°C/°F)
(4)
(°C/°F)
Sensor Type
0…100 mV
-32768…32767
0…10000
0…1000
0…10000
(5)
(6)
Sensor Type
0…500 ohms
(7)
0…5000
(8)
0…500
Convert Analog Value to Data Format Value
The formula for converting an analog value x to a data format value y, or
converting data format value y to analog value x, is as follows:
Y = ((X - Minimum Value of X Range)*(Range of Y)/(Range of X)) +
(Minimum Value of Y Range)
Example:
Find the temperature value Y of thermocouple type K when the Raw/
Proportional Data X is -20000.
Given:
X = -20000 (Raw/Proportional Value)
Minimum value of X Range = -32768 (Minimum value of Raw/
Proportional Data)
Range of X = 32767 - (-32768) = 65535 (Range of Raw/Proportional
Data)
Range of Y = 1372 - (-270) = 1642 (Range of Thermocouple K in °C)
Minimum value of Y Range = -270 °C (Minimum value of Thermocouple
K)
Then:
Y = (-20000 - (-32768))*1642/65535 + (-270 °C) = 49.9 °C
Rockwell Automation Publication 2080-UM003A-EN-E - March 201313
Chapter 2 Discrete and Analog Expansion I/O Features
TIP
Temperature Units
Temperature value can be set to °C (default) or °F.
Open circuit response
This parameter defines the response to be taken by the module during an open
circuit.
Filter frequency
• Upscale – Sets input to full upper scale value of channel data word. The
full-scale value is determined by the selected input type, data format, and
scaling.
• Downscale – Sets input to full lower scale value of channel data word. The
low scale value is determined by the selected input type, data format, and
scaling.
• Hold Last State – Sets input to last input value.
• Zero – Sets input to 0 to force the channel data word to 0.
The 2085-IRT4 module uses a digital filter that provides noise rejection for the
input signals. The filter is set by default at 4 Hz. The digital filter provides
-3 dB (50% amplitude) attenuation at a filter frequency of 4 Hz.
The -3 dB frequency is the filter cut-off frequency. The cut-off frequency is
defined as the point on the frequency response curve where frequency
components of the input signal are passed with 3 dB of attenuation. All input
frequency components at or below the cut-off frequency are passed by the digital
filter with less than 3 dB of attenuation. All frequency components above the
cutoff frequency are increasingly attenuated.
The cut-off frequency for each channel is defined by its filter frequency selection
and is equal to the filter frequency setting. Choose a filter frequency so that your
fastest changing signal is below that of the filter’s cut-off frequency. The cut-off
frequency should not be confused with the update time. The cut-off frequency
relates to how the digital filter attenuates frequency components of the input
signal. The update time defines the rate at which an input channel is scanned and
its channel data word is updated.
A lower filter frequency provides a better noise rejection, but it also increases the
update time. Conversely, a higher filter frequency provides a faster update time,
but it decreases the noise rejection and effective resolution.
For quickstart instructions on how to add, configure, delete and replace
your expansion I/O module, see Configure Your Expansion I/O Module
Summary
14Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
This chapter discussed the features of the analog and discrete Micro800
expansion I/O modules.
.
Chapter
L1
L2
I-00
I-01
COM
I-02
I-03
COM
I-04
I-05
COM
COM
I-06
I-07
120V AC (2085-IA8)
240V AC (2085-IM8)
45313
3
Wiring Connections
In solid-state control systems, grounding and wire routing helps limit the effects
of noise due to electromagnetic interference (EMI).
ATTENTION: Do not wire more than 2 conductors on any single terminal.
Input/Output Wiring
Basic wiring of devices to the expansion I/O modules are shown below.
2085-IA8 or 2085-IM8
Rockwell Automation Publication 2080-UM003A-EN-E - March 201315
Chapter 3 Wiring Connections
I-00
I-01
COM0
I-02
I-03
COM0
I-04
I-05
COM0
I-06
I-07
COM0
I-08
I-09
COM1
I-10
I-11
COM1
I-12
I-13
COM1
I-14
I-15
COM1
45299
Terminal Block 1Terminal Block 2
-DC (sinking)
+DC (sourcing)
O-00
O-01
L1
O-02
O-03
L1
O-04
O-05
L1
L1
O-06
O-07
L1
L2
120V / 240V AC
45314
2085-IQ16
2085-OA8
16Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
2085-IQ32T
45300
See Wiring Options for the 2085-IQ32T Module on page 21.
Wiring Connections Chapter 3
COM0
COM0
I-00
I-01
I-02
I-03
I-04
I-05
I-06
I-07
I-08
I-09
I-10
I-11
COM2
COM2
I-16
I-17
I-18
I-19
I-20
I-21
I-22
I-23
I-24
I-25
I-26
I-27
I-12
I-13
I-14
I-15
COM1
COM1
I-28
I-29
I-30
I-31
COM3
COM3
Rockwell Automation Publication 2080-UM003A-EN-E - March 201317
Chapter 3 Wiring Connections
+CM0
O-00
O-01
O-02
O-03
-CM0
O-04
O-05
O-06
O-07
-CM0
NC
+CM1
O-08
O-09
O-10
O-11
-CM1
O-12
O-13
O-14
O-15
-CM1
NC
24V DC (Source)
+CM0
O-00
O-01
O-02
O-03
-CM0
O-04
O-05
O-06
O-07
-CM0
NC
+CM1
O-08
O-09
O-10
O-11
-CM0
O-12
O-13
O-14
O-15
-CM0
NC
24V DC (Sink)
45306
2085-OV16
2085-OB16
45327
Terminal Block 1Terminal Block 2
Terminal Block 1Terminal Block 2
CM0
O-00
O-01
CM1
O-02
O-03
CM2
O-04
O-05
CM3
O-06
O-07
L1 or +DC or -DC
L2 or -DC or +DC
45310
2085-OB16 and 2085-OV16
18Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
2085-OW8
2085-OW16
CM0
O-00
O-01
CM1
O-02
O-03
CM2
O-04
O-05
CM3
O-06
O-07
CM4
L1 or +DC or -DC
L2 or -DC or +DC
O-08
O-09
CM5
O-10
O-11
CM6
O-12
O-13
CM7
O-14
O-15
45311
Terminal Block 1
Terminal Block 2
45320
Wiring Connections Chapter 3
2085-IF4
CI-0
VI-0
COM0
CI-1
VI-1
COM1
CI-2
VI-2
COM2
CI-3
VI-3
COM3
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Rockwell Automation Publication 2080-UM003A-EN-E - March 201319
Chapter 3 Wiring Connections
CI-0
VI-0
COM0
CI-1
VI-1
COM1
CI-2
VI-2
COM2
CI-3
VI-3
COM3
Current
transmitter
Shielded cable
Current
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
Voltage
transmitter
Shielded cable
CI-4
VI-4
COM4
CI-5
VI-5
COM5
CI-6
VI-6
COM6
CI-7
VI-7
COM7
Current
transmitter
Shielded cable
Current
transmitter
Shielded cable
Volta ge
transmitter
Shielded cable
Volta ge
transmitter
Shielded cable
45322
Terminal Block 1
Terminal Block 2
45321
2085-IF8
2085-OF4
CO-0
VO-0
COM0
CO-1
VO-1
COM1
CO-2
VO-2
COM2
CO-3
VO-3
COM3
20Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Current
load
Shielded cable
Voltage
load
Shielded cable
Voltage
load
Shielded cable
Current
load
Shielded cable
2085-IRT4
CH0+
CH0H
CH0L
CH0-
CH1+
CH1H
CH1L
CH1-
NC
NC
NC
NC
CH2+
1
2
1
2a
1a
2
CH2H
CH2L
CH2-
CH3+
CH3H
CH3L
CH3-
CJC+
CJC+
TH
CJC-
TH
CJC-
NC
Shielded cable
Shielded cable
1
2
1
2
1a
Shielded cable
2-wire RTD
4-wire RTD
3-wire RTD
Thermocouple
Shielded cable
mV
OR
45326
If a thermocouple is used, the use of the
supplied CJC assembly is compulsory.
Terminal Block 1Terminal Block 2
Ohm input
OR
1
2
Wiring Connections Chapter 3
Wiring Options for the 2085-IQ32T Module
Included with your 2085-IQ32T module is a keyed 40-pin female connector and
crimp type pins. These components allow you to wire I/O devices to the module
using a 40-conductor cable or individual wires.
ATTENTION: To comply with UL restrictions, this equipment must be
powered from a source compliant with the following:
Class 2 or Limited Voltage/Current.
When assembled, align the female connector over the module’s male header using
the keying slot as a guide. Firmly lock them together with the upper and lower
retaining arms.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201321
Chapter 3 Wiring Connections
Keyed female connector
Included with the module.
44924
2085-IQ32T module
Keyed male
connector
Panel buttons,
sensors
Contact pins provided with
female connector can
accept 22...26 AWG wires.
User terminal connector
4 mm
(5/32 in.)
44916
Wire stop
Wire barrel
Tang
Stripped wire
Option 1 – Wire the Connector with Available 40-pin Connector
Assemble the Wire Contacts
1. Strip the wire insulation to expose 4 mm (5/32 in.) of wire. Crimp pins can
accept 22...26 AWG wire.
ATTENTION: Be careful when stripping wires. Wire fragments that fall
into the module could cause damage. Once wiring is complete, be sure
the module is free of all metal fragments before removing the protective
debris strip. Failure to remove the strip before operating can cause
overheating.
2. Insert the wire into the crimp pin as far as the wire stop.
3. Crimp the wire barrel around the wire using small needle nose pliers.
4. Crimp the insulation barrel around the wire insulation using small needle
nose pliers.
Stripped wire
Tang
Insulation barrel
5. Solder wire and wire barrel together using lead-free solder and soldering
pencil.
44921
22Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Wiring Connections Chapter 3
44922
Terminal connector
Terminal sockets
Wire contact
46045
(1) Maximum user cable length is dependent on how much voltage drop (current x (ohms/ft.) x (feet)) the user system can
tolerate. The user system should take into account the minimum turn-on voltage required by external loads connected to the
module, the minimum turn-on voltage required by the module, and all of the voltage drops associated with wiring to and
from the load, sensors, terminal blocks, power sources and the module itself. See the table on page 24
for voltage drop
values for the 1492 cables shown above.
6. Insert the assembled wire contact into the terminal socket. Push the wire
contact in until the tang latches. Make sure the tang is properly latched by
lightly pulling on the wire.
Option 2 – Use Allen-Bradley 1492 Connector Cables with Flying Leads
Preassembled 40-conductor cables with the 40-pin connector on one end and
flying leads on the other end are also available from Allen-Bradley. They are
available in 1 m, 2.5 m, and 5 m lengths. The catalog numbers from shortest to
longest are:
• 1492-CAB010U62 (or 1492-CAB010P62)
• 1492-CAB025U62 (or 1492-CAB025P62)
• 1492-CAB050U62 (or 1492-CAB050P62)
The “U62” cables route the cable upward when plugged into the module, while
“P62” cables route the cable downward when plugged into the module.
Option 3 – Use Allen-Bradley 1492 Cables with Keyed Connectors
2085-IQ32T Module
(1)
0.32 in. (8 mm) REF.
24…12 AWG
(0.2…4 mm
Male
MIL-C-83503
Header
1492-CABLExx
Connects module
to DIN rail mountable
terminal block
1492-IFM40xx DIN rail mountable terminal block
2
)
Rockwell Automation Publication 2080-UM003A-EN-E - March 201323
Chapter 3 Wiring Connections
Allen-Bradley 1492 wiring systems are available for connecting the I/O module
to external I/O. These wiring systems include a pre-wired cable available in four
lengths: 0.5m (1.6 feet), 1.0m (3.3 feet), 2.5m (8.2 feet), 5.0m (16.4 feet). An
Interface Module for connecting external devices is also available. Cables are
equipped with keyed connectors at both ends for proper connections. Interface
modules are DIN rail mountable and are available with or without field side
status indicating LEDs. Stick-on labels are provided with the Interface modules to
identify I/O wiring termination points.
1492 Cables
Catalog No.Voltage Drop @ 30 °CVoltage Drop @ 60 °C
Series C CablesV DC and DC
Com Wires
1492-CABLE005H127 mv34 mv144 mv38 mv
1492-CABLE010H173 mv45 mv196 mv51 mv
1492-CABLE025H334 mv83 mv388 mv95 mv
1492-CABLE050H574 mv147 mv686 mv169 mv
(1)
Output Channel
(2)
Wires
V DC and DC
Com Wires
Output
Channel Wires
Summary
(1) Voltage drop @ maximum rated current of 2 amps per conductor.
(2) Voltage drop at maximum rated current of 0.5 amps per output channel.
This chapter covered the input and output wiring connections for the different
analog and discrete Micro800 expansion I/O modules.
24Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Chapter
Install Your Micro800 Expansion I/O
This chapter includes information on installing the Micro800 expansion I/O
modules with the Micro850 controller.
WARNING: If you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed before proceeding.
4
Mount the Module
For more information on proper grounding guidelines, see the Industrial
Automation Wiring and Grounding Guidelines, publication 1770-4.1
.
Module Spacing
Maintain spacing from objects such as enclosure walls, wireways and adjacent
equipment. Allow 50.8 mm (2 in.) of space on all sides for adequate ventilation,
as shown:
Rockwell Automation Publication 2080-UM003A-EN-E - March 201325
Chapter 4 Install Your Micro800 Expansion I/O
45309
Mounting dimensions do not include mounting feet or DIN rail latches.
87 mm
(3.42 in.)
90 mm
(3.54 in.)
150 mm (5.91 in.)
44.5 mm (1.75 in.)
2085-OW8
2085-OW16
Micro850 Controller
Bus
terminator
28 mm (1.10 in.)
TIP
Mounting Dimensions and DIN Rail Mounting
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm x 1 mm
(EN 50 022 - 35 x 7.5)
Before mounting the module on a DIN rail, use a flat-blade screwdriver in the
DIN rail latch and pry it downwards until it is in the unlatched position.
1. Hook the top of the DIN rail mounting area of the module onto the DIN
2. Push the DIN rail latch back into the latched position.
.
For environments with greater vibration and shock concerns, use the panel
mounting method, instead of DIN rail mounting.
ATTENTION: This product is grounded through the DIN rail to chassis
ground. Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (for example, aluminum or
plastic) that can corrode, oxidize, or are poor conductors, can result in
improper or intermittent grounding. Secure DIN rail to mounting surface
approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
rail, and then press the bottom until the module snaps onto the DIN rail.
Use DIN rail end anchors (Allen-Bradley part number 1492-EAJ35 or
1492-EAHJ35) for vibration or shock environments.
26Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Install Your Micro800 Expansion I/O Chapter 4
To remove your module from the DIN rail, pry the DIN rail latch downwards
until it is in the unlatched position.
Panel Mounting
The preferred mounting method is to use two M4 (#8) per module. Hole spacing
tolerance: ±0.4 mm (0.016 in.).
Follow these steps to install your module using mounting screws.
1. Place the module next to the controller against the panel where you are
mounting it. Make sure the controller and module are spaced properly.
2. Mark drilling holes through the mounting screw holes and mounting feet
then remove the module.
3. Drill the holes at the markings, then replace the module and mount it.
Leave the protective debris strip in place until you are finished wiring the
module and any other devices.
System Assembly
The Micro850 expansion I/O module is attached to the controller or another
I/O module by means of interconnecting latches and hooks. The Micro850
controller and expansion I/O modules must terminate with a 2085-ECR Bus
Term in at or m o du l e.
ATTENTION: Failure to connect a bus terminator module to the last
expansion I/O module will result in a controller fault.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201327
Chapter 4 Install Your Micro800 Expansion I/O
Slide up both locks located at either side
of each expansion I/O and then attach the
I/O to the connecting latch hooks and bus
connector on the controller or the last
expansion I/O. After latching, slide down
both locks to securely fasten the I/O to
the controller.
45928
2085-ECR serves as an end cap and terminates the end of the serial communication bus.
The end cap is connected to the last I/O module in the system.
Summary
This chapter provided a step-by-step description of the process for assembling,
mounting, and installing the Micro850 controller with the expansion I/O
modules.
28Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Chapter
TIP
TIP
Configure Your Expansion I/O Module
5
Overview
Add an Expansion I/O
The following sample project guides you through the step-by-step process of
adding, configuring, deleting, and replacing Micro800 expansion I/O modules in
Connected Components Workbench.
For more information about using the Connected Components
Workbench software, you can refer to the Connected Components
Workbench Online Help (it comes with your software).
In this sample project, you need to create a Connected Components Workbench
project with a 2080-LC50-24QWB controller. Then, configure four expansion
I/O devices (2085-IF4, 2085-IQ32T, 2085-OB16, 2085-IRT4) following the
instructions below.
These instructions make use of the drag-and-drop mechanism available in
Connected Components Workbench release 2 and higher, which allows the user
to easily add, replace, and delete devices through simple drag-and-drop motion.
Expansion I/O modules are automatically added to a project when using
the "Discover" feature in Connected Components Workbench.
To add Expansion I/O modules to an existing Micro850 controller project, do
the following:
1. On the Project organizer pane, right-click Micro850 and choose Open.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201329
Chapter 5 Configure Your Expansion I/O Module
The Micro850 project page opens in the center pane with a graphical
replica of the Micro850 controller on the first tier, Controller properties
on the second tier, and an Output box on the last tier.
2. On the Device Toolbox pane, found at the rightmost corner of the
Connected Components Workbench window, go to the Expansion
Modules folder.
30Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
Expansion I/O slots
2085-IQ32T
2085-ECR
Drag and drop the expansion I/O
device in the slot.
The device appears in the slot
where you have dropped it.
TIP
2085-IF4
3. Click and drag 2085-IQ32T to the right of the controller graphic at the
center pane. Four blue slots appear to indicate available slots for expansion
I/O modules. Drop 2085-IQ32T on the first and rightmost slot against
the controller.
4. From the Expansion Modules folder on the Device Toolbox pane, drag and
drop 2085-IF4 on the second Expansion I/O slot, next to 2085-IQ32T.
To move an expansion I/O device to another slot, simply drag and drop
the device to the preferred slot. For step-by-step instructions on how to
delete and replace expansion I/O devices, see Delete and Replace an
Expansion I/O Configuration on page 42.
5. From the Expansion Modules folder on the Device Toolbox, drag and drop
2085-OB16 on the third Expansion I/O slot, next to 2085-IF4.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201331
Chapter 5 Configure Your Expansion I/O Module
TIP
Slot 1: 2085-IQ32T
Slot 2: 2085-IF4
Slot 3: 2085-OB16
Slot 4: 2085-IRT4
IMPORTANT
6. From the Expansion Modules folder on the Device Toolbox pane, drag and
drop 2085-IRT4 on the fourth Expansion I/O slot, next to 2085-IRT4.
You can edit default configuration by following the procedure provided in
the next section, Edit Expansion I/O Configuration on page 32
.
After you have added all four expansion I/O modules, your Connected
Components Workbench project should look like this:
Edit Expansion I/O
Configuration
The Expansion Modules list should appear as shown below. To see device details
for each of the expansion I/O you have just added, click General. To see default
configuration properties, click Configuration, if available.
You can edit default I/O configuration through the Expansion Modules Details
box located right below the controller graphic.
To download configuration to your device, see Build, Save, Download a
Project with Expansion I/O Configuration on page 44.
32Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
1. Select the Expansion I/O device you want to configure.
2. Click Configuration. Edit module and channel properties according to
your requirements and application.
The next sections show you configuration properties for each of the
expansion I/O module.
2085-IA8 and 2085-IM8
These two AC input modules only have general device details available for the
user in Connected Components Workbench software. No configuration
properties are available.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201333
Chapter 5 Configure Your Expansion I/O Module
2085-IF4 and 2085-IF8
For the analog input modules, 2085-IF4 and 2085-IF8, you can configure
properties such as input range, format, filter and alarm limits for each individual
channel.
Configuration Parameters for 2085-IF4 and 2085-IF8
Configuration
Property
Enable ChannelSelect or deselect the
Minimum-Maximum
Input Range
Data formatSelect from the following
Input filterChoose from the following
What to doDescription
checkbox. The box is selected
by default.
Choose from a range of
values:
• 0…20 mA
• 4…20 mA (default)
• -10…10 V
• 0…10 V
options:
• Raw/Proportional Data
• Engineering Units (default)
• Percent Range
values:
Enable or disable a channel through this
checkbox. By default, each channel is
enabled.
Defines the input mode for the channel as
either voltage or current, with current as
default mode.
See Data formats on page 7
information.
See Input Filter on page 9
information.
for detailed
for detailed
34Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
Configuration Parameters for 2085-IF4 and 2085-IF8
Configuration
Property
High High AlarmCheck the checkbox to enable
High Alarm
Low Alarm
Low Low Alarm
What to doDescription
an alarm. By default, High
High and Low Low Alarms
are disabled and High and
Low alarms are enabled.
Process level alarms alert you when the
module has exceeded configured high, high
high, low, and low low limits for each
channel.
2085-IQ16 and 2085-IQ32T
For the 16- and 32-channel DC input modules, 2085-IQ16 and 2085-IQ32T
respectively, you can configure OFF to ON and ON to OFF ranges.
The output modules, 2085-OV16, 2085-OB16, 2085-OW16, 2085-OA8,
2085-OW8, only have device details available to the user in Connected
Components Workbench. There are no user configuration pages for these
modules in the Connected Components Workbench software.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201335
Chapter 5 Configure Your Expansion I/O Module
2085-OF4
For the analog output module, 2085-OF4, you can configure output unit,
minimum to maximum output range, high clamp and low clamp values, and
overrange and underrange values.
36Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configuration Parameters for 2085-OF4
Configure Your Expansion I/O Module Chapter 5
Configuration
Property
Enable channelSelect or deselect the
Minimum-maximum
output range
Data formatSelect from the following
High clamp valueClick the checkbox to enable
Low clamp valueClick the checkbox to enable
What to doDescription
checkbox. Channel is not
enabled by default.
Choose from a range of
values:
• 0…20 mA
• 4…20 mA (default)
• -10…10 V
• 0…10 V
options:
• Raw/Proportional Data
• Engineering Units (default)
• Percentage Data
and enter a high clamp value.
and enter a low clamp value.
Enable or disable a channel through this
checkbox. By default, each channel is
disabled.
For more information, see:
• Input/Output Types and Ranges on page 7
• Valid Range of the Data Formats for
2085-IF4, 2085-IF8, and 2085-OF4 on
page 8
See Data formats on page 7
information.
Sets an appropriate alarm that limits the
output from the analog module to remain
within a range configured by the controller,
even when the controller commands an
output outside that range. This safety
feature sets a high clamp and a low clamp.
Once clamps are determined for a module,
any data received from the controller that
exceeds those clamps sets an appropriate
limit alarm and transitions the output to that
limit but not beyond the requested value.
for detailed
Rockwell Automation Publication 2080-UM003A-EN-E - March 201337
Chapter 5 Configure Your Expansion I/O Module
Configuration Parameters for 2085-OF4
Configuration
Property
Overrange alarm
trigger
Underrange alarm
trigger
What to doDescription
If you enabled and entered a
High Clamp value, you can
check High Clamp Value as
overrange alarm trigger.
If you did not enable and
entered a High Clamp value,
you can check Maximum
Output Value as your
overrange alarm trigger.
If you enabled and entered a
Low Clamp value, you can
check Low Clamp Value to set
it as underrange alarm trigger.
The overrange and underrange feature
detects when the output module is operating
beyond limits set by the output range. The
trigger could be set based on clamp values or
minimum/maximum output values.
If you did not enable and
entered a Low Clamp value,
you can check Minimum
Output Value as underrange
alarm trigger.
Latch over and
under alarm
Restore defaultsClick button to restore
Click to latch.Check the box to latch an alarm in the set
defaults.
position even if the condition that causes the
alarm disappears.
Restores default device properties.
38Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
2085-IRT4
For the RTD and Thermocouple expansion I/O, 2085-IRT4, you can configure
sensor type, data format, temperature units, and other properties, on each of the
four individual channels.
Configuration Parameters for 2085-IRT4
Configuration Property What to doDescription
Enable channelClick the box to enable.This parameter enables the particular
Sensor TypeSelect from the following
sensors:
• 100Ω Platinum 385
• 200Ω Platinum 385
• 100Ω Platinum 3916
• 200Ω Platinum 3916
• 100Ω Nickel 618
• 200Ω Nickel 618
• 120Ω Nickel 672
• 100Ω Copper 427
• 0…500 Ohm
• 0…100 mV
• Thermocouple B
• Thermocouple C
• Thermocouple E
• Thermocouple J
• Thermocouple K
• Thermocouple TXK/XK (L)
• Thermocouple N
• Thermocouple R
• Thermocouple S
• Thermocouple T
channel for operation.
Defines the RTD or Thermocouple sensor
type for the channel.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201339
Chapter 5 Configure Your Expansion I/O Module
Configuration Parameters for 2085-IRT4
Configuration Property What to doDescription
UnitsSet as °C or °FSets the temperature unit to be used by
RTD Wiring TypeSet as any of the following:
• 2-wire
• 3-wire
• 4-wire
RTD 2Wire Cable
Resistance
Data FormatChoose from the following
Replace value from 0.0
ohms…500.00 ohms to
0.0 ohms…655.35 ohms.
options:
• Raw/Proportional Data
• Engineering Units*1
• Engineering Units*10
• Percent range
the channel.
The wiring type for channel x.
This parameter is only available when the
Sensor Type for the channel is RTD or (0
to 500 Ohm).
The specified cable resistance for the
2-wire cable. When the RTD 2Wire Cable
Resistance value is smaller than the input
value, it is subtracted from the input
value during each read. When the value
is greater than the input value, the
under-range or open status bit is set (1).
To configure the wire resistance, the
Sensor Type must be RTD or (0…500
Ohm) and the RTD Wiring Type must be
2-wire.
Otherwise, this parameter is not
available.
For more information, see:
• Data format on page 12
• Valid Range of the Data Formats for
2085-IRT4 on page 12
40Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
Configuration Parameters for 2085-IRT4
Configuration Property What to doDescription
Filter Update TimeSet as the following (in
msec):
• 4
• 8
• 16
• 32
• 40
• 48
• 60
• 101
• 120
• 160
• 200
• 240
• 320
• 480
Filter Frequency (-3dB)Set as the following (in Hz):
• 114
• 60
• 30
• 14
• 12
• 9.4
• 8.0
• 4.7
• 4.0
• 3.0
• 2.4
• 2.0
• 1.5
• 1.0
50/60 Hz Noise Rejection Set as:
• Both (default)
• 50 Only
• 60 Only
• Neither
See Filter frequency on page 14
NOTE: Filter update time 4 ms is not
available for Thermocouple sensor types
B, R, S, E, J, C, K, L, N, or T or 0…10 mV.
Filter update time 8 ms is not available
for Thermocouple sensor types B, R, S.
See Noise Rejection on page 10
.
.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201341
Chapter 5 Configure Your Expansion I/O Module
Configuration Parameters for 2085-IRT4
Configuration Property What to doDescription
Open Circuit ResponseChoose from the following
options:
• Upscale
• Downscale
• Hold Last State
• Zero
Defines the response to be taken during
an open circuit, whether to upscale,
downscale, hold last state, or zero.
Upscale – Sets input to full upper scale
value of channel data word. The
full-scale value is determined by the
selected input type, data format, and
scaling.
Downscale – Sets input to full lower
scale value of channel data word. The
low scale value is determined by the
selected input type, data format, and
scaling.
Hold Last State – Sets input to last
input value.
Zero – Sets input to 0 to force the
channel data word to 0.
Delete and Replace an Expansion I/O Configuration
Using our example project, let us try to delete 2085-IF4 in slot 2 and 2085-OB16
in slot 3. Then, let us replace the modules with 2085-OW16 and another
2085-IQ32T module in slots 2 and 3, respectively. To do this:
1. On the project graphic in the center pane, right-click 2085-IF4 and click
Delete.
2. Another message box appears asking you if you want to empty the
placeholders to the left to fill the empty slot. Click No.
42Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Configure Your Expansion I/O Module Chapter 5
2085-OW16
2085-IQ32T
TIP
After deleting 2085-IF4 from slot 2, the project graphic should look
like this:
3. On the empty slot (slot 2), right-click and select 2085-OW16.
4. Next, replace 2085-OB16 in slot 3 with a 2085-IQ32T device.
Right-click 2085-OB16 in slot 3, and choose 2085-IQ32T.
The project graphic and Expansion Modules list should look like these
after the modules are replaced:
You can also delete and replace an expansion I/O through the Expansion
Modules list. To replace, right-click the expansion I/O module you would
like to replace, then select the Expansion I/O module you would like to
replace it with, from the list that appears. To delete the Expansion I/O,
choose Delete.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201343
Chapter 5 Configure Your Expansion I/O Module
Build, Save, Download a
Project with Expansion I/O
Configuration
Summary
To learn how to build, save, and download the project to your controller, see the
Connected Components Workbench Online Help.
This chapter provided instructions on how to add, edit, configure, delete, and
replace expansion I/O module configuration through the Connected
Components Workbench software.
44Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Appendix
MinMax
Solid0.34 mm2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
A
Specifications
The following tables provide specifications for digital and analog expansion I/O
modules.
Discrete Expansion I/O
2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules
Attribute2085-IQ162085-IQ32T
Number of inputs16 sink/source32 sink/source
Dimensions, HxWxD44.5 x 90 x 87 mm
Shipping weight,
approx.
Bus current draw, max170 mA @ 5V DC190 mA @ 5V DC
Wire size
Wiring category
Terminal screw torque,
max
Input circuit type24V AC/DC sink/source or 24V AC 50/60 Hz
Power dissipation, total 4.5 W7 W
Power supply24V DC
(2)
(1.75 x 3.54 x 3.42 in.)
220 g (7.76 oz)
2 – on signal ports
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(3)
(1)
Rockwell Automation Publication 2080-UM003A-EN-E - March 201345
Appendix A Specifications
30
26.4
30°C
65°C
Input voltage (V)
45302
Tem p
30
26.4
32
24
30°C
65°C
1
8
2
4
Input voltage (V)
45301
Number
of inputs
2085-IQ16 and 2085-IQ32T DC Sink/Source Input Modules
(1)
Attribute2085-IQ162085-IQ32T
Status indicators16 yellow indicators32 yellow indicators
Isolation voltage50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V DC for 60 s
Enclosure type ratingMeets IP20
North American temp
T4
code
Operating voltage
range
10…30V DC, Class 2
21.6…26.4V AC, 50/60 Hz, Class 2
See Derating Curve for 2085-IQ16
and Derating Curve for 2085-IQ32T on
page 46
Off-state voltage, max5V DC
Off-state current, max1.5 mA1.2 mA
On-state current, min1.8 mA @ 10V DC
On-state current, nom6.0 mA @ 24V DC5.2 mA @ 24V DC
On-state current, max8.0 mA @ 30V DC7.0 mA @ 30V DC
Input impedance, max3.9 kΩ 4.6 kΩ
IEC input compatibilityType 3Type 1
(1) Meets IEC Type 1 24V DC Input Specifications.
(2) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
(3) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
.
Derating Curve for 2085-IQ16
Derating Curve for 2085-IQ32T
46Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
MinMax
Solid0.34 mm2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C (194
°F), or greater, 1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
2085-OV16 Sink and 2085-OB16 Source DC Output Module
Attribute2085-OV162085-OB16
Number of outputs16 sinking16 sourcing
Dimensions, HxWxD 44.5 x 90 x 87 mm
Shipping weight,
approx.
Bus current draw,
max
Wire size
(1.75 x 3.54 x 3.42 in.)
220 g (7.76 oz)
200 mA @ 5V DC
Specifications AppendixA
Rockwell Automation Publication 2080-UM003A-EN-E - March 201347
Wiring category
Terminal screw
torque, max
(1)
2 – on signal ports
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
Output circuit type24V DC sink24V DC source
Power dissipation,
5 W
total
Power supply24V DC, Class 2
Status indicators16 Yellow channel indicators
Isolation voltage50V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 720V AC for 60 s
Enclosure type
Meets IP20
rating
North American
T4
temp code
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1.
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
Output Specifications – 2085-OV16 and 2085-OB16
Attribute2085-OV162085-OB16
Operating voltage range10…30V DC
On-state voltage, min10V DC
On-state voltage, nom24V DC
On-state voltage, max30V DC
On-state current, max0.5 A @ 30V DC, per output
On-state voltage drop, max1.0V DC @ 0.5 A
Off-state leakage current, max1 mA @ 30V DC
8 A, per module
Appendix A Specifications
MinMax
Solid0.34 mm2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
2085-IA8, 2085-IM8, 2085-OA8 AC Input/Output Modules
Attribute2085-IA82085-IM82085-OA8
Number of I/O8
Dimensions, HxWxD28 x 90 x 87 mm
Shipping weight,
approx.
Bus current draw, max 5V DC, 150 mA5V DC, 180 mA
Wire size
(1.10 x 3.54 x 3.42 in.)
140 g (4.93 oz)
Insulation stripping
10 mm (0.39 in.)
length
Wiring category
(1)
2 – on signal ports
Wire typeCopper
Terminal screw torque,
max
Input/output circuit
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
120V AC input240V AC input120V/240V AC output
type
Power supply120V AC, 50/60 Hz240V AC, 50/60 Hz120V/240V AC,
50/60 Hz
Power dissipation,
2.36 W2.34 W5.19 W
total
Enclosure type ratingMeets IP20
Status indicators8 yellow indicators
Isolation voltage150V (continuous),
Reinforced Insulation
Type, channel to
240V (continuous), Reinforced Insulation Type,
channel to system
Type tested @ 3250V DC for 60 s
system
Type tested @ 1950V
DC for 60 s
North American temp
T4
code
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
.
48Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Input Specifications – 2005-IA8 and 2085-IM8
Attribute2085-IA82085-IM8
Number of Inputs8
Voltage category120V AC240V AC
Operating voltage range74…120V AC, 50/60 Hz159…240V AC, 50/60 Hz
Off-state voltage, max20V AC40V AC
Specifications AppendixA
MinMax
Solid0.34 mm2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
Input Specifications – 2005-IA8 and 2085-IM8
Attribute2085-IA82085-IM8
Off-state current, max2.5 mA
On-state current, min5.0 mA @ 74V AC4.0 mA @ 159V AC
On-state current, max12.5 mA @ 120V AC7.0 mA @ 240V AC
Input impedance, max22.2 kΩ
Inrush current, max450 mA
Input filter time
<
20 ms
Off to On
On to Off
IEC type complianceType 3
Output Specifications – 2085-OA8
Attribute2085-OA8
Number of inputs8
Voltage category120V/230V AC
Operating voltage range120…240V AC, 50/60 Hz
Output voltage, min85V AC
Output voltage, max240V AC
Off-state leakage current, max2.5 mA
On-state current, min10 mA per output
On-state current, max0.5 A per output
On-state current, per module, max4 A
Off-state voltage drop, max1.5V AC @ 0.5 A
FusingNot protected. A suitable rating fuse is recommended to
Output signal delay
Off to On
On to Off
Surge current, max5 A
2.5V AC @10 mA
protect outputs.
9.3 ms for 60 Hz, 11 ms for 50 Hz
9.3 ms for 60 Hz, 11 ms for 50 Hz
Rockwell Automation Publication 2080-UM003A-EN-E - March 201349
2085-OW8 and 2085-OW16 Relay Output Module
Attribute2085-OW82085-OW16
Number of outputs8, relay16, relay
Dimensions, HxWxD28 x 90 x 87 mm
(1.10 x 3.54 x 3.42 in.)
Shipping weight,
140 g (4.93 oz)220 g (7.76 oz)
approx.
Wire size
Insulation strip length10 mm (0.39 in.)
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
Appendix A Specifications
Max
Volts
AmperesAmperesVolt Amperes
MakeBreakContinuous MakeBreak
120V AC15 A1.5 A2.0 A1800V A180V A
240V AC7.5 A0.75 A
24V DC1.0 A1.0 A28V A
125V DC0.22 A
2085-OW8 and 2085-OW16 Relay Output Module
Attribute2085-OW82085-OW16
Wiring category
Wire typeCopper
Terminal screw
torque. max
Bus current draw, max 5V DC, 120 mA
Load current, max2 A
Power dissipation,
total
Relay contact,
(0.35 power factor)
(1)
2 – on signal ports
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
24V DC, 50 mA
2.72 W5.14 W
5V DC, 160 mA
24V DC, 100 mA
Analog Expansion I/O
50Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Minimum load, per
10 mA per point
point
Off-state leakage, max 1.5 mA
Status indicators8 yellow indicators16 yellow indicators
Isolation voltage240V (continuous), Reinforced Insulation Type, channel to system
Type tested @ 3250V DC for 60 s
Pilot duty ratingC300, R150
Enclosure type ratingMeets IP20
North American temp
T4
code
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
.
2085-IF4, 2085-IF8, 2085-OF4 Analog Input and Output Modules
Attribute2085-IF42085-OF42085-IF8
Number of I/O48
Dimensions, HxWxD28 x 90 x 87 mm
(1.1 x 3.54 x 3.42 in.)
Shipping weight,
140 g (4.93 oz)220 g (7.76 oz)
approx.
Bus current draw,
max
5V DC, 100 mA
24V DC, 50 mA
5V DC, 160 mA
24V DC, 120 mA
44.5 x 90 x 87 mm
(1.75 x 3.54 x 3.42 in.)
5V DC, 110 mA
24V DC, 50 mA
Specifications AppendixA
MinMax
Solid0.34 mm
2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
2085-IF4, 2085-IF8, 2085-OF4 Analog Input and Output Modules
Attribute2085-IF42085-OF42085-IF8
Wire size
Rockwell Automation Publication 2080-UM003A-EN-E - March 201351
Wiring category
(1)
2 – on signal ports
Wire typeShielded
Terminal screw
torque
Power dissipation,
0.5…0.6 Nm
(4.4…5.3 lb-in.)
(2)
1.7 W3.7 W1.75 W
total
Enclosure type rating Meets IP20
Status indicators1 green health
indicator
1 green health
indicator
1 green health indicator
8 red error indicators
Isolation voltage50V (continuous), Reinforced Insulation Type, channel to system and channel
to channel.
Type tested @ 720V DC for 60 s
North American
T4
temp code
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
(2) RTB hold down screws should be tightened by hand. They should not be tightened using a power tool.
.
Input Specifications – 2085-IF4 and 2085-IF8
Attribute2085-IF42085-IF8
Number of inputs48
Resolution
Voltage
Current
Data formatLeft justified, 16 bit 2s complement
Conversion typeSAR
Update rate< 2 ms per enabled channel without 50 Hz/60 Hz rejection,
Step response time up to 63%
2-point Moving Average Filter
4-point Moving Average Filter
8-point Moving Average Filter
50/60 Hz Rejection Filter
Input current terminal, user
configurable
Input voltage terminal, user
configurable
Input impedanceVoltage terminal >1 MΩ
14 bits (13 bits plus sign bit)
1.28 mV/cnt unipolar; 1.28 mV/cnt bipolar
1.28 μA/cnt
< 8 ms for all channel,
8 ms with 50 Hz/60 Hz rejection
4…16 ms (for 1…8 enabled channels)
6…24 ms (for 1…8 enabled channels)
12…60 ms (for 1…8 enabled channels)
600 ms (for 1…8 enabled channels)
4…20 mA (default)
0…20 mA
±10V
0…10V
Current terminal <100 Ω
Appendix A Specifications
Input Specifications – 2085-IF4 and 2085-IF8
Attribute2085-IF42085-IF8
Absolute accuracy±0.10% Full Scale @ 25 ° C
Accuracy drift with tempVoltage terminal – 0.00428 % Full Scale/° C
Calibration requiredFactory calibrated. No customer calibration supported.
Overload, max.30V continuous or 32 mA continuous, one channel at a time.
Channel diagnosticsOver and under range or open circuit condition by bit reporting
Current terminal – 0.00407 % Full Scale/° C
Output Specifications – 2085-OF4
Attribute2085-OF4
Number of outputs4
Resolution
Voltage
Current
Data formatLeft justified, 16 bit 2s complement
Step response time up to 63%2 ms
Conversion rate, max2 ms per channel
Output current terminal, user
configurable
Output voltage terminal, user
configurable
Current load on voltage output, max3 mA
Absolute accuracy
Voltage terminal
Current terminal
Accuracy drift with tempVoltage terminal – 0.0045 % Full Scale/° C
Resistive load on mA output15…500 ohm @ 24V DC
12 bits unipolar; 11 bits plus sign bipolar
2.56 mV/cnt unipolar; 5.13 mV/cnt bipolar
5.13 μA/cnt
0 mA output until module is configured
4…20 mA (default)
0…20 mA
±10V
0…10V
0.133 % Full Scale @ 25 ° C or better
0.425 % Full Scale @ 25 ° C or better
Current terminal – 0.0069 % Full Scale/° C
Specialty Expansion I/O
52Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
2085-IRT4 Temperature Input Module
Attribute2085-IRT4
Number of inputs4
Dimensions, HxWxD44.5 x 90 x 87 mm
Shipping weight,
approx.
Bus current draw, max 5V DC, 160 mA
(1.75 x 3.54 x 3.42 in.)
220 g (7.76 oz)
24V DC, 50 mA
2085-IRT4 Temperature Input Module
MinMax
Solid0.34 mm
2
(22 AWG)
2.5 mm
2
(14 AWG)
Copper wire rated @ 90 °C
(194 °F), or greater,
1.2 mm
(3/64 in.) insulation max
Stranded
0.20 mm
2
2.5 mm
2
(14 AWG)
Attribute2085-IRT4
Wire size
Specifications AppendixA
Wiring category
Terminal screw torque 0.5…0.6 Nm
(1)
2 – on signal ports
(4.4…5.3 lb-in.)
(2)
Input typeThermocouple type: B, C, E, J, K, TXK/XK (L), N, R, S, T
25 g for DIN Rail Mounting
35 g for Panel Mounting
EmissionsCISPR 11:
Group 1, Class A
ESD ImmunityIEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF ImmunityIEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM @ 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz
EFT/B ImmunityIEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
Surge Transient ImmunityIEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on power ports
±2 kV line-earth(CM) on shielded ports
Conducted RF ImmunityIEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
54Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Certifications – All Micro800 Expansion I/O Modules
Specifications Appendix A
Certification (when
product is marked)
Value
(1)
c-UL-usUL Listed Industrial Control Equipment, certified for US and Canada.
See UL File E322657.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations,
certified for U.S. and Canada. See UL File E334470
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
KCKorean Registration of Broadcasting and Communications Equipment,
compliant with:
Article 58-2 of Radio Waves Act, Clause 3
(1) See the Product Certification link athttp://www.rockwellautomation.com/products/certification/ for
Declaration of Conformity, Certificates, and other certification details.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201355
Appendix A Specifications
Notes:
56Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Discrete I/O Data Mapping
TIP
Appendix
B
Expansion I/O Data Mapping
This section includes I/O data mapping for the discrete, analog, and specialty
expansion I/O modules.
Use the Connected Components Workbench software to see
Global Variables.
2085-IQ16 and 2085-IQ32T I/O Data Mapping
Discrete input states can be read from Global Variables _IO_Xx_DI_yy, where x
represents the expansion slot number 1…4 and yy represents the point number
00…15 for 2085-IQ16 and 00…31 for 2085-IQ32T.
2085-OV16 and 2085-OB16 I/O Data Mapping
Discrete output states can be read from Global Variables _IO_Xx_ST_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…15.
Discrete output states can be written to Global Variables _IO_Xx_DO_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…15.
2085-IA8 and 2085-IM8 I/O Data Mapping
Discrete input states can be read from Global Variables _IO_Xx_DI_yy, where x
represents the expansion slot number 1…4 and yy represents the point number
00…07.
2085-OA8 I/O Data Mapping
Discrete output states can be read from Global Variables _IO_Xx_ST_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…07.
Discrete output states can be written to Global Variables _IO_Xx_DO_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…07.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201357
Appendix B Expansion I/O Data Mapping
TIP
2085-OW8 and 2085-OW16 I/O Data Mapping
Discrete output states can be read from Global Variables _IO_Xx_ST_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…07 for 2085-OW8 and 00…15 for 2085-OW16.
Discrete output states can be written to Global Variables _IO_Xx_DO_yy, where
“x” represents the expansion slot number 1…4 and yy represents the point number
00…07 for 2085-OW8 and 00…15 for 2085-OW16.
Analog I/O Data Mapping
2085-IF4
(1)
Status Data Mapping
The following sections provide I/O and status mapping for the following analog
expansion I/O modules:
Catalog NumberDescription
2085-IF44-channel, 14-bit analog voltage/current input module
2085-IF88-channel, 14-bit analog voltage/current input module
2085-OF44-channel, 12-bit analog voltage/current output module
2085-IRT44-channel, 16-bit RTD and Thermocouple input module
Use the Connected Components Workbench software to see
Global Variables.
2085-IF4 I/O Data Mapping
Analog input values are read from Global Variables _IO_Xx_AI_yy, where “x”
represents the expansion slot number 1…4 and yy represents the channel number
00…03.
Analog input status values can be read from Global Variables IO_Xx_ST_yy,
where “x” represents the expansion slot number 1…4 and yy represents the status
word number 00…02.
WordR/W1514131211109 8 7 6 5 4 3 2 1 0
Status 0RPUGFCRCReserved
Status 1RReservedHHA1 LLA1HA1LA1DE1S1ReservedHHA0 LLA0HA0LA0DE0S0
Status 2RReservedHHA3 LLA3HA3LA3DE3S3ReservedHHA2 LLA2HA2LA2DE2S2
(1) See Field Descriptions table for definition of each bit.
2085-IF8 I/O Data Mapping
Analog input values are read from Global Variables _IO_Xx_AI_yy, where “x”
represents the expansion slot number 1…4 and yy represents the channel number
00…07.
58Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Expansion I/O Data Mapping Appendix B
Analog input status values can be read from Global Variables IO_Xx_ST_yy,
where “x” represents the expansion slot number 1…4 and yy represents the status
word number 00…04. Individual bits within a status word can be read by
appending a .zz to the Global Variable name, where "zz" is the bit number 00...15.
2085-IF8
Word R/W151413121110987654 3210
Status 0RPUGFCRCReserved
Status 1RReservedHHA1 LLA1HA1LA1DE1S1ReservedHHA0 LLA0HA0LA0DE0S0
Status 2RReservedHHA3 LLA3HA3LA3DE3S3ReservedHHA2 LLA2HA2LA2DE2S2
Status 3RReservedHHA5 LLA5HA5LA5DE5S5ReservedHHA4 LLA4HA4LA4DE4S4
Status 4RReservedHHA7 LLA7HA7LA7DE7S7ReservedHHA6 LLA6HA6LA6DE6S6
(1) See Bit Field Descriptions table for a detailed definition of each bit.
(1)
Status Data Mapping
Field Descriptions for 2085-IF4 and 2085-IF8 Input Modules
FieldDescription
CRCCRC error This bit is set (1) when there is a CRC error on the data
DE#Data Error These bits are set (1) when the enabled input channels are
GFGeneral Fault This bit is set (1) when any of these faults occur: RAM test
HA#High Alarm
Overrange
HHA#High High Alarm
Overrange
LA#Low Alarm
(underrange)
LLA#Low Low Alarm
(underrange)
PUPower Up 1. This bit is set after a power on. It is cleared when good
S#Channel fault These bits are set(1) if the corresponding channels are
received. It gets cleared when the next good data is
received.
not getting any reading for the current sampling. The
respective returned Input Data value remains the same as
the previous sample.
failure, ROM test failure, EEPROM failure, and reserved
bits. All channel fault bits (S#) are set too.
These bits are set (1) when the input channel exceeds a
preset high limit defined by the configuration selected (UL#
is set).
These bits are set (1) when the input channel exceeds a
preset high-high limit defined by the configuration selected
(UL# is set).
These bits are set (1) when the input channel goes below
the configured low alarm limit.
These bits are set (1) when the input channel goes below
the configured low-low alarm limit.
configuration data is accepted by the module.
2. It is set when an unexpected MCU reset occurs in RUN
mode. All channel fault bits (S#) are set too. The module
stays connected with no configuration after the reset. PU
and channel fault bits (S#) are cleared when a good
configuration is accepted.
open, have data error or under/overrange.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201359
Appendix B Expansion I/O Data Mapping
2085-OF4 I/O Data Mapping
Analog output data can be written to Global Variables _IO_Xx_AO_yy, where
“x” represents the expansion slot number 1…4 and yy represents the channel
number 00…03.
Control bit states can be written to Global Variable _IO_Xx_CO_00.zz, where
“x” represents the expansion slot number 1…4 and “zz” represents the bit number
00…12.
2085-OF4 Control Data Mapping
WordBit Position
1514131211109876543210
Control 0 ReservedCE3CE2CE1CE0UU3UO3UU2UO2UU1UO1UU0UO0
Channel Alarm/Error Unlatch
UUx and UOx are written during run mode to clear any latched lunder- and
over-range alarms. The alarm is unlatched when the unlatch bit is set (1) and the
alarm condition no longer exists. If the alarm condition persists, then the unlatch
bit has no effect.
2085-OF4 Status Data Mapping
WordBit Position
1514131211109876543210
Status 0Channel 0 Data Value
Status 1Channel 1Data Value
Status 2Channel 2 Data Value
Status 3Channel 3 Data Value
CEx are written during run mode to clear any DAC hardware error bits and re-
enable the error-disabled channel x.
You need to keep the unlatch bit set until verification from the appropriate input
channel status word says that the alarm status bit has cleared(0), then you need to
reset(0) the unlatch bit.
Status Data
Analog output status can be read from Global Variables IO_Xx_ST_yy, where “x”
represents the expansion slot number 1…4 and “yy” represents the status word
number 00…06. Individual bits within a status word can be read by appending a
.zz to the Global Variable name, where "zz" is the bit number 00...15.
60Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Expansion I/O Data Mapping Appendix B
2085-OF4 Status Data Mapping
WordBit Position
1514131211109876543210
Status 4PUGFCRCReservedReservedE3E2E1E0S3S2S1S0
Status 5ReservedU3O3ReservedU2O2ReservedU1O1ReservedU0O0
Status 6Reserved
Field Descriptions for 2085-OF4 Status Word
FieldDescription
CRC CRC errorIndicates there is a CRC error on data receive. All channel fault bits
ExErrorIndicates there is an DAC hardware error, broken wire or high load
GF General FaultIndicates a fault has occurred, including: RAM test failure, ROM test
OxOver-Range
Flag
PU Power UpIndicates an unexpected MCU reset has occurred in RUN mode. All
SxChannel FaultIndicates there is an error associated with the channel x.
UxUnder-Range
Flag
(Sx) are also set. The error is cleared when the next good data is
received.
resistance associated with the channel x, an error code may be
displayed on the respective input word (0…3) and the corresponding
channel is locked (disabled) until user clears the error by writing the
CEx bit in output data.
failure, EEPROM failure, and reserved bits. All channel fault bits (Sx)
are also set.
Indicates the controller is attempting to drive the analog output above
its normal operating range or above the channel's High Clamp level.
However the module continues to convert analog output data to a
maximum full range value if clamp levels are not set for the channel.
channel error bits (Ex) and fault bits (Sx) are also set. The module stays
connected with no configuration after the reset. PU and channel fault
bits are cleared when a good configuration is downloaded.
Indicates the controller is attempting to drive the analog output below
its normal operating range or below the channel's Low Clamp level (if
clamp limits are set for the channel).
Specialty I/O Data Mapping
2085-IRT4 I/O Data Mapping
Analog input values can be read from Global Variables _IO_Xx_AI_yy, where “x”
represents the expansion slot number 1…4 and yy represents the channel number
00…03.
Analog input status can be read from Global Variables IO_Xx_ST_yy, where “x”
represents the expansion slot number 1…4 and yy represents the status word
number 00…02. Individual bits within a status word can be read by appending a
.zz to the Global Variable name, where "zz" is the bit number 00...15.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201361
Appendix B Expansion I/O Data Mapping
2085-IRT4 Status Data Mapping
WordBit Position
1514131211109876543210
Status 0DE3DE2DE1DE0OC3OC2OC1OC0R3R2R1R0S3S2S1S0
Status 1O3O2O1O0U3U2U1U0T3 T2 T1 T0CJC
over
CJC
under
CJC OCCJC
DE
Status 2PUGFCRCReserved
Field Descriptions for 2085-IRT4
FieldDescription
CJC OCCold Junction
Compensation
Open Circuit
CJC DECold Junction
Compensation
Data Error
CJC overCold Junction
Compensation
overrange
CJC underCold Junction
Compensation
underrange
CRCCRC errorIndicates there is a CRC error on data receive. All channelfault
DExData ErrorIndicates that the current input data is not reliable. The
GFGeneral FaultIndicates a fault has occurred, including: RAM test failure, ROM
OCxOpen-Circuit FlagIndicates that an open-circuit condition exists on the channel x.
OxOver-Range FlagIndicates the controller is attempting to drive the analog output
PUPower UpIndicates an unexpected MCU reset has occurred in RUN mode.
RxRTD compensationIndicates that the RTD compensation of channel x is not
Indicates that the cold junction sensor is open-circuit. CJC DE
bit, when set, indicates the cold junction sensor current
readings is not reliable. The previous reading shall be used
instead. It indicates internal compensation status if Tx is set.
Indicates that the cold junction sensor current readings is not
reliable. The previous reading will be used instead. It indicates
internal compensation status if Tx is set.
Indicates cold junction sensor is underrange (below -25 °C).
bits (Sx) are also set. The error is cleared when the next
good data is received.
previous input data is sent to the controller instead. Diagnostic
status bits are for internal use only.
test failure, EEPROM failure, and reserved bits. All channel
fault bits (Sx) are also set.
above its normal operating range or above the channel's High
Clamp level. However the module continues to convert analog
output data to a maximum full range value if clamp levels are
not set for the channel.
All channel error bits (Ex) and fault bits (Sx) are also set. The
module stays connected with no configuration after the reset.
PU and channel fault bits are cleared when a good
configuration is downloaded.
working. This is effective for RTD and ohm type only.
62Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
Expansion I/O Data Mapping Appendix B
Field Descriptions for 2085-IRT4
FieldDescription
SxChannel FaultIndicates there is an error associated with the channel x.
TxThermocouple
compensation
UxUnderrangeIndicates that the input of channel x is at the minimum end of
Indicates that the thermocouple compensation of channel x is
not working. This is effective for thermocouple type only.
its normal operating range. The module automatically resets
the bit when the under-range condition is cleared and the data
value is within the normal operating range.
Calibration of Analog
Modules
Specifications
The analog modules are shipped to you calibrated.
See Expansion I/O on page 240 for a list of specifications for each of the analog
and digital expansion I/O modules.
Rockwell Automation Publication 2080-UM003A-EN-E - March 201363
Appendix B Expansion I/O Data Mapping
64Rockwell Automation Publication 2080-UM003A-EN-E - March 2013
configuration parameters 39
data format 12
data formats valid range 13
filter frequency 14
open circuit response 14
sensor type 11, 39
wiring 21
2085-OA8 1, 35
I/O data mapping 57
wiring 17
2085-OB16 1, 35
configuration parameters 35
I/O data mapping 57
wiring 18
2085-OF4 2, 7, 10, 36
configuration parameters 36, 37
data format 37
I/O data mapping 60
Latch over and under alarm 38
minimum-maximum output range 37
Restore defaults 38
wiring 20
2085-OV16 1, 35
I/O data mapping 57
wiring 18
2085-OW16 1, 35
configuration parameters 35
I/O data mapping 58
wiring 19
2085-OW8 1, 35
I/O data mapping 58
wiring 18
A
additional resources iii
alarm status bit 10
Allen-Bradley 1492 connector cables 23
Allen-Bradley 1492 wiring 24
analog expansion I/O 6
I/O Type/Range 7
analog-to-data format conversion 13
conversion formula 9
average filter 10
C
channel status byte 10
clamping
alarm 10
default high/low values 11
limits 10
common mode rejection 10
configuration
add 29
edit expansion I/O 32
Connected Components Workbench v, 5, 6, 7, 12, 29, 35
continuous current 6
crimp pin 22
current 7, 8
D
65Rockwell Automation Publication 2080-UM002E-EN-E - March 2013
66 Index
data format 11, 34, 40
engineering units 8
percent range 8
raw/proportional data 7
valid range 8
valid range for 2085-OF4 8
digital filter 10, 14
DIN rail mounting 27
discrete input 5
discrete output 6
double-width expansion I/O 3
downscale 14
E
engineering units 8, 11, 12
expansion I/O
analog 7
compatibility 1
configuration 29
data mapping 57
discrete 5
discrete input 5
discrete output 6
hardware features 2
panel mounting 27
raw/proportional data 8, 11, 12
resolution 8
RTD types 11
RTD wiring type 40
S
single-width expansion I/O 2
solenoids 6
status data 60
status indicator 5
surge 6
system assembly 27
T
Thermocouple and RTD 12
sensor types 11
thermocouple types 11
Rockwell Automation Publication 2080-UM002E-EN-E - March 2013
U
UL restrictions
Class 2 or Limited Voltage/Current 21
underrange alarm trigger 38
V
voltage 7, 8
W
wiring
2085-IQ32T 21
connections 15
Index 67
Rockwell Automation Publication 2080-UM002E-EN-E - March 2013
68 Index
Notes:
Rockwell Automation Publication 2080-UM002E-EN-E - March 2013
Rockwell Automation Publication 2080-UM003A-EN-E - March 201369
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator
your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.
Rockwell Automation Publication 2080-UM003A-EN-E - March 2013 70