Product Information
Bulletin 193 Input Interface Module
(Cat 193-EIMD; 193-EIMD60)
WARNING: To prevent electrical shock, disconnect from power source before installing or servicing. Follow NFPA 70E requirements. Install in suitable enclosure. Keep free from contaminants.
The 193-EIMD60 module is designed for applications in 120VAC 60 Hz control circuits only.
Installation, adjustments, putting into service, use, assembly, disassembly, and maintenance shall be carried out by suitably trained personnel in accordance with applicable code of practice. In case of malfunction or
damage, no attempts at repair should be made. The product should be returned to the manufacturer for repair. Do not dismantle the product.
ATTENTION: Do not install, congure, operate or maintain this product until you have read the product documentation and the documents in the Additional Resources section for installing, conguring, operating or maintaining
equipment. To get the product documentation go to http://www.rockwellautomation.com/literature or contact your local sales oce or Rockwell Automation representative.
ATTENTION: Ne pas installer, congurer, exploiter ou maintenir ce produit tant que vous n’avez pas lu sa documentation et les documents de la rubrique Documents connexes pour l’installation, la conguration, l’exploitation et la
maintenance de l’équipement. Pour obtenir de la documentation, rendez-vous sur le site http://www.rockwellautomation.com/literature ou contactez votre agence commerciale Rockwell Automation locale ou son représentant.
ACHTUNG: Für die Installation, Konguration, den Betrieb und die Wartung dieses Produkt lesen Sie sich bitte zunächst die Produktdokumentation sowie die Dokumente im Abschnitt „Weitere Informationen“ durch. Die
entsprechende Produktdokumentation nden Sie unter http://www.rockwellautomation.com/literature oder kontaktieren Sie Ihr lokales Vertriebsbüro bzw. einen Rockwell Automation-Mitarbeiter.
ATENCIÓN: No instale, congure, opere ni mantenga este producto hasta que haya leído la documentación del producto y los documentos en la sección Recursos adicionales para la instalación, conguración, operación o
mantenimiento de equipo. Para conseguir la documentación, diríjase a http://www.rockwellautomation.com/literature o póngase en contacto con su ocina regional de ventas o representante de Rockwell Automation.
ATENÇÃO: Não instale, congure, opere ou mantenha este produto até que você leia a documentação do produto e os documentos na seção Recursos adicionais para a instalação, conguração, operação ou manutenção do
equipamento. Para conseguir a documentação, visite http://www.rockwellautomation.com/literature ou entre em contato con seu escritório de vendas regional ou representante da Rockwell Automation.
ATTENZIONE: Non installare, congurare, attivare o riparare questo prodotto senza avere prima letto la relativa documentazione nonchè i documenti indicati nella sezione Ulteriori Risore riguardanti l’installazione, la congurazione,
l’attivazione o la riparazione dell’apparecchiatura. Per la documentazione sul prodotto visitare il sito http://www.rockwellautomation.com/literature o contattare l’ucio vendite o il rappresentate Rockwell Automation di zona.
Additional Resources:
1) Go to http://www.rockwellautomation.com/literature; 2) Go to Search, select Publication Number. Type in: 41053-157-01 or 193-UM002
Installation
0.55 Nm
x 7
1
3
5 lb-in
x 7
2
Terminal
Designation
1
Funtional only with the E3 Plus Overload Relay
Reference
1 IN 1 General-purpose AC input number 1
2 IN 2 General-purpose AC input number 2
3 IN 3 General-purpose AC input number 3
4 IN 4 General-purpose AC input number 4
5 AC COM AC supply common
6 AC COM
EGND
Description
AC supply common
Earth Ground
Wire Size and Torque Specications
1X
2X
1
1
1X
2X
1X
2X
24 ....12 AWG
24 ....16 AWG
5 lb-in
0.25 ..... 2.5 mm
0.5 ......0.75 mm
0.55 N.m
0.2 ...... 4.0 mm
0.2 .......1.5 mm
0.55 N.m
2
2
2
2
Wiring Diagram
Basic wiring of input devices is shown below.
WARNING: Be careful when stripping wires. Wire fragments that fall into the module could cause damage at power up. Once wiring is complete, ensure the module is free of all metal fragments. For reliable
input signal processing, input wiring shall be routed in raceways separate from power cabling. For distances exceeding 200 M (656 Ft), the use of shielded cable is recommended.
Commons are connected internally.
Input Specications
Catalog Number
Voltage Category
Operating Voltage Range 79V ac to 132V ac
Frequency Range 47 Hz to 63 Hz
Number of Inputs 4
Heat Dissipation 0.10 W per input
Signal Delay (max.)
O-State Voltage (max.) 20V ac
O-State Current (max.) 1.0 mA
On-State Voltage (min.) 79V ac
On-State Current
Inrush Current (max.) 150 mA
Nominal Impedance
IEC Input Compatibility Type 1
IN 1
1234 56
IN 2 IN 3 IN 4 EGND
AC
COM
AC
COM
EIMD = 110/120 V ac 50/60 Hz
L1 L2
EIMD60 = 120 V ac 60 Hz
193-EIMD 193-EIMD60
110V / 120V ac
120V ac
79V ac to 132V ac
57 Hz to 63 Hz
4
0.10 W per input
On Delay: 30 ms
O Delay: 30 ms
On Delay: 30 ms
O Delay: 30 ms
20V ac
1.0 mA
79V ac
2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)
2.0 mA at 79V ac (min.)
10.0 mA at 132V ac (max.)
150 mA
28k ohm at 50 Hz
21k ohm at 60 Hz
21k ohm at 60 Hz
Type 1
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 193-IN054A-EN-P - May 2012