This document describes how to install and configure the ControlNet 1788-CNC and
-CNCR daughtercards. In this document, we use the term ‘the card’ to refer to both
daughtercards collectively. When one card is different from the other, we refer to the
daughtercard by name.
For information aboutSee page
Important User Information 2
European Hazardous Location Approval 4
North American Hazardous Location Approval 5
About the Daughtercards6
Setting the Node Address7
Installing the Card8
Daughtercard Performance8
Connecting the Card to the Network8
Connect to the Network Using a Tap 10
Connect to the Network Using a 1786-CP Cable 12
Interpreting the Status Indicators14
Specifications17
If you are connecting the card directly to a ControlNet network, you should also refer to these
publications:
• ControlNet Tap Installation Instructions, publication 1786-5.7
• ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002
Publication 1788-IN002C-EN-P - April 2004
2 ControlNet Daughtercard
Important User Information
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and
hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves
that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a
hazardous environment, which may lead to personal injury or death, property damage,
or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of the
product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment to alert people that dangerous
voltage may be present.
Labels may be located on or inside the equipment to alert people that surfaces may be
dangerous temperatures.
Publication 1788-IN002C-EN-P - April 2004
ControlNet Daughtercard 3
ATTENTION
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial
environment, in overvoltage Category II applications (as defined in IEC
publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate
precautions, there may be potential difficulties ensuring electromagnetic
compatibility in other environments due to conducted as well as radiated
disturbance.
This equipment is supplied as “open type” equipment. It must be
mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately designed
to prevent personal injury resulting from accessibility to live parts. The
interior of the enclosure must be accessible only by the use of a tool.
Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication
60529, as applicable, for explanations of the degrees of protection
provided by different types of enclosure. Also, see the appropriate
sections in this publication, as well as the Allen-Bradley publication
1770-4.1 (“Industrial Automation Wiring and Grounding Guidelines”),
for additional installation requirements pertaining to this equipment.
ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can cause
internal damage and affect normal operation. Follow these guidelines
when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• When not in use, store the equipment in appropriate static-safe
packaging.
Publication 1788-IN002C-EN-P - April 2004
4 ControlNet Daughtercard
European Hazardous Location Approval
European Zone 2 Certification
(The following applies when the product bears the EEx Marking.)
This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has
been found to comply with the Essential Health and Safety Requirements relating to the
design and construction of Category 3 equipment intended for use in potentially explosive
atmospheres, given in Annex II to this Directive. The examination and test results are
recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 50021.
IMPORTANT
• This equipment is not resistant to sunlight or other sources of UV
radiation.
• The secondary of a current transformer shall not be open-circuited
when applied in Class I, Zone 2 environments.
• Equipment of lesser Enclosure Type Rating must be installed in an
enclosure providing at least IP54 protection when applied in Class I,
Zone 2 environments.
• This equipment shall be used within its specified ratings defined by
Allen-Bradley.
• Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied
in Class I, Zone 2 environments.
Publication 1788-IN002C-EN-P - April 2004
ControlNet Daughtercard 5
North American Hazardous Location Approval
The following information applies when operating
this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are
suitable for use in Class I Division 2 Groups A, B, C,
D, Hazardous Locations and nonhazardous locations
only. Each product is supplied with markings on the
rating nameplate indicating the hazardous location
temperature code. When combining products within
a system, the most adverse temperature code
(lowest "T" number) may be used to help determine
the overall temperature code of the system.
Combinations of equipment in your system are
subject to investigation by the local Authority
Having Jurisdiction at the time of installation.
Do not disconnect equipment
unless power has been
removed or the area is known
to be nonhazardous.
Do not disconnect connections
to this equipment unless power
has been removed or the area
is known to be nonhazardous.
Secure any external
connections that mate to this
equipment by using screws,
sliding latches, threaded
connectors, or other means
provided with this product.
Informations sur l'utilisation de cet équipement en
environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne
conviennent qu'à une utilisation en environnements de
Classe I Division 2 Groupes A, B, C, D dangereux et non
dangereux. Chaque produit est livré avec des
marquages sur sa plaque d'identification qui indiquent
le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés
dans un système, le code de température le plus
défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température
global du système. Les combinaisons d'équipements
dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de
l'installation.
Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher l'équipement.
Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher les connecteurs.
Fixer tous les connecteurs
externes reliés à cet
équipement à l'aide de vis,
loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.
Substitution of components
may impair suitability for Class
I, Division 2.
If this product contains
batteries, they must only be
changed in an area known to
be nonhazardous.
La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
S'assurer que l'environnement
est classé non dangereux avant
de changer les piles.
Publication 1788-IN002C-EN-P - April 2004
6 ControlNet Daughtercard
WARNING
• If you connect or disconnect the communications cable with
power applied to this module or any device on the network, an
electrical arc can occur. This could cause an explosion in
hazardous location installations.
• If you insert or remove the card while host power is on, an
electrical arc can occur. This could cause an explosion in
hazardous location installations.
• Be sure that power is removed or the area is nonhazardous
before proceeding.
About the Daughtercards
The network daughtercard architecture defines a common
hardware and software interface that several different
network interface cards will support. This allows products
that have been designed to support the network
daughtercard option to support several different Rockwell
Automation networks.
About the ControlNet Daughtercard
You can install the 1788-CNC or -CNCR ControlNet daughtercard in any host device that
supports the ControlNet daughtercard.
Every ControlNet network requires at least one module that is able to store parameters and
configure the network with those parameters upon start-up. This module is called a ‘keeper’
since it keeps the network configuration.
Any 1788-CNC or -CNCR card can keep the network parameters at any legal node address
(01 to 99). Multiple devices on any one network can act as the network keeper. Each device
capable of being the network keeper acts to back up the current keeper. This backup function
is automatic and requires no action on your part.
IMPORTANT
(1)
The host device must provide a suitable power source per the restrictions in the specifications table.
Publication 1788-IN002C-EN-P - April 2004
On the 1788-CNC or -CNCR card, the non-volatile keeper data is erased
when a firmware update is performed.
(1)
ControlNet Daughtercard 7
Setting the Node Address
You must set two switch assemblies to configure the daughtercard with its unique network
address. Figure 1 shows the location of the switches. These switches are read on powerup to
establish the network address of the card.
Set the node address to a value between 01 and 99. For optimum throughput, assign
addresses to your ControlNet nodes in a sequential order starting with 01.
Node address 00 is not a valid ControlNet address. You should only use node address 00 if
the product that uses the ControlNet daughtercard has the ability to set the node address
using the host device interface.
This feature is typically used on products that do not allow easy customer access to the node
address switches. If you set the node address switch to 00, it allows the host in which the
daughtercard resides to set the node address, rather than allowing the daughtercard to read
the node address from the switch settings.
Figure 1 Setting the Node Address
module
channel A connector
I/O
status
LED
NAP
status
LED
node address
switches
channel A connector
network status indicators (A and B)
network status indicators (A and B)
channel B connector
31044-M
Publication 1788-IN002C-EN-P - April 2004
8 ControlNet Daughtercard
Installing the Card
Due to wide variation in available host devices, we cannot provide specific installation
instructions in this document. For instructions on how to install the daughtercard in a host
device, refer to the user manual for the particular host device.
IMPORTANT
Do not install or remove the daughtercard while the host is under power.
Daughtercard Performance
Due to wide variation in available host devices, we cannot provide specific performance
capabilities in this document. For information concerning host/daughtercard performance
characteristics, refer to the user manual for the particular host device.
Connecting the Card to the Network
After you have installed the card, you can connect it to the network. You must connect the
card to the network using an approved ControlNet tap:
• 1786-TPR (T-tap right angle)
• 1786-TPS (T-tap straight)
• 1786-TPYR (Y-tap right angle)
• 1786-TPYS (Y-tap straight)
We recommend the straight taps.
Publication 1788-IN002C-EN-P - April 2004
ControlNet Daughtercard 9
Figure 2 1788-CNCR Daughtercard
example ControlNet nodeexample ControlNet node
trunk cable A
trunk cable B
example ControlNet node
When you connect the daughtercard to a ControlNet network, you should also refer to this
documentation:
• ControlNet Coax Tap Installation Instructions, publication 1786-5.7
• ControlNet Coax Media Planning and Installation Guide, publication CNET-IN002
See page 14 for information about status indicators.
IMPORTANT
If you use a non-redundant cable system, all ControlNet devices must be
on the same channel, we recommend channel A.
Publication 1788-IN002C-EN-P - April 2004
10 ControlNet Daughtercard
Connect to the Network Using a Tap
1. Remove and save the dust cap(s) from the ControlNet tap(s).
ATTENTION
dust cap
segment 1
trunk cable A
Do not allow any metal portions of the tap to contact any
conductive material. If you disconnect the tap from the module,
place the dust cap back on the straight or right angle connector
to prevent the connector from accidentally contacting a metallic
grounded surface.
trunk cable B
dust cap
Note:
1788-CNC use trunk cable A.
1756-CNB use segment 1
1788-CNCR use trunk cable A and B.
1756-CNBR use segment 1 and segment 2
segment 2
20955-M
Publication 1788-IN002C-EN-P - April 2004
ControlNet Daughtercard 11
2. Connect the tap’s straight or right-angle connector to the module’s BNC connector.
If your network supportsConnect the tap’s straight or right-angle connector
non-redundant media
(1788-CNC or -CNCR)
redundant media
(1788-CNCR)
1. Rockwell Automation recommends using channel A for non-redundant media.
to the channel A connector on the module
(channel B on the 1788-CNCR is not used.)
1
from trunk-cable A to channel A on the 1788-CNCR and
from trunk-cable B to channel B on the 1788-CNCR.
IMPORTANT
trunk cable A
To prevent inadvertent reversal of the tap connections (resulting in
incorrect status displays and troubleshooting), check the tap drop cable
for a label indicating the attached cable before you make your connection.
A
tap
trunk cable A
A
tap
B
trunk cable B
tap
Publication 1788-IN002C-EN-P - April 2004
12 ControlNet Daughtercard
Connect to the Network Using a 1786-CP Cable
Follow this illustration to connect a programming terminal to the network using a 1786-CP
cable.
A
B
ControlNet network
1
The 1786-CP cable can be plugged into any ControlNet product's NAP to provide programming
capability on the ControlNet network. A programming terminal connected through this cable is
counted as a node and must have a unique address.
ATTENTION
Use the 1786-CP cable when you connect a programming terminal to the
network through the network access port (NAP); using another cable
Any ControlNet
interface card
1786-CP
cable
1
could result in possible network failures or product damage.
The NAP port is for temporary local programming purposes only and not
intended for permanent connection.
-
Publication 1788-IN002C-EN-P - April 2004
This table shows the wiring for the 1786-CP connector cable.
Connector 1
Wire NumberSignal MnemonicSignal Name
1ISO-GNDIsolated Ground
2N.C.No Connection
3PTTX-HTransmit Data High
4PTTX-LTransmit Data Low
5PTRX-LReceive Data Low
6PTRX-HReceive Data High
7N.C.No Connection
8ISO-GNDIsolated Ground
Connector 2
Wire NumberSignal MnemonicSignal Name
1ISO-GNDIsolated Ground
2N.C.No Connection
3PTRX-HReceive Data High
4PTRX-LReceive Data Low
5PTTX-LTransmit Data Low
6PTTX-HTransmit Data High
7N.C.No Connection
8ISO-GNDIsolated Ground
ControlNet Daughtercard 13
Publication 1788-IN002C-EN-P - April 2004
14 ControlNet Daughtercard
Interpreting the Status Indicators
Status indicators provide information about the card and the network when you are
connected via the BNC connectors. Tables 1 and 2 on the following pages outline the
possible states, explain what each state means to you, and indicate what action you should
take, if any, to correct that state.
Definition of terms:
• steady - indicator is on continuously in the defined state.
• alternating - the two indicators alternate between the two defined states at the same
time (applies to both indicators when viewed together); the two indicators are always in
opposite states, out of phase.
• flashing - the indicator alternates between the two defined states (applies to each
indicator viewed independent of the other); if both indicators are flashing, they flash
together, in phase.
IMPORTANT
Keep in mind that the Module Status indictor reflects the module state,
e.g., self-test, firmware update, normal operation but no connection
established, etc. The network status LEDs, A and B, reflect network
status. Remember that the host is able to engage in local messaging with
the card although it is detached from the network. Therefore, the Module
Status LED is flashing green if the host has successfully started the card.
Note, however, that until the host removes reset, all LEDs on the
daughtercard will remain off.
When you view the indicators, always view the Module Status indicator
first to determine the state of the daughtercard. This information may
help you to interpret the network status indicators. As a general practice,
view all three status indicators (Module Status, I/O Status, and Network
Status) together to gain a full understanding of the daughtercard’s status.
Major faultThere is a hardware fault with the module. Cycle power.
• Minor fault
• Firmware
update in
progress
• Node address
switch change
• Invalid module
firmware
• Duplicate node
address
No connections
established
Connections
established
Self-testThe module is performing self-diagnostics. Wait briefly to
• Check the power supply.
• Ensure that the daughtercard is firmly seated in the
slot.
• Cycle power. If the indicator remains off, replace the
daughtercard or the host.
If the problem persists, replace the daughtercard.
• No action required (firmware update in progress.)
• The daughtercard’s node address switches may have
been changed since power-up. Change the node
address switches back to the original setting. The
module will continue to operate properly.
• Update module firmware with ControlFlash Update
utility.
• The daughtercard’s node address duplicates that of
another device. Remove power, change the node
address to a unique setting, then apply power.
No action required.
No action required.
see if problem corrects itself.If problem persists, check the
host. If the daughtercard cannot communicate with the
host, it may remain in self-test mode.
This LED is on during the LED portion of the self-tests.
ControlNet Daughtercard 15
Publication 1788-IN002C-EN-P - April 2004
16 ControlNet Daughtercard
Table 2 Interpreting Network Status
IndicatorColorProbable CauseRecommended Action
A
B
or
(when viewed
independently)
IndicatorColorProbable CauseRecommended Action
A
and
(when viewed
together)
OffChannel disabledProgram network for redundant media,
if required.
Steady GreenNormal operationNo action required.
Flashing
Green/Off
Temporary network
errors
Node is not
configured to go on
None, unit will self-correct
Make sure the configuration keeper node is
present and working.
line
Flashing
Red/Off
Media fault• Check media for broken cables, loose
connectors, missing terminators, etc.
• If condition persists, refer to ContolNet
Coax Media Planning and Installation
Manual, publication CNET-IN002.
No other nodes
Add other nodes to the network.
present on network
Flashing
Red/Green
Incorrect network
configuration
Cycle power or reset unit. If fault persists,
contact your Rockwell Automation
representative or distributor.
B
OffSee the MS indicator
No action required or apply power.
for additional
information.
Steady RedFaulted unitCycle power or reset unit. If fault persists,
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0 to 60°C (32 to 140°F)
It is accebtable for the ambient slot temperature immediately surrounding this
product to reach 85°C (185°F) maximum
10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
±4kV at 2.5kHz on communications ports
±2kV line-earth(CM) on shielded ports
10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
5V dc @ 450 mA (maximum)
5V dc @ 475 mA (maximum)
2.25 watts
2.375 watts
2.25 watts or 7.68 BTU/hour
2.375 watts or 8.1 BTU/hour
2 - on communications ports
Publication 1788-IN002C-EN-P - April 2004
18 ControlNet Daughtercard
Weight
1788-CNC, 1788-CNCR
Agency Certification
(when product is marked)
0.1 Kg (0.2 lb)
c-UR-us: UL Recognized Component Industrial Control Equipment, certified for
US and Canada
c-UR-us: UL Recognized Component Industrial Control Equipment for Class I,
Division 2, Group A,B,C,D Hazardous Locations, certified for US and Canada
CSA: CSA Certified Process Control Equipment
CSA: CSA Certified Process Control Equipment for Class I, Division 2, Group
A,B,C,D Hazardous Locations
(3)
CE
: European Union 89/336/EEC EMC Directive, compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
(3)
C-Tick
: Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
(3)
EEx
: European Union 94/9/EC ATEX Directive, compliant with:
EN 50021; Potentially Explosive Atmospheres, Protection "n" (Zone 2)
CI: ControlNet International conformance tested to ControlNet specifications
(1)
To comply with UL and CSA restrictions, this equipment must be powered from a source compliant with the following: Class
2 or Limited Voltage/Current, as defined in UL 508 Seventeenth Edition Section 32; and Separated Extra-Low-Voltage
(SELV), as defined in CSA C22.2 No 1010, Annex H.
(2)
Use this Conductor Category information for planning conductor routing. Refer to Publication 1770-4.1, "Industrial
Automation Wiring and Grounding Guidelines".
(3)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification
details.
Publication 1788-IN002C-EN-P - April 2004
Notes:
ControlNet Daughtercard 19
Publication 1788-IN002C-EN-P - April 2004
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using our
products. At http://support.rockwellautomation.com, you can find technical manuals, a
knowledge base of FAQs, technical and application notes, sample code and links to software
service packs, and a MySupport feature that you can customize to make the best use of these
tools.
For an additional level of technical phone support for installation, configuration and
troubleshooting, we offer TechConnect Support programs. For more information, contact
your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation,
please review the information that's contained in this manual. You can also contact a special
Customer Support number for initial help in getting your module up and running:
United States1.440.646.3223
Outside United
States
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell tests all of our products to ensure that they are fully operational when shipped from
the manufacturing facility. However, if your product is not functioning and needs to be
returned:
United StatesContact your distributor. You must provide a Customer Support case number
Outside United
States
(see phone number above to obtain one) to your distributor in order to
complete the return process.
Please contact your local Rockwell Automation representative for return
procedure.
Publication 1788-IN002C-EN-P - April 2004PN 957867-24