Rockwell Automation 1788-CN2DN User Manual

Installation Instructions
ControlNet-to-DeviceNet Linking Device

Catalog Number 1788-CN2DN

Topic Page
Important User Information 2
About the CN2DN Linking Device 7
Parts List 8
Install the CN2DN Device 9
Mount the CN2DN Device on a DIN Rail 10
Mount the CN2DN Device on a Panel or Other Fixture 12
Wire a Power Supply to the CN2DN Device 13
Set the Node Addresses and Communication Rate 15
Connect the CN2DN Device to a ControlNet Network 16
Connect the CN2DN Device to a DeviceNet Network 17
Uninstall the CN2DN Linking Device 19
Interpret the LED Indicators 21
Troubleshoot the DeviceNet Network 29
Troubleshoot the ControlNet Network 46
Specifications 47
Additional Resources 51
Publication 1788-IN052D-EN-P - February 2007
2 ControlNet-to-DeviceNet Linking Device

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
) describes some important differences between solid state
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Publication
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you to identify a hazard, avoid a hazard and recognize the consequences.
Labels may be located on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment, for example, a drive or motor, to alert people that surfaces may be at dangerous temperatures.
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 3
T
North American Hazardous Location Approval
The following Information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMEN
Publication
RISQUE D'EXPLOSION
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.
1788-IN052D-EN-P - February 2007
4 ControlNet-to-DeviceNet Linking Device
European Hazardous Location Approval
European Zone 2 Certification (The following applies when the product bears the EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15.
IMPORTANT
Publication
This equipment is not resistant to sunlight or other sources of UV radiation.
Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments.
This equipment shall be used within its specified ratings defined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
1788-IN052D-EN-P - February 2007
Environment and Enclosure
ControlNet-to-DeviceNet Linking Device 5
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 m (1.24 mi) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
Besides this publication, see:
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
Publication
1788-IN052D-EN-P - February 2007
6 ControlNet-to-DeviceNet Linking Device
Prevent Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when
not in use.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 7
About the CN2DN Linking Device
Use following graphic to identify the components of your ControlNet-to-DeviceNet linking device.
CN2DN Linking Device Components
Power Port and Connector
DeviceNet Port and Connector
DeviceNet Baud Rate Switch
Network Access Port
DeviceNet Node Address Switches
LED Indicators
ControlNet Connection Ports
ControlNet Node Address Switches
The DeviceNet connection port is located on the top left corner of the device. See the section titled Connect the CN2DN Device to a DeviceNet Network for more information.
Rotary switches to set the ControlNet node address, DeviceNet node address, and the DeviceNet communication rate are located just below the power and DeviceNet ports. See the section titled Uninstall the CN2DN Linking Device for more information.
ATTENTION
The Network Access Port (NAP) is intended for local temporary programming use only. It is not for permanent connection.
Use only specified NAP cable to the network.
Located below the rotary switches, the ControlNet network access port allows for easy access of the ControlNet network using a laptop and 1784-PCC card. Use 1786-CP connection cable to access the ControlNet network using the NAP port.
Publication
1788-IN052D-EN-P - February 2007
8 ControlNet-to-DeviceNet Linking Device
Two ControlNet connection ports are located on the bottom left side of the device and provide the availability to connect a redundant network. See the section titled Connect the CN2DN Device to a ControlNet Network on page 16 for more information.
For more information about the power port and connector, see the section titled Wire a Power Supply to the CN2DN Device on page 13.
For more information about the LED indicators, see the section titled Interpret the LED Indicators on page 21.

Parts List

The following parts are included with the 1788-CN2DN linking device.
1788-CN2DN Parts
1788-CN2DN
One 1788-CN2CN linking device
One power input connector
One DeviceNet 10-pin linear connector
Five 121 resistors
Two end anchors
Publication
1788-IN052D-EN-P - February 2007
DeviceNet Connector
Power
Connector
121 Ω Resistors
End Anchors
31670-M
ControlNet-to-DeviceNet Linking Device 9

Required System Components

In order to install your 1788-CN2DN device, you will need the following system components.
A 24V dc power supply and
A securely installed zinc-plated, yellow-chrome steel, DIN rail, panel, or other suitable fixture.

Install the CN2DN Device

Complete the following tasks to install the CN2DN Linking Device.
Mount the CN2DN Device on a DIN Rail
Mount the CN2DN Device on a Panel or Other Fixture
Wire a Power Supply to the CN2DN Device
Uninstall the CN2DN Linking Device
Set the Node Addresses and Communication Rate
Connect the CN2DN Device to a ControlNet Network
Connect the CN2DN Device to a DeviceNet Network
Publication
1788-IN052D-EN-P - February 2007
10 ControlNet-to-DeviceNet Linking Device

Mount the CN2DN Device on a DIN Rail

ATTENTION
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum and plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.87 in.) and use end-anchors appropriately.
IMPORTANT
The DIN rail must be properly grounded. See publication Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 for more information about DIN rail grounding.
Complete the following steps to mount the CN2DN device on a DIN rail.
1. Align the CN2DN device over the DIN rail.
2. Press the CN2DN device onto the DIN rail until the DIN rail
latches lock the linking device in place.
Press Forward and Down
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 11
3. Clip each of the end anchors onto the DIN rail next to the
CN2DN device.
End Anchor onto DIN Rail
DIN Rail
Clip On
End Anchors Next to Device
Slide the Anchor Against the CN2DN Device
Tighten the Clamping Screws
Grounded DIN Rail
4. Slide each anchor against the device and tighten the screws on
the front of the end anchor.
Publication
1788-IN052D-EN-P - February 2007
12 ControlNet-to-DeviceNet Linking Device
5. If you are mounting your CN2DN device in a high-vibration
area, insert screws (not included) into the holes of the mounting tabs and tighten so that the screws are firmly anchored into the panel behind the device.
Mount Tabs (Optional Use)
Ground Connection (Optional) - For use if DIN rail or panel is not grounded. If used, this tab must be properly connected to the earth ground.
Mount Tabs (Optional Use)
You have completed mounting your CN2DN device on a DIN rail.

Mount the CN2DN Device on a Panel or Other Fixture

IMPORTANT
If mounting the CN2DN device to a panel, ensure that the panel is conductive metal and properly grounded. Paint or other coatings should be sanded from the panel to ensure the CN2DN device makes sufficient conductive contact with the panel.
To mount the CN2DN device on a panel or other suitable fixture, insert five screws (not included) through the module’s mounting tabs and into the panel or fixture behind the module. Use screws long enough to penetrate the panel or fixture for a secure mount.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 13

Wire a Power Supply to the CN2DN Device

ATTENTION
To comply with the CE Low Voltage Directive (LVD), power to this equipment and DeviceNet must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
To comply with UL restrictions, DeviceNet must be powered from a source compliant with the following: Class 2 or Limited Voltage/Current.
ATTENTION
24V dc power connection wiring length must be less than 10 m (32.81 ft).
The CN2DN device requires 18...30V dc input power provided by a power supply that is separate from the DeviceNet network power supply.
Complete the following steps to wire the power supply to the CN2DN linking device.
1. Disconnect power to the power supply.
2. Locate the orange power connector.
Power Connector
Power Connector, Top
+ - + -
+ -
Power Supply
Wiring
Terminals
Publication
Daisy Chain
to Device
Wiring
Ter mi na ls
(Optional Use)
1788-IN052D-EN-P - February 2007
14 ControlNet-to-DeviceNet Linking Device
3. Loosen the two left-most terminal screws of the power
connector.
IMPORTANT
Do not connect more than two wires to any terminal.
4. Insert the bare power supply wire ends into the left-side
terminals of the power supply connector using the diagram as a guide.
5. Tighten the two left terminal screws using 0.6 Nm (7 in-lb)
torque.
IMPORTANT
The power supply connector must be inserted into the CN2DN device for power to reach any devices daisy chained from the CN2DN power supply connector.
6. If you choose to connect another device to the power supply
connector of the CN2DN device, loosen the two terminal screws on the right side of the connector.
7. Insert the bare device power wire ends into the two right
terminals using the diagram as a reference.
8. Tighten the two right terminal screws using 0.6 Nm (7 in-lb)
torque.
9. Insert the power supply connector into the power supply
connector port.
10. Reapply power to the dc power supply.
The LED indicators on the right side of the CN2DN device will flash red to indicate power has been connected.
You have completed wiring the power supply to the CN2DN device.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 15
Set the Node Addresses and Communication Rate
Complete the following steps to set the node addresses using the switches on the front of the CN2DN device.
CN2DN Device Switches
DeviceNet Address Switches
ControlNet
DeviceNet Baud Rate Switch
1. To set the DeviceNet node address, use a small flat-head
screwdriver to turn the arrows of the switches towards the desired node numbers.
Address Switches
DeviceNet switches shown set to node 14.
2
0
8
2
4
0
6
8
MSD LSD
4
6
2. To set the DeviceNet communication rate, turn the DeviceNet
baud rate switch to the communication rate your DeviceNet network is configured to, for example 125 K, 250 K, or 500 K.
3. To set the ControlNet node address, use a small Phillips-head
screwdriver to turn the arrows of the switches towards the desired node numbers.
ControlNet switches shown set to node 26.
2
0
PGM
2
4
0
6
8
MSD LSD
4
6
You have completed setting the ControlNet and DeviceNet node addresses and communication rate.
Publication
1788-IN052D-EN-P - February 2007
16 ControlNet-to-DeviceNet Linking Device

Connect the CN2DN Device to a ControlNet Network

Complete the following steps to connect your CN2DN linking device to the ControlNet network.
WARNING
If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
1. Attach the BNC connector of the ControlNet cable to
ControlNet port A.
If using redundant
Attach the BNC Connector of the ControlNet tap to ControlNet port A.
Main ControlNet Network Cable
IMPORTANT
Redundant ControlNet Network Cable (Optional)
Main ControlNet Network Cable
Do not connect more than one ControlNet network to the CN2DN
cabling, attach the BNC connector of the ControlNet tap to ControlNet port B.
device at a time. Connecting the CN2DN device to two networks at one time will cause erratic behavior of the CN2DN device.
2. If you are connecting to redundant media, attach the BNC
connector of the other ControlNet cable to ControlNet port B.
The CN2DN linking device is now connected to the ControlNet network.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 17

Connect the CN2DN Device to a DeviceNet Network

WARNING
If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Complete the following steps to connect your CN2DN device to a DeviceNet network using the 10-pin linear connector included with the CN2DN device.
You may also use the following DeviceNet connectors not included with the device.
5-pin linear connector (1799-DNETSCON or 1799-DNETCON)
5-pin linear to micro connector (1799-DNC5MMS)
Consult the DeviceNet Media Design and Installation Guide, publication DNET-UM072, for more information about using the connectors not included with the 1788-CN2DN linking device.
1. Strip 65 mm (2.6 in.) to 75 mm (2.96 in.) of the outer jacket
from the end of the DeviceNet cable, leaving no more than 6.4 mm (0.25 in.) of the braided shield exposed.
Braided Shield
6.4 mm (0.25 in.)
Jacket
65 mm (2.6 in.)
Publication
1788-IN052D-EN-P - February 2007
18 ControlNet-to-DeviceNet Linking Device
2. Wrap the end of the cable with 38 mm (1.5 in.) of shrink wrap,
covering part of the exposed conductors and part of the trunk line insulation.
38 mm
Jacket
(1.5 in.)
Shrink Wrap
41841
3. Strip 8.1 mm (0.32 in.) of the insulation from the end of each
of the colored insulated conductors.
Jacket
Shrink Wrap
8.1 mm (0.32 in.)
41842
4. Insert each colored conductor into the matching color-coded
terminal cavity of the open-style connector.
5. If the CN2DN device is the first or last node on the DeviceNet
network, insert an end of a 121resistor into the blue and white terminal cavities of the DeviceNet port connector.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 19
The resistor should bridge the blue and white terminal cavities.
121
Resistor
Black
Blue
Bare or Shield
Red
White
41827
6. Tighten all of the terminal screws using 0.6 Nm (7 in-lb)
torque.
You have completed connecting to the DeviceNet network.

Uninstall the CN2DN Linking Device

Complete the following steps to uninstall the CN2DN linking device.
1. Remove power from the CN2DN device.
2. Disconnect the power, DeviceNet, and ControlNet connectors.
3. If end anchors are in place, remove by loosening the screws
and unclipping the anchor from the DIN rail.
Publication
1788-IN052D-EN-P - February 2007
20 ControlNet-to-DeviceNet Linking Device
4. To remove the CN2DN linking device from the DIN rail, pull
down on the two latches at the bottom of the device while pulling the CN2DN device away from the DIN rail.
Pull down on DIN rail latches.
You may need to insert a flat-head screwdriver between the DIN rail latch and the tab that locks the latch into place in order to remove the device.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 21

Interpret the LED Indicators

Use the LED indicators on the CN2DN linking device to monitor the following:
Module Status
Linking Activity Status
DeviceNet Network Status
ControlNet Network Status
CN2DN Device LED Indicators
DeviceNet Network Status Indicators
Module Status and Linking Activity Status Indicators
ControlNet Status Indicators
Publication
1788-IN052D-EN-P - February 2007
22 ControlNet-to-DeviceNet Linking Device

Module Status

Use the following table to interpret your Module Status LED indicators and determine if corrective action is necessary.
Module Status Indicator
LED Indicator Device Status Recommended Action
Off No power to device. A. Verify that the power supply is
functioning properly.
B. Cycle power supply.
C. Remove power and check input power
wiring. Reapply power.
D. Replace the CN2DN linking device.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 23
Module Status Indicator
LED Indicator Device Status Recommended Action
Green, flashing The CN2DN device is
functioning but not communicating with devices.
Green, steady Fully operational. The
CN2DN device is communicating with all configured DeviceNet nodes or there are no configured devices.
Red, flashing The linking device is
not communicating with one or more modules.
Red, steady Unrecoverable
communication fault.
Use RSNetworx software to configure the CN2DN device. See Additional Resources for publications with more information about configuring the CN2DN device.
None. The device has passed self-tests and is functioning properly if devices have been configured.
A. Verify that DeviceNet switches are not
set at PGM.
B. Verify that connected devices are
functioning properly.
C. Verify that devices have been
configured properly.
See Additional Resources for publications with more information about configuring the CN2DN device.
A. Verify that the CN2DN device has been
assigned a unique node address during configuration.
B. Verify that all devices are set at the
same baud rate.
C. Cycle CN2DN power.
D. Replace the CN2DN device.
Publication
1788-IN052D-EN-P - February 2007
24 ControlNet-to-DeviceNet Linking Device

Linking Activity Status

The Linking Activity LED indicator displays the status of communication between the DeviceNet and ControlNet networks as well as the amount of traffic.
Use the following table to interpret the Linking Activity LED indicator.
Linking Activity LED Indicator
LED Indicator Linking Activity Status
Off No network traffic is occurring between the ControlNet to
DeviceNet networks. I/O traffic may be present.
Green, flashing ControlNet to DeviceNet (non-I/O) communication traffic
present (flash rate indicates amount of traffic).
Red and Green, flashing Module is running boot code only (used for FLASH upgrades).
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 25

ControlNet Network Status

The CNet A and CNet B LED indicators display the status of the ControlNet network and individual channels.
The ControlNet network may recognize more than one network status a time. If more than one status is present, the CN2DN linking device will display the highest priority status.
Use the following table to interpret the ControlNet LED indicators.
ControlNet LED Indicators, CNet A and CNet B
LED Indicator State LED View Priority
Off Both CNet A
and CNet B1 (highest
Red, steady Both CNet A
Red and green, alternating
Red, alternating Both CNet A
Off One, CNet A
Red and green, flashing One, CNet A
Red, flashing One, CNet A
Green, flashing One, CNet A
Green, steady One, CNet A
and CNet B
Both CNet A and CNet B
and CNet B
or CNet B
or CNet B
or CNet B
or CNet B
or CNet B9 (lowest)
Level
priority)
2 No ControlNet network found.
3 Device self-testing.
4 Incorrect ControlNet node
5 ControlNet channel disabled or not
6 Incorrect ControlNet network
7 No data received from network.
8 Temporary channel error or
ControlNet Network Status
No power.
configuration.
supported.
configuration.
listen-only channel.
Normal network operation.
Publication
1788-IN052D-EN-P - February 2007
26 ControlNet-to-DeviceNet Linking Device

DeviceNet Network Status

The DeviceNet network indicators, DNet Network Status and DNet I/O Status, indicate the state of the DeviceNet network and the state of DeviceNet I/O modules.
Use the following tables to interpret your DeviceNet LED indicators located at the top right corner of the CN2DN device.
DNet Network Status Indicator
LED Indicator DeviceNet Network
Status
Off No DeviceNet connection. If a DeviceNet connection has been
Green, flashing DeviceNet network found,
not communicating with devices.
Recommended Action
made:
A. Verify that the DeviceNet
network is powered.
B. Check DeviceNet cables and
connections.
If devices should be communicating:
A. Check DeviceNet cables and
connections.
B. Verify that all devices on the
DeviceNet network are functioning properly.
Publication
1788-IN052D-EN-P - February 2007
DNet Network Status Indicator
ControlNet-to-DeviceNet Linking Device 27
LED Indicator DeviceNet Network
Status
Green, steady One or more devices
connected and communicating.
Red, flashing One or more connections
timed-out.
Red, steady Communication error (bus
off condition).
Recommended Action
None needed.
Use programming software to view tags specific to the devices in order to troubleshoot the DeviceNet network.
See DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004, for more information about using controller tags to troubleshoot connection errors.
A. Verify that each device has be
assigned a unique node address.
B. Verify that specified DeviceNet
baud rates are the same.
C. Cycle power to the CN2DN
device.
See DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004, for more information about using controller tags to troubleshoot connection errors.
Publication
1788-IN052D-EN-P - February 2007
28 ControlNet-to-DeviceNet Linking Device
DNet I/O Status Indicator
LED Indicator I/O Device Status Recommended Action
Off No connection to device. A. Verify that the
Green, flashing Device is in program mode
(idle).
Green, steady Device is in run mode. To put the device in program
DeviceNet network is powered.
B. Verify the connected
device is functioning properly.
To put the device in run mode, use programming software.
mode, use programming software.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 29

Troubleshoot the DeviceNet Network

If DeviceNet network communications fail, you need to complete one or both of these tasks to troubleshoot the DeviceNet network.
View and interpret DeviceNet network status codes.
View and interpret the controller status tags using RSLogix5000
software.
View and Interpret DeviceNet Status Codes on the DeviceNet Scanner
In order to view the DeviceNet status code, locate the scanner on the DeviceNet network. The status code is viewed on the character display on the front of the scanner module, for example a 1756-DNB, DeviceNet bridge module.
IMPORTANT
The DeviceNet status codes display only on the DeviceNet scanner module. Status codes do not display on the 1788-CN2DN linking device.
Use the DeviceNet Status Codes table to interpret your status code.
DeviceNet Status Codes
Status Code Description of Status Recommended Action
0-63 Scanner’s DeviceNet node address. None.
65 The AutoScan option is on and the
device is in idle mode.
67 Scanner is Secondary scanner. None.
68 Primary scanner has detected no
Secondary scanner.
69 Primary and Secondary configurations
are mismatched.
Publication
None.
Configure another scanner to be the Secondary scanner.
Check configuration of the Secondary scanner.
1788-IN052D-EN-P - February 2007
30 ControlNet-to-DeviceNet Linking Device
DeviceNet Status Codes
Status Code Description of Status Recommended Action
70 The address of the device is already
in use by another device on the network. The scanner failed the duplicate node address check.
71 Invalid data in scan list. Use RSNetworx software to
72 Slave device stopped communicating.
If the slave device does not recover communication during next scan, status code changes to 78.
73 Slave device’s identity information
does not match electronic key in scanner.
74 Scanner detected data overrun on
DeviceNet communication port.
Change the address of the device to an unused address.
reconfigure the scan list.
Verify slave device’s:
power.
communication
connections.
If slave device is polled, verify that interscan delay time is adequate for the device to return data.
Make sure that the correct device is connected at this address.
Make sure that the device matches the specified electronic key (vendor, product code, product type).
Modify your configuration and check for invalid data.
Check network communication traffic.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 31
DeviceNet Status Codes
Status Code Description of Status Recommended Action
75 Either or both of the following:
Verify that the device has:
The device does not have a scan list.
The device has not received communication from any other device.
76 No direct network traffic for scanner.
The scanner hears other network communication but does not hear any directed to it.
77 During initialization, the data size
expected by the device does not match the scan list entry.
a configured scan list.
a properly-wired connection
to the network
None.
Use RSNetWorx software to check the slave device and the scan list for the correct input and output sizes for the slave device.
Publication
1788-IN052D-EN-P - February 2007
32 ControlNet-to-DeviceNet Linking Device
DeviceNet Status Codes
Status Code Description of Status Recommended Action
78 Device is configured in scan list, but
not communicating. It has failed to communicate during the scanner’s second scan, which followed the display of status error code 72.
79 Scanner has failed to transmit a
message. The error status usually displays after the duplicate node check completes at power-up.
Verify device’s:
power.
communication
connections.
If the device is polled, make sure the interscan delay is long enough for the device to return its data.
If needed, use RSNetWorx software to:
– add the device to the
DeviceNet network.
– delete the device from
scanner’s scan list.
– inhibit the device in the
scanner’s scan list.
Make sure that your scanner is connected to a valid network.
Check for disconnected cables.
Verify network baud rate.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 33
DeviceNet Status Codes
Status Code Description of Status Recommended Action
80 Scanner is in idle mode. If desired, put network in run
mode by completing the following steps.
1. Put the controller in run or remote run mode using the keyswitch on the controller or through RSLogix5000 software.
2. Turn on the bit O.CommandRegister.Run for the scanner.
81 Controller has set the scanner to the
faulted mode. The Command bit also indicates a DeviceNet network fault state.
82 Error detected in sequence of
fragmented I/O messages from device.
Bit O.CommandRegister.Fault for the scanner is on. Correct condition that caused controller to set this bit and then turn this bit off.
Use RSNetWorx software to:
– check scan list of the
device to make sure that its input and output data sizes are correct.
Publication
– check the configuration of
the device.
1788-IN052D-EN-P - February 2007
34 ControlNet-to-DeviceNet Linking Device
DeviceNet Status Codes
Status Code Description of Status Recommended Action
83 Device returns error responses when
the scanner attempts to communicate with it.
Use RSNetWorx software to:
– check the accuracy of the
scan list.
– check the configuration of
the device. The device may be in another scanner’s scan list.
Use the slave device’s documentation to verify that the device supports the message type used by the scanner.
– If the device’s message
type does not match the scanner’s, then use use RSNetWorx to access the scanner’s scanlist and change the scanner’s message type to one that is compatible with the slave device.
84 Scanner is initializing the DeviceNet
network.
85 During runtime, the data size sent by
the slave device does not match the size in the corresponding scan list entry.
Publication
1788-IN052D-EN-P - February 2007
Cycle power to the device.
None. This code clears itself once the scanner attempts to initialize all the devices on the network.
Since variable length poll data is not supported, verify that the slave device is functioning properly.
ControlNet-to-DeviceNet Linking Device 35
DeviceNet Status Codes
Status Code Description of Status Recommended Action
86 The device is in idle mode, or not
producing data, while the scanner is in run mode.
87 Scanner cannot listen to shared
inputs from slave device because the owning scanner has not established communication with that slave device.
88 Scanner cannot listen to shared
inputs from slave device because I/O parameters (for example, polled or strobed, electronic key, data size) for that slave device are configured differently between this scanner and the owning scanner.
89 Scanner failed to configure a device
using the Automatic Device Recovery (ADR) parameters.
90 Controller has set the scanner to the
disabled mode.
Check the configuration and status of the device.
If you set up an interlock between 2 scanners (controllers), make sure both scanners are in run mode.
Verify primary scanner connection and configuration.
Slave device may not be producing data.
In this scanner, reconfigure the I/O parameters for the shared inputs scan list entry so that they match those same parameters in the owning scanner.
Make sure that you installed a compatible device.
If the offline configuration of the device does not match the actual (online) configuration of the device, change the offline configuration to match the online configuration.
If desired, turn enable the scanner by locating the O.CommandRegister.DisableNetw ork bit of the command register and turn if off.
Publication
1788-IN052D-EN-P - February 2007
36 ControlNet-to-DeviceNet Linking Device
DeviceNet Status Codes
Status Code Description of Status Recommended Action
91 Bus-off condition likely due to cable
or signal errors.
92 DeviceNet cable not supplying power
to the device’s communication port.
95 A device’s firmware is being updated
or a configuration is being downloaded.
Cycle power to the device.
Verify that all devices are set
to the same baud rate.
Check DeviceNet cabling to make sure no short circuits exist between CAN (blue and white) wires and power or shield (black, red, and shield) wires.
Check the media system for the following noise sources:
– Device located near
high-volt power cable.
– Incorrect or no termination
resistor used.
Improper grounding.
Device on network
producing noise or incorrect data for the network.
Verify the network’s 24V dc power supply is operating properly.
Verify good cable condition.
Check cable connections to
the device.
None. Do not disconnect the device while the update is in process as existing data in device memory will be lost.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 37
DeviceNet Status Codes
Status Code Description of Status Recommended Action
96 Communication port is in test mode. None.
97 The controller has placed the scanner
in halt mode.February
98 General firmware error. Replace device.
99 System Failure. Replace device.
If the O.CommandRegister.HaltScanner bit is on, turn it off then cycle scanner power.
View and Interpret Controller Status Tags
Use the following procedure to troubleshoot the DeviceNet network using the controller status tags in RSLogix5000 software.
1. Use RSLogix5000 software to verify that the controller is in run
mode and that the program is online with the controller.
2. In the program’s organization tree, double-click Controller
Tags.
Double-click to open.
The Controller Tags display.
Publication
1788-IN052D-EN-P - February 2007
38 ControlNet-to-DeviceNet Linking Device
3. Determine which tags you need to view using the following
procedure.
a. Determine the first part of the tag title specific to your
device using the table below.
If Your DeviceNet Module Is Then the Tag Title
Begins With
Local 1756-DNB module Local:slot number Local:3:
Remote 1756-DNB module Name of the module:slot
number in remote chassis
CompactLogix 1769-SDN module
SoftLogix5800 1784-PCIDS module
DriveLogix/FlexLogix 1788-DNBO
Linking Device, 1788-EN2DN or 1788-CN2DN
Local:slot number Local:4
Local:slot number Local:0
Name of module entered in the module Properties dialog.
Name of the module entered in the module Properties dialog.
Example
1756-DNB:3
My_Flex_Bridge
As_You_Name_
b. Decide which tag type you need to view using the
following table as a reference.
If You Are Troubleshooting Then Check Tag
Ty pe
A problem specific to the DeviceNet scanner or the DeviceNet network.
The DeviceNet scanner and the DeviceNet network status.
A problem corresponding to a specific device on the DeviceNet network.
Status Register StatusRegister
Command Register CommandRegister
Status Tag S
Indicated By
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 39
4. Scroll through the list of tags to locate the specific tag you
need.
Use the following examples as references when determining which tags to view.
1756-DNB Tag Title Example
Tag Titled Local:3:I:StausRegister used to troubleshoot a problem specific to the DeviceNet module or network.
Tag Titled Local:3:S used to troubleshoot a problem specific to a device connected to the DeviceNet network.
Tag Titled Local:3:O.CommandRegister to determine the command of the DeviceNet scanner and its effect on the DeviceNet network.
Publication
1788-IN052D-EN-P - February 2007
40 ControlNet-to-DeviceNet Linking Device
788-CN2DN Tag Title Example
Tag Titled As_You_Name:I:StausRegister used to troubleshoot a problem specific to the DeviceNet module or network.
Tag Titled As_You_Name:S used to troubleshoot a problem specific to a device connected to the DeviceNet network.
Tag Titled As_You_Name:O.CommandRegister to determine the command of the CN2DN device and its effect on the DeviceNet network
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 41
5. If need to troubleshoot Status Register tags, use the following
table as a reference to interpret module or network status.
Status Register Tag Values
If Tag Member Displays
Valu e
Run 0 Scanner in idle mode.
Run 1 Scanner in run mode.
Fault 0 Scanner not faulted.
Fault 1 Scanner faulted.
DisableNetwork 0 Scanner not disabled.
DisableNetwork 1 Scanner disabled.
DeviceFailure 0 Scanner communicating with all devices.
DeviceFailure 1 Scanner not communicating with at least 1 device.
AutoVerify 0 Data size of each device matches the amount of
AutoVerify 1 Data size of at least 1 device does not match the
CommFailure 0 No network-wide communication problem exists
CommFailure 1 Network-wide communication problem exists
DupNodeFail 0 Scanner is on the network at a unique address
DupNodeFail 1 Scanner is trying to get on the network at an
DnetPowerDetect 0 Network connector of the scanner has power.
DnetPowerDetect 1 Network connector of the scanner does not have
Then Status Is
memory allocated for the device in the scanner.
amount of memory allocated for the device in the scanner.
address that is already in use.
power.
Publication
1788-IN052D-EN-P - February 2007
42 ControlNet-to-DeviceNet Linking Device
6. If you need to troubleshoot Status Tags (:S), use the following
table as a reference to interpret device status.
If You Want Information About Then See
Member Data
I/O scans count. ScanCounter DINT
Indication that a device is not communicating on the network.
Use the following information to interpret status:
There is 1 bit for each address on the DeviceNet network (0 -63).
The position of a bit = address of a device.
If a bit = 1, then the device at that address
has failed.
Indication that the data size of a device does not match the amount of memory allocated for the device in the scanner.
Use the following information to interpret status:
DeviceFailureRegister SINT[8]
AutoverifyFailureRegister SINT[8]
Ty pe
There is 1 bit for each address on the DeviceNet network (0 -63).
The position of a bit = address of a device.
If a bit = 1, then their is a mismatch with that
address.
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 43
If You Want Information About Then See
Member Data
Ty pe
Indication that a device is idle.
Use the following information to interpret status:
There is 1 bit for each address on the DeviceNet network (0 -63).
The position of a bit = address of a device.
If a bit = 1, then the device at that address is
idle.
Indication that a device is online.
Use the following information to interpret status:
There is 1 bit for each address on the DeviceNet network (0 -63).
The position of a bit = address of a device.
If a bit = 1, then the device at that address is
online.
ASCII representation of scanner status/display. StatusDisplay SINT[4]
Address of the scanner. ScannerAddress SINT
Status code of scanner. ScannerStatus SINT
DeviceIdleRegister SINT[8]
ActiveNodeRegister SINT[8]
Publication
1788-IN052D-EN-P - February 2007
44 ControlNet-to-DeviceNet Linking Device
If You Want Information About Then See
Member Data
Ty pe
Address with an error.
Use the following information to interpret status:
Scrolls through the addresses with errors.
ScrollingDeviceStatus member shows the
status code.
A status code of an address with an error.
Use the following information to interpret status:
Scrolls through addresses with errors.
ScrollingDeviceAddress member shows the
address.
Status code of all devices – 1 byte per device. DeviceStatus SINT[64]
ScrollingDeviceAddress SINT
ScrollingDeviceStatus SINT
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 45
7. If you need to troubleshoot the CommandRegister tags, use
the following table to interpret or change the status associated with the data bit.
If Bit Bit Name Status Indicates
0 Run Device and Network:
1 Fault Network:
2 Disable Network Network:
3 Halt Scanner Device:
4 Reset Device:
1 = run mode 0 = idle mode
1 = fault present 0 = normal
1 = disabled 0 = normal
1 = halt device (device stops all functions) 0 = normal operation
1 = need to reset device (change to 0) 0 = normal
Publication
1788-IN052D-EN-P - February 2007
46 ControlNet-to-DeviceNet Linking Device

Troubleshoot the ControlNet Network

If ControlNet network communications fail, you need to complete one or more of the following tasks to troubleshoot the ControlNet network.
Interpret the LED Indicators of ControlNet devices on the network.
View and interpret the status indicators displayed on the ControlNet network devices.
Check ControlNet network for media problems.
For more information about completing each troubleshooting task, consult the following publications.
Task Publication Title Publication No.
Interpret LED indicators of a ControlNet module
View and interpret ControlNet network status indicators
Check for ControlNet media problems
Installation instructions specific to the module
- or ­ControlNet Modules in Logix5000 Control Systems User Manual
ControlNet Modules in Logix5000 Control Systems User Manual
ControlNet Fiber Media Planning and Installation Guide
Varies by module
- or -
CNET-UM001
CNET-UM001
CNET-IN001
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 47

Specifications

CN2DN Linking Device, 1788-CN2DN
Attribute Value
Dimensions (H x W x D), Approx.
Enclosure Type None (Open-style)
IEC Temp Code T4
Isolation Voltage 30V, Basic Insulation Type
North American Temp Code T4A
Wiring Category
(1)
Wire Size, Power
Wire Size, DeviceNet Refer to the DeviceNet Media Design and Planning Guide,
Wire Size, ControlNet RG6
(1)
Use this conductor category information for planning conductor routing as described in Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
120 x 200 x 87 mm (4 11/16 x 7 7/8 x 3 7/16 in.)
Tested at 720V dc for 60 seconds, between all ports
3 - on power ports
2 - on communication ports
2
(14 AWG)… 0.25 mm2 (22 AWG) solid or stranded
2.5 mm copper wire rated at 75 °C (167 °F) or greater 3/64 inch (1.2 mm) insulation max
publication DNET-UM072, for information specific to your DeviceNet network.
Publication
1788-IN052D-EN-P - February 2007
48 ControlNet-to-DeviceNet Linking Device
Environmental Specifications
Attribute Value
Conducted RF Immunity IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
EFT/B Immunity IEC 61000-4-4:
Emissions CISPR 11:
ESD Immunity IEC 61000-4-2:
Radiated RF Immunity IEC 61000-4-3:
Relative Humidity IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
Shock, Non-Operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Shock, Operating IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Surge Transient Immunity IEC 61000-4-5:
±4 kV at 2.5 kHz on power ports ±2 kV at 5 kHz on communications ports
Group 1, Class A
6 kV contact discharges 8 kV air discharges
10V/m with 1 KHz sine-wave 80% AM from 30...2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
5...95% noncondensing
50 g
30 g
±2 kV line-earth(CM) on communications ports
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 49
Environmental Specifications
Attribute Value
Temperature, Operating IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F)
Temperature, Storage IEC 60068-2-1 (Test Ab, Unpackaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Non-operating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Non-operating Thermal Shock):
-40...85 °C (-40...185 °F)
Vibration IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz
Publication
1788-IN052D-EN-P - February 2007
50 ControlNet-to-DeviceNet Linking Device

Certifications

The following certifications apply when the product is marked.
Certification
C-Tick Australian Radiocommunications Act, compliant with:
c-UL-us UL Listed Industrial Control Equipment, certified for US and
CE European Union 89/336/EEC EMC Directive, compliant with:
CI ControlNet Int'l conformance tested to ControlNet
CSA CSA Certified Process Control Equipment. See CSA File
EEx
ODVA ODVA conformance tested to DeviceNet specifications.
(1)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
(1)
Valu e
AS/NZS CISPR 11; Industrial Emissions
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810
EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
specifications.
LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2 Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (Zone 2)
Publication
1788-IN052D-EN-P - February 2007
ControlNet-to-DeviceNet Linking Device 51

Additional Resources

Use the following table to determine which publication best suits your information needs.
Topic Publication Title Publication No.
Programming, configuring, using, and troubleshooting of ControlNet modules.
Planning and installating a ControlNet network.
Planning and installating a DeviceNet network.
Programming, configurating, using, and troubleshooting of DeviceNet modules.
ControlNet Modules in Logix5000 Control Systems
ControlNet Coax Media Planning and Installation Guide
DeviceNet Media Design and Installation Guide
DeviceNet Modules in Logix5000 Control Systems
You can view or download publications at http://www.literature.rockwellautomation.com copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
CNET-UM001
CNET-IN002
DNET-UM072
DNET-UM004
. To order paper
Allen-Bradley, ControlLogix, and RSNetworx are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication
1788-IN052D-EN-P - February 2007
Rockwell Automation Support
Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
United States 1.440.646.3223 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for any
technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for return
(see phone number above to obtain one) to your distributor in order to complete the return process.
procedure.
, you can find
.
Publication 1788-IN052D-EN-P - February 2007 PN 953014-33
Supersedes Publication 1788-IN052C-EN-P - May 2001 Copyright © 2007 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...