Rockwell Automation 1771-DCM User Manual

AllenBradley
Direct Communication
User
Module
(Cat. No. 1771-DCM)
Manual

Table of Contents

To Our Customers 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manual's Purpose 11 Intended Audience 11 Terminology 11 Related
Publications
Overview of Direct Communication Module 21. . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview Describing the 1771DCM 21 Choosing 1771DCM or Data Highway 22 Selecting Example Compatible Processors 23 Keying 23
of Direct Communication Module
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
Options
Applications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21. . . . . . . . . . . . . . . . . .
22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting Options 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Selecting Switch Bank 0 32 Switch Bank 1 34
Options
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting Cables 41. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Connector 41 Daisy Chain Hookup 42 Trunkline/Dropline Hookup 43
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Status Word 51. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using the Status Word 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Examining Status Bits Read by the Local Processor 52 Status Bits Read by the Supervisory Processor 53
Status Bits
51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . .
Programming the 1771-DCM 61. . . . . . . . . . . . . . . . . . . . . . .
Programming the 1771-DCM 61. . . . . . . . . . . . . . . . . . . . . . . . . . .
Local Processor Logic 61 1771-DCM Supervisory Processor Logic 63 Processor/Module
Switch Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Compatibility
63. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
613. . . . . . . . . . . . . . . . . . . . . . . . .
Table of Contentsii
Calculating Transfer Time 71. . . . . . . . . . . . . . . . . . . . . . . . .
Calculating Transfer Time 71. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Discrete Transfer Time 71 Block Transfer Time 74 Block Transfer with a PLC3 Supervisory Processor 76
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . .
Troubleshooting Your 1771-DCM 81. . . . . . . . . . . . . . . . . . . .
Troubleshooting Your 1771-DCM 81. . . . . . . . . . . . . . . . . . . . . . . .
LED Display for Normal Operation 81 LED
Display for Fault Conditions Causes of Block Transfer Errors 82 Errors
Indicated by Status Bits
Specifications 84
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
81. . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
83. . . . . . . . . . . . . . . . . . . . . . . . . .

To Our Customers

Chapter
1
To Our Customers

Manual's Purpose

Intended Audience

The following information may be helpful when using this manual:
The purpose of this manual is to help you understand the intended application of your Direct Communication Module (cat. no. 1771-DCM) and operate your 1771-DCM correctly in the shortest possible time. We show you how to:
Select Module Options to Fit your Application Chapter 3 Install and Connect Your 1771-DCM Chapter 4 Use Status Bits to Detect Faults Chapter 5 Program the Transfer of Data between Processors Chapter 6 Compute the Transfer Time between Processors Chapter 7 Troubleshoot Module or System Malfunctions Chapter 8
We assume you are familiar with installing and using Allen-Bradley programmable controllers and that you have written ladder diagram programs. If not, we suggest that you study the Programming and Operations Manual of your processor(s) listed below under Related Publications.

Terminology

Related Publications

We have written this manual using current programmable controller terminology and have attempted to keep it free of jargon. If you encounter terms that you do not understand, we suggest that you obtain the current booklet, Programmable Controller Terms, listed below under Related Publications.
You should be able to install and operate your 1771-DCM without the need for additional publications. If not, the following publications may be of interest to you:
11
Chapter 1
To Our Customers
Title Publication
1771ASB
Programmable Controller T
PLC2/05 Programming Manual
PLC2/15 Programming Manual
PLC2/02, 2/16, 2/17 User's Manual
PLC2/30 Programming Manual
PLC3 Programming Manual
PLC5 Family Processor Manual
PLC5/250 Programmer's Manual
Remote I/O Adapter
erms PCGI7.2
17716.5.37
17726.8.6
17726.8.2
17726.5.8
17726.8.3
17756.4.1
17856.8.2
50006.4.1
12
Chapter
2
Overview of Direct Communication Module
Overview of Direct Communication Module
Describing the 1771DCM
Local Proc.
PLC-2 PLC-5
Allen-Bradley has introduced the Direct Communication Module (cat. no. 1771-DCM) to meet the growing need for communication between PC processors.
The 1771-DCM is a chassis-mounted single-slot I/O module that allows communication between a supervisory processor and local processors (Figure 2.1). The local processor can be chassis-mounted or configured as a local or remote system.
Figure 2.1
and Remote Configurations
Local
Local Configuration
Bidirectional
Block Transfer
S C
D C
M
A N N E R
Supervisory
Processor
PLC–2/30 PLC–3 Family PLC–5/15 PLC–5/25 PLC–5/250
Local
Processor
PLC–2/30 PLC–3 Family PLC–5/250
S C A N
N E R
Remote I/O Link
1771–ASB Protocol
1 7 7 1
­A
S
Remote I/O Link
1771–ASB Protocol
Remote Configuration
Bidirectional
Block Transfer
D C
M
Remote I/O Link
1771–ASB Protocol
S C A N
N E R
Supervisory
Processor
PLC–2/30 PLC–3 Family PLC–5/15 PLC–5/25 PLC–5/250
12825
21
Chapter 2
Overview of Direct Communication Module
The 1771-DCM passes data table values such as command bits, status bits, and data blocks between supervisory and local processors. The supervisory processor typically writes commands and/or data table values to the local processor, and reads resulting status, diagnostic data, and data values from the local processor (or vice versa).
The supervisory processor communicates serially with the 1771-DCM as though it were a 1771-ASB Adapter Module, and addresses the 1771-DCM as though it were addressing a separate I/O chassis. You select the mode of transfer between the supervisory processor and 1771-DCM: discrete transfer (up to eight words) or block transfer (up to 64 words). Either mode includes one status word.
The local processor communicates with the 1771-DCM over the backplane using block transfers and addresses the 1771-DCM as an intelligent I/O module. When the local processor is remotely configured, it communicates with the 1771-DCM via block transfer through its scanner-adapter link.
Choosing 1771DCM or Data Highway

Selecting Options

The 1771-DCM and data highway allow communication between PC processors. Consider the following factors when determining the appropriate choice. Use the 1771-DCM to:
Transfer data table words Obtain predictable transfer times Transfer up to eight words when transfer time over a remote I/O
channel is adequate, in addition to the transfer time of the local processor and 1771-DCM
Transfer up to 64 words when transfer time for block transfers over a
remote I/O channel is adequate, in addition to the transfer time of the local processor and 1771-DCM
Decrease data highway traffic
At least one processor must have a remote I/O scanner.
You cannot transfer ladder diagram programs nor messages stored in the message area of memory using the 1771-DCM.
You can select one or more of the following options depending on your application requirements using switches on the module:
22
Chapter 2
Overview of Direct Communication Module
Baud
Rate/Distance
T
ransfer Method
Rack Size
Protected Data
I/O Rack Address Designate the I/O rack number, the number of the first module group
Select the communication rate and distance to the supervisory proces sor as either 57.6K baud to a distance of 10,000 feet, or 1 to a distance of 5,000 feet.
Select block transfer or discrete data transfer between the 1771DCM and the supervisory processor
When using discrete data transfer termines how the 1771DCM appears to the scanner of the superviso ry processor (the size of the I/O chassis simulated by the 1771DCM). This also determines the number of words transferred.
Select protected data to prevent block transfers from the local proces sor until the supervisory processor has received the previous block transfer.
of the I/O chassis simulated by the 1771DCM, and whether it has the highest starting module group address of two or more chassis as signed to the same rack address.
.
, select the number of slots that de
15.2K baud

Example Applications

Compatible Processors

Keying

These options are described in Chapter 3.
You can use the 1771-DCM in a variety of applications where the transfer of data table values is required. For example, consider using it to:
Call messages stored in the data table of the supervisory processor and
outputted through an ASCII I/O module (cat. no. 1771-DA) or BASIC module (cat. no. 1771-DB)
Download recipe data table values from supervisory to local
processor(s) where you want local processor(s) to execute different versions of the same program
Download commands from the supervisory processor to execute
different sections of a ladder diagram program at the local processor
Use the 1771-DCM with any Allen-Bradley programmable controller that uses block transfer and the 1771 I/O structure.
Reserve an I/O slot for this module by placing keying bands on the backplane connector. Position keying bands between the following numbers labeled on the backplane adjacent to the upper backplane connector. The keying bands mate with corresponding slots in the module connector:
Between 2 and 4 Between 16 and 18
23

Selecting Options

Chapter
3
Selecting Options
Select one or more of the following options depending on your application requirements. Do this by setting switches in Switch Banks 0 and 1 on the left (metal cover) side of the 1771-DCM. To assist you, we have printed a table of switch settings for each switch bank on the module’s cover next to the switches (Figure 3.1).
Figure 3.1 Tables
for Switch Settings
BANK 0
SW SW SW SW SW SW SWITCH
BAUD
RATE
57.6
115.2
I/O RACK
NUMBER
1
P
P
2
L
L
3
C
C
4
-
_
5
5
6
2
7
&
5 / 2 5 0
P L C _
3
NOTE: DO NOT USE OTHER SWITCH POSITIONS
LAST
RACK
12 3 45 6 78
Not
NO
Used
YES
12 34 5 6
00
01 02 03 04 05 06 07 10 11 12 13 14 15 16 17 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37
TRAN S
MTHD
BLOCK DSCRT
BANK 1
SWITCH SWITCH
DATA
PTCT
Not
NO
Used
YES
FIRST
MODULE
GROUP NO.
0 2 4 6
ON
CLOSED
OFF
OPEN
RACK
SIZE
1/4 1/2 3/4
FULL
78
1
B
2
A
3
N
4
K
5 6
0
7 8
1
B
2
A
3
N
4
K
5 6
1
7 8
17906
31
Chapter 3
Selecting Options
Each switch bank has eight switches. Set each switch to the ON (closed) position by depressing the right-hand side of the switch or to the OFF (open) position by depressing the left-hand side of the switch (Figure 3.2).
Figure 3.2 Example
Switch Bank
OPEN
1
2 3 4 5 6 7 8
Switches 1 and 3 are OFF (open) Shading represents the switch position

Switch Bank 0

12826
The options that you select with Switch Bank 0 are as follows:
Switch 1  Baud Rate
ON (Closed) for 57.6K Baud OFF (Open) for 115.2K Baud
Set the baud rate equal to that of the scanner of your supervisory processor. You can transmit data up to 10,000 feet at a data rate of
57.6K baud or up to 5,000 feet at a data rate of 115.2K baud.
Switch 2  Not Used
32
Chapter 3
Selecting Options
Switch 3  Last Rack
ON (Closed) Not Last Rack OFF (Open) Last Rack
If the 1771-DCM is assigned the same I/O rack number as other I/O chassis, designate whether this I/O chassis is the last chassis (has the highest starting module group number) of those assigned the same rack number. (Refer to I/O Rack Number below.)
Switch 4  Transfer Method
ON (Closed) for Block Transfer OFF (Open) for Discrete Data Transfer
Choose either discrete data transfer or block transfer between the supervisory processor and 1771-DCM. With discrete transfer, the rack size you select determines the number of words transferred as either 2, 4, 6, or 8 words including a status word. Data is transferred between the 1771-DCM and the supervisory processor as serial remote I/O data for each slot of the simulated I/O chassis. The supervisory processor updates the 1771-DCM as if it were an I/O chassis on a remote I/O link.
With block transfer, you can transfer up to 64 words including a status word. The 1771-DCM appears to the supervisory processor as a remote 1/4 rack. Data is transferred between the first I/O slot simulated by the 1771-DCM and the supervisory processor when the supervisory processor’s ladder program executes block transfers.
Communication between the 1771-DCM and local processor is always block transfer regardless of the mode of communication between 1771-DCM and supervisory processor.
Switch 5  Not Used
Switch 6  Protected Data
ON (Closed) for Unprotected Data OFF (Open) for Protected Data
This option maintains data integrity and maintains the order of data blocks sent from the local processor to the supervisory processor only when you select block transfer. The 1771-DCM does not recognize the start of a
33
Chapter 3
Selecting Options
new write block transfer from the local processor until the supervisory processor has read the previous data from the 1771-DCM.
When you select unprotected data, the local processor updates the 1771-DCM continually, regardless of whether the supervisory processor has read the data from the 1771-DCM.
Switches 7 and 8  Rack Size
Switch
7
ON ON 1/4
ON OFF 1/2
OFF ON 3/4
Switch 8
Rack Size

Switch Bank 1

OFF OFF Full
When your application requires the transmission of discrete data words, the 1771-DCM appears to the scanner of the supervisory processor as a 4-, 8-, 12-, or 16-slot remote I/O chassis for the transfer of either 2, 4, 6, or 8 words respectively. Select the equivalent rack size depending on the number of words of discrete data you want to write or read. One slot is equivalent to eight discrete data bits. One module group is equivalent to a word. A full rack is equivalent to eight data words. The 1771-DCM inserts one status word in the transfer regardless of the equivalent rack size you select.
When you set the 1771-DCM for block transfer, the 1771-DCM appears to the scanner of the supervisory processor as a block transfer module in the first module group of a four-slot chassis (1/4 rack). You can read and write up to 64 words including one status word. Slots 1 through 3 are not used.
The options that you select with Switch Bank 1 are as follows:
34
Switches 1 through 6  I/O Rack Number
PLC2
Family
1  7
PLC3 and PLC5/250
0 thru 37 octal
PLC5/15 PLC5/25
1  3 1  7
Chapter 3
Selecting Options
Designate the I/O rack number that you assign to the 1771-DCM with Switches 1 - 6 of Switch Bank 1 (Table 3.A).
Table 3.A
Rack Number Selection for PLC2, PLC3, and PLC5 Family Processors
I/O
Switch
I/O Rack Number (Octal)
1 0 ON ON ON ON ON ON
P 2 1 ONON ON ON ON OFF
L 3 2 ONON ON ON OFF ON
C 4 3 ONON ON ON OFF OFF
5 4 ONON ON OFF ON ON
2 6 5 ONON ON OFF ON OFF
7 6 ONON ON OFF OFF ON
PLC-3 & PLC5/250
PLC­5/15
7 ON ON ON OFF OFF OFF
10 ON ON OFF ON ON ON
11 ON ON OFF ON ON OFF
12 ON ON OFF ON OFF ON
13 ON ON OFF ON OFF OFF
14 ON ON OFF OFF ON ON
15 ON ON OFF OFF ON OFF
16 ON ON OFF OFF OFF ON
17 ON ON OFF OFF OFF OFF
20 ON OFF ON ON ON ON
21 ON OFF ON ON ON OFF
22 ON OFF ON ON OFF ON
23 ON OFF ON ON OFF OFF
24 ON OFF ON OFF ON ON
25 ON OFF ON OFF ON OFF
26 ON OFF ON OFF OFF ON
27 ON OFF ON OFF OFF OFF
1 2 3 4 5 6
PLC­5/25
35
Chapter 3
Selecting Options
Switch
I/O Rack Number (Octal)
30 ON OFF OFF ON ON ON
31 ON OFF OFF ON ON OFF
32 ON OFF OFF ON OFF ON
33 ON OFF OFF ON OFF OFF
34 ON OFF OFF OFF ON ON
35 ON OFF OFF OFF ON OFF
36 ON OFF OFF OFF OFF ON
37 ON OFF OFF OFF OFF OFF
1 2 3 4 5 6
Switches 7 and 8  First (Starting) Module Group Number
First
Module
Group Number
0 ON ON
2 ON OFF
4 ON ON
6 OFF OFF
7 8
Switch
Assign a unique stating module group number--such as 0, 2, 4, or 6--in accordance with the number of chassis you assigned to the same I/O rack number. You can assign from one to four 1771-DCMs and I/O adapters to the same I/O rack number, provided that the combination does not exceed a full rack. For example, assign starting module group numbers to each I/O chassis or 1771-DCM in the following combinations:
Rack
Configuration
Four 1/4 Racks
T
wo 1/2 Racks
One 1/4 and One 3/4 Rack
One 3/4 and One 1/4 Rack
Assign Module Group Numbers
0, 2, 4, and 6
0 and 4
0 and 2
0 and 6
36
You selected the equivalent rack size of your 1771-DCM with Switch Bank 0, Switches 7 and 8, above.

Connecting Cables

Chapter
4
Connecting Cables

Module Connector

The communications channel between the 1771–DCM and a supervisory processor is the same serial communications channel as used between the 1771–ASB Remote I/O Adapter (Series A) and the scanner of a supervisory processor. You insert the 1771–DCM in a local or remote I/O chassis and configure the 1771–DCM as an I/O chassis unique to the supervisory processor. You can connect the 1771–DCM in a daisy chain or trunkline/dropline hookup with other remote I/O chassis.
Make your connections to the connector at the bottom of the module (Figure 4.1). Connector terminals are labeled at the bottom of the left cover plate. Connector terminals accommodate two cables––one for the incoming line of a daisy chain hookup, the other for the outgoing line. Use either set of connector terminals for the dropline in the trunkline/dropline hookup. Terminal 1 is connected to Terminal 4, Terminal 2 to Terminal 5, and Terminal 3 to Terminal 6 inside the 1771–DCM.
WARNING: Do not disconnect this connector in a daisy chain hookup when the system is operating because you disconnect the remaining I/O chassis in the daisy chain. The connection between terminals is inside the 1771–DCM.
Figure 4.1 Cable
Connections
Line 2
Shield
Line 1
Line 2
Shield
Line 1
Connector on 1771-DCM
(Clear)
(Blue)
(Clear)
(Blue)
Mating Connector
1
I/O Cable
Install a 150 ohm 1/2 watt resistor when the 1771-DCM
1
is simulating the last I/O chassis in the daisy chain.
12827
41
Chapter 4
Connecting Cables

Daisy Chain Hookup

When using the daisy chain hookup (Figure 4.2), splice each I/O chassis into the main communication line (serial I/O channel). Install a 150 ohm terminator resistor between the terminals of Lines 1 and 2 at the scanner and at the last hookup on the main communications line to terminate both ends of the line.
Figure 4.2 Example
PLC -2/ 30
Daisy Chain Hookup
1772 - SD2
1
Blue
1
Shield
Clear
2
Blue Shield Clear
Blue
1
Shie ld
2
Clear
3
1771 - ASB
Clear
Shie ld
Blue
2
1
2
1
1771 - DCM
Cle ar Shield
Blue
1771 - ASB
Remote I/O Chassis
1771 - ASB
1
Install Terminator Resistor: 150oh m 1/2 watt
1771 - DCM
12661
42
Chapter 4
Connecting Cables

Trunkline/Dropline Hookup

PLC -2/30
When using the trunkline/dropline hookup, connect the 1771–DCM to the serial I/O channel trunkline using a dropline that does not exceed 100 feet in length (Figure 4.3). Connect the dropline to the trunkline using a T connector (cat. no. 1770–XG) or a station connector (cat. no. 1770–SC). There are no restrictions as to the spacing between station connectors or T connectors if you do not exceed the maximum cable distance. Terminate the open port at the first and last T connector or station connector using a Terminator Set (cat. no. 1770–XF).
Figure 4.3 Example
Trunkline/Dropline Hookup with T Connectors
Blue
1772 - SD2
1
2
Shie l d
Clear
1771 - ASB
Bl ue Shield Clear
1 2 3
1771 - ASB
2
1
2
1
1771 - DCM
Cle ar
Shield
Blue
1
Remote I/O Chassis
1
1771 - ASB
1771 - DCM
1
Install Terminator Resistor (cat. no. 1770XF)
12662
43

Using the Status Word

Chapter
5
Using the Status Word
The 1771-DCM sets status/alarm bits in the upper byte of the first word transferred to either processor, regardless of whether you select block transfer or discrete data transfer. In block transfer operation, the status word is the first word of the read data block. In discrete data transfer, the status word is found in the equivalent of the first module group of the I/O chassis simulated by the 1771-DCM.
Important: Reserve the first transferred word for status data inserted by the 1771-DCM. Be sure this word contains zeros when you initialize the ladder program for either processor. The upper byte contains status data. The lower byte is not available for transferring data under any circumstances.
When you select discrete data transfer and set your rack size for the number of words required for your application, keep in mind that the number of words available for your data is one less than the number of words transferred.
Rack
Size
Number of
T
ransfer W
ords
W
ords A
vailable
For Your Data

Examining Status Bits

1/4 2 1
1/2 4 3
3/4 6 5
Full 8 7
Examine bits in the upper byte of the status word using your ladder program so it can take appropriate action when the 1771-DCM detects an error or change in status. Upon detecting an error or change in status, the 1771-DCM sets an invalid data bit along with one or more bits that indicate the nature of the error or change in status. These bits are non-retentive.
51
Chapter 5
Using the Status Word
Bits in the status word read by the supervisory processor differ from those read by the local processor. Some bits apply only when the 1771-DCM is communicating with the supervisory processor by block transfer.
Status Bits Read by the Local Processor
When the 1771-DCM detects an error in its communication with the supervisory processor, it indicates this condition in the status word read by the local processor as follows:
17 16 15 14 13 12 11 10
Insuf Excess Scanner No Inhibit Invalid
Data Data Comm 0 Data 0 Outputs Data
Error
Bit 17  Insufficient Data Available
Set by the 1771-DCM when data received from the supervisory processor is less than that requested by the local processor. It appends zeroed data words to provide the requested number of words.
Bit 16  Excessive Data Available
Set by the 1771-DCM when the data received from the supervisory processor is more than that requested by the local processor. It truncates the data and returns only the number of words requested.
52
Important: In block transfer mode, the 1771-DCM sets Bit 17 or 16 (defined above) when it detects that the length of a read block transfer request from one processor differs from the number of words previously written by the other processor. In discrete data transfer, the 1771-DCM sets Bit 17 or 16 when it detects that the number of words read by one processor differs from the number of words that the 1771-DCM temporarily stored. This depends on the equivalent rack size that you set, such as eight slots for four words.
Bit 15  Scanner Communications Error
Set by the 1771-DCM when it detects a loss in communications with the scanner of the supervisory processor followed by a request for a read block transfer from the local processor. The 1771-DCM returns the last data received from the scanner, or zeroed data words if communications had not been established. The 1771-DCM turns off the serial communications LED until communications are restored.
Chapter 5
Using the Status Word
Bit 14  Not Used
Bit 13  No Data Available
Set by the 1771-DCM at power-up. The 1771-DCM rests this bit when it receives data from the supervisory processor.
Bit 12  Not Used
Bit 11  Inhibit Outputs
Set by the 1771-DCM to inform the local processor that the supervisory processor has been switched to program or test mode, has switched itself to program mode because of a dependent I/O fault (PLC-2 family), or that the 1771-DCM has lost communication with the supervisory processor.
Status Bits Read by the Supervisory Processor
Bit 10  Invalid Data
Set by the 1771-DCM whenever it sets any other status bit. As long as this bit is reset, the 1771-DCM has detected no error condition or change in status.
When the 1771-DCM detects an error in its communication with the local processor, it indicates this condition in the status word read by the supervisory processor as follows:
17 16 15 14 13 12 11 10
Insuf Excess Backplane Backplane No Old 0 Invalid
Data Data Reset Error Data Data Data
Bits 17, 16, 13, and 10  Same as Local Processor
Bit 15  Backplane Reset
Set by the 1771-DCM to inform the supervisory processor that the local processor has reset the backplane. The local processor typically resets the backplane when switched to program/test mode, or when it detects a fault condition and turns off outputs. The 1771-DCM cannot detect a backplane reset due to a fault condition resulting in outputs remaining in last state. You determine the last state condition (hold last state or turn off) by a DIP switch on the I/O chassis.
53
Chapter 5
Using the Status Word
Bit 14  Backplane Error
Set by the 1771-DCM whenever it detects that a block transfer operation by the local processor was not completed on time, was out of sequence, or contained a checksum error. The 1771-DCM returns the last valid data received from the local processor. It returns zeroed data words if communications had not been established. It inhibits block transfers to the local processor until it detects a backplane reset or a scan from the local processor.
Bit 12  Old Data
Set by the 1771-DCM whenever it detects that it has not received data from the local processor after a delay of 14 read scans by the supervisory processor (discrete data transfer), or since the last read block transfer by the supervisory processor. The 1771-DCM passes old data to the supervisory processor until it detects new data, passes it, and resets this bit.
Bit 11  Not Used
54
Chapter

Programming the 1771-DCM

6
Programming the 1771-DCM

Local Processor Logic

We assume that you are familiar with block transfer programming, that you can allocate data table areas for read and write data blocks, and that you can manipulate data to and from these data blocks. We will confine this discussion to programming characteristics unique to the 1771–DCM.
The local processor, typically a PLC–2 family mini–processor or PLC–5 family processor, reads and writes data to the 1771–DCM using block transfers. Programming examples (Figure 6.1, Figure 6.2) assume that the 1771–DCM is set for six–word block transfers.
Figure 6.1 Local
Processor Programming Example (PLC-2)
013
131
06
EN 17
113 DN
17
BLOCK XFER READ Data Address: Module Address: Block Length: File:
0030
0300-0305
BTR Done Bit
11310300
17
Data Valid Bit
Buffer File
FILE TO FILE MOVE Counter Address: Position: File Length: File A: File R: 0400-0405
Rate per Scan: 006
BLOCK XFER WRITE Data Address: Module Address: Block Length: File:
0040
001 006
0300-0305
0031
131
06
0200-0205
0040 EN
17 0040
DN 15
013
EN
16 113 DN 16
61
Chapter 6
Programming the 1771-DCM
Block Transfer and File Move Instructions
Enter these instructions using the following information:
BTR/BTW Module Address
The module address of BTR and BTW instructions in the local processor’s program is the physical location of the 1771–DCM. It is the I/O rack, module group, and slot number (RGS) of the 1771–DCM:
In the same I/O chassis with the local processor In an I/O chassis connected to a processor configured for local or
remote I/O operation
Block Length/File Length
Generally, set them to the number of words that you set for the 1771–DCM. If you have reason to set the read block length different from the write block length (PLC–2 family processors), be sure that both the BTR and BTW instructions cannot be enabled in the same scan. When moving or transferring words into the BTW file for transfer to the 1771–DCM, be sure to avoid placing data in the first word because the 1771–DCM inserts status in this word.
File–to–File Move (FFM)
Use this instruction to store data received from the 1771–DCM. File A address of the FFM is the same as the BTR file address. File R address is a storage file for data received from the 1771–DCM.
Your ladder program must place data into the BTW file for transfer to the 1771–DCM. We leave this ladder logic to you because your application and processor’s set of instructions determine how you would do this.
Examine the status word received from the 1771–DCM as a condition for using the read block transfer data. Zero the status word at power–up and be sure that your program does not use this word for any other purpose.
62
Chapter 6
Programming the 1771-DCM
Figure 6.2
Processor Programming Example (PLC-5)
Local
Rung 2:0 PLC5 local write rung. The DCM is located in the same I/O chassis as the PLC5, and is set for block transfer. The local proces sor's write length must match the supervisory processor's read length.
BTR ENABLE BIT
N12:0
15
Rung 2:1 PLC5 local read rung. The DCM is located in the same I/O chassis as the PLC5, and is set for block transfer. The local proces sor's read length must match the supervisory processor's write length.
BTR ENABLE BIT
N12:0
15
BTW ENABLE BIT
N12:5
15
BTW ENABLE BIT
N12:5
15
BTW BLOCK TRNSFR WRITE Rack Group Module Control Block Data file Length Continuous
BTR BLOCK TRNSFR READ Rack Group Module Control Block Data file Length Continuous
N12:5
N13:30
N12:0
N13:30
17
21
EN
0
DN
3 1
ER
N
EN
0 3
DN
1
ER
N

1771-DCM Switch Settings

Supervisory Processor Logic

Select module operating conditions by setting switches on the module for discrete data transfer or block transfer as follows:
Discrete Data Transfer Block Transfer
Transfer Method Transfer Method
Rack Size Data Protect (If Applicable)
Set other switches as required by your application.
The addresses that you use for the 1771–DCM in the supervisory processor’s ladder program are the addresses (RGS) to which you configure your 1771–DCM using Switch Banks 0 and 1:
I/O Rack Number (Switch Bank 1, Switches 1 through 6).
63
Chapter 6
Programming the 1771-DCM
First (Starting) Module Group Number (Switch Bank 1, Switches 7 and
8) The slot number will always be zero for block transfer only. Equivalent rack size for discrete data transfer only (Switch Bank 0,
Switches 7 and 8). The equivalent rack size for block transfer mode is fixed at 1/4 rack.
Discrete Data Transfer
The supervisory processor transfers discrete data to and from the 1771–DCM automatically via its I/O scan. You do not program these transfers.
To transfer discrete data words to and from the 1771–DCM, you must use I/O image table addresses in the supervisory processor’s ladder program starting with the addresses (RGS) to which you configured your 1771–DCM. Use the number of image table words equal to the equivalent I/O rack size that you set for the 1771–DCM.
The ladder program of your supervisory processor must move discrete data, read from the 1771–DCM, from input image table words to a storage location (Figure 6.3).
Figure 6.3 Supervisory
FFM Done Bit
04110120
15
Processor Programming Example for Discrete Data T
Data Valid Bit
Buffer File
FILE TO FILE MOVE Counter Address: Position: File Length: File A: File R: 0700-0707
Rate per Scan: 008
ransfer (PLC-2/30)
0120-0127
Your ladder program must place data into output image table words for transfer to the 1771–DCM. Avoid placing data in the first word because the 1771–DCM inserts status in this word. We leave this ladder logic to you because your application and processor’s set of instructions determine how you would do this.
0041
001 008
0041 EN
17
0041 DN
15
64
Chapter 6
Programming the 1771-DCM
Example 1:
Suppose you want to transfer six words, and you have configured the 1771–DCM to simulate a 3/4 I/O rack with the following address: Rack Number = 2, First Module Group = 0. Also, suppose that the 1771–DCM is located in the same chassis with the local processor, that the 1771–DCM’s actual location (RGS) is 131, that the local processor’s block transfer read block is 300 through 305, and that the block transfer write block is 200 through 205.
Data transfers would occur as follows:
Supervisory
Output Image Table Words Match the I/O
Chassis Slots Simulated by the 1771-DCM
020 Status Word (Zeroed)
021 First Data Word 022 Second Data Word
: :
025 Fifth Data Word
Local
BTW Instruction Writes Data to the
1771-DCM from Words 200 through 205
200 Status Word (Zeroed)
201 First Data Word 202 Second Data Word
: :
205 Fifth Data Word
Processor
Processor
To
BTR Instruction Reads Data from the 1771-DCM
into Words 300 through 305
300 Status Word (Inserted by DCM)
301 First Data Word 302 Second Data Word
: :
305 Fifth Data Word
To
Input Image Table Words Match the I/O Chassis
Slots Simulated by the 1771-DCM
120 Status Word (Inserted by DCM)
121 First Data Word 122 Second Data Word
: :
125 Fifth Data Word
Local Processor
Supervisory Processor
65
Chapter 6
Programming the 1771-DCM
Your ladder program for the supervisory processor must place data in output image table word addresses for transfer to the 1771–DCM and move data from input image table word addresses as needed by your application. We leave this ladder logic to you because your application and processor’s set of instructions determine how you would do this.
Block Transfer
We present block transfer rungs for the supervisory processor when the 1771–DCM is operating in block transfer mode (Figure 6.4 for a PLC–2/30 supervisory processor, Figure 6.5 for PLC–3, and Figure 6.6 for a PLC–5 family processor).
66
LOCAL PROCESSOR
Chapter 6
Programming the 1771-DCM
Figure 6.4
T
ransfer Programming Example for PLC-2 Family Local and Supervisory Processor
Block
BTR Done Bit
11310300
17
Data Valid Bit
SUPERVISORY PROCESSOR
BTR Done Bit
12010600
07
Data Valid Bit
Buffer File
Buffer File
BLOCK XFER READ Data Address: Module Address: Block Length: File:
FILE TO FILE MOVE Counter Address: Position: File Length: File A: File R: 0400-0477
Rate per Scan: 064
BLOCK XFER WRITE Data Address: Module Address: Block Length: File:
BLOCK XFER READ Data Address: Module Address: Block Length: File:
FILE TO FILE MOVE Counter Address: Position: File Length: File A: File R: 0700-0777
Rate per Scan: 064
0030
131
0300-0377
0040
001 064
0300-0377
0031
131
0200-0277
0032
200
00
0600-0677
0042
001 064
0600-0677
00
00
013 EN
17
113 DN
17
0040
EN
17
0040
DN
15
013 EN
16
113
DN
16
020 EN
07
120 DN
07
0042
EN
17
0042 DN
15
BLOCK XFER WRITE Data Address: Module Address: Block Length: File:
0500-0577
0033
200
00
020
EN
06
120
DN
06
67
Chapter 6
Programming the 1771-DCM
Figure 6.5
T
ransfer Programming Example for PLC-3 Supervisory Processor
Block
BTR Done Bit
WB001:0000
15
BTR Done Bit
WB001:000010WB002:0000
15
Data Valid Bit
Read Request
WB001:0000
17
Buffer File
BTR
BLOCK XFER READ Rack: Group: Module: Data: Length: 064
CNTL: FB001:0000
MVF
BTW
BLOCK XFER WRITE Rack: Group: Module: Data: Length: 064
CNTL: FB001:0000
MVF
FILES FROM A TO R
File A: File R: Counter: Pos/Len: 0/ 64
Mode: ALL/SCAN
002
0 = Low
FB002:0000
002
0 = Low
FB003:0000
FB002:0000 FB004:0000
C0005
CNTL LE
12
CNTL
0
DN
15 CNTL ER
13
CNTL
LE
02 CNTL
0
DN 05
CNTL
ER
03
C0005
EN
12
C0005
DN
15
C0005
ER
13
68
Chapter 6
Programming the 1771-DCM
Figure 6.6 Block T
ransfer Programming Example for PLC-5 Family Supervisory Processor
Rung 2:2 PLC5 supervisory write rung. The DCM is connected via remote I/O to the PLC5, and is set for 57.6K baud, block transfer, and rack 3. The supervisory processor's write length must match the local processor's read length.
BTR ENABLE BIT
N22:0
15
Rung 2:3 PLC5 supervisory read rung. The DCM is connected via remote I/O to the PLC5, and is set for 57.6K baud, block transfer, and rack 3. The supervisory processor's read length must match the local processor's write length.
BTR ENABLE BIT
N22:0
15
BTW ENABLE BIT
N22:5
15
BTW ENABLE BIT
N22:5
15
BTW BLOCK TRNSFR WRITE Rack Group Module Control Block Data file Length Continuous
BTR BLOCK TRNSFR READ Rack Group Module Control Block Data file Length Continuous
N22:0 N19:0
31
N22:5
N19:40
27
EN
3 0
DN
0
ER
N
EN
3 0
DN
0
ER
N
69
Chapter 6
Programming the 1771-DCM
Rung 1STEP0:0 PLC5/250 supervisory write rung. The DCM is connected via remote I/O to the PLC5/250. The DCM baud rate switch setting must match that of its scanner channel. The DCM rack switches are set for rack 7. The local processor's read length must match the supervisory processor's write length.
Figure 6.7
T
ransfer Programming Example for PLC-5/250 Supervisory Processor
Block
BTW ENABLE BIT BW070:0
EN
Rung 1STEP0:1 PLC5/250 supervisory read rung. The DCM is connected via remote I/O to the PLC5/250. The DCM baud-rate switch setting must match that of its scanner channel. The DCM rack switches are set for rack 7. The local processor's write length must match the supervisory processor's read length.
BTW ENABLE BIT BW070:0
EN
BTR ENABLE BIT
BR070:0
EN
BTR ENABLE BIT
BR070:0
EN
BTW BLOCK TRNSFR WRITE Rack Group Module Control Block Data file Length Continuous BT Timeout 4
BTR BLOCK TRNSFR READ Rack Group Module Control Block Data file Length Continuous BT Timeout 4
BW070:0
1BTD2:1
BR070:0 1BTD3:1
007
NO
007
NO
17
15
EN
0
DN
0
ER
EN
0
DN
0
ER
610
Chapter 6
Programming the 1771-DCM
BTR/BTW Module Address
The module address of BTR and BTW instructions in the supervisory processor’s program is the configured address of the 1771–DCM. It is the I/O rack number and starting module group number (its slot number is always zero for block transfer) that you set using Switch Banks 0 and 1).
Block Length/File Length
Generally, set them to the number of words that you set for the 1771–DCM. If you have reason to set the read block length different from the write block length (PLC–2 family processors), be sure that both the BTR and BTW instructions cannot be enabled in the same scan. When moving or transferring words into the BTW file for transfer to the 1771–DCM, be sure to avoid placing data in the first word because the 1771–DCM inserts status in this word.
File–to–File Move (FFM) or (MVF)
Use this instruction to store data received from the 1771–DCM. File A address of the FFM or MVF is the same as the BTR file address. File R address of the FFM or MVF is a storage file for data from the 1771–DCM.
Your ladder program for the supervisory processor must place data into the BTW file for transfer to the 1771–DCM. We leave this ladder logic to you because your application and processor’s set of instructions determine how you would do this.
Examine the status word received from the 1771–DCM as a condition for using the read block transfer data. Zero the status word at power–up and be sure that your ladder program does not use this word for any other purpose.
611
Chapter 6
Programming the 1771-DCM
Example 2:
Suppose you want to transfer 64 words, and you have configured the 1771–DCM to simulate a block transfer module in Rack 2, First Module Group = 0. Also suppose that the 1771–DCM is located in the same chassis with the local processor, and that the 1771–DCM’s actual location (RGS) is 131. In this example, you allocated data blocks for block transfer as follows: (Refer to Figure 6.4 for PLC–2/30, or Figure 6.5 for PLC–3 Programming)
Data
Block Supervisory Processor Local Processor
Read
Write
600 through 677 300 through 377
500 through 577 200 through 277
Data transfers would occur as follows for PLC–2 family processors:
Supervisory
BTW Instruction W 1771-DCM from W 577
500 Status W 501 First Data W 502 Second Data Word
: :
577 Last Data W
Local Processor
BTW Instruction W 1771-DCM from W 277
Processor
rites Data to the
ords 500 through
ord (Zeroed)
ord
ord
rites Data to the
ords 200 through
To
BTR Instruction Reads Data from the 1771-DCM into W
300 Status Word (Inserted by DCM) 301 First Data W 302 Second Data W
377 Last Data W
To
BTR Instruction Reads Data from the 1771-DCM into W
Local Processor
ords 300 through 377
ord
: :
ord
Supervisory Processor
ords 600 through 677
ord
612
200 Status W 201 First Data W 202 Second Data W
277 Last Data W
ord (Zeroed)
ord
: :
ord
ord
600 Status Word (Inserted by DCM) 601 First Data W 602 Second Data W
677 Last Data W
ord
ord : :
ord
Chapter 6
Programming the 1771-DCM

Processor/Module Compatibility

Your 1771–DCM must have the following revision (or later) for compatible block transfer operation with your processor.
Processor
Family
PLC-3 F
PLC-5 E
PLC-5/250 E
1771-DCM Revision
Data transfers would occur as follows when the supervisory processor is a PLC–3:
Supervisory
BTW Instruction Writes Data to the
1771-DCM from Binary File 3, Words 0 through 63
FB003:0000 Status Word (Zeroed)
FB003:0001 First Data Word FB003:0002 Second Data Word
: :
FB003:0063 Last Data Word
Processor
To
BTR Instruction Reads Data from the 1771-DCM
into Words 300 through 377
300 Status Word (Inserted by DCM)
301 First Data Word 302 Second Data Word
: :
377 Last Data Word
Local Processor
Local
Processor
BTW Instruction Writes Data to the
1771-DCM from Words 200 through 277
200 Status Word (Zeroed)
201 First Data Word 202 Second Data Word
: :
277 Last Data Word
To
BTR Instruction Reads Data from the 1771-DCM
FB002:0000 Status Word (Inserted by DCM)
Supervisory Processor
into Binary File 2, Words 0 through 63
FB002:0001 First Data Word FB002:0002 Second Data Word
: :
FB002:0063 Last Data Word
613

Calculating Transfer Time

Chapter
7
Calculating Transfer Time

Discrete Transfer Time

The time required for the transfer of data from supervisory to local processor (and vice versa) is the sum of three events:
Supervisory Processor and Remote I/O Scan Time Transfer Time through the 1771-DCM Local Processor Scan Time
The time required for the supervisory processor to communicate with the 1771-DCM depends on whether you select discrete data transfer (up to eight words) or block transfer (up to 64 words), the number of other remote I/O chassis, and the number of block transfer modules in the local and remote I/O systems.
You select the mode of transfer between the supervisory processor and the 1771-DCM as either discrete data transfer or block transfer. Discrete data transfer is faster than block transfer.
Calculate the transfer time between processors when the 1771-DCM is transferring discrete data by calculating the times associated with the supervisory processor, 1771-DCM, and the local processor. Assume the supervisory and local processor systems contain no other block transfer modules.
Supervisory Processor
The supervisory processor reads discrete input data or writes discrete output data to/from its I/O through its remote I/O scanner. Calculate the total scan time of the supervisory processor as the sum of the program scan, processor I/O scan if applicable, and the remote I/O scan using values in the table as follows:
Scan PLC2/30 PLC3
Program 5 ms/K Words 2.5 ms/K Words
Processor I/O 0.5 ms/Rack N/A
Remote I/O 7 ms/Chassis 6 ms/Chassis
71
Chapter 7
Calculating Transfer Time
Total Scan (PLC-2) = Program + Processor I/O + Remote I/O
Total Scan (PLC-3) = Program + Remote I/O
1771DCM
The delay from the time the 1771-DCM receives data until it is ready for data transfer is 15 ms. During this time, it detects errors and changes in status and formats data.
Local Processor
The local processor reads data from or writes data to the 1771-DCM using block transfer instructions, regardless of how data is transferred between 1771-DCM and supervisory processor. The time required is equal to the program scan plus block transfer time which depends on the number of words transferred.
Time
for
Program Scan 15 ms/K 18 ms/K 5 ms/K
I/O Scan 1 ms 4 ms 0.7 ms
Block Transfer 0.08 ms/W 0.08 ms/W 0.08 ms/W
PLC2/05 PLC2/15
PLC2/30 (Local)
W = Number of Words Transferred
Total Scan = Program and I/O Scan + (Multiplier) x (Number of Words Transferred)
See the appropriate processor manual for times for other processors.
Addition of Block Transfer Modules
Block transfer modules in the local I/O chassis can lengthen the I/O scan time by the time required for each to perform a block transfer (worst case). The delay depends on the number of block transfer modules waiting to transfer and the number of words each will transfer. Calculate the additional block transfer time for your processor as follows for each block transfer module:
72
Time (Local) = Multiplier x (Number of Words Transferred)
Chapter 7
Calculating Transfer Time
Processor Multiplier
PLC2/05, 2/15 0.08
PLC2/30 (Local) 0.08
PLC2 Family Example Computation
Suppose that a PLC-2/30 supervisory processor has a 6K program and seven assigned rack numbers and the PLC-2/05 local processor has a 2K program. There are no other block transfer modules in either the supervisory or local systems.
1. Calculate the time required to transfer eight words from supervisory
to local processor.
2. Calculate the total time required if there are two additional block
transfer modules in the local chassis, transferring 64 words each. Assume worst case.
Solution Part 1:
PLC-2/30 Supervisory Processor Scan Time:
Scan PLC2/30
Program 5 ms/K Words
Processor I/O 0.5 ms/Rack
Remote I/O 7 ms/Chassis
Time (PLC-2/30) = Program + Processor I/O + Remote I/O
= (5 ms)(6) + (0.5 ms)(7) + (7 ms)(7) = 30 ms + 3.5 ms + 49 ms = 82.5 ms
1771-DCM Delay: 15 ms
Local Processor Scan Time:
Time
for
I/O Scan 1 ms
Program Scan 15 ms/K
Block Transfer 0.08 ms/W
PLC2/05
73
Chapter 7
Calculating Transfer Time
W = Number of Words Transferred
Scan = Program Scan + I/O Scan + (Multiplier) x (Number of Words
Transferred) = (15 ms)(2) + 1 ms + (0.08)(8) ms = 30 ms + 1 ms + 0.64 ms = 31.6 ms
Transfer Time = Supervisory + 1771-DCM + Local
= 82.5 ms + 15 ms + 31.6 ms = 129 ms
Solution Part 2:

Block Transfer Time

Additional time for two block transfer modules in the local chassis:
Time (PLC-2/05) = 2(0.08 ms) x (Number of Words Transferred)
= 2(0.08 ms)(64) 1 = 10.2 ms
Total Transfer Time = Discrete Transfer + Block Transfer
= 129 ms + 10.2 ms = 139 ms (Worst Case)
When you select block transfer as the mode of transfer between the supervisory processor and 1771-DCM, you can transfer up to 64 words but the transfer time increases.
The time required for the transfer of data from supervisory to local processor (and vice versa) is the sum of three events:
Supervisory Processor and Remote I/O Scan Time Transfer Time through the 1771-DCM Local Processor Scan Time
74
1771DCM and Local Processor
Refer to Discrete Data Transfer, above, for the time required by the 1771-DCM and the local processor. These times are the same for either method of transfer between the supervisory processor and the 1771-DCM.
Chapter 7
Calculating Transfer Time
PLC2 Family Supervisory Processor
The time required by the supervisory processor is the sum of the program scan, processor I/O scan, and remote I/O scan. The time is lengthened by the number of enabled block transfer modules transferring data, one module after the other, and on the number of words that each module transfers. Calculate the time for a read or write operation for each enabled block transfer module as follows:
Scan PLC2/30
Program 5 ms/K Words
Processor I/O 0.5 ms/Rack
Remote I/O 7 ms/Chassis
Time (1 Module) = Program + Processor I/O + 2(Remote I/O) + 0.5W + 10
Where W = number of words transferred and 10 is an average constant (typically, this constant is 4 for a read and 13 for a write).
If it is possible that all block transfer modules in the supervisory system could be enabled at the same time, the worst case time for any one transfer would include the waiting time for all other other block transfers.
PLC2 Family Example Computation
Suppose there are four block transfer modules in addition to the 1771-DCM that could be enabled simultaneously in a PLC-2/30 supervisory system. The local system has no additional block transfer modules. Assume that the program has 4.8K words, there are six assigned rack numbers in the remote I/O link, and that each block transfer is 64 words.
1. Calculate the worst case time for the five modules to block transfer
their data.
2. Calculate the worst case time for a block transfer from the
supervisory to the local processor.
75
Chapter 7
Calculating Transfer Time
Solution Part 1:
Time (1 Module) = (5 ms)(4.8) + (0.5 ms)(6) + 2(7 ms)(6) + (0.5)(64) +
10 = 24 ms + 3 ms + 84 ms + 32 ms + 10 ms = 153 ms
Total Time (All Five Modules) = 5(153)
= 765 ms (Worst Case)
Solution Part 2:
To calculate the worst case time for block transfer from supervisory to local processor via the 1771-DCM, add times for the 1771-DCM and local processor: 15 ms and 31.6 ms, respectively, assuming no other block transfer modules in the local chassis.
Block Transfer with a PLC3 Supervisory Processor
Total Time = 765 ms + 15 ms + 31 ms
= 811 ms
The time required to complete a read or write block transfer depends on factors that include the number of:
Words of user program Active I/O channels on the scanner I/O chassis entries in the rack list for the channel I/O channels on the scanner that contain block transfer modules Block transfer modules on the channel (if the I/O chassis containing a
block transfer module appears more than once in the I/O chassis rack list, count the module once each time the chassis appears in the rack list)
Typical time required to complete a read or write block transfer depends on the program scan and the scanner scan as follows:
Time (Read or Write) = Program Scan + 2(Scanner Scan)
76
Program Scan
The program scan is approximately 2.5 ms per 1K words of user program when using a mix of examine ON/OFF and block instructions.
Chapter 7
Calculating Transfer Time
Scanner Scan
The time required for the scanner to complete a read or write block transfer depends on the number of other block transfer modules on the same scanner channel that are enabled simultaneously. Use the following procedure to calculate the time required for the PLC-3 processor to perform all block transfers on the channel.
1. Determine the number of active I/O channels on the scanner.
2. Determine the number of I/O channels with block transfer modules.
3. Use these tables to determine the nominal block transfer time using
the numbers from Steps 1 and 2.
Nominal Block Transfer Times (ms) for a BTW
Channels
Block Transfer Modules
with
1 45 50 60 65
2  70 70 75
3   85 95
4    100
1 Active Channel
2 Active
Channels
Nominal Block Transfer Times (ms) for a BTR
Channels
Block Transfer Modules
with
1 35 50 50 60
2  60 60 65
3   70 80
1 Active Channel
2 Active
Channels
3 Active
Channels
3 Active
Channels
4 Active
Channels
4 Active
Channels
4    90
Block transfer times typically are similar regardless of the type of block transfer module or the number of words transferred. Nominal read block transfer times typically are faster than nominal write block transfer times by approximately 10 ms. In this example, consider them the same.
77
Chapter 7
Calculating Transfer Time
4. Count the number of block transfer modules on the channel. If a
chassis containing block transfer modules is repeated in the rack list, count chassis and modules as often as listed.
5. Count the number of I/O chassis entries in the rack list for the
channel.
6. Calculate the block transfer time for the scanner as follows:
Scanner Time
=
Nominal Time
BT Modules
#
x
on the Channel
# I/O Chassis1
+
in Rack List
x
9 ms
PLC3 Example Computation
As an example, we will compute the read or write block transfer time between the supervisory processor and a 1771-DCM in an I/O channel with no other block transfer modules and in an I/O channel with two other block transfer modules in the following system:
User program contains 20K words. Channel 1 contains four I/O chassis, with a total of three block transfer
modules including one 1771-DCM. Channel 2 contains two I/O chassis with no block transfer modules. Channel 3 contains two I/O chassis with one 1771-DCM. Channel 4 is made inactive through processor LIST.
You can compute the read or write block transfer times for the supervisory processor in this example in four steps. Each of the following steps is explained by an accompanying figure:
78
1. Diagram the I/O channels of your PLC system (Figure 7.1), showing
the number of:
Block transfer modules in each I/O chassis Block transfer I/O channels I/O chassis entries in the rack list for each block transfer I/O
channel
Active I/O channels per scanner
A block transfer I/O channel is a channel that contains one or more block transfer modules located in any chassis connected to the channel.
An I/O chassis can appear more than once in a rack list of I/O chassis. Count it and the block transfer module(s) that it contains as often as it is listed.
Figure 7.1 Diagramming
Step 1  Diagram the chassis connected in series to each channel
(up to 4) of your scanner module. Then, fill in the information called fo below. Example values have been added.
I/O Channels
Chapter 7
Calculating Transfer Time
1
2
3
4
1 0 2 0
0 0
1 0
Make interactive thru processor LIST
Description Number Ch 1 Ch 2 Ch 3 Ch 4
Active I/O channels
Block-transfer I/O channels
Block-transfer modules on each I/O block transfer channel
I/O chassis on each block transfer I/O channel (I/O chassis in rack list)
3
2
3
4
= I/O chassis
n = number of block tranfer
modules in chassis
0
0
1
2
0
0
12828
2. Using information from the diagram of I/O channels (Figure 7.1),
look up the nominal time from the table in Figure 7.2.
79
Chapter 7
Calculating Transfer Time
Figure 7.2
T
ime T
Nominal
Step 2  Determine a time from the table. Example values have been added for a BTW instruction.
Number of Active I/O Channels
1 2 3 4
1
Active I/O channels containing one or more blocktransfer modules
45 50 60 65
2
3
4
Time (ms)
able
70 70 75
85 95
100
Number of active I/O channels: 3
Number of active I/O channels containing one or more blocktransfer module: 2
Time from table: 70 ms
3. Compute the approximate transfer time for each block transfer I/O
channel. Use values from your channel diagram (Figure 7.1), a value from the table (Figure 7.2), and the formula from Step 6 above. We make these calculations for you in Figure 7.3.
12829
Figure 7.3 Computing
STEP 3
CT =
CT =
CT1
CT2
CT3
CT4 =
Channel T
:
imes
Compute the scanner time for each block transfer channel. Example values have been added.
Channel T
Nominal Time
=
[ 70 ms ] x [ 3 ] + [ 41 ] x 9 ms
ime
x
210 ms + 3 x 9 ms 237 ms
=
Not a Block T
=
[ 70 ms ] x [ 1 ] + [ 21 ] x 9 ms
ransfer Channel
70 ms + 9 ms 79 ms
Not an Active Channel
# BT Modules on BT Channel
I/O Chassis
+
on BT Channel
-1
x
9 ms
710
Chapter 7
Calculating Transfer Time
4. Compute the approximate read or write block transfer time for
Channel 1 and Channel 3 (Figure 7.4).
Figure 7.4 Computing
Block T
STEP 4
:
Program Scan Time (Program)
Scanner Scan Time (Read or W
Block T
ransfer
T
ime Per Channel
ransfer for Each Channel
Compute the read or write block transfer time. Example values have been added.
Channel 1
Channel 3
rite) =
=
2.5 ms/K Words x 20K W
2.5 ms x 20
=
50 ms
=
237 ms for Channel 1 and 79 ms for Channel 3 (from Step 3)
Program Scan + 2 [Scanner Scan]
=
50 ms + 2 [ 237 ms ] 50 ms + 474 ms 524 ms
=
Program Scan + 2 [Scanner Scan] 50 ms + 2 [ 79 ms ] 50 ms + 158 ms 208 ms
ords
Reducing PLC3 Scan Time
Due to the asynchronous scan relationship between program and scanner and the serial operation of each channel in the scanner, we suggest that you optimize the overall scan time. Although recommendations are application dependent, we make the following recommendations as general guidelines:
Whenever possible, control the manner in which block transfer
instructions are enabled. For example, if only a few block transfer
modules require frequent transfer of data, program them to run
continually. Inhibit block transfer instructions of those modules that
require less frequent transfer until enabled by a timer and/or some
application dependent condition. Program the read and write block transfer instructions of your
1771-DCM in the same rung (Figure 6.5). Distribute your block transfer modules equally between all four scanner
channels.
711
Chapter 7
Calculating Transfer Time
Distribute block transfer instructions equally throughout your program.
Place an equal number of non-block transfer rungs between block
transfer rungs. For large numbers of block transfer instructions, distribute groups of
block transfer rungs equally throughout your program. Place no more
than four block transfer rungs consecutively in one group. Within each
group, condition the next rung using the done bit of the previous block
transfer instruction. Consider an additional I/O scanner module (cat. no. 1775-S4A) if you
cannot otherwise reduce the block transfer times to meet your timing
requirements.
Special Timing Considerations
When using one 1775-S4A I/O scanner with thumbwheel switch set to 1, only part of its data handling capacity is available for handling block transfers. This scanner can store and transfer a maximum of 72 words at any one time. This scanner can do four block transfer modules across any of the active channels.
If a block transfer read instruction is enabled but the scanner’s buffer cannot accept the instruction’s block length (the scanner is processing other blocks of data), the block transfer instruction must wait for a subsequent scan when the scanner’s buffer can accept all the words that the module has to transfer. The same applies for a write block transfer instruction. We suggest that you add an additional scanner if necessary.
Block Transfer Errors
Once enabled, a block transfer instruction in a PLC-3 ladder program will set either a done bit or an error bit. The instruction indicates an error when it illuminates the -(ER)- symbol. Typical block transfer errors occur when:
You do not correctly enter the instruction:
- The rack, group, and module numbers do not match the location of the installed module.
- You entered a file length greater than 64.
- You did not create the data file or the address that you entered does not match the file you created.
712
Read and write error bits illuminate at the same time when the error source is the module address entry or the file length entry in the instruction block.
Chapter 7
Calculating Transfer Time
You have a communications problem. You did not correctly connect the twin-axial cable to the scanner. You did not connect a terminator resistor to each end of the twin-axial
cable.
When the scanner encounters a communication fault, it tries twice to complete the transfer. It sets the error bit after the second unsuccessful try.
When the scanner and/or processor detects a block transfer error, the transfer is halted. Transfers from that module are prevented until:
Your program clears the instruction’s control word (clears the error,
Figure 7.5).
You locate and correct the error.
Figure 7.5 Resetting
Control Word
the Control W
03
13
ord after a Block T
ransfer Error
MOV
Move from A to R A : Storage Word 0000000000000000 R : Control Word 0000000000000000
713
Chapter
8

Troubleshooting Your 1771-DCM

Troubleshooting Your 1771-DCM
LED Display for Normal Operation

LED Display for Fault Conditions

When troubleshooting your 1771–DCM, check each of the following sources in the order given for the cause of the fault:
LEDs on the 1771–DCM Block transfer rungs in the ladder program of your local or supervisory
processor
Status bits in the status word read by the local or supervisory processor
Under normal operating conditions, the LEDs are lit as follows:
Power
(PWR)
Serial Communication (SER COM)
Backplane Communications (BCKPLN COM)
Module Fault (DCM FL
T) OFF
ON
ON
ON
If a fault should occur, the LED display changes to indicate the source of the fault which you diagnose as follows:
LED Status Diagnosis
PWR OFF The
SER COM
Blinking
OFF
1771-DCM is not getting +5V DC. Check the backplane
power supply
Supervisory processor is in program or test mode. Check mode selection.
Supervisory processor is not connected to the scanner the cable between processor and scanner (PLC-2/30 proces sor).
Supervisory processor detected a fault and turned off outputs. Check processor LEDs and status of outputs.
The supervisory processor is not communicating with the 1771-DCM. Check cable connections in the remote I/O link to the 1771-DCM.
.
. Check
81
Chapter 8
Troubleshooting Your 1771-DCM
LED Status Diagnosis
BCKPLN COM
DCM FL
Blinking The
OFF
T ON
1771-DCM turns on this LED for half a second at the com
pletion of a read or write block transfer
The local processor performs block transfers at a rate slower than once every 1/2 second.
With the 1771-DCM in protected data mode, the supervisory processor performs block transfers at a rate slower than once every 1/2 second.
Reduce program scan and/or I/O scan time if possible in either processor.
No block transfers are occurring across the backplane between the local processor and 1771-DCM. Refer to Block T Errors for the local processor
The 1771-DCM has detected an internal fault and is not operat ing. Cycle power to the I/O chassis containing the 1771-DCM. Replace it if the LED remains lit when you restore power
If the 1771-DCM is the only thing connected to a supervisory PLC-3, and the scanner baud is 115.2K, the DCM will stop communicating and turn on the red fault light after approximate ly 20 minutes of communication.
, below
. This LED blinks when:
ransfer
.
.

Causes of Block Transfer Errors

Observe block transfer rungs in the ladder diagram program of the processor not performing block transfers. You have a block transfer error when you observe one or both of the following:
The block transfer error bit is intensified (PLC–3 processor). Enable and done bits of block transfer instructions either do not
intensify or remain intensified. They should alternately turn ON (intensify) and turn OFF.
Block transfer errors are caused if one more more of the following are incorrect:
The 1771–DCM’s location (RGS) in the local I/O chassis must match
the RGS of block transfer instructions in the local processor’s ladder program.
The address of the I/O chassis simulated by the 1771–DCM (RGS)
must match the module address (RGS) of block transfer instructions in the supervisory processor’s ladder program.
The block lengths of read and write block transfer instructions should
be equal (PLC–2 family processors); or if different, do not enable BTR and BTW instructions in the same scan.
82
Chapter 8
Troubleshooting Your 1771-DCM
You assigned valid areas of data table for read and write blocks. For
example, if operating in discrete data transfer mode, I/O image table addresses of the supervisory processor’s ladder program match the RGS to which you configured the 1771–DCM.
Your conditioning instructions in block transfer rungs allow the rungs
to turn ON and OFF.
If using a PLC–2/30 supervisory processor, set the scanner for block
transfer operation.
If using a PLC–3 supervisory processor, create block transfer data files.

Errors Indicated by Status Bits

Display status bits in the status word read by either processor by displaying the read block of the read block transfer instruction. Refer to your processor’s manual for the procedure.
The first word in the data block is the status word. Hex codes of some typical fault conditions are tabulated below:
Hex
Code Fault Condition
Read by Local Processor
0300
2300
0900 or 2B00
4100 or 8100 Number of words transferred between the supervisory proces
Read by Supervisory Processor
0500
0900 or 0D00 1771-DCM has not received data from the local processor
1100
2300
4100 or 8100 Number of words transferred between the local processor and
Supervisory processor is in program or test mode.
No communication between the supervisory processor and its scanner.
1771-DCM has not received data from the supervisory proces sor since power-up.
sor and 1771-DCM is not equal to the number read by the local processor.
1771-DCM has not received data from the local processor since the last time it was read by the supervisory processor
since power-up.
Local processor is not performing block transfers due to a time out, out-of-sequence transfer
Local processor is not performing block transfers because it reset the backplane.
1771-DCM is not equal to the number read by supervisory processor.
, or checksum error
.
.
83
Chapter 8
Troubleshooting Your 1771-DCM

Specifications

Function
Provides
Between Supervisory and Local Processors
Serial Communication
Discrete Data T Seven W Block T
One Status W
Transmission
10,000 Cable Feet at 57.6K Baud
5,000 Cable Feet at 1
Response T
Less than 15 ms
Direct Communication
ransfer: Up to
ords Plus One Status W
ransfer: Up to 63 W
ord
ime
ords Plus
15.2K Baud
ord
Interconnect Cable
1770-CD (Belden 9463 or Equivalent)
Backplane Current
1.2A
Keying
op Connector:
T
Between 2 and 4 Between 16 and 18
Environmental
Operational T
0o to 60oC (32o to 140oF)
Storage T
-40o to 85oC (-40o to 185oF)
Relative Humidity:
5% to 95% (Without Condensation)
emperature:
emperature:
84

Index

A
Application Examples, 23
Audience, 11
B
Baud Rate, 32
Block Length, 62, 611
Block Transfer, 66
Errors, Causes of, 82
C
Connections to Module, 41
D
Data Highway, 22
Data Transfer
Block Transfer Example, 612 Discrete Data Example, 64
Data Words, Available, 51
Description of 1771-DCM, 21
Discrete Data Transfer, 71
E
Module Group Number, 36
O
Options, Selection of, 22, 31
Overview of 1771-DCM, 21
P
Processors, Compatible, 23
Programming, PLC-2 Family Processors
Local Processor, 61 Programming, PLC-3 Supervisory
Processor, 61, 63, 64, 67,
68, 69, 610
Supervisory Processor, 63
Protected Data, 33
Publications, Related, 11
Purpose of Manual, 11
R
Rack
Address, 23 Number, 34 Size, 34
Rack, Last, 33
Errors, Indicated by Status Bits, 83
I
Instructions
Block Transfer, 62 File Move, 62, 611
K
Keying, 23
L
LED Displays, 81
M
Module Address, 62, 611
S
Specifications, 84
Status Bits, 51
Status Word
Read by Local Processor, 52 Read by Supervisory Processor, 53
Switch Bank Settings on 1771-DCM, 32,
63
T
Terminator Resistor, 42, 43
Terminology, 11
Timing Considerations, PLC-3
Program Scan, 76 Reducing Scan Time, 711 Scanner Scan, 77 Special, 712
I–2
Index
Transfer Method, 33
Transfer Time, Block Transfer, 74
Example PLC-2/30 Supervisory
Processor, 75
Example PLC-3 Supervisory Processor,
78
Transfer Time, Discrete Data Transfer, 71
Example PLC-2 Family Processors, 73
Troubleshooting, 81
AllenBradley ductivity and quality for more than 90 years. W
, a Rockwell Automation Business, has been helping its customers improve pro
e design, manufacture and support a broad range of automation products worldwide. They include logic processors, power and motion control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the worlds leading technology companies.
Worldwide representation.
Argentina Australia Austria Bahrain Belgium Brazil Bulgaria Canada Chile China, PRC Colombia • Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala • Honduras Hong Kong Hungary Iceland India Indonesia Ireland
Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia • Mexico Netherlands •New Zealand Norway Pakistan Peru
Philippines Sweden
AllenBradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, T
Poland • Portugal • Puerto Rico • Qatar • Romania • RussiaCIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •
Switzerland Taiwan Thailand Turkey • United Arab Emirates United Kingdom United States Uruguay V
enezuela
Yugoslavia
el: (1) 414 3822000 Fax: (1) 414 3824444
Publication 1771-6.5.27  October, 1987 Supersedes 1771-6.5.27 - June 1985
Copyright
1987 AllenBradley Company
Publication 1771-6.5.27  October, 1987
PN 955102-95
, Inc. Printed in USA
Loading...