The following information may be helpful when using this manual:
The purpose of this manual is to help you understand the intended
application of your Direct Communication Module (cat. no.
1771-DCM) and operate your 1771-DCM correctly in the shortest
possible time. We show you how to:
Select Module Options to Fit your ApplicationChapter 3
Install and Connect Your 1771-DCMChapter 4
Use Status Bits to Detect FaultsChapter 5
Program the Transfer of Data between ProcessorsChapter 6
Compute the Transfer Time between ProcessorsChapter 7
Troubleshoot Module or System MalfunctionsChapter 8
We assume you are familiar with installing and using Allen-Bradley
programmable controllers and that you have written ladder diagram
programs. If not, we suggest that you study the Programming and
Operations Manual of your processor(s) listed below under Related
Publications.
Terminology
Related Publications
We have written this manual using current programmable controller
terminology and have attempted to keep it free of jargon. If you
encounter terms that you do not understand, we suggest that you obtain
the current booklet, Programmable Controller Terms, listed below under
Related Publications.
You should be able to install and operate your 1771-DCM without the
need for additional publications. If not, the following publications may be
of interest to you:
11
Chapter 1
To Our Customers
TitlePublication
1771ASB
Programmable Controller T
PLC2/05 Programming Manual
PLC2/15 Programming Manual
PLC2/02, 2/16, 2/17 User's Manual
PLC2/30 Programming Manual
PLC3 Programming Manual
PLC5 Family Processor Manual
PLC5/250 Programmer's Manual
Remote I/O Adapter
ermsPCGI7.2
17716.5.37
17726.8.6
17726.8.2
17726.5.8
17726.8.3
17756.4.1
17856.8.2
50006.4.1
12
Chapter
2
Overview of Direct Communication Module
Overview of Direct
Communication Module
Describing the 1771DCM
Local
Proc.
PLC-2
PLC-5
Allen-Bradley has introduced the Direct Communication Module (cat. no.
1771-DCM) to meet the growing need for communication between PC
processors.
The 1771-DCM is a chassis-mounted single-slot I/O module that allows
communication between a supervisory processor and local processors
(Figure 2.1). The local processor can be chassis-mounted or configured
as a local or remote system.
Figure 2.1
and Remote Configurations
Local
Local Configuration
Bidirectional
Block Transfer
S
C
D
C
M
A
N
N
E
R
Supervisory
Processor
PLC–2/30
PLC–3 Family
PLC–5/15
PLC–5/25
PLC–5/250
Local
Processor
PLC–2/30
PLC–3 Family
PLC–5/250
S
C
A
N
N
E
R
Remote I/O Link
1771–ASB Protocol
1
7
7
1
A
S
Remote I/O Link
1771–ASB Protocol
Remote Configuration
Bidirectional
Block Transfer
D
C
M
Remote I/O Link
1771–ASB Protocol
S
C
A
N
N
E
R
Supervisory
Processor
PLC–2/30
PLC–3 Family
PLC–5/15
PLC–5/25
PLC–5/250
12825
21
Chapter 2
Overview of Direct
Communication Module
The 1771-DCM passes data table values such as command bits, status
bits, and data blocks between supervisory and local processors. The
supervisory processor typically writes commands and/or data table values
to the local processor, and reads resulting status, diagnostic data, and data
values from the local processor (or vice versa).
The supervisory processor communicates serially with the 1771-DCM as
though it were a 1771-ASB Adapter Module, and addresses the
1771-DCM as though it were addressing a separate I/O chassis. You
select the mode of transfer between the supervisory processor and
1771-DCM: discrete transfer (up to eight words) or block transfer (up to
64 words). Either mode includes one status word.
The local processor communicates with the 1771-DCM over the
backplane using block transfers and addresses the 1771-DCM as an
intelligent I/O module. When the local processor is remotely configured,
it communicates with the 1771-DCM via block transfer through its
scanner-adapter link.
Choosing 1771DCM or Data
Highway
Selecting Options
The 1771-DCM and data highway allow communication between PC
processors. Consider the following factors when determining the
appropriate choice. Use the 1771-DCM to:
Transfer data table words
Obtain predictable transfer times
Transfer up to eight words when transfer time over a remote I/O
channel is adequate, in addition to the transfer time of the local
processor and 1771-DCM
Transfer up to 64 words when transfer time for block transfers over a
remote I/O channel is adequate, in addition to the transfer time of the
local processor and 1771-DCM
Decrease data highway traffic
At least one processor must have a remote I/O scanner.
You cannot transfer ladder diagram programs nor messages stored in the
message area of memory using the 1771-DCM.
You can select one or more of the following options depending on your
application requirements using switches on the module:
22
Chapter 2
Overview of Direct
Communication Module
Baud
Rate/Distance
T
ransfer Method
Rack Size
Protected Data
I/O Rack AddressDesignate the I/O rack number, the number of the first module group
Select the communication rate and distance to the supervisory proces
sor as either 57.6K baud to a distance of 10,000 feet, or 1
to a distance of 5,000 feet.
Select block transfer or discrete data transfer between the 1771DCM
and the supervisory processor
When using discrete data transfer
termines how the 1771DCM appears to the scanner of the superviso
ry processor (the size of the I/O chassis simulated by the 1771DCM).
This also determines the number of words transferred.
Select protected data to prevent block transfers from the local proces
sor until the supervisory processor has received the previous block
transfer.
of the I/O chassis simulated by the 1771DCM, and whether it has the
highest starting module group address of two or more chassis as
signed to the same rack address.
.
, select the number of slots that de
15.2K baud
Example Applications
Compatible Processors
Keying
These options are described in Chapter 3.
You can use the 1771-DCM in a variety of applications where the transfer
of data table values is required. For example, consider using it to:
Call messages stored in the data table of the supervisory processor and
outputted through an ASCII I/O module (cat. no. 1771-DA) or BASIC
module (cat. no. 1771-DB)
Download recipe data table values from supervisory to local
processor(s) where you want local processor(s) to execute different
versions of the same program
Download commands from the supervisory processor to execute
different sections of a ladder diagram program at the local processor
Use the 1771-DCM with any Allen-Bradley programmable controller that
uses block transfer and the 1771 I/O structure.
Reserve an I/O slot for this module by placing keying bands on the
backplane connector. Position keying bands between the following
numbers labeled on the backplane adjacent to the upper backplane
connector. The keying bands mate with corresponding slots in the module
connector:
Between 2 and 4
Between 16 and 18
23
Selecting Options
Chapter
3
Selecting Options
Select one or more of the following options depending on your
application requirements. Do this by setting switches in Switch Banks 0
and 1 on the left (metal cover) side of the 1771-DCM. To assist you, we
have printed a table of switch settings for each switch bank on the
module’s cover next to the switches (Figure 3.1).
Each switch bank has eight switches. Set each switch to the ON (closed)
position by depressing the right-hand side of the switch or to the OFF
(open) position by depressing the left-hand side of the switch (Figure 3.2).
Figure 3.2
Example
Switch Bank
OPEN
1
2345678
Switches 1 and 3 are OFF (open)
Shading represents the switch position
Switch Bank 0
12826
The options that you select with Switch Bank 0 are as follows:
Switch 1 Baud Rate
ON (Closed) for 57.6K Baud
OFF (Open) for 115.2K Baud
Set the baud rate equal to that of the scanner of your supervisory
processor. You can transmit data up to 10,000 feet at a data rate of
57.6K baud or up to 5,000 feet at a data rate of 115.2K baud.
Switch 2 Not Used
32
Chapter 3
Selecting Options
Switch 3 Last Rack
ON (Closed) Not Last Rack
OFF (Open) Last Rack
If the 1771-DCM is assigned the same I/O rack number as other I/O
chassis, designate whether this I/O chassis is the last chassis (has the
highest starting module group number) of those assigned the same rack
number. (Refer to I/O Rack Number below.)
Switch 4 Transfer Method
ON (Closed) for Block Transfer
OFF (Open) for Discrete Data Transfer
Choose either discrete data transfer or block transfer between the
supervisory processor and 1771-DCM. With discrete transfer, the rack
size you select determines the number of words transferred as either 2, 4,
6, or 8 words including a status word. Data is transferred between the
1771-DCM and the supervisory processor as serial remote I/O data for
each slot of the simulated I/O chassis. The supervisory processor updates
the 1771-DCM as if it were an I/O chassis on a remote I/O link.
With block transfer, you can transfer up to 64 words including a status
word. The 1771-DCM appears to the supervisory processor as a remote
1/4 rack. Data is transferred between the first I/O slot simulated by the
1771-DCM and the supervisory processor when the supervisory
processor’s ladder program executes block transfers.
Communication between the 1771-DCM and local processor is always
block transfer regardless of the mode of communication between
1771-DCM and supervisory processor.
Switch 5 Not Used
Switch 6 Protected Data
ON (Closed) for Unprotected Data
OFF (Open) for Protected Data
This option maintains data integrity and maintains the order of data blocks
sent from the local processor to the supervisory processor only when you
select block transfer. The 1771-DCM does not recognize the start of a
33
Chapter 3
Selecting Options
new write block transfer from the local processor until the supervisory
processor has read the previous data from the 1771-DCM.
When you select unprotected data, the local processor updates the
1771-DCM continually, regardless of whether the supervisory processor
has read the data from the 1771-DCM.
Switches 7 and 8 Rack Size
Switch
7
ONON1/4
ONOFF1/2
OFFON3/4
Switch 8
Rack Size
Switch Bank 1
OFFOFFFull
When your application requires the transmission of discrete data words,
the 1771-DCM appears to the scanner of the supervisory processor as a
4-, 8-, 12-, or 16-slot remote I/O chassis for the transfer of either 2, 4, 6,
or 8 words respectively. Select the equivalent rack size depending on the
number of words of discrete data you want to write or read. One slot is
equivalent to eight discrete data bits. One module group is equivalent to a
word. A full rack is equivalent to eight data words. The 1771-DCM
inserts one status word in the transfer regardless of the equivalent rack
size you select.
When you set the 1771-DCM for block transfer, the 1771-DCM appears
to the scanner of the supervisory processor as a block transfer module in
the first module group of a four-slot chassis (1/4 rack). You can read and
write up to 64 words including one status word. Slots 1 through 3 are not
used.
The options that you select with Switch Bank 1 are as follows:
34
Switches 1 through 6 I/O Rack Number
PLC2
Family
1 7
PLC3 and PLC5/250
0 thru 37 octal
PLC5/15PLC5/25
1 31 7
Chapter 3
Selecting Options
Designate the I/O rack number that you assign to the 1771-DCM with
Switches 1 - 6 of Switch Bank 1 (Table 3.A).
Table 3.A
Rack Number Selection for PLC2, PLC3, and PLC5 Family Processors
I/O
Switch
I/O Rack Number (Octal)
1 0ONONONONONON
P2 1ONONONONONOFF
L3 2ONONONONOFFON
C4 3ONONONONOFFOFF
5 4ONONONOFFONON
26 5ONONONOFFONOFF
7 6ONONONOFFOFFON
PLC-3
&
PLC5/250
PLC5/15
7ONONONOFFOFFOFF
10ONONOFFONONON
11ONONOFFONONOFF
12ONONOFFONOFFON
13ONONOFFONOFFOFF
14ONONOFFOFFONON
15ONONOFFOFFONOFF
16ONONOFFOFFOFFON
17ONONOFFOFFOFFOFF
20ONOFFONONONON
21ONOFFONONONOFF
22ONOFFONONOFFON
23ONOFFONONOFFOFF
24ONOFFONOFFONON
25ONOFFONOFFONOFF
26ONOFFONOFFOFFON
27ONOFFONOFFOFFOFF
123456
PLC5/25
35
Chapter 3
Selecting Options
Switch
I/O Rack Number (Octal)
30ONOFFOFFONONON
31ONOFFOFFONONOFF
32ONOFFOFFONOFFON
33ONOFFOFFONOFFOFF
34ONOFFOFFOFFONON
35ONOFFOFFOFFONOFF
36ONOFFOFFOFFOFFON
37ONOFFOFFOFFOFFOFF
123456
Switches 7 and 8 First (Starting) Module Group Number
First
Module
Group Number
0ONON
2ONOFF
4ONON
6OFFOFF
78
Switch
Assign a unique stating module group number--such as 0, 2, 4, or 6--in
accordance with the number of chassis you assigned to the same I/O rack
number. You can assign from one to four 1771-DCMs and I/O adapters to
the same I/O rack number, provided that the combination does not exceed
a full rack. For example, assign starting module group numbers to each
I/O chassis or 1771-DCM in the following combinations:
Rack
Configuration
•
Four 1/4 Racks
• T
wo 1/2 Racks
•
One 1/4 and One 3/4 Rack
•
One 3/4 and One 1/4 Rack
Assign Module Group Numbers
0, 2, 4, and 6
0 and 4
0 and 2
0 and 6
36
You selected the equivalent rack size of your 1771-DCM with Switch
Bank 0, Switches 7 and 8, above.
Connecting Cables
Chapter
4
Connecting Cables
Module Connector
The communications channel between the 1771–DCM and a supervisory
processor is the same serial communications channel as used between the
1771–ASB Remote I/O Adapter (Series A) and the scanner of a
supervisory processor. You insert the 1771–DCM in a local or remote I/O
chassis and configure the 1771–DCM as an I/O chassis unique to the
supervisory processor. You can connect the 1771–DCM in a daisy chain
or trunkline/dropline hookup with other remote I/O chassis.
Make your connections to the connector at the bottom of the module
(Figure 4.1). Connector terminals are labeled at the bottom of the left
cover plate. Connector terminals accommodate two cables––one for the
incoming line of a daisy chain hookup, the other for the outgoing line.
Use either set of connector terminals for the dropline in the
trunkline/dropline hookup. Terminal 1 is connected to Terminal 4,
Terminal 2 to Terminal 5, and Terminal 3 to Terminal 6 inside the
1771–DCM.
WARNING: Do not disconnect this connector in a daisy chain
hookup when the system is operating because you disconnect
the remaining I/O chassis in the daisy chain. The connection
between terminals is inside the 1771–DCM.
Figure 4.1
Cable
Connections
Line 2
Shield
Line 1
Line 2
Shield
Line 1
Connector on 1771-DCM
(Clear)
(Blue)
(Clear)
(Blue)
Mating Connector
1
I/O Cable
Install a 150 ohm 1/2 watt resistor when the 1771-DCM
1
is simulating the last I/O chassis in the daisy chain.
12827
41
Chapter 4
Connecting Cables
Daisy Chain Hookup
When using the daisy chain hookup (Figure 4.2), splice each I/O chassis
into the main communication line (serial I/O channel). Install a 150 ohm
terminator resistor between the terminals of Lines 1 and 2 at the scanner
and at the last hookup on the main communications line to terminate both
ends of the line.
Figure 4.2
Example
PLC -2/ 30
Daisy Chain Hookup
1772 - SD2
1
Blue
1
Shield
Clear
2
Blue
Shield
Clear
Blue
1
Shie ld
2
Clear
3
1771 - ASB
Clear
Shie ld
Blue
2
1
2
1
1771 - DCM
Cle ar
Shield
Blue
1771 - ASB
Remote I/O Chassis
1771 - ASB
1
Install Terminator Resistor:
150oh m 1/2 watt
1771 - DCM
12661
42
Chapter 4
Connecting Cables
Trunkline/Dropline Hookup
PLC -2/30
When using the trunkline/dropline hookup, connect the 1771–DCM to the
serial I/O channel trunkline using a dropline that does not exceed 100 feet
in length (Figure 4.3). Connect the dropline to the trunkline using a T
connector (cat. no. 1770–XG) or a station connector (cat. no. 1770–SC).
There are no restrictions as to the spacing between station connectors or T
connectors if you do not exceed the maximum cable distance. Terminate
the open port at the first and last T connector or station connector using a
Terminator Set (cat. no. 1770–XF).
Figure 4.3
Example
Trunkline/Dropline Hookup with T Connectors
Blue
1772 - SD2
1
2
Shie l d
Clear
1771 - ASB
Bl ue
Shield
Clear
1
2
3
1771 - ASB
2
1
2
1
1771 - DCM
Cle ar
Shield
Blue
1
Remote I/O Chassis
1
1771 - ASB
1771 - DCM
1
Install Terminator Resistor
(cat. no. 1770XF)
12662
43
Loading...
+ 37 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.