Chapter
PLC2 Family Processors 42
Adding
Setting
Expanding
Changing
Justifying
Demonstrating EndofString Delimiter 49
Removing the Fill Character 414
Removing Header and Trailing Characters 415
Demonstrating Data Conversion 417
Selecting Report Generation Mode, Data Conversion,
Formatting a SingleLine Message 421
Formatting a MultiLine Message 424
PLC3 Processors 427
Adding
Setting
Expanding
Changing
Justifying
Demonstrating EndofString Delimiter 435
Removing the Fill Character 440
Removing Header and Trailing Characters 442
Selecting Report Generation Mode, Data Conversion,
Formatting a SingleLine Message 446
Formatting a MultiLine Message 449
Demonstrating Data Conversion 452
Summary 455
Complete Getting Started Program, PLC2 Family A1. . . . . . . . . . . . .
Block Transfer Programming A3
Block Transfer Timing A5
Example Read (Only) Program A15
Example Write (Only) Program A18
Example Read/Write Program A19
Example Application Write Program A22
For PLC-3 Family Processor A26
Complete Getting Started Program, PLC-3 A26
Block Transfer Programming A30
Example Read (Only) Program A41
Example Write (Only) Program A45
Example Read/Write Program A47
Example Application Read/Write Program A50
Block Transfer Programming B5
Example Read (Only) Program B16
Example Write (Only) Program B20
Example Read/Write Program B22
Example Application Read/Write Program B25
This manual tells you in a tutorial manner how to install and use your
ASCII module.
In
Chapter
1
2
3
4Handshaking
5
6T
Appendix
Getting Started with
Y
our ASCII Module
Choosing Module
Features
ASCII Module T
Functions of Control
and Status Bits
roubleshooting Y
Module
EntitledW
Read data from your ASCII module and write data to it
using an industrial terminal
Choose module features so you can match your ASCII
module with your ASCII device
utorial
our ASCII
Select and demonstrate module features, and format
messages
Program the handshaking logic that controls
communication between your ASCII module and your PC
processor
Select desired features and read module status by
describing the function of bits in command and status
words
Interpret status indicators and status codes, and use a
simple program to test your ASCII module.
Program block transfer communication and estimate the
time required for read/write handshaking. W
included numerous example programs
e W
ill Show Y
ou How T
o
e have
Intended Audience
Notational Conventions
Index
Locate concepts and definitions in the text
We assume that you are familiar with operating and programming your
Allen-Bradley controller. Because of the functions that your module
performs, your programming skills should include file manipulation and
message formatting. Refer to the Programming and Operations Manual
for your PLC-2 family controller or to the Programming Manual for your
PLC-3 controller.
Some chapters in this manual contain examples of how you enter data or
commands. When you read these chapters, remember the following
notational conventions:
1
Preface
To Our Customers
A symbol or word in brackets represents a single key you would press.
These include keys such as [ENTER], [SHIFT], or [
].
Spaces would be entered as shown, except that the space preceding and
following the brackets is not an entered space. (We put a space before
the left bracket and after the right bracket to make it easier to read).
Numbers and capital letters not in brackets would be entered as shown.
Punctuation such as commas, and symbols such as / would be entered
as shown.
For example, typical data and a typical command that you would enter on
the industrial terminal keyboard are as follows:
Enter: ALLEN 123/AB[ENTER] (data)
Enter: DD,O3:0,[SHIFT]%A[ENTER] (PLC-3 command)
Some Tips on Using This Manual
We have included numerous examples of CRT displays resulting from
data or commands that you enter. All CRT displays are shown with a
shaded background. Enter all commands on the industrial terminal
keyboard. The only exception is for some PLC-3 entries where we tell
you to use the PLC-3 front panel.
Read chapters 1 and 2 before proceeding to other chapters of this manual
that pertain to your needs. For example, you may want to use only
selected module features (chapter 3) and read only selected bit
descriptions (chapter 5).
We have developed forms to assist you in selecting module features and in
troubleshooting. Make a copy of each of the following and refer to them
as needed.
Initialization Words for Data ModeForm 5175, chapter 2
Initialization Words for Report
Generation ModeForm 5176, chapter 2
Command and Status WordsFigure 5.2-5.4 chapter 5
Fault StatusTable 6.E, chapter 6
2
Preface
To Our Customers
You will use several procedures frequently in the tutorial chapters of this
manual. You may want to memorize the steps or have a reference copy of
the following procedures:
Reading Data From Your ASCII Device
Writing Data To Your ASCII Device
Setting Bits in Initialization Words
Typical Applications
You can use an ASCII I/O module to input data to the processor from a
data source such as a bar code reader, output messages from the processor
to a display device, or bidirectionally exchange messages and/or data
between an intelligent data terminal and the processor. Typical examples
are as follows:
Type
of
Devices
Bar code readers
KeypadsInput
Dotmatrix scrolling
displays, terminals, or
printers
Intelligent data
terminals
ComputersInput/Output
DeviceApplications
Input
Output
Input/Output
Part recognition, sorting, inventory control
Enter values, change data
Display warnings or diagnostic messages,
print production reports
Enter values, change data, monitor or
troubleshoot a process
Exchange data files
3
Chapter
2
Getting Started With Your ASCII Module
ASCII is the acronym for American Standard Code for Information
Interchange. The standard includes a 7-bit code for 128 data and control
characters.
With your ASCII I/O module you can transfer data, by means of the I/O
scan, from an ASCII device to the PC processor data table, and vice versa.
The module has two modes of operation, data mode and report generation
mode. In data mode, you can transfer ASCII, BCD, or hex characters.
Generally, use this mode to transfer data to the processor data table. In
report generation mode, you can include BCD values in the string of
ASCII characters. Generally, use this mode when you want to transfer
messages.
You can use your ASCII module with any Allen-Bradley programmable
controller that has an expandable data table, block transfer capability, and
uses the 1771 I/O structure. If you use a PLC-2/20 controller (cat. no.
1772-LP2), your programming will be lengthier because its processor
does not have file move or block transfer instructions.
Getting Started with Your ASCII Module is a hands-on exercise. By
going step by step through two easy examples, you will quickly learn
operation of your module’s basic features.
This chapter is divided into two sections, one for PLC-2 family
processors, the other for PLC-3 processors. Proceed to the section that
pertains to your processor.
21
Chapter 2
Getting Started with Your ASCII Module
PLC2 Family Processors
What You Need to Get Started
You will demonstrate the operation of your ASCII module by reading data
from the industrial terminal to the processor data table, and by writing
data from the data table to the industrial terminal. You will use your
industrial terminal as an ASCII device for entering data (read), and for
displaying data (write).
You will need to set up a PC processor with an I/O chassis, power supply,
industrial terminal, cables, and your ASCII module. You will need about
an hour to complete the tutorial exercises in this chapter, and about two
hours to complete those of chapter 3, once you have the equipment
operating properly.
Equipment That You Need
You will need the following equipment (Table 1.A) using your existing
system and/or spare equipment.
Table 1.A
Equipment
(PLC2 Family)
22
Equipment
ASCII I/O module
Industrial T
PLC2 Family Keytop Overlay
Alphanumeric Keytop Overlay
Processor Interface Cable
IT/DH Adapter Cable
Processor PLC2/20, 2/30
I/O Interconnect Cable1777CB, CA
Local Adapter Module
T
ermination Plug
erminal1770T3
I/O Chassis
Power Cable
Catalog Number
1771DA
1770KCB
1771KAA optional
1772TC
1770CB (figure 1.4)
1771A1, A2, A4
1771CJ, CK
1771AL
1777CP
Chapter 2
Getting Started with Your ASCII Module
or
Processor
MiniPLC2/15
Power Supply
Power Cable
1771P1
1771CL
Note: You must use battery back-up.
The ASCII module draws 1.3A from the backplane. Be sure that the total
current drain of all modules in the chassis does not exceed the maximum
for the backplane and power supply.
If you use an existing system, consider disconnecting all other chassis
except the one containing your ASCII module. Disconnect field wiring
arms from output modules for safety purposes.
How to Connect Your Equipment
Connect your equipment with the appropriate cables (Figure 1.1 for
Mini-PLC-2/15 controllers, Figure 1.2 for PLC-2/20 or-2/30 controllers).
Be sure that the end of your IT/DH adapter cable labeled CHANNEL B is
connected to channel B on the industrial terminal.
23
Chapter 2
Getting Started with Your ASCII Module
1771-P1
Power Supply
1771-CL
Power Cable
Figure 1.1
Connections
Mini-PLC-2/15
Processor
for MiniPLC2/l5 Controller
Module Group 1,
Slot 1
1771-DA ASCII
I/O Module
1771-A1, -A2, -A4
I/O Chassis
1772-TC
Processor Interface Cable
See WARNING in section titled How
to Connect Your Equipment." Using Channels
A & B
Channel A
1770-T3
Industrial Terminal
(rear view)
Channel B
1770-CB IT/DH
Adapter Cable
11817
1.Connect the power cable between the power supply and the I/O
chassis. The cable connects to the backplane of the I/O chassis
behind the processor/adapter slot.
2.Connect the processor interface cable between the PC processor and
channel A on the industrial terminal.
3.Connect the IT/DH adapter cable between the ASCII module and
channel B on the industrial terminal.
24
Chapter 2
Getting Started with Your ASCII Module
1771-CK,-CJ
PowerCable
Figure 1.2
Connections
PLC-2/30
Processor
1771-ALLocal
AdapterModule
for PLC2/20 or PLC2/30 Controller
1772-TCProcessor
InterfaceCable
1771-CA,-CB
I/OInterconnect
Cable
ModuleGroup1,
Slot1
ChannelA
1771-DAASCII
I/OModule
See WARNING in section titled How
to Connect Your Equipment." Using Channels
A & B
1770-T3
IndustrialTerminal
(rearview)
ChannelB
1770-CBIT/DH
AdapterCable
1771-A1,-A2,-A4
I/OChassis
1777-CP
TerminationPlug
11818
4. (PLC-2/20, -2/30, only) Connect the I/O interconnect cable between
the PC processor and the I/O adapter module
If the IT/DH adapter cable is too short or not available, make your own.
It should not exceed 50 feet (Figure 1.4).
Using Channels A and B
You may or may not be able to connect cables to channels A and B at the
same time depending on the revision of your industrial terminal.
25
Chapter 2
Getting Started with Your ASCII Module
Industrial terminals manufactured before May 1982 allow cross talk
between channels A and B. As a result, data table values could be altered.
Therefore, you should alternate cables between channels for the tutorials
of this manual when using these terminals. When using a series A
industrial terminal, you must alternate cables.
Your industrial terminal has a date code stamped in white on the upper
right corner of the rear label. If your industrial terminal (cat. no.
1770-T3/TA series B) is date coded T 8218 or earlier, or is not date coded,
alternate cables and observe the following warning:
WARNING: When cables are connect to channels A and B at
the same time, cross talk between these channels could cause
the processor to misread inputs and/or misapply outputs, with
possible damage to equipment and/or injury to personnel. For
this reason, do not remove the slide bar that prevents you from
connecting cables to channels A and B at the same time.
If your industrial terminal (cat. no. 1770-T3/TA series B) is date coded T
8219 or later, you can use channels A and B at the same time.
If alternating between channels A and B, connect the 1770-CB cable to
channel B when using the industrial terminal in alphanumeric mode as a
data terminal. Connect the 1772-TC cable to channel A when using the
industrial terminal in PLC-2 (ladder diagram) mode.
As an alternative, use a second industrial terminal in alphanumeric mode
on channel B, or use a Silent 700 data terminal. Connect either to the
1770-CB cable.
Checking ASCII Module Configuration
Your module is configured for RS-232-C operation when shipped from
the factory. If you suspect that its internal configuration (settings of
internal programing plugs) has been altered, you should check module
configuration (refer to section titled Choosing the Mode of
Communication in chapter 3). Do this as follows:
26
1.Remove covers from the module’s printed circuit board.
Chapter 2
Getting Started with Your ASCII Module
2. Locate the programming plugs and set them according to RS-232-C
without control lines (figure 2.8).
Entering the ““Getting Started Program””
You may want to record on tape the ladder diagram of your application
program before proceeding because you will need to load ASCII logic
into a cleared memory for chapters 1 and 3.
Using your industrial terminal, enter the ““Getting Started Program””
(Figure 1.3) into processor memory. At this point, you do not need to
understand how the program works, but you should enter it exactly as
shown.
27
Chapter 2
Getting Started with Your ASCII Module
Figure 1.3
Getting
LADDER DIAGRAM DUMP
020
02
252
07
020
02
063
15
252
15
252
327
G
000
063
17
200
15
200
Started Program" (PLC2 Family)
START
200
PUT
000
200
07
063
TON
.01
PR 300
AC 000
035
00
15
15
03500252
15
03500252
15
251
063
G
000
020
063
G
000
02001252
02001252
=
100
01
247
=
200
16
16
020
00
200
L
OFF 15
200
U
OFF 15
020
01
020
L
OFF 00
020
U
OFF 00
200
L
ON 16
200
U
ON 16
28
Chapter 2
Getting Started with Your ASCII Module
011
BLOCK XFER READ
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:
BLOCK XFER WRITE
DATA ADDR:
MODULE ADDR:
BLOCK LENGTH:
FILE:
252 - 271
200 - 217
030
111
16
031
111
16
EN
17
111
DN
17
011
EN
16
111
DN
16
020
END 00460
NOTE: Configure the data table for two racks using [SEARCH][5][0]
before entering this program.
Installing Your ASCII Module
Be sure that power to the I/O chassis is turned off when installing (or
removing) your ASCII module as follows:
1.Remove power from the I/O chassis.
2.Insert the ASCII module in rack 1, module group 1, slot 1. The
program makes the processor communicate with the ASCII module
at that specific location. (If you must use another rack location and
are familiar with block transfer operation, change the rack, group,
and slot number of the module address in the block transfer read and
write instructions, accordingly.)
02
3.Turn on power to the I/O chassis. Three LED indicators on the
ASCII module illuminate momentarily. Their functions are:
FAULT: Normally off. This red LED indicator illuminates when the
module detects an internal fault.
29
Chapter 2
Getting Started with Your ASCII Module
BUFFER FULL: Normally off. This yellow LED indicator
illuminates when the input buffer becomes full.
CHANNEL ACTIVE: This green LED indicator illuminates when
the industrial terminal is on, properly connected to the ASCII
module’s interface port, and set for alphanumeric mode.
Reading Data from Your ASCII
Device
In this demonstration, you will enter data and observe how it is stored in
the processor data table. You will use the industrial terminal in
alphanumeric mode as an ASCII data terminal when you enter data. Then
you will change the industrial terminal to PLC-2 mode and observe the
transferred data by displaying the contents of the block transfer read file.
You will use the following procedures:
In
Procedure
P1
P2
P3
P4
Set your industrial terminal to alphanumeric mode
Enter your data
Set your industrial terminal to PLC2 mode
See how data is stored in the data table
Y
ou W
ill
Later in this chapter and in chapter 3 you will combine these procedures
with others. The order in which you will perform them may vary.
Even if you are familiar with these procedures, we suggest that you read
them completely. If you deviate from them, proper operation may not
occur.
210
If you have not already done so, load the “Getting Started Program”
(Figure 1.3) into processor memory.
Procedure P1
Set Your Industrial Terminal to Alphanumeric Mode
1. Turn on the industrial terminal.
2. Insert the Alphanumeric Keytop Overlay (cat. no. 1770-KAA).
Chapter 2
Getting Started with Your ASCII Module
To avoid switching keytop overlays every time you change the industrial
terminal operating mode, you can label numbers, letters, and [RETURN]
on the corresponding keytops of the PLC-2 family overlay.
3. Select alphanumeric mode.
Press 12 on the keyboard
The ASCII module’s CHANNEL ACTIVE LED illuminates.
4. Set the communication rate to 300 baud.
Press 13 [RETURN]
The cursor in the upper left corner of a blank screen tells you the terminal
is ready for your input.
5. Change the processor mode select switch to the RUN/PROG
position. (Failure to do this step now will prevent a transfer.)
Procedure P2
Enter Your Data
1. Be sure the processor mode select switch is in the RUN/PROG
position.
2. Enter data such as your first name followed by a couple of numbers.
Enter 11 characters including a space between your name and
numbers (Table 1.B).
A 41
B 42
C 43
D 44
E 45
F 46
G 47
H 48
I 49
J 4A
K 4B
L 4C
M 4D
N 4E
O 4F
P 50
Q 51
R 52
S 53
T 54
U 55
V 56
W 57
X 58
Y 59
Z 5A
The industrial terminal displays the characters as you enter them. If
characters are not displayed, check the program that you loaded into
memory. If you find no errors, refer to Need Help? below.
3.Change the processor mode select switch to the PROG position.
(Failure to do this step now will prevent correct operation.)
Procedure P3
Set Your Industrial Terminal to PLC-2 Mode
1.Press [MODE SELECT]
2.Change the keytop overlay to PLC-2 family.
3.Select PLC-2 mode.
Press 11 on the keyboard
Procedure P4
See How Data Is Stored in the Data Table
1.Move the cursor to the rung containing the read block transfer
instruction (rung 14). The cursor will illuminate the instruction title
BLOCK XFER READ.
2.Display the contents of the read block transfer file in hex.
212
Chapter 2
Getting Started with Your ASCII Module
Press [DISPLAY] 1
Results The industrial terminal displays the name and numbers (first 10
characters) that you entered in step 2. For example,
ALLEN 12345 would be displayed as:
POSITIONFILE
001E010
0020000
003414C
0044C45
0054E20N
00631321 2
00733343 4
DA
TA
ASCII Equivalent
status word one
status word two
A L
L E
Entering the eleventh character caused the module to transfer the data.
Note the space entered between ALLEN and 12345.
The display of status word one (E010) and status word two (0000)
indicates normal status of the module.
3.Terminate this display by pressing [CANCEL COMMAND], and
return to ladder diagram.
Need Help?
If your display was all zeros, the data did not transfer. You may have
altered the procedure.
Did you enter your program exactly as shown?
Did the module’s CHANNEL ACTIVE LED go on?
Did you perform Procedure P1 before P2?
Did you perform Step 1 in Procedure P2?
Did you perform Step 3 in Procedure P2?
213
Chapter 2
Getting Started with Your ASCII Module
If you are still having trouble, refer to “Testing the ASCII Module and
Cables,” to verify communication between the ASCII module and the
industrial terminal. If you suspect a cable problem, check the 1770-CB
cable (Figure 1.4).
Then try again, starting at Procedure P1.
Figure 1.4
Minimum
Connections in the 1770CB Cable
1
2
3
7
18
25
ASCII Module
Interface Port
* Protective Ground
Transmitted Data
Received Data
Ground
1
2
3
7
18
25
Industrial Terminal
Channel B
Connectors:
25pin DShell
Male Connector
Cable Kit
1770XXP (each
end)
Cable:
Belden 8723 or
equivalent
* In cable but not
required for ASCII
module
11819
Writing Data to Your ASCII
Device
214
In this demonstration, you will load data characters into the write block
transfer file and observe how they are displayed. You will use the
industrial terminal in PLC-2 mode to load data. Then you will change the
industrial terminal to alphanumeric mode and observe the transferred data.
Chapter 2
Getting Started with Your ASCII Module
You will use the following procedures where Procedures P1 and P3 are
repeated from the section titled Reading Data from Your ASCII Device.
In
Procedure
Y
ou W
ill
P3
P5
P1
Set your industrial terminal to PLC2 mode
Load data into the write block transfer file
Set your industrial terminal to alphanumeric mode (and
observe the transferred data)
Procedure P3
Set Your Industrial Terminal to PLC-2 Mode
NOTE: Skip this procedure if your processor is already in PLC-2 mode.
1.Press [MODE SELECT]
2.Check that the PLC-2 family keytop overlay is in place.
3.Select PLC-2 mode.
Press 11 on the keyboard
The beginning of your ladder diagram program will be displayed.
Procedure P5
Load Data into an Instruction File
1.Check that the processor mode select switch is in the PROG position.
2.Move the cursor to the instruction whose file you want to load
(BLOCK XFER WRITE).
3.Display the file in hex.
Press [DISPLAY] 1
4.Load new data starting in position 003 for a write block transfer
instruction, position 001 for other file instructions. (Positions 001
and 002 are reserved for command words in a write block transfer
instruction.)
215
Chapter 2
Getting Started with Your ASCII Module
For example, load the following hex codes that are equivalent to
BRADLEY 12345 as follows: (Note the space between BRADLEY and
12345.)
POSITIONFILE
0034252B R
0044144A D
0054C45
0065920Y
00731321 2
00833343 4
00935005
DA
TA
ASCII Equivalent
L E
Check your display of FILE DATA to be sure that you entered all data
exactly as shown.
Don’t forget to press [INSERT][
] after entering data in each position.
Use the shift key to enter the hex character C.
Procedure P1
Set Your Industrial Terminal to Alphanumeric Mode
216
1.Insert the alphanumeric keytop overlay.
2.Select alphanumeric mode.
Press [MODE SELECT] 12
3.Set the communication rate to 300 baud.
Press 13 [RETURN]
The module’s CHANNEL ACTIVE LED turns on.
4.Change the processor mode select switch to the RUN/PROG
position.
Chapter 2
Getting Started with Your ASCII Module
Results The following display appears at the upper left corner of the
industrial terminal:
BRADLEY 12345
5.Terminate the display and return to ladder diagram. Use the PLC-2
family keytop overlay.
Press [MODE SELECT] 11
Summary
Now that you have demonstrated the transfer of data from your ASCII
device to the data table and vice versa, you are ready to use these
procedures further. First, read the next chapter, “Choosing Module
Features.” It defines key words and concepts. Then in chapter 3, “ASCII
Tutorial”, you will use these procedures to demonstrate operating
characteristics of your module.
217
Chapter 2
Getting Started with Your ASCII Module
PLC3 Processors
What You Need To Get Started
You will demonstrate the operation of your ASCII module by reading data
from the industrial terminal to the processor data table, and by writing
data from the data table to the industrial terminal. You will use your
industrial terminal as an ASCII device for entering data (read), and for
displaying data (write).
You will set up a test I/O chassis with a PC processor, power supply,
industrial terminal, cables, and your ASCII module. You will need about
an hour to complete the procedures in this chapter and about two hours to
complete the procedures in chapter 3.
You may want to record your application ladder diagram program before
proceeding because you will need to load ASCII logic into a cleared
memory for tutorial chapters 1 and 3 in this manual.
Equipment That You Need
You will need the following equipment (Table 1.C) using your existing
system and/or spare equipment.
218
Chapter 2
Getting Started with Your ASCII Module
Table 1.C
Equipment
PLC3 Main Chassis
Main Processor Module
I/O ScannerProgrammer Interface Module
Memory Module
Power Supply
winaxial I/O Interface Cable
IT/DH Adapter Cable
PLC3 Industrial T
Chassis Power Cable
I/O Power Cable
Terminators
[1]
[2]
(PLC3)
Equipment
erminal
erminal Cable
Supplied with the Industrial T
Supplied with the PLC3 Main Chassis
erminal
Catalog Number
1775A1
1775L1,L2
1775S4A
1775MR
1775P1
1770T4
1770KDA
1771Al,A2,A4
1771AS
1771DA
1770CD
1770CB
1775CAT
1775CAP
1775CH
1775XT
[1]
[2]
If you use an existing system, place the ASCII module in a chassis on a
separate channel. Use a spare scanner module (cat. no. 1775-S4A,-S4B)
if necessary.
The ASCII module draws 1.3A from the backplane. If you place the
module in a chassis containing other modules, be sure that the total
current drain of all modules in the chassis does not exceed the maximum
for the backplane and power supply.
219
Chapter 2
Getting Started with Your ASCII Module
How to Connect Your Equipment
Connect your equipment using the appropriate cables (Figure 1.5).
120V AC
L2
L1
1775-P1
Power Supply
1775-CAP
Chassis
Power Cable
Figure 1.5
Connections
UNIT
(CPU)
RAM
G
CENTRAL
PROCESSIN
for PLC3 Controller
1775-CAT
Industrial Terminal Cable
O
I/O
S
M
C
E
A
M
N
O
N
R
E
Y
R
O
P
P
T
T
I
I
O
O
N
N
A
A
L
L
1775-S4A
Scanner
PLC-3
Processor Chassis
1771-DA ASCII
I/O Module
1771-T4
Industrial Terminal
(rear view)
Channel B
Change Cables
as required
220
1771-CH
I/O Power
Cable
1770-CD
Twinaxial Cable,
10,000 ft. Max.
total each
I/O Channel
1771-AS Romote
I/O Adapter Module
1771-A1, -A2, -A4
I/O Chassis
1772-TC
Processor Interface Cable
1770-CB IT/DH
Adapter Cable
1.Connect the chassis power cable between the power supply and the
processor chassis.
11820
Chapter 2
Getting Started with Your ASCII Module
2.Connect the I/O power cable between the power supply and the I/O
chassis.
3.Connect the twin axial cable between the I/O scanner in the
processor chassis and the remote I/O adapter module in the I/O
chassis (Figure 1.6).
Figure 1.6
Twinaxial
Cable T
erminations
Terminals on I/O Scanner Module
Channel
No. 3
Channel
No. 1
Line 1
Shield
Line 2
Blue
Shield
Clear
Line 2
Terminator Resistor
(Cat. No. 1770-XS or 1770-XT)
150 ohm 0.5 W
1770CD Twinaxial Cable
Terminals on field Wiring Arm
of 1770-AS Adapter Module
Blue
Shield
Clear
Line 1
Shield
Line 2
Line 1
Shield
Line 2
Terminator Resistor
(Cat. No. 1770-XT)
150 ohm 0.5 W
Channel
No. 4
Channel
No. 2
Absence of a terminator resistor can cause block
NOTE:
transfer errors
4.Connect the industrial terminal cable between channel B of the
industrial terminal and the processor chassis.
11821
221
Chapter 2
Getting Started with Your ASCII Module
5.Connect the IT/DH adapter cable between the ASCII module and
Channel B
Periodically you will have to switch the cables that connect to channel B
of the industrial terminal.
channel B of the industrial terminal.
You will use the industrial terminal cable (cat. no. 1775-CAT) when
using the industrial terminal in PLC-3 mode and entering or displaying
data in the PLC-3 data table.
You will use the IT/DH adapter cable (cat. no. 1770-CB) when using
the industrial terminal in alphanumeric mode as an ASCII device
connected to your ASCII module.
Be sure to observe the labels on the cable connectors and connect each
to its designated port.
Also, if the IT/DH adapter cable is too short or not available, make your
own. It should not exceed 50 feet (Figure 1.7).
Figure 1.7
Minimum
18
25
ASCII Module
Interface Port
Connections in the 1770CB Cable
1
2
3
7
* Protective Ground
Transmitted Data
Received Data
Ground
1
2
3
7
18
25
Industrial Terminal
Channel B
Connectors:
25pin DShell
Male Connector
Cable Kit
1770XXP (each
end)
Cable:
Belden 8723 or
equivalent
* In cable but not
required for ASCII
module
222
11819
Chapter 2
Getting Started with Your ASCII Module
Refer to your PLC-3 Programmable Controller Installation and Operation
Manual (publication 1775-800) for additional installation information
such as switch settings for the adapter module and I/O chassis, and for
grounding information.
Checking ASCII Module Configuration
Your module is configured for RS-232-C operation when shipped from
the factory. If you suspect that its internal configuration (settings of
internal programming plugs) has been altered, you should check module
configuration (refer to section titled ”Choosing the Mode of
Communication,” in chapter 2). Do this as follows:
1. Remove the covers from the module’s printed circuit board.
2. Locate the programming plugs, and set them according to RS-232-C
without control lines (Figure 2.8).
Entering the Getting Started Program"
Using your industrial terminal, enter the “Getting Started Program”
(Figure 1.8) into processor memory. At this point, you do not need to
understand how the program works, but you should enter it exactly as
shown.
223
Loading...
+ 232 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.