Rockwell Automation 1756-CNB Installation Instructions

Installation Instructions
ControlLogix ControlNet Interface Module
Catalog Numbers 1756-CNB, 1756-CNBR, Series E
Contents
Important User Information 2 European Hazardous Location Approval 3 North American Hazardous Location Approval 4 Environment and Enclosure 5 Prevent Electrostatic Discharge 6 About the 1756-CNB and 1756-CNBR Series E Modules 6 Understand Standalone and Redundant Control 7 Before You Begin 8 Install or Remove the Module Under Power 14 Install the Module 15 Remove the Module 16 Connect the Module to the Network 17 Troubleshoot the Module 23 Interpret the Module Status Indicator and Display 24 ControlNet Network Channel Status Indicators 28 Specifications 30 Rockwell Automation Support BackCover

About This Publication

Use this document as a guide to install the ControlLogix ControlNet Bridge module.
Publication 1756-IN604A-EN-P - February 2006
2 ControlLogix ControlNet Interface Module
S

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com/) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liab le for indir ect or consequen tial damage s resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of th is manual, in whole or in part, without writ t en p e r mission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practic es or circu mstances th at can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
HOCK HAZARD
BURN HAZARD
Publication
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Labels may be located on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment (for example, drive or motor) to alert people that surfaces may be dangerous temperatures.
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 3

European Hazardous Location Approval

European Zone 2 Certification
(The following applies when the product bears the EEx Marking.)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC.
The LCIE (Laboratoire Central des Industries Electriques) certifies that this equipment has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive. The examination and test results are recorded in confidential report No. 28 682 010.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 50021.
IMPORTANT
This equipment is not resistant to sunlight or other sources of UV radiation.
The secondary of a current transformer shall not be open-circuited when applied in Class I, Zone 2 environments.
Equipment of lesser Enclosure Type Rating must be installed in an enclosure providing at least IP54 protection when applied in Class I, Zone 2 environments.
This equipment shall be used within its specified ratings de fined by Allen-Bradley.
Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Class I, Zone 2 environments.
Publication
1756-IN604A-EN-P - February 2006
4 ControlLogix ControlNet Interface Module
T

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked “CL I, DIV 2, GP A, B, C, D” are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest “T” number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
WARNING
Publication
EXPLOSION HAZARD Do not disconnect equipment
unless power has been removed or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power has been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
Substitution of components may impair suitability for Class I, Division 2.
If this product contains batteries, they must only be changed in an area known to be nonhazardous.
1756-IN604A-EN-P - February 2006
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués “CL I, DIV 2, GP A, B, C, D” ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMEN
RISQUE D'EXPLOSION Couper le courant ou s'assurer
que l'environnement est classé non dangereux avant de débrancher l'équipement.
Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit .
La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
S'assurer que l'environnement est classé non dangereux avant de changer les piles.

Environment and Enclosure

ControlLogix ControlNet Interface Module 5
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publicatio n 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, see the appropriate sections in this publication, as well as Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional installation requirement s pe rt aining to this equipment.
Publication
1756-IN604A-EN-P - February 2006
6 ControlLogix ControlNet Interface Module

Prevent Electrostatic Discharge

ATTENTION
This equipment is sensitive to electrostatic disch ar ge , which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in appropr iate st atic-safe
packaging.
For additional information, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.

About the 1756-CNB and 1756-CNBR Series E Modules

The 1756-CNB and 1756-CNBR Series E modules work for all nonredundant ControlLogix applications.
IMPORTANT
Only the 1756-CNB and 1756-CNBR, Series D modules are supported in ControlLogix Redundancy releases 8, 11, 13, and 15. After a firmware upgrade to version 11.xx, Series E will be supported in ControlLogix Redundancy releas e 15 or lat er.
You cannot upgrade a Series D module to a Series E module.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 7

Understand Standalone and Redundant Control

You can use the 1756-CNB and 1756-CNBR Series E modules as standalone or in firmware version 11.xx as redundant control. For standalone control, only one set of modules is required. For redundant control, two ControlLogix chassis are populated with identical pairs of modules called partners. The chassis that performs active control is called the primary chassis and the modules in the chassis are called primary modules. The other chassis is called the secondary chassis and the modules in the chassis are called secondary modules. These installation instructions discuss both standalone and redundant control; read them carefully to distinguish the procedures and requirements for each type of control.
IMPORTANT
Primary Chassis
Redundant Control Chassis Pair
Secondary Chassis
If you use redundant control, you must select the same ControlNet network address for each set of partner modules. You must also place the partner modules in the same corresponding slots in their respective redundant control chassis pair.
1756-SRM
1756-CNB
1756-CNB/CNBR
1756-CNBR
1756-SRM
1756-CNB
1756-CNB/CNBR
1756-CNBR
I/O Chassis
Publication
1756-CNB 1756-CNBR
ControlNet Network
1756-IN604A-EN-P - February 2006
8 ControlLogix ControlNet Interface Module
5
l)

Before You Begin

Before you install the module you need to make sure you:
Know how to handle the module.
Refer to the section Prevent Electrostatic Discharge.
Have all of the necessary components:
1756-CNB or 1756-CNBR
1786-TPR,1786 -TPS 1786-TPYR, or1786 -TPYS
(1)
1786-TPS or 1786-TPYS taps recommended for network connections.
1756-A4, 1756-A7, 1756-A10, 1756-A13, or 1756-A17
(1)
1786-TP (temporary network connections)
1756-PA72/75 or 1756-PB72/7
Power Supply
Small Screwdriver (optiona
Know the type of ControlNet network:
There are two types of scheduled traffic networks for ControlNet: single-keeper networks and multi-keeper networks.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 9
All 1756-CNB and 1756-CNBR modules are keeper-capable, as listed.
1756-CNB and 1756-CNBR Major/Minor Revision Keeper Type
A 1.xx Single-keeper B 2.xx Multi-keeper C 3.xx Single-keeper C 4.xx Multi-keeper D 5.xx Multi-keeper D 7.xx Multi-keeper E 10.xx Multi-keeper E 11.xx Multi-keeper
You must match the keeper to the type of network, or upgrade the firmware of the module at MAC ID 01 to be multi-keeper capable. Refer to the ControlNet Modules in Logix5000 Control Systems User Manual, publication CNET-UM001, for more information.
Publication
1756-IN604A-EN-P - February 2006
10 ControlLogix ControlNet Interface Module

Identify Module Features

Refer to the figure Module Features to identify the hardware components of the 1756-CNB and 1756-CNBR modules.
Module Features
Module Status Alphanumeric Display
ControlNet Network Channel Status Indicators
Network Access Port
Channel B
BNC Connector
(1756-CNBR only)
Front View
Module Status Indicator
Channel A
Channel A BNC Connector
Network Address Switches
Side View
Backplane Connector
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 11
Side of Module
Front of Module
Top of Module

Set the Module’s Network Address Switches

Use your fingers or a small screwdriver to set the module’s network address switches. For modules in a standalone chassis, you must specify a unique ControlNet network address; for modules in a redundant chassis, you must specify the same address for the secondary module that you specified for the corresponding primary module.
This module’s network address is 23.
TIP
You can select an address of 01 to 99 for modules in a standalone chassis or 01 to 98 for modules in redundant chassis. 00 is an invalid ControlNet network address.
Publication
1756-IN604A-EN-P - February 2006
12 ControlLogix ControlNet Interface Module

Prepare the Chassis for Module Installation

Before you install the module, you must install and connect a ControlLogix chassis and power supply. A 4-slot chassis with a power supply is shown in the
Chassis and Power Supply.
figure
Chassis and Power Supply
Power Supply
Chassis
For information on installing these products, refer to the table Chassis Installation Publications.
Chassis Installation Publications
Chassis Type Chassis Installation Power Supply Power Supply
Installation
Series B 1756-A4 1756-A7 1756-A10 1756-A13
Publication 1756-IN080
1756-PA72/B Publication 1756-5.67 1756-PB72/B 1756-PA75/A Publication 1756-5.78 1756-PB75/A
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 13
Slot 0
Slot 2

Determine Module Slot Location

The figure Chassis Slot Numbering shows chassis slot numbering in a 4-slot chassis. Slot 0 is the first slot and is always the leftmost slot in the rack (the first slot to the right of the power supply). You can use any size ControlLogix chassis and install the module in any slot. You can also install multiple 1756-CNB and 1756-CNBR modules in the same chassis. You can install as many modules as your power supply can accommodate (such as the number for which the power supply is rated).
IMPORTANT
If you plan to install a redundant system, you must place the primary and redundant modules in the same corresponding slot in their respective chassis. For example, if you place a 1756-CNB R module in slot 3 (from the left) in the primary chassis, you must also place a 1756-CNBR module in slot 3 in the redundant chassis.
Chassis Slot Numbering
Slot 1
Power Supply
Slot 3
Chassis
Publication
1756-IN604A-EN-P - February 2006
14 ControlLogix ControlNet Interface Module

Install or Remove the Module Under Power

You can install or remove the module while chassis power is applied if you observe the following precautions.
WARNING
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
Publication
1756-IN604A-EN-P - February 2006

Install the Module

Slide the module into the chassis. Make sure the module backplane connector properly connects to the chassis backplane
The module is properly installed when it is flush with the power supply or other installed modules.
ControlLogix ControlNet Interface Module 15
Align the circuit board with top and bottom guides in the chassis.
Circuit Board
ATTENTION
Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module into the chassis can damage the backplane connector or the module.
Publication
1756-IN604A-EN-P - February 2006
16 ControlLogix ControlNet Interface Module

Remove the Module

Upper Tab
Push on the upper and lower tabs to disengage them. Then slide the module out of the chassis.
If you are replacing an existing module with an identical one, and you want to resume identical system operation, you must install the new module with the same ControlNet address in the same slot.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 17

Connect the Module to the Network

You can connect the module to the ControlNet network using a tap (1786-TPR, 1786-TPS, 1786-TPYR, or 1786-TPYS) or a network access cable
(1786-CP).
WARNING
If you connect or disconnect the communications cable with power applied to this module or any device on the n etwork, an electrica l arc can occur. This could cause an explosion in hazardous location installations.
TIP
Use the 1786-CP cable for temporary connections, such as programming software. For permanent connections, use a tap.
The following figure shows an example ControlNet network using redundant media.
ControlNet Network
Node
ControlNet Link
ControlNet Node
Redundant Media
(optional)
1756-CNBR Module (in a 1756-A4 chassis)
Publication
1756-IN604A-EN-P - February 2006
18 ControlLogix ControlNet Interface Module
When connecting the module to a ControlNet network, you should also refer to the following documentation:
ControlNet Coax Tap Installation Instructions, publication 1786-5.7
ControlNet Cable System Planning and Installation Manual,
publication CNET-IN002
TIP
For network connections we recommend taps with a straight connector (1786-TPS or 1786-TPYS) because of the location of the BNC connectors on the bottom of the module.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 19
D
2

Connect to the Network with a Tap

Perform the following steps to connect the module to the network using a tap.
1. Remove and save the dust caps from the ControlNet network taps.
ATTENTION
Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the module , place the dust cap back on the straight or right-angle connector to prevent the connector from accidentally contacting a metallic grounded surface.
Segment 1
ust Cap
Segment 2
1756-CNB - Segment 1 1756-CNBR - Segments 1 and
Dust Cap
2. Connect the tap’s straight or right-angle connector to the module’s BNC connector.
If Your Node Suppor ts Connect The T ap’s Connecto r
nonredundant media 1756-CNB
redundant media • from trunkline A to channel A on the
(1)
While both channels are active, Rockwell recommends us ing channel A for nonred undant media.
to the channel A connector on the module (channel B on the 1756-CNBR is not used)
1756-CNBR
from trunkline B to channel B on the 1756-CNBR
(1)
Publication
1756-IN604A-EN-P - February 2006
20 ControlLogix ControlNet Interface Module
IMPORTANT
Segment 1
T o preven t ina dverte nt re versal of t he t ap co nnection s (re sulting in incorrect status displays requiring troubleshooting), check the tap drop cable for the label indicating the attached segment before making your connection.
T o work properly, when you use modules in a redundant control chassis pair, the primary and redundant partner modules must be connected to the same network segment. If you are usin g redundant media, connect the channel of each partner to the same netwo rk segment.
Segment 2
A
Tap
Tap
B
A
Tap
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 21
3. Apply power to the module and check module status.
Use the following flowchart as a guide.
Turn the chas sis power supply on.
Module status indicator red?
Yes
Module performs a power-on self-test initialization.
INIT
Module status indicator red?
Yes
INIT has failed, and the module displays an error message. Refer to Troubleshoot section.
Replace the module.
See the
No
Troubleshoot section.
OR
Initialization is
No
complete. The status indicator blinks green.
Channel A and B indicators alternately flash.
Module is functional and operating.
Module status displays OK?
Yes
Modules are in a redundant control chassis pair.
No
OK
A#xx
WAIT
SRM
Channel A and B indicators display the network condition as listed on page 28.
See the Troubleshoot section.
Publication
1756-IN604A-EN-P - February 2006
22 ControlLogix ControlNet Interface Module
1784-KTC, KTCx,

Connect a Programming Terminal to the Network with a 1786-CP Cable

To connect a programming terminal to the network using a 1786-CP cable, you have the following options:
Use a 1784-KTC, 1784-KTCx, or 1784-PCC communication card and a 1786-CP cable:
1756-CNBR
PCIC, or PCC Card
1786-CP Cable
ControlNet Link
IMPORTANT
To work properly, the primary and redundant partner module must be connected to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.
Use a 1770-KFC communication interface, a serial or parallel connection, and a 1786-CP cable:
1756-CNBR
1770-KFC
1786-CP Cable
Serial or Parallel Connections
ControlNet Link
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 23
e
The 1786-CP cable can be plugged into any ControlNet network product’s network access port (NAP) to provide programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique network address.
ATTENTION
Use a 1786-CP cable when connecting a prog ramming terminal to the network through network access port (NAP). Using a commercially available RJ-style cable could result in netwo rk fail ur e.

Troubleshoot the Module

The 1756-CNB and 1756-CNBR modules have the diagnostic indicators as shown:
1756-CNB
1756-CNBR
ControlNet Channel Status Indicators - See Page 28.
Channel A BNC Connector
Channel B BNC Connector
Module Status Display - Se Pages 24 to 27.
Module Status Indicator ­See Pages 24 to 27.
Publication
1756-IN604A-EN-P - February 2006
24 ControlLogix ControlNet Interface Module
OK

Interpret the Module Status Indicator and Display

The Module Status Indicator LED and Module Status Display table provide diagnostic information.
Module Status Indicator LED and Module Status Display
LED Display
Cause Action
Off None The module is not
Red Msg
scrolls
BPA# ERR
BPRX ERR
BPIC
ERR
CNIC
communicating due to a power supply fault or internal fault.
The module’ s network address is
(1)
set to 00, an invalid ControlNet network address, or 99, an invalid ControlNet network address if you are using redundant control. See footnote at end of table.
The module detected a different slot address from that latched in at power-up. Excessive noise on the backplane causes this error.
There are too many CRC errors being generated by the multicast backplane receiver, so the backplane multicast receivers have been shut off.
There is a hardware fault within the module.
ERR
1. Check the power supply.
2. Check the cable connectors.
3. Make sure the module is firmly seated in the chassis.
4. If the indicator remains off, replace the module.
1. (Optional, see page 12.) Turn chassis power supply off.
2. Remove the module from the chassis.
3. Set the network address switches to a unique address (01-99, or 01-98 if redundant control)
4. Install the module in the chassis.
5. If off, turn chassis power supply on.
Replace the chassis or module.
Replace the module.
Replace the module.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 25
OK
Module Status Indicator LED and Module Status Display
LED Display
Cause Action
Red DUPL
NODE
RACK ERR STOP The module commanded to stop
WAIT SRM
Flashing Red
BOOT The module has invalid
ROM
UPDT SNGL KPR!
For a redundant system this may be a temporary condition during chassis switchover. Otherwise, the module’s network address is the same as another module’ s on the link.
Cannot read backplane EEPROM, or rack/slot address incorrect
functioning by the redundancy module. This occurs when a nonredundancy compliant module is placed into a redundant secondary chassis. The module waiting for the
(2)
redundancy module to complete power-up.
firmware. Flash update is in progress. None required.
The module detected that it has been connected to a ControlNet
1.5 (single-keeper) network.
1. (For redundant systems only.)
2. (Optional, see page 12.)
3. Remove the module from the
4. Set the network address
5. Install the module in the
6. If off, turn chassis power
Replace the chassis.
Remove nonredundancy compliant module from redundant secondary chassis and replace wit h redundancy compliant module.
None required.
Update module firmware with ControlFlash Update Utility.
Update the module’s firmware at MAC ID 01 and reschedule the network.
Wait 10 seconds; if the condition persists, perform the following steps:
Turn chassis power supply off. chassis. switches to a unique address
(01-99). chassis. supply on.
Publication
1756-IN604A-EN-P - February 2006
26 ControlLogix ControlNet Interface Module
OK
Module Status Indicator LED and Module Status Display
LED Display
Cause Action
Green OK Normal operation None required
INIT The module is initializing. BW
>MAX
CMPT
DSNP
PwDS
PwQg
PwQS
PwNS
Qfng
QS SW
ERR
The module is receiving too much network traffic and connections are timing out. The network bandwidth has been exceeded.
(2)
The secondary module is compatible with its partner.
(2)
The secondary module is disqualified with no partner.
(2)
The module is primary with a disqualified secondary partner.
(2)
The module is primary with a qualifying secondary partner.
(2)
The module is primary with a qualified secondary partner.
(2)
The module is primary with no secondary partner.
(2)
The secondary module is qualifying.
(2)
The secondary module is qualified. The node address switch changed after power-up.
None (temporary condition).
If this happens frequently, add another 1756-CNB or 1756-CNBR and split the traffic between them.
None required.
Check corresponding slot of primary chassis for type and revision of module.
Check the type and revision of the 1756-CNB module. Redundant system status. No action required.
Check corresponding slot of secondary chassis for correct module. Redundant system status. No action required.
None required, but we recommend that you either return switches to their original settings or replace the module, since this could indicate a latent hardware problem.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 27
OK
Module Status Indicator LED and Module Status Display
LED Display
Cause Action
Flashing Green
CNFG ERR NET
ERR
ControlNet network configuration error. Network cabling error or no other active nodes on network.
Recheck configuration.
Re-check your network cabling and make sure another node on the network is active (online).
Green or Off
(1)
If switches are set to 00 the display scrolls: “FAULT: ADDRESS SWITCHES = 00, ILLEGAL” If switches are set to 99 in a redundant chassis, the display scrolls: “FAULT: ADDRESS SWITCHES =
99, ILLEGAL IN REDUNDANT SYSTEM”
(2)
Messages are for redundant control. These messages will be available in Series E firmware version
11.xx.
SO_1
SO_2
SO_3
SN_1
SN_2
SN_3
?Cpt
!Cpt
(2)
Old primary switchover phase 1 in progress.
(2)
Old primary switchover phase 2 in progress.
(2)
Old primary switchover phase 3 in progress.
(2)
New primary switchover phase 1 in progress.
(2)
New primary switchover phase 2 in progress.
(2)
New primary switchover phase 3 in progress.
(2)
the module has not determined if it is compatible.
(2)
the module has determined that it is not compatible.
If the display shows any message for more than three seconds, then the module failed during transition from one redundancy phase to another. Replace one or both redundancy modules.
Replace the module with correct type and revision.
Publication
1756-IN604A-EN-P - February 2006
28 ControlLogix ControlNet Interface Module

ControlNet Network Channel Status Indicators

The ControlNet network channel status indicators appear in one of the following states:
Steady - indicator is on continuously in the defined state.
Alternating - the two indicators alternate between the two defined
states at the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase.
Flashing - the indicator alternates between the two defined states (applies to each indicator viewed independent of the other). If both indicators are flashing, they must flash together, in phase.
The ControlNet Network Channel Status Indicators table summarizes the meanings of these states.
ControlNet Network Channel Status Indicators
Cause Action
and
AB
Off No power None or power up. Steady red Faulted unit Cycle power or reset unit.
If fault persists, contact A-B representative or distributor.
Alternating red/green Alternating red/off Incorrect node configuration Check network address and other
or
AB
Off Channel disabled Program network for redundant
Steady green Normal operation None Flashing green/off Temporary errors None; unit will self-correct.
Self-test None
ControlNet network configuration parameters.
Cause Action
media, if required.
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 29
ControlNet Network Channel Status Indicators
Cause Action
and
AB
Node is not configured to go on line
Flashing red/off Media fault Check media. For example: broken
No other nodes present on network
Flashing red/green Incorrect network configuration Cycle power or reset unit .
(1)
The configuration manager node is the node responsible for distributing ControlNet network configuration data to all nodes on the network.
Make sure the configuration manager node is present and working and selected address is
not greater than selected UMAX
cables, loose connectors, missing terminators. Add other nodes to the network.
If fault persists, contact A-B representative or distributor.
(1)
.
Publication
1756-IN604A-EN-P - February 2006
30 ControlLogix ControlNet Interface Module

Specifications

ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute Value
Connectors
1756-CNB
1756-CNBR
Cable Quad shield RG-6 coaxial cable Ground isolation Transformer ControlNet network
communication rate Diagnostics Yes Weight
1756-CNB
1756-CNBR Mounting type Chassis Mounting location 1756 ControlLogix Chassis Number of nodes, max 99 Slot width 1 Connections supported, max 64 Communication interface type Bridge Device type Communication interface Power dissipation 5.14 W Thermal dissipation 17.5 BTU/hr
1 BNC connector for nonredundant media operation 1 NAP (RJ-45 8-pin with shield) 2 BNC connectors for redundant media operation 1 NAP (RJ-45 8-pin with shield)
5 M
0.260 kg (0.57 lb)
0.293 kg (0.64 lb)
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 31
ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute Value
Backplane current 970 mA @ 5.1 V
1.7 mA @ 24 V
Isolation voltage (continuous-voltage withstand rating)
Wiring category
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
(1)
50V Tested to 500V ac for 60 seconds
2 - on communications ports
Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute Value
Operational temperature IEC 60068-2-1 (Test Ad, Operating Cold),
Storage temperature IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
Relative humidity IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
Vibration IEC 60068-2-6 (Test Fc, Operating):
Operating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Nonoperating shock IEC 60068-2-27 (Test Ea, Unpackaged Shock):
Emissions CISPR 11:
IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 0…60 °C (32…140 °F)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):
-40…85 °C (-40…185 °F)
5…95% noncondensing
2 g @ 10…500 Hz
30 g
50 g
Group 1, Class A
Publication
1756-IN604A-EN-P - February 2006
32 ControlLogix ControlNet Interface Module
Environmental Specifications ControlLogix ControlNet Interface Module 1756-CNB, 1756-CNBR, Series E
Attribute Value
ESD immunity IEC 61000-4-2:
Radiated RF immunity Series E
EFT/B immunity IEC 61000-4-4:
Surge transient immunity IEC 61000-4-5:
Conducted RF immunity IEC 61000-4-6:
Enclosure type rating None (open-style)
6 kV contact discharges 8 kV air discharges
IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 900 MHz 10 V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz 1 V/m with 1 kHz sine-wave 80%AM from 2000 MHz…2700 MHz
±2 kV at 5 kHz on communications ports
±2 kV line-earth(CM) on communications ports
10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz
Publication
1756-IN604A-EN-P - February 2006
ControlLogix ControlNet Interface Module 33
Certifications 1756-CNB Series E and 1756-CNBR, Series E
Certification Value
Certifications (when product is marked)
UL UL Listed Industrial Control Equipment
(1)
cULus UL Liste d for Class I, Division 2 Group A,B,C,D
Hazardous Locations, certified for U.S. and Canada
CSA CSA Certified Process Control Equipment
CSA CSA Certified Process Control Equipment for Class I,
Division 2 Group A,B,C,D Hazardous Locations
FM FM Approved Equipment for use in Class I Division 2
Group A,B,C,D Hazardous Locations
CE European Union 89/336/EEC EMC Directive, compliant
with:
EN 50082-2; Industrial Immunity EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
C-TickAustralian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
EEx European Union 94/9/EC ATEX Directive, compliant
with:
EN 50021; Potentially Explosive Atmospheres, Protection “n” (Zone 2)
CI ControlNet Int'l conformance tested to ControlNet
network specifications
(1)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
Publication
1756-IN604A-EN-P - February 2006
34 ControlLogix ControlNet Interface Module

Additional Resources

Publication Title Publication Number
Industrial Automation Wiring and Grounding Guidelines 1770-4.1 ControlNet Modules in Logix5000 Control Systems CNET-UM001 ControlLogix Chassis Installation Instructions 1756-IN080 ControlLogix Power Supplies Installation Instructions 1756-IN078 ControlLogix Power Supplies Installation Instructions 1756-IN596 ControlNet Coax Tap Installation Instructions 1786-5.7 ControlNet Coax Media Planning and Installation Guide CNET-IN002 ControlNet Fiber Media Planning and Installation Guide CNET-IN001
ControlLogix is a trademark of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication
1756-IN604A-EN-P - February 2006
Notes:
ControlLogix ControlNet Interface Module 35
Publication
1756-IN604A-EN-P - February 2006

Rockwell Automation Support

Rockwell Automation provides technical information on the web to assist you in using its products. At http://support.rockwellautomation.com, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com.

Installation Assistance

If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running:
United States 1.440.646.3223 Monday – Friday, 8am – 5pm EST Outside United States Please contact your local Rockwell Automation representative for any
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned:
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for return
technical support issues.
(see phone number above to obtain one) to your distributor in order to complete the return process.
procedure.
Publication 1756-IN604A-EN-P - February 2006 PN 953002-64
Copyright © 2006 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
ö
Loading...