Rockwell Automation 1756-CN2RXT Installation Instructions

Page 1
Installation Instructions
ControlLogix-XT ControlNet Interface Module
Catalog Number 1756-CN2RXT
Top ic Page
Important User Information 2 About the ControlLogix-XT ControlNet Module 6 About ControlLogix-XT Systems 8
ControlLogix-XT with Traditional ControlLogix Compone
Using the 1756-CN2RXT for Standalone or Redundant Control 9
Example Redundant ControlLogix-XT System 10 Before You Begin 10 Parts 11 Set the Module’s Network Address 11 Reset the Module to the Original Factory Settings 12 Prepare the Chassis for Module Installation 13 Determine the Module Slot Location 13 Removal and Insertion Under Power (RIUP) 14 Install the ControlNet Module 14 Connect the Module to the Network 16 Remove the Module 19 Install the EDS File 20 Configure RSLinx Software to Use the USB Port 21 Set Up the USB Driver 22 Status Indicators 23
Module Status Indicator and Display 23
Channel Status Indicators 29 General Specifications - 1756-CN2RXT 31 Environmental Specifications - 1756-CN2RXT 32 Certifications - 1756-CN2RXT 34 Additional Resources 35
nts 8
Page 2
2 ControlLogix-XT ControlNet Interface Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
) describes some important differences between solid state
Publication
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
1756-IN634A-EN-P - April 2009
Page 3
Environment and Enclosure
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for additional
installation requirements, Allen-Bradley publication 1770-4.1
NEMA Standards 250 and IEC 60529, as applicable, for explanations of
the degrees of protection provided by different types of enclosure.
ControlLogix-XT ControlNet Interface Module 3
.
Publication
1756-IN634A-EN-P - April 2009
Page 4
4 ControlLogix-XT ControlNet Interface Module
WARNING
AVERTISSEMENT

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D " are suitable for use in Class I Division 2 Groups A, B, C, D, H azardous Locations and nonhazardous locations only. Each product is supplied with markings on the ra ting nameplate indicating the hazardous locati on temperature code. When combining products within a system, the most adverse temperature code (lowest "T" numb er) may be used to help determine the overall tem perature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD -
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power has been removed or the area is kn own to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en en vironnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements danger eux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de tempér ature le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'en vironnement est classé non dangereux avant de changer les piles.
Publication
1756-IN634A-EN-P - April 2009
Page 5
ControlLogix-XT ControlNet Interface Module 5
WARNING
ATTENTION

European Hazardous Location Approval

European Zone 2 Certification (The following applies when the product bears the Ex or EEx Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
This equipment must be installed in an enclosure providing at least IP54
protection when applied in Zone 2 environments.
This equipment shall be used within its specified ratings defined by
Allen-Bradley.
Provision shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
This equipment must be used only with ATEX certified backplanes.
Secure any external connections that mate to this equipment by using
screws, sliding latches, threaded connectors, or other means provided with this product.
Do not disconnect equipment unless power has been removed or the
area is known to be nonhazardous.
This equipment is not resistant to sunlight or other sources of UV radiation.
Publication
1756-IN634A-EN-P - April 2009
Page 6
6 ControlLogix-XT ControlNet Interface Module
ATTENTION

Preventing Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.

About the ControlLogix-XT ControlNet Module

Configure and use the 1756-CN2RXT module as you would a traditional 1756-CN2R/B module. For more information about configuring and using the 1756-CN2RXT and 1756-CN2R/B modules, see the ControlNet Modules in Logix5000 Control Systems User Manual, publication
CNET-UM001.
Publication
1756-IN634A-EN-P - April 2009
Page 7
ControlLogix-XT ControlNet Interface Module 7
00 ­Factory Reset on Power Up (Invalid Network Address)
01 - 99 Normal Operation (Valid Network Address)
1
2
3
4
5
6
Features of the 1756-CN2RXT Module
These are the hardware features of the 1756-CN2RXT module.
Item Description
1 Module status display - an alphanumeric display that indicates module status 2 Status indicators that show channel and module status 3 USB port for temporary connection 4 Channel A BNC connector 5 Channel B BNC connector 6 Backplane connector
Publication
1756-IN634A-EN-P - April 2009
Page 8
8 ControlLogix-XT ControlNet Interface Module
IMPORTANT

About ControlLogix-XT Systems

The ControlLogix-XT products include control and communication system components that, when used with FLEX I/O-XT products, provide a complete control system solution that can be used in environments where temperatures range from -20...70 °C (-4...158 °F).
When used independently, the ControlLogix-XT system can withstand
ironments where the temperature ranges from -25...70 °C
env (-13...158 °F).
ControlLogix-XT with Traditional ControlLogix Components
ControlLogix-XT system components are rated for extreme environmental conditions only when used properly with other Logix-XT system components. The use of ControlLogix-XT components
with traditional ControlLogix system components nullifies extreme-environment ratings.
If a ControlLogix-XT module is used with traditional ControlLogix products, that is, ControlLogix products not designed for extreme environments, the ControlLogix-XT module can withstand only the environments specified for the traditional ControlLogix version of the module. For example, if a 1756-CN2RXT module is used in a traditional 1756-A10 chassis, the 1756-CN2RXT module can withstand only the environment specified for the traditional 1756-CN2R/B module.
The ControlLogix-XT system components are designed to meet the same
greater operational and environmental requirements as traditional
and ControlLogix products.
When a ControlLogix-XT component is traditional ControlLogix component, the functional and environmental requirements of the traditional ControlLogix component apply.
used as a replacement for a
For more information about standard ControlLogix component specifications and installation requirements, see the resources listed in the Additional Resources table on page
Publication
1756-IN634A-EN-P - April 2009
35.
Page 9
ControlLogix-XT ControlNet Interface Module 9
IMPORTANT

Using the 1756-CN2RXT for Standalone or Redundant Control

You can use the 1756-CN2RXT modules either in standalone or redundant configurations.
A standalone configuration uses:
• one control chassis that contains the 1756-CN2RXT and the 6-L63XT controller.
175
• one or both channels of the 1756-CN2RXT module connected
to the ControlNet network.
A redundant configuration uses:
• two controller chassis called the redundant chassis pair. Each ssis of the pair must contain at least these modules:
cha
1756-L63XT controller.1756-CN2RXT ControlNet module.1756-RMXT redundancy module.
• one or both channels of the 1756-CN2RXT module connected
to the ControlNet network.
If you are using the 1756-CN2RXT in a redundant system, these hardware considerations must be made:
Each redundant chassis of the pair must be configured with identical
modules placed in identical slots. These module pairings between the two chassis are called partners.
All partner modules in redundant chassis pairs must be at the same
firmware revision.
For ControlNet module partners, the ControlNet network address must
be the same for each module of the pair.
These modules cannot be used in redundant chassis pairs that contain
1756-CN2RXT modules:
1756-DHRIOXT or 1756-DHRIO1756-SRM
For more information about redundancy control, refer to the ControlLogix Redundancy System User Manual, publication
1756-UM523.
Publication
1756-IN634A-EN-P - April 2009
Page 10
10 ControlLogix-XT ControlNet Interface Module
Primary Chassis
Secondary Chassis
Redundant ControlNet Media
To Remote I/O
To Remote I/O
To Remote I/O
To Remote I/O
Example Redundant ControlLogix-XT System
This example of a redundant ControlLogix-XT system shows the chassis components listed in this table.
This chassis Contains these modules
Primary chassis 1756-A5XT, 1756-PBXT, 1756-L63XT, 1756-RMXT, 1756-CN2RXT Secondary chassis 1756-A5XT, 1756-PBXT, 1756-L63XT, 1756-RMXT, 1756-CN2RXT

Before You Begin

Before you install your module, complete these tasks:
Publication
11.
11.
• Obtain Appropriate Parts, page
• Set the Module’s Network Address, page
• Prepare the Chassis for Module Installation, page
• Determine the Module Slot Location, page 13.
1756-IN634A-EN-P - April 2009
13.
Page 11
ControlLogix-XT ControlNet Interface Module 11
-
1756-CN2RXT
1756-A5XT or 1756-A7LXT
1756-PBXT
1786-TPR, 1786-TPS, 1786-TPYR, or 1786-TPYS
Top of Module

Parts

To use your ControlNet module, you need these system components.
X
X
T
X
T
X
T
X
T
T

Set the Module’s Network Address

Use a small screwdriver to set the module’s network address switches. For modules in a standalone chassis, you must specify a unique ControlNet network address. You can select an address of
01...99 for modules in a standalone chassis. Address 00 is an invalid ControlNet address.
This example shows the network address switches set to 23.
Publication
1756-IN634A-EN-P - April 2009
Page 12
12 ControlLogix-XT ControlNet Interface Module
IMPORTANT
IMPORTANT

Reset the Module to the Original Factory Settings

If you need to reset the module to its original settings and clear all keeper information, complete the following steps.
The following procedure instructs you to remove power from the chassis before removing the module. This is only necessary if the module is in a Class I, Division 2 hazardous location. For more information, see Removal and Insertion Under Power (RIUP) on page 14
1. Remove power from the chassis.
2. Remove the module from the chassis.
3. Reset the switches to 00.
Do not use the 00 switch setting during normal module operation.
4. Replace the module in the chassis.
5. Apply power to the chassis.
6. After the module status display reads, ‘Reset Complete-Change tch Settings,’ remove power from the chassis.
Swi
.
7. Remove the module from the chassis.
8. Set the switches to their final value.
9. Replace the module in the chassis.
10. Apply power to the chassis.
Publication
1756-IN634A-EN-P - April 2009
Page 13
ControlLogix-XT ControlNet Interface Module 13
Slot 0
Slot 1
Slot 2
Slot 3
Slot 4

Prepare the Chassis for Module Installation

Complete these tasks using the resources listed as references before you install your ControlNet module.
Task Resource
Install a ControlLogix-XT chassis ControlLogix-XT Chassis, Series B Installation
Install a ControlLogix-XT power supply ControlLogix-XT Power Supply Installation
Instructions, publication 1756-IN637
Instructions, publication 1756-IN639

Determine the Module Slot Location

When installing your ControlLogix-XT ControlNet Interface module, remember that you can install:
• a 1756-CN2RXT module in any open slot of the chassis.
• multiple 1756-CN2RXT modules in the same chassis.
• as many modules as your power supply can accommodate, that is, the number for which the power supply is rated.
Publication
1756-IN634A-EN-P - April 2009
Page 14
14 ControlLogix-XT ControlNet Interface Module
WARNING

Removal and Insertion Under Power (RIUP)

When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.

Install the ControlNet Module

To install the module, perform this procedure.
1. Align the circuit board with top and bottom guides in the ssis.
cha
2. Slide the module into the chassis.
Publication
1756-IN634A-EN-P - April 2009
X T
X T
Page 15
ControlLogix-XT ControlNet Interface Module 15
ATTENTION
3. Make sure the module backplane connector properly connects
to the chassis backplane.
Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module into the chassis can damage the backplane connector or the module.
The module is properly installed when it is flush with the pow
er supply or other installed modules.
Publication
1756-IN634A-EN-P - April 2009
Page 16
16 ControlLogix-XT ControlNet Interface Module
WARNING
ATTENTION
Dust Cap

Connect the Module to the Network

If you connect or disconnect the communications cable with power applied to this module or any device on the network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
Connect the module to the ControlNet network by using one of these taps:
• 1786-TPR • 1786-TPYS
• 1786-TPS • 1786-TCT2BD1
• 1786-TPYR
However, taps with a straight connector (catalog numbers 1786-TPS and
1786-TPYS) are recommended because the BNC connectors are
located on the bottom of the module.
To connect the module to the network with a tap, perform this
dure.
proce
1. Remove and save the dust caps from the ControlNet taps.
Publication
Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the module, place the dust cap back on the straight or right-angle connector to prevent the connector from accidentally contacting a metallic grounded surface.
1756-IN634A-EN-P - April 2009
Page 17
ControlLogix-XT ControlNet Interface Module 17
IMPORTANT
Tap
Tap
B
A
X T
X T
2. Attach the tap’s straight or right-angle connector to the
appropriate BNC connector on the module.
Avoid accidentally reversing the tap connections. Before making your connection, check the tap drop cable for the label indicating the attached segment. Accidental connection reversals produce incorrect status displays and require troubleshooting.
To use modules in a redundant-control chassis pair, you must connect the primary and redundant partner modules to the same network segment. If you are using redundant media, connect the channel of each partner to the same network segment.
For trunkline Attach the connector to
A Channel A on the 1756-CN2RXT module B Channel B on the 1756-CN2RXT module
Publication
1756-IN634A-EN-P - April 2009
Page 18
18 ControlLogix-XT ControlNet Interface Module
Turn the chassis power supply on.
Module status indicator red?
See Status Indicators on page 23
.
Module performs a self-test initialization.
No
Yes
TEST
No
Yes
Module status indicator red?
Self-test has failed, and the module displays an error message. See
page 23
.
Replace the module.
Self-test is complete. The status indicator flashes green.
Channel A and B status indicators alternately flash.
Channel A and B status indicators display the network condition as listed on page 29
.
Module status displays OK?
No
See the troubleshooting table on page 23
.
Yes
Module is functional and operating.
OK
A#xx

Apply Power and Check Status

If not yet applied, apply power to the chassis power supply. Use this flowchart as a reference to determine module status after power is applied.
Publication
1756-IN634A-EN-P - April 2009
Page 19
ControlLogix-XT ControlNet Interface Module 19
IMPORTANT

Remove the Module

To remove the module, perform this procedure.
1. Push on the upper and lower tabs to disengage them.
2. Slide the module out of the chassis.
X
X
T
T
If you are removing and replacing an existing module with an identical one, and you want to resume identical system operation, you must install the new module with the same ControlNet address in the same slot.
Publication
1756-IN634A-EN-P - April 2009
Page 20
20 ControlLogix-XT ControlNet Interface Module

Install the EDS File

The EDS file can be uploaded directly from the module. This feature lets you register the EDS file for your module from within RSLinx software by following the steps listed below.
1. Open RSLinx software, version 2.55 or later, and browse for
the module.
2. Right-click the module and select Upload EDS file from device.
The Upload EDS wizard opens.
3. Complete the EDS wizard to register the EDS file.
The EDS file can also be downloaded from
www.ab.com/networks/eds.html
Hardware Installation Tool.
and installed with the RSLinx EDS
Publication
1756-IN634A-EN-P - April 2009
Page 21
ControlLogix-XT ControlNet Interface Module 21
WARNING
WARNING
ATTENTION

Configure RSLinx Software to Use the USB Port

The ControlNet interface module has a USB device port that uses a Type B receptacle. The port is USB 1.1-compatible and runs at 12 Mbps. To use the USB port of the 1756-CN2RXT, you must have
inx software, version 2.55 or later, installed on your workstation.
RSL Use a USB cable to connect your workstation to the USB port. With this connection, you can download programs to controllers and configure other devices, which are accessible by the module, directly from your workstation.
The USB port is intended for temporary local programming purposes only and not intended for permanent connection. If you connect or disconnect the USB cable with power applied to this module or any device on the USB network, an electrical arc can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding. A Samtec Inc. RSP-119350 USB cable is required to ma
location certifications.
The 1756-CN2RXT modules, series B, have an industrial Type B USB port. The port has the same electrical characteristics as other Type B ports, but a higher cable pull-out rating.
For typical applications in nonhazardous environments, you may use any high-quality USB cable. If used in a hazardous location, a Samtec Inc. RSP-119350 USB cable is required to meet the 15-Newton pull test for hazardous environments.
intain hazardous
The USB cable is not to exceed 3.0 m (9.84 ft) and must not contain hubs.
Publication
1756-IN634A-EN-P - April 2009
Page 22
22 ControlLogix-XT ControlNet Interface Module
Virtual Chassis Driver
USB Port Driver

Set Up the USB Driver

To configure RSLinx software to use a USB port, first set up a USB driver by performing this procedure.
1. Connect your 1756-CN2RXT module to your workstation by alling a USB cable in your module’s USB port.
inst
The workstation monitor displays the Found New Hardware
izard dialog box.
W
2. Click Install the software automatically (Recommended) and k Next.
clic
The software is installed.
3. Click Finish to set up your USB driver.
4. To view your 1756-CN2RXT module in RSLinx software, click
the RSWho
The RSLinx Workstation organizer appears.
button.
Your 1756-CN2RXT module appears under two different
ers, a virtual chassis and the USB port. You can use either
driv driver to browse through to your ControlNet module.
Publication
1756-IN634A-EN-P - April 2009
Page 23
ControlLogix-XT ControlNet Interface Module 23
Module Status Display
Module Status Indicator
Channel Status Indicators

Status Indicators

The ControlLogix-XT ControlNet module has these status indicators.
Module Status Indicator and Display
The Module Status indicator and Module Status display provide diagnostic information. Use this table to interpret the Module Status Indicator and Display.
OK Indicator
Off None The module is not
Display Cause Recommended Action
1. Check the power supply.
communic
ating due to a power supply fault or internal fault.
Publication
Check the cable connectors.
2.
3. Make sure the module is firmly seated in the chassis.
4. If the indicator remains off, replace the module.
1756-IN634A-EN-P - April 2009
Page 24
24 ControlLogix-XT ControlNet Interface Module
OK Indicator
Red Reset
Display Cause Recommended Action
Complete­Change
itch
Sw Settings
FAIL This code is displayed when
Backplane
(1)
t
Ini
Stop Service
eived
Rec
Module’s network address is
et to 00, an invalid
s ControlNet address.
the power-up test fails. The module is waiting for the redundant module to complete power up. A non-redundant module is placed into a redundant
secondary chassis. The module was commanded to stop functioning by the redundancy module (RM/SRM). This could occur if a
-CN2RXT module running
1756 Boot code is inserted into a chassis along with a 1756-SRM or 1756-RM module.
For redundant control, the
-CN2RXT module is to be
1756 used with a 1756-RM module. It should not be used with a 1756-SRM module.
1. Remove power from the chassis.
2. Remove the module from the chassis.
3. Set the switches to their final value. See page
.
page 11
4. Replace the module in the chassis.
5. Apply power to the chassis.
Replace the module.
None required.
1. Remove the non-redundant
le from the redundant
modu secondary chassis
2. Replace the non-redundant module with the redundant module.
1. Insert the module into a
that does not
chassis contain a 1756-SRM or 1756-RM module.
2. Update the module’s firmware using ControlFlash software.
Publication
1756-IN634A-EN-P - April 2009
Page 25
ControlLogix-XT ControlNet Interface Module 25
OK
dicator
In
Flashing red
Display Cause Recommended Action
Image update Needed
DUPLICATE NODE DETECTED
Flash in progress
TEST Module is executing a
Boot image running. Main firmware image needs to be update
The module’s network address is the same as module’s on the link.
Flash update is in progress. No action is required. If communication to the
module is lost during a F Update, this message will continue to be displayed even though the module will not be able to finish the update.
power
d.
another
-up test.
Update the module’s firmware
using the ControlFlash
by utility.
1. Remove power from the chassis.
2. Remove the module from the chassis.
3. Set the switches to their final value. See page 11
4. Replace the module in the chassis.
5. Apply power to the chassis.
You must remove power from
lash
module to recover, and
the then flash again.
No action is required.
If the display persists for more tha
n 45 seconds, replace the
module because it has failed.
.
Publication
1756-IN634A-EN-P - April 2009
Page 26
26 ControlLogix-XT ControlNet Interface Module
OK
dicator
In
Solid green
Display Cause Recommended Action
OK This is normal operation. There is at least one
connection to or through the
module. No action is required. INIT Module is initializing. No action is required. PAS S This message is displayed
momentarily
upon completion
No action is required.
of a successful power-up test.
(1)
CMPT
DSNP
The secondary module is compatible with its partner.
(1)
The secondary module is disqualified with no partner.
No action is required.
Check the corresponding slot
of the primary chassis for the
module type and revision.
(1)
PwDS
The module is primary with a disqualified secondary
Check the type and revision of
1756-CN2RXT module.
the
partner.
(1)
PQgS
PwQS
PwNS
The module is primary with a qualifying secondary partner.
(1)
The module is primary with a qualified secondary partner.
(1)
The module is primary with no secondary partner.
Redundant system status. No
action is required.
Check corresponding slot of
secondary chassis for correct
module.
(1)
QgS
(1)
QS
A#XX This message is the node
The secondary module is qualifying.
The secondary module is qualified.
addre
ss where XX is an
Redundant system status. No
action is required.
No action is required.
address from 01...99.
MACID
ITCH
SW ERROR
Node address switch changed after you cy
cled power.
No action is required, but we
recommend that you either
return switches to their
original settings or replace the
module, since this could
indicate a latent hardware
anomaly.
Publication
1756-IN634A-EN-P - April 2009
Page 27
ControlLogix-XT ControlNet Interface Module 27
OK
dicator
In
Solid or flashing green
Flashing green
Display Cause Recommended Action
CPU=XX% This message is the CPU
OK Module is operating normally. No action is required. OK This is normal operation. No connections to or through
Invalid Network
onfiguration
C
NET
ERR
Rev XX
utilization rate where XX is the amount of CPU used, ranging from 0...99%. This message occurs only if the CPU utilization exceeds 80%.
ControlNet configuration error. Recheck configuration.
A network cabling error exists, or there are no other active nodes on the network.
.XX When you start the module,
its major and minor revisions are disclosed, causing this message to briefly appear.
The display shows these
ions where the major
revis revision appears to the left of the decimal point, and the minor revision to the right.
No action is required.
module exist. No action is
the
required.
Verify that the module’s
net
work address is less than or equal to the maximum unscheduled network address (UMAX). Recheck your network cabling
make sure another node
and on the network is active (online).
No action is required.
Publication
1756-IN634A-EN-P - April 2009
Page 28
28 ControlLogix-XT ControlNet Interface Module
OK Indicator
Any Keeper:
Display Cause Recommended Action
Unconfigured
Keeper: Unconfigured (data format changed)
Keeper: Unconfigured (slot changed)
Keeper: Unconfigured (net address changed)
The network configuration data maintained in flash memory by the keeper object has been erased or corrupted.
The network configuration data maintained in memory by the keeper object is in a format incompatible with the current revision of firmware.
After the keeper object’s network-conf was downloaded, the module was moved to a different spot in the chassis.
The network address switches on the module have changed since the keeper object’s network-configuration data was downloaded.
flash
iguration data
been
Perform any of these steps:
· Use RSNetWorx software to
download or update the keeper object in the module.
· See Reset the Module to
the Original Factory Settings, on page 12
Perform any of these steps:
.
· Use RSNetWorx software to
download or update the keeper object in the module.
· See Reset the Module to
the Original Factory Settings, on page 12
Perform any of these steps:
.
· Return the module to the
proper slot.
· Use RSNetWorx software to
download or update the keeper object in the module.
· See Reset the Module to
the Original Factory Settings, on page 12
Perform any of these steps:
.
· Return the network address
switches to their original setting.
· Use RSNetWorx software to
download or update the keeper object in the module.
· See Reset the Module to
the Original Factory Settings, on page 12
.
Publication
1756-IN634A-EN-P - April 2009
Page 29
ControlLogix-XT ControlNet Interface Module 29
OK Indicator
Any (cont.)
(1)
Display Cause Recommended Action
Keeper: Signature Mismatch
Keeper: None V on Network
Messages are for redundant control.
The network configuration data maintained in flash memory by the keeper object does not match the current network configuration.
There is a valid master keeper on the network.
The network configuration
alid
data maintained in flash memory by the keeper object does not match the current network configuration, and there is no valid master keeper on the network.
Use RSNetWorx software to download or update the keeper object in the module, or see Reset the Module to the Original Factory Settings, on
page
Use RSNetWorx software to down object in the module.
Important: The Reset the Module to the Original Factory Settings procedure on page will not work because there is no valid master keeper from which to
12.
load or update the keeper
crossload data.
Channel Status Indicators
The ControlNet channel status indicators appear in one of these states:
• Steady - status indicator is on continuously in the defined state.
• Alternating - while viewed together, the two indicators simultaneously alternate between the two defined states. The two indicators are always in opposite states, out of phase.
• Flashing - when each status indicator is viewed apart from the other, each status indicator alternates between the two defined states. If both indicators are flashing, they must flash together, in phase.
12
Publication
1756-IN634A-EN-P - April 2009
Page 30
30 ControlLogix-XT ControlNet Interface Module
ControlNet Indicator States (A AND B)
State Cause Action
Off There is no power. No action is required, or apply
.
power
Steady red Unit has faulted. Cycle power or reset unit.
If fault persists, contact a
well Automation
Rock representative or distributor.
Alternating
d/green
re Alternating
re
d/off
A self-test is being conducted. No action is required.
Node has been configured incorrectly.
Check network address and other ControlNet configuration
ters.
parame
ControlNet Channel Troubleshooting (A OR B)
State Cause Action
Off Channel has been disabled. Program network for redundant media,
if required. Steady green This is normal operation. No action is required. Flashing
reen/off
g
Flashing red/off A media fault exists. Check media for broken cables, loose
(1)
The configuration manager node (keeper) is the node responsible for distributing ControlNet configuration data to all nodes on the network.
Temporary errors exist. None; unit will self-correct. Node is not configured to go
line.
on
Make sure the configuration manager
node (keeper) is present and working,
and the selected address is not
greater than the maximum
unscheduled node address (UMAX).
connectors, or missing terminators.
No other nodes are present
the network.
on
Add other nodes to the network.
(1)
Publication
1756-IN634A-EN-P - April 2009
Page 31
ControlLogix-XT ControlNet Interface Module 31

General Specifications - 1756-CN2RXT

Attribute Value
ControlNet connectors 2 BNC connectors Number of ControlNet nodes, max 99 ControlNet communication rate 5 MB USB port USB 1.1 USB Device USB, series B, receptacle USB cable for USB port, recommended Samtec cable, P/N RSP-199350 Connections supported, max 131
Note that 3 of the 131 connections are always reserved for redundant control. Therefore, 128
connections are available for standard use. Weight, approx. 0.293 kg (0.64 lb) North American temperature code T4A IEC temperature code T4 Slot width 1 Enclosure type rating None (open-style) Power consumption, max 6.6 W Power dissipation, max 22.5 BTU/hr Backplane current @ 5.1V DC 1.3 A @ 5.1V dc Backplane current @ 24V DC 3 mA @ 24V dc Isolation voltage 30V (continuous), Basic Insulation Type
Type tested at 853V AC for 60 s, ControlNet to
system and ControlNet port to ControlNet port
Wiring category
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
(1)
2 - on communication ports
.
Publication
1756-IN634A-EN-P - April 2009
Page 32
32 ControlLogix-XT ControlNet Interface Module

Environmental Specifications - 1756-CN2RXT

Attribute Value
Temperature, Operating
IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
-25…70 °C (-13…158 °F)
Temperature, Nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)
Vibration
IEC 60068-2-6 (Test Fc, Operating)
Operating Shock
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Shock, Non-operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)
Emissions
CISPR 11
ESD Immunity
IEC 61000-4-2
-40…85 °C (-40…185 °F)
5…95% noncondensing
2 g @ 10…500 Hz
30 g
50 g
Group 1, Class A
6 kV contact discharges
8 kV air discharges
Publication
1756-IN634A-EN-P - April 2009
Page 33
ControlLogix-XT ControlNet Interface Module 33
Attribute Value
Radiated RF Immunity
IEC 61000-4-3
10V/m with 1 kHz sine-wave 80%
AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse
100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80%
AM from 2000…2700 MHz
EFT/B Immunity
IEC 61000-4-4
±2 kV at 5 kHz on ControlNet ports
Surge Transient Immunity
IEC 61000-4-5
Conducted RF Immunity
IEC 61000-4-6
±1 kV line-earth(CM) on communications ports
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz
Publication
1756-IN634A-EN-P - April 2009
Page 34
34 ControlLogix-XT ControlNet Interface Module

Certifications - 1756-CN2RXT

Certification
c-UL-us
CE European Union 2004/108/EC EMC Directive, compliant with:
(1) (2)
Valu e
UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810.
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8,
Zone A & B)
C-Tick
Ex
Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions
European Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres,
Protection "n" (II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
CI
(1)
When the product is marked.
(2)
See the Product Certification link at http://www.ab.com for Declarations of Conformity, Certificates, and other certification details.
ControlNet Int'l conformance tested to ControlNet specifications
Publication
1756-IN634A-EN-P - April 2009
Page 35
ControlLogix-XT ControlNet Interface Module 35

Additional Resources

These documents contain additional information concerning related Rockwell Automation products.
Resource Description
Industrial Automation Wiring and Grounding
uidelines, publication
G
ControlNet Modules in Logix5000 Control Systems User
CNET-UM001
ControlLogix-XT Chassis Installation Instructions, pub
ControlLogix Power Supplies Installa Instructions, publication
ControlNet Coax Taps Installation Instructions, pub
ControlNet Fiber Media Planning and
tion Guide, publication
Installa
ControlNet Coax Media Planning and
tion Guide, publication
Installa
1770-4.1
Manual, publication
1756-IN637
lication
1756-IN639
lication
1786-IN007
CNET-IN001
CNET-IN002
tion
Contains general guidelines for installing a Rockwell Automation industrial automation system.
Contains information on how to use ControlNet modules with various Logix5000 controllers.
Contains information on how to install a ControlLogix-XT chassis.
Contains information on how to install the ControlLogix-XT power supply.
Contains information on how to install ControlNet coaxial taps.
Contains procedures and specifications for the installation of ControlNet fiber media components.
Contains general guidelines for the installation of ControlNet coax media.
You can download publications at
http://literature.rockwellautomation.com. To order paper copies of
technical documentation, contact your local sales office or Rockwell
omation distributor.
Aut
Publication
1756-IN634A-EN-P - April 2009
Page 36
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Outside United States Please contact your local Rockwell Automation representative for any
Monday – Friday, 8 a.m. – 5 p.m. EST
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for the return
Allen-Bradley, ControlFlash, ControlLogix, ControlLogix-XT, FlexI/O-XT, Logix5000, RSLinx, RSLogix 5000, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(call the phone number above to obtain one) to your distributor in order to complete the return process.
procedure.
, you can find
.
Publication 1756-IN634A-EN-P - April 2009 PN-36806
Copyright © 2009 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...