Rockwell Automation 160 C User Manual

• Motor Does Not Start
(No output voltage to motor)
1. Check power circuit.
- Check supply voltage.
- Check all fuses and disconnects.
2. Check the motor – Verify that it is connected properly.
3. Check control input signals.
- Verify that the contact closure signal is present at TB3-8.
- Verify that either the RUN FORWARD or RUN REVERSE signal is active, but NOT both.
4. Check P46 - [Input Mode].
- If P46 - [Input Mode] is set to 2, only the program keypad module Start button will start the motor.
5. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode].
• Drive Started but Motor NOT Rotating
(P01 - [Output Frequency] displays “0.0”)
1. Check the motor – Verify that it is connected properly.
2. Check frequency source P06 - [Frequency Command].
- Verify that a frequency signal is present at terminal block
TB3. Either a –10 to +10V or 4-20 mA signal.
- Verify that Preset Frequencies are set properly.
3. Check control input signals.
- Verify that SW1, SW2 and SW3 are correct. (Refer to the
chart in the User Manual at the end of Chapter 5).
4. Check parameter settings.
- Verify that P59 - [Frequency Select] is showing the desired
frequency source.
- Verify that P58 - [Internal Frequency] is the desired value.
5. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode].
• Motor Not Accelerating Properly
1. Check the motor – Verify that it is connected properly and that
no mechanical problems exist.
2. Check parameter settings.
- Verify that P30 - [Accel Time 1] or P69 - [Accel Time 2]
(whichever is current used) is set properly.
- Verify that P43 - [Current Limit] is set properly.
- Verify that P38 - [Boost Select] is set properly.
• Can Not Operate in “RUN FWD/RUN REV” Mode
1. Verify that P46 - [Input Mode] is set to 1.
2.
Verify that the contact closure signal is present at TB3-8.
3. Verify that P73 - [Reverse Disable] and P74 - [Analog Select] are not set to 1.
4. Verify that power has been cycled for above change to take effect.
5. Verify that both RUN FORWARD and RUN REVERSE switches are NOT closed simultaneously.
6. Cycle power or use P56 - [Reset Functions] if you changed P46 - [Input Mode].
Control Wiring – TB3Power Wiring – TB1, TB2
Control WiringTB3
Motor & Capacitor Module Wiring
TB2
Line Power & Dynamic Brake Module Wiring
TB1
SELESC
DC+
W/T3
1
3
4 5 6 7 8 9 10 112
V/T2
U/T1
DC–
BR+
T/L3
S/L2
R/L1
BR–
Required Branch
Circuit Disconnect
Dynamic Brake
Module (optional)
Capacitor Module
(optional)
Input Line
Protective Device
TB2
TB1
PE
BR+
T/L3
S/L2
R/L1
BR–
DC+
W/T3
V/T2
U/T1
DC–
Motor
Wire Size and Torque Ranges
For single phase input applications, connect the AC input line to input terminals
S (L2) and T (L3).
10V DC Supply Wiper Common 4 – 20 mA Input Reverse Start Common Stop/Programmable Normally Closed Relay Common Normally Open
SW1 SW2
Common SW3 Run Reverse Run Forward Common Stop/Programmable Normally Closed Relay Common Normally Open
Three-Wire Control Shown
(Factory Default)
Two-Wire Control Shown
(Factory Default is Three-Wire)
1 23
4 567
89
10 11
1 23
4 567
89
10 11
N.O. Momentary Contact
N.C. Momentary Contact
N.O. Maintained Contact
N.C. Maintained Contact
Wires must be shielded.
Preset Speed Model
Analog Signal Follower Model
Model
4.0 kW (5 HP) Three Phase
1.5 kW (2 HP) Single Phase
All Other Ratings
Terminal
TB1, TB2 TB3 TB1, TB2 TB3 TB1, TB2 TB3
Min./Max. Wire Size
mm2 (AWG)
5.26-3.31 (10-12)
2.50-0.50 (14-22)
5.26-3.31 (10-12)
2.50-0.50 (14-22)
3.31-0.82 (12-18)
2.50-0.50 (14-22)
Min./Max. Torque
Nm (lb.-in.)
1.35-0.90 (12-8)
0.80-0.40 (8-4)
1.35-0.90 (12-8)
0.80-0.40 (8-4)
1.35-0.90 (12-8)
0.80-0.40 (8-4)
Troubleshooting
Fault Codes
Fault No. Fault Indication and Corrective Action
03 Power Loss Fault
Monitor incoming AC line for low voltage or line power interruption.
04 UnderVoltage Fault
Monitor incoming AC line for low voltage or line power interruption.
05 OverVoltage Fault
Bus overvoltage caused by motor regeneration. Monitor incoming AC line for excessive voltage. Extend the decel time or install dynamic brake module or external capaci­tor module.
06 Motor Stall Fault
Longer acceleration time or a reduced load required.
07 Motor Overload Fault
Reduce motor load until drive output current does not exceed the current set by P42 - [Motor Overload Current]. Reduce P38 - [Boost Select].
08 Over Temperature Fault
Clear blocked or dirty heat sink fins. Check ambient tem­perature. Check for blocked or non-operating fan.
11 Operator Error
Clear fault. Do not remove keypad under power.
12 Overcurrent FauIt
Check short circuit at the drive output or excessive load conditions at the motor.
13 Software Overcurrent Fault
A longer acceleration time, reduced load, or removal of motor shaft blockage is required.
Parameter 07 - [Active Fault]
Fault Number
IMPORTANT: This publication is designed as a reference tool. The 160 SSC User Manual (publication 0160-5.15) must be consulted for more detailed information about parameters, faults and hazards of personal injury.
160 SSC™ Variable Speed Drive
Quick Reference Series C, FRN 7.xx
Publication 0160-5.16 – June, 2000 P/N 189339 (02)
Supersedes October, 1998
20 Drive Overload Fault
Clear blocked or dirty heat sink fins. Check ambient tem­perature. Check for blocked or non-operating fan. Reduce motor load current.
32 EEPROM Fault
Reset EEPROM using P56 - [Reset Functions]. Set to 1. Cycle Power
33 Max Retries Fault
Repair system fault.
36 Incompatible Fault
Check the wiring between the drive and the motor. Check the motor for a grounded phase.
38 Phase U Fault
Check the wiring between the drive and motor. Check motor for grounded phase.
39 Phase V Fault
Check the wiring between the drive and motor. Check motor for grounded phase.
40 Phase W Fault
Check the wiring between the drive and motor. Check motor for grounded phase.
41 UV Short Fault
Check the motor and external wiring to the drive output terminals for a shorted condition.
42 UW Short Fault
Check the motor and external wiring to the drive output terminals for a shorted condition.
43 VW Short Fault
Check the motor and external wiring to the drive output terminals for a shorted condition.
46 Intermittent Power Output Fault
Check the wiring between the drive and motor. Check the motor for more than one shorted output.
48 Reprogram Fault
Clear fault.
These faults have an auto reset feature. This feature automatically clears overvolt-
age, undervoltage and overtemperature faults 1 second after the fault condition is removed. Refer to P51 - [Restart Time].
Loading...
+ 2 hidden pages