Reference Manual
egaP egaP
1.
Intended Use .......................................................3
2. Installation Requirements...................................3
3. AC-Input...............................................................4
4. Input Inrush Current ...........................................5
5. Output .................................................................6
6. Hold-up Time.......................................................7
7. DC-Input...............................................................7
8. Efciency and Power Losses................................8
9. Functional Diagram.............................................9
10. Front Side and User Elements.............................9
11. Terminals and Wiring........................................10
12. Lifetime Expectancy and MTBF.........................10
13. EMC....................................................................11
14. Environment ......................................................12
15. Protection Features ...........................................13
16. Safety Features..................................................13
17. Dielectric Strength ............................................14
18. Certications .....................................................15
19. Physical Dimensions and Weight......................16
20. Accessory........................................................... 17
20.1. 1606-XLSBUFFER24 Module ........................17
21. Application Notes............................................. 18
21.1. Peak Current Capability ...........................18
21.2. Back-feeding Loads ..................................18
21.3. Charging Batteries ...............................19
21.4. External Input Protection.........................19
21.5. Parallel Use to Increase Output Power.... 19
21.6. Daisy Chaining of Outputs .......................20
21.7. Inductive and Capacitive Loads................20
21.8. Series Operation .......................................21
21.9. Operation on Two Phases ........................21
21.10. Use Without PE on the Input ...................21
21.11. Use at Low Temperatures (-25°C / -40°C).22
21.12. Use in a Tightly Sealed Enclosure ............22
21.13. Mounting Orientations ............................23
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLP60EQT
Index
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• AC 230V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery, whether it is full (13.7V) or flat (10V)
• 230Vac—A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances included.
• 50Hz vs. 60Hz—As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains frequency and 120V parameters
are valid at 60Hz mains frequency.
•may—A key word indicating flexibility of choice with no implied preference.
•shall—A key word indicating a mandatory requirement.
•should—A key word indicating flexibility of choice with a strongly preferred implementation.
Bulletin 1606 Switched Mode Power Supplies
Power Supply
100-240V Wide Range Input
NEC Class 2 Compliant
Adjustable Output Voltage
Efciency up to 90.4%
Low No-load Losses and Excellent Partial-load Efciency
Compact Design, Width only 45mm
Electronic Inrush Current Limitation
Operation down to -40°C
Full Output Power up to +60°C
Large International Approval Package
3 Year Warranty
Description
Compact size, light weight, simple mounting onto the
DIN rail and the exclusive selection of quality components
are what makes this power supply so easy to install and
use within seconds.
A rugged electrical and mechanical design as well as a
high immunity against electrical disturbances on the
mains ensures reliable output power. This power supply
offers superior protection for equipment connected
to the public mains network or exposed to a critical
industrial environment.
This series of power supplies offers output voltages from
5 to 56Vdc and power ratings from 15W to 120W.
Principal characteristics of the 1606-XLP60EQT are the
electronic inrush current limitation and our power
supply's perfect suitability to very low ambient
temperatures. The unit is fully specied down to -40°C.
Specication Quick Reference
Output voltage DC 24V
Adjustment range 24 - 28V
Output current 2.5A at 24V
2.1A at 28V
Output power 60W
Output ripple < 50mVpp 20Hz to 20MHz
Input voltage AC 100-240V -15% / +10%
Mains frequency 50-60Hz ±6%
AC Input current 1.05 / 0.66A at 120 / 230Vac
Power factor 0.54 / 0.44 at 120 / 230Vac
AC Inrush current typ. 6A input voltage
and temperature
independent
DC Input 88-375Vdc below 100Vdc
derating required
Efciency 88.5 / 90.4% at 120 / 230Vac
Losses 7.8 / 6.4W at 120 / 230Vac
Temperature range -40°C to +70°C operational
Derating 1.5W/°C +60 to +70°C
Hold-up time typ. 24 / 107ms at 120 / 230Vac
Dimensions 45x75x91mm WxHxD
Weight 250g / 0.55lb
Catalog Numbers
Power Supply 1606-XLP60EQT 24-28V Standard unit
Accessory 1606-XLSBUFFER24 Buffer Module
Certication Marks
UL 508
UL 60950-1
NEC Class 2
Marine
EMC, LVD, RoHS
GOST R
Marine RINA
C-TICK
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
• This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
• Do not use this power supply in equipment where malfunction may cause severe personal injury or threaten human life.
2. Installation Requirements
• This device may only be installed and put into operation by qualified personnel.
• This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
• Should damage or malfunction occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
• Mount the unit on a DIN rail so that the input terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document.
• This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid
(e.g. cable conduits) by more than 30%!
• Keep the following installation clearances: 40mm on top, 20mm on the bottom, 0mm on the left and right sides. Increase this clearance to
15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless
power has been switched off or the area is known to be non-hazardous.
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM014A-EN-P — March 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. AC Input
AC input nom. AC 100-240V -15% / +10%, TN/TT/IT-mains
AC input range
85-264Vac continuous operation, reduce output power linearly to
50W between 90Vac and 85Vac at ambient
temperatures above +45°C, see Fig. 3-5
264–300Vac < 0.5s
Allowed voltage L or N to earth max. 264Vac or 375Vdc
Input frequency nom. 50–60Hz ±6%
Turn-on voltage typ. 75Vac steady-state value, see Fig. 3-1
Shut-down voltage typ. 65Vac steady-state value, see Fig. 3-1
AC 100V AC 120V AC 230V
Input current (rms) typ. 1.24A 1.05A 0.66A at 24V, 2.5A see Fig. 3-5
Power factor *) typ. 0.56 0.54 0.44 at 24V, 2.5A see Fig. 3-4
Crest factor **) typ. 3.4 3.7 4.0 at 24V, 2.5A
Start-up delay typ. 170ms 110ms 90ms see Fig. 3-2
Rise time typ. 50ms 50ms 60ms at 24V, 2.5A, 0mF, see Fig. 3-2
120ms 110ms 140ms at 24V, 2.5A, 2.5mF
Turn-on overshoot max. 200mV 200mV 200mV see Fig. 3-2
*) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range Fig. 3-2 Turn-on behavior, denitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
V
OUT
65V 300Vac264V
Shut-down
75V
Start-up
delay
Rise
Time
Overshoot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 24V Fig. 3-4 Power factor vs. output load at 24V
2.5A
0.5 1.50
0
0.5
1.5A
Input Current, typ.
2.0
1.0
1.0
1.25
0.75
0.25
b
c
a
a) 100Vac
b) 120Vac
c) 230Vac
Output Current
2.5A
0 0.5 1.0 2.0
0.35
0.40
0.45
0.50
0.55
0.60
Power Factor, typ.
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
1.5
Output Current
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
4 Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
Allowable
Output Power
60W
50
40
30
20
10
Fig. 3-5 De-rating requirements for
0
85Vac
low input voltages
A
B
90Vac
A
B
Input Voltage
.
<
.
.
+
5
4
C
°
.
.
<
.
+
0
6
°
C
4. Input Inrush Current
An electronic inrush current circuit limits the input inrush current after turn-on of the input voltage. The inrush current
is input voltage and ambient temperature independent.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
Inrush current max. 8A
typ. 6A
Inrush energy max. 0.2A
AC 100V AC 120V AC 230V
8A
peak
6A
peak
2
s 0.2A2s 0.3A2s between -40°C and +70°C
8A
peak
6A
peak
Fig. 4-1 Input inrush current, typical behavior
Input Current
peak
peak
between -40°C and +70°C
between -40°C and +70°C
Input Voltage
Output Voltage
Input: 230Vac
Output: 24V, 2.5A
Ambient: 25°C
Upper curve: Input current 2A/DIV
Middle curve: Input voltage 200V/DIV
Lower curve: Output voltage 5V/DIV
Time basis: 20ms / DIV
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM014A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
5. Output
Output voltage nom. 24V
Adjustment range min. 24-28V guaranteed
max. 30V *) at clockwise end position of potentiometer *)
Factory setting 24.5V ±0.2%, at full load, cold unit
Line regulation max. 10mV 85-264Vac
Load regulation max. 100mV static value, 0A 2.5A
Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm
Output capacitance typ. 1 600μF
Output current nom. 2.5A at 24V, see Fig. 5-1
nom. 2.1A at 28V, see Fig. 5-1
Output power nom. 60W
Short-circuit current min. 3.6A load impedance 400mOhm, see Fig. 5-1
max. 6.2A load impedance 400mOhm, see Fig. 5-1
*) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no
guarantee this value will be achieved. The typical value is about 28.6V.
Fig. 5-1 Output voltage vs. output current,
typ.
Output Voltage
0
0
4
8
12
28V
16
20
24
6A54
Adjustment
Range
Output Current
a) 100Vac
b) 120Vac
c) 230Vac
b
c
a
Peak current capability (up to several milliseconds)
The power supply can deliver a peak current which is higher than the specied short term current. This helps to start
current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the power supply. During this event, the capacitors will be
discharged and causes a voltage dip on the output. Detailed curves can be found in section 21.1.
Peak current voltage dips typ. from 24V to 16V at 5A for 50ms, resistive load
typ. from 24V to 15V at 12.5A for 2ms, resistive load
typ. from 24V to 10.5V at 12.5A for 5ms, resistive load
123
6 Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
6. Hold-up Time
AC 100V AC 120V AC 230V
Hold-up Time typ. 36ms 54ms 218ms at 24V, 1.25A, see Fig. 6-1
typ. 15ms 24ms 107ms at 24V, 2.5A, see Fig. 6-1
Note:
At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time
Fig. 6-1 Hold-up time vs. input voltage Fig. 6-2 Shut-down behavior, denitions
0
20
40
100
120ms
85 120 155 190 230Vac
Input Voltage
Hold-up Time
60
80
a) 24V 1.25A typ.
b) 24V 1.25Amin.
c) 24V 2.5A typ.
d) 24V 2.5A min.
a b c
d
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
7. DC Input
The power supply can also be supplied from a DC source. Use a battery or similar DC source. For other sources, contact
RA. Connect the + pole to L and the – pole to N. Connect the PE terminal to an earth wire or to the machine ground.
DC input nom. DC 110-300V -20%/+25%
DC input range min. 88-375Vdc continuous operation, reduce output power according
Fig. 7-2 at voltages below 110Vdc
Allowed Voltage L/N to Earth max. 375Vdc IEC 62103
DC input current typ. 0.62A / 0.22A 110Vdc / 300Vdc, at 24V, 2.5A
Turn-on voltage typ. 90Vdc steady state value
Shut-down voltage typ. 57Vdc similar behavior as shown in Fig. 3-1
Fig. 7-1 Wiring for DC Input
Fig. 7-2 Allowable output current below
110Vdc input voltage
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
0
10
20
30
40
60W
80 90 100 110 130Vdc
Input Voltage Vdc
Output Power
50
120
(
b
)
(
a
)
(a) Continuous
(b) Short-term
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
Rockwell Automation Publication 1606-RM014A-EN-P — March 2014 7
Bulletin 1606 Switched Mode Power Supplies
8. Efciency and Power Losses
AC 100V AC 120V AC 230V
Efciency typ. 87.4% 88.5% 90.4% at 24V, 2.5A (full load)
Power losses typ. 0.45W 0.5W 0.85W at 0A
typ. 3.9W 3.7W 3.9W at 24V, 1.25A (half load)
typ. 8.6W 7.8W 6.4W at 24V, 2.5A (full load)
Fig. 8-1 Efciency vs. output current at 24V,
typ.
Fig. 8-2 Losses vs. output current at 24V,
typ.
Efciency
0
82
86
90
80
92%
2.5A0.5 1.5 2.0
Output Current
1.0
84
88
a) 230Vac
b) 120Vac
c) 100Vac
b
c
a
Power Losses
0
1
4
8
0
9W
2.5A0.5 1.5 2.0
Output Current
1.0
2
6
b
c
a
3
7
a) 230Vac
b) 120Vac
c) 100Vac
5
Fig. 8-3 Efciency vs. input voltage at 24V,
2.5A, typ.
Fig. 8-4 Losses vs. input voltage at 24V, 2.5A,
typ.
Efciency
85 120
155
190 225 260Vac
Input Voltage
91%
86
88
90
89
87
85
Power Losses
0
2
4
6
8
10
12W
85 120
155
190 225 260Vac
Input Voltage
8 Rockwell Automation Publication 1606-RM014A-EN-P — March 2014
All parameters are specified at 24V, 2.5A, 230Vac input, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.