Rockwell Automation 1606-XLDC92D User Manual

Reference Manual
egaP egaP
1.
Intended Use .......................................................3
3. Input Voltage ......................................................4
4. Soft-start and Input Inrush Current Surge .........5
5. Output .................................................................6
6. Hold-up Time.......................................................7
7. Efciency and Power Losses................................8
8. Functional Diagram.............................................9
9. Front Side and User Elements.............................9
10. Terminals and Wiring ........................................10
11. Reliability ...........................................................10
12. EMC ....................................................................11
13. Environment ......................................................12
14. Protection Features ...........................................12
15. Safety Features ..................................................13
16. Dielectric Strength ............................................13
17. Environmental Compliance .............................13
18. Certications
................................................... 14
19. Physical Dimensions and Weight ..................... 15
20. Accessories ........................................................ 16
21. Application Notes ............................................. 17
21.1. Peak Current Capability ...........................17
21.2. Back-feeding Loads ..................................17
21.3. Inductive and Capacitive Loads ................ 17
21.4. External Input Protection .........................18
21.5. Requirements for the Supplying Source .. 18
21.6. Parallel Use to Increase Output Power ....18
21.7. Parallel Use for Redundancy ....................18
21.8. Series Operation ....................................... 19
21.9.Charging Batteries ...............................19
21.10. Use in a Tightly Sealed Enclosure ............ 19
21.11. Mounting Orientations ............................ 20
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLDC92D
Index
Terminology and Abbreviations
•PE and symbol—PE is the abbreviation for Protective Earth and has the same meaning as the symbol .
•Earth, Ground—This document uses the term “earth” which is the same as the U.S. term “ground”.
• T.b.d.—To be defined, value or description will follow later.
• DC 24V—A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances included.
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V)
• 24Vdc—A figure with the unit (Vdc) at the end is a momentary figure without any additional tolerance included.
Bulletin 1606 Switched Mode Power Supplies
Description
The 1606-XLDC92D DC/DC converter is installable on a DIN rail and provides a 92-120W output power range in a very compact housing. This DC/DC converter is allowed to run with a battery or similar source. It may also be used to refresh and stabilize the 24Vdc on the end of long cable runs. This unit includes all the essential basic functions, with a powerboost of 20% incorporated. This extra power can even be used continuously, up to +45°C.
DC/DC Converter
24V DC-Input Isolated 24Vdc Output NEC Class 2 Output Efciency up to 90.5% Width only 32mm Full Power Between -25°C and +60°C Soft-start Function Included Minimal Inrush Current Surge Reverse Input Polarity Protection 3 Year Warranty
Specication Quick Reference
Output voltage DC 24V Adjustment range not adjustable Output current 3.8A NEC Class 2 Output power 92W Output ripple < 50mVpp 20Hz to 20MHz Input voltage DC 24V Input voltage range 14.4 to 32.4Vdc full specied Input current typ. 4.25A at 24Vdc input Input inrush current typ. 1.2A peak Efciency 90.5% at 24Vdc input Losses 9.7W at 24Vdc input Temperature range -25°C to +70°C operational Derating 0W/°C +60 to +70°C Hold-up time typ. 7ms at 24Vdc input Dimensions 32x124x102mm WxHxD
Catalog Numbers
DC/DC Converter 1606-XLDC92D Standard unit
Accessory 1606-XLB Wall mount bracket
Certications
C-Tick
ATEX
Ind. Cont. Eq.
UL 508, NEC Class 2
IECEx
II 3G Ex nA IIC T4 Gc
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
2 Rockwell Automation Publication 1606-RM023A-EN-P — January 2014
Class I Div 2
Class I Div 2
Marine RINA
Marine
UL 60950-1 UL 61010-1
EMC, LVD
Gost R
Bulletin 1606 Switched Mode Power Supplies
1. Intended Use
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office, communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
This device is designed for use in hazardous (pending), non-hazardous, ordinary or unclassified locations.
2. Installation Requirements
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the factory for inspection.
Mount the unit on a DIN rail so that the terminals are located on the bottom of the unit. For other mounting orientations, refer to derating
requirements in this document.
This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover ventilation grid (e.g. cable conduits) by more than 30%!
Keep the following installation clearances: 40mm on top, 20mm on the bottom, 5mm on the left and right sides are recommended when the device is loaded permanently with more than 50% of the rated power. Increase this clearance to 15mm in case the adjacent device is a heat source (e.g. another power supply).
SHOCK HAZARD: Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input
block for earth connection and not one of the screws on the housing.
- Turn power off before working on the device. Protect against inadvertent re-powering
- Make sure that the wiring is correct by following all local and national codes
- Do not modify or repair the unit
- Do not open the unit as high voltages are present inside
- Use caution to prevent any foreign objects from entering the housing
- Do not use in wet locations or in areas where moisture or condensation can be expected
- Do not touch during power-on, and immediately after power-off. Hot surfaces may cause burns.
WARNING: EXPLOSION HAZARDS!
Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the voltage adjustment or S/P jumper unless power has been switched off or the area is known to be non-hazardous.
Notes for use in hazardous location areas:
The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM023A-EN-P — January 2014 3
Bulletin 1606 Switched Mode Power Supplies
3. Input Voltage
Input voltage nom. DC 24V Input voltage range 14.4-32.4Vdc full specied max. 36.0Vdc absolute maximum continuous input voltage with no
damage to the DC/DC converter
Allowed voltage between input and earth
max. 60Vdc or
42.2Vac
in case the output voltage is not grounded.
Allowed input ripple voltage
max. 5Vpp 47Hz-40kHz, the momentary input voltage must always
be within the specied limits. Turn-on voltage typ. 17.5Vdc steady-state value, see Fig. 3-1 Shut-down voltage typ. 14.0Vdc steady-state value, see Fig. 3-1 typ. 35.0Vdc steady-state value, see Fig. 3-1 Input current typ. 4.25A at 24Vdc input and output 24V, 3.8A, see Fig. 3-3 Start-up delay typ. 290ms see Fig. 3-2 Rise time typ. 520ms 0mF, 24V, resistive load 3.8A, see Fig. 3-2 typ. 610ms 3.8mF, 24V, resistive load 3.8A, see Fig. 3-2 Turn-on overshoot max. 500mV see Fig. 3-1 Input capacitance typ. 3 000μF external capacitors on the input voltage bus are allowed
without any limitations.
Fig. 3-1 Input voltage range
Turn-on
17.
5Vdc
V
IN
P
OUT
Shut-down
4Vdc
0Vdc
4Vdc
32.
14.
14.
Rated input range
35.
0Vdc
Fig. 3-2 Turn-on behavior, denitions Fig. 3-3 Input current vs. output load
Start-up
delay
Rise
Time
Ov
4A
ershoot
- 5%
Output Voltage
Input Voltage
1
1.5 2
3
0
1
3
5
6A
Output Current
2.5
3.5
0.5
Input Current, typ
I
n
p
u
t
:
1
8
V
d
c
2
4
I
n
pu
t
:
2
4
Vdc
4 Rockwell Automation Publication 1606-RM023A-EN-P — January 2014
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
4. Soft-start and Input Inrush Current Surge
Inrush current limitation
An active inrush limitation circuit (inrush limiting resistor which is bypassed by a relay contact) limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the rst microseconds after switch-on.
Inrush current max. 1.6A
peak
-25°C to +70°C, input: 24Vdc
typ. 1.2A
peak
-25°C to +70°C, input: 24Vdc
Inrush energy typ. negligible -25°C to +70°C, input: 24Vdc
Fig. 4-1 Input inrush current, typical behavior
Input Current
Input Voltage
Output Voltage
Input: 24Vdc Output: 24V, 3.8A, constant current load Ambient: 25°C
Upper curve: Input current 2A / DIV Middle curve: Input voltage 20V / DIV Lower curve: Output voltage 20V / DIV Time basis: 100ms / DIV
Soft-start function:
After the DC/DC converter is turned on, the internal output current rises slowly to its nominal value. This method charges the output capacitors (internal and external capacitors) slowly and avoids high input currents during turn-on. High input currents can produce a high voltage drop on the input wiring (especially with long and thin cables) which reduces the terminal voltage on the DC/DC converter. If the terminal voltage is below the shut-down voltage, the DC/DC converter will turn-off and will make a new start-up attempt. This effect is avoided with the integrated soft­start function. Please note, that this function increases the rise time of the output voltage by a small amount.
Fig. 4-2 Soft-start behavior
Input Current
Input: 24Vdc Output: 24V, 3.8A, constant current load Ambient: 25°C
No additional external output capacitors
Upper curve: Input current 2A / DIV Lower curve: Output voltage 10V / DIV Time basis: 20ms / DIV
Output Voltage
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM023A-EN-P — January 2014 5
Bulletin 1606 Switched Mode Power Supplies
5. Output
Output voltage nom. 24V Adjustment range min. - not adjustable Factory setting 24.1V ±0.2%, at full load, cold unit Line regulation max. 25mV Input voltage variations between 18 to 32.4Vdc Load regulation max. 100mV static value, 0A 3.8A Ripple and noise voltage max. 50mVpp 20Hz to 20MHz, 50Ohm Output current nom. 3.8A see Fig. 5-1 Output power nom. 92W Short-circuit current min. 3A continuous current, short circuit impedance 200mOhm max. 6A continuous current, short circuit impedance 200mOhm Output capacitance typ. 2 200μF
Fig. 5-1 Output voltage vs. output current,
typ.
Fig. 5-2 Current limitation vs. input voltage,
(23V constant voltage load), typ.
Output Voltage
0
024
4
8
12
28V
16
20
24
6
A
315
Output Current
Output Current
3.8
14 18 22
3.9
4.0
4.1
4.3A
4.2
Input Voltage
3.7 610242 26283032Vd
c
Peak current capability (up to several milliseconds)
The DC/DC converter can deliver a peak current, which is higher than the specied short term current. This helps to start current demanding loads or to safely operate subsequent circuit breakers.
The extra current is supplied by the output capacitors inside the DC/DC converter. During this event, the capacitors will be discharged and causes a voltage dip on the output. Detailed curves can be found in section 22.1.
Peak current voltage dips typ. from 24V to 16V at 7.6A for 50ms, resistive load typ. from 24V to 12.5V at 15.2A for 2ms, resistive load typ. from 24V to 8.5V at 15.2A for 5ms, resistive load
6 Rockwell Automation Publication 1606-RM023A-EN-P — January 2014
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Bulletin 1606 Switched Mode Power Supplies
6. Hold-up Time
The input side of the DC/DC converter is equipped with a bulk capacitor which keeps the output voltage alive for a certain period of time when the input voltage dips or is removed. The bulk capacitor can be discharged by loading the DC/DC converter on the output side or through a load which is parallel to the input. There is no protection in the DC/DC converter which prevents current from owing back to the input terminals. If prevention is needed, an external diode should be used.
Hold-up Time typ. 13.8ms input 24Vdc, output: 24Vdc, 1.9A, see Fig. 6-1 typ. 7ms input 24Vdc, output: 24Vdc, 3.8A, see Fig. 6-1
Fig. 6-1 Hold-up time vs. input voltage
0
2
4
6
8
12ms
18 20 22 24 28Vdc
Input Voltage
Hold-up Time
(a) 24V, 1.9A, typ. (b) 24V, 1.9A, min. (c) 24V, 3.8A, typ. (d) 24V, 3.8A, min.
10
26
(
a
)
(
b
)
(
c
)
(
d
)
Fig. 6-2 Shut-down test setup Fig. 6-3 Shut-down behavior, denitions
Load
+
-
DC/DC
Converter
DC
Source
+
-
Input
Output
+
-
S1
- 5%
Hold-up Time
Output Voltage
Intput Voltage
S1 opens
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on at this time.
All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
Rockwell Automation Publication 1606-RM023A-EN-P — January 2014 7
Loading...
+ 15 hidden pages