Rockwell Automation 1606-XL240-UPSE User Manual

Page 1
Reference Manual
1.
General Description ............................................1
2. Specication Quick Reference .............................1
3. Catalog Numbers .....................................................1
4. Certication Marks
...................................................1
6. Output in Normal Mode
........................................4
7. Output in Buer Mode
............................................5
8. Battery Input
..............................................................6
9. Buer Time ...............................................................7
10. Eciency and Power Losses .................................8
11. Functional Diagram .............................................8
12. Check Wiring and Battery Quality Tests
............9
13. End-of-Charge Voltage
..........................................9
14. Relay Contacts and Inhibit Input .....................10
15. Front Side User Elements ....................................11
16. Terminals and Wiring
...........................................12
17. Reliability .......................................................... 12
18. EMC ...................................................................... 13
19. Environment ................................................... 14
20. Protection Features .................................... 14
21. Safety .................................................................. 15
22. Certications
..................................................... 15
23. Environmental Compliance ......................... 16
24. Physical Dimensions and Weight
.............. 16
25. Installation Notes ......................................... 17
26. Accessories ........................................................ 18
27. Application Notes ......................................... 19
27.1. Battery Replacement Intervals
...... 19
27.2. Parallel and Serial Use
....................... 20
27.3. Using the Inhibit Input ..................... 21
27.4. Troubleshooting
................................. 21
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLS240-UPSE
Index
Terminology and Abbreviations
•DC UPS—Uninterruptible power supply with DC input.
•Normal mode—Describes a condition where the battery is charged, the input voltage is in range and the output is loaded within the
allowed limits..
Buffer mode—Describes a condition where the input voltage is below the transfer threshold level, the unit is running on battery (buffering) and the output is loaded within the allowed limits.
Charging mode—Describes a condition where the battery is being charged, the input voltage is in range and the output is loaded within the allowed limits.
Inhibit mode—Describes a condition where buffering is disabled intentionally by using the inhibit input of the DC UPS (e.g. for service actions or to save battery capacity).
•Buffer time—Equivalent to the term “hold-up time.”
T.b.d.—To be defined, value or description will follow later.
Page 2
Bulletin 1606 Switched Mode Power Supplies
1. Description
This uninterruptible power supply (UPS) controller 1606-XLS240-UPSE is an addition to standard 24V power supplies to bridge power failures or emergency systems which must be kept fully in operation for e.g. 72 hours.
The DC-UPS includes an internal temperature sensor and a professional battery management system which charges and monitors the battery to achieve the longest battery service life as well as many diagnostic functions that ensure a reliable operation of the entire system.
A unique feature of the 1606-XLS240-UPSE is that only one 12V battery is required to buer the 24V output. This makes matching batteries unnecessary and allows a precise battery charging and testing.
1606-XLS240-UPS Series
Related products
1606-XLS240-UPS
battery
included
larger
battery sizes
additional
12V output
1606-XLS240-UPSC
1606-XLS240-UPSE
1606-XLS240-UPSD
DC-UPS Control Unit
Requires Only One 12V Battery for a 24V Output
Allows Batteries Between 17Ah and 130Ah
Battery Charging with Temperature Tracking
Stable Output Voltage in Buer Mode
Superior Battery Management for Longest Battery Life
Comprehensive Diagnostic and Monitoring Functions
Replace Battery Signal Included
Electronically Overload and Short Circuit Protected
50% Power Reserves
3 Year Warranty
2. Specication Quick Reference
Input voltage nom. 24Vdc range 22.5-30Vdc Output current min.15A Normal mode min. 10A Buer mode Output voltage typ. 0.23V lower
22.25V Buer mode, 10A Allowed batteries 17Ah to 130Ah VRLA lead acid Temperature range -25 to +50°C Dimensions 49x124x117mm WxHxD Buer time (at 10A) typ. 55 minutes 26Ah battery typ. 4 hours 100Ah battery
Typical setup of a DC-UPS system:
AC
24V Power Supply
e.g.:
as input voltage
24V
DC-UPS
12V
Battery
Normal mode
DC
24V
Load
e.g.: PLC
3. Catalog Numbers
DC UPS
Accessories 1606-XLSBAT2 Battery module 12V 26Ah 1606-XLSBATBR23 Mounting kit w/o battery
1606-XLS240-UPSE Controller
1606-XLB Panel/Wall mount bracket
4. Certication Marks
IND. CONT. EQ.
UL 508
C-Tick
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
2 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
UL 60950-1
UL 508
GOST R
EMC, LVD
Marine RINA
Marine
Page 3
Bulletin 1606 Switched Mode Power Supplies
Intended Use
This device may only be installed and put into operation by qualified personnel.
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 3
Page 4
Bulletin 1606 Switched Mode Power Supplies
5. Input
Input voltage
nom. DC 24V
Input voltage ranges
nom. 22.5 to 30Vdc Continuous operation, see Fig. 5-1
30 to 35Vdc Temporarily allowed, no damage to the DC-UPS *)
35Vdc Absolute maximum input voltage with no damage to the
DC-UPS
0 to 22.5Vdc The DC-UPS switches into buer mode and delivers
output voltage from the battery if the input was above the turn-on level before and all other buer conditions are fullled.
Allowed input voltage ripple
max. 1.5Vpp Bandwidth <400Hz 1Vpp Bandwidth 400Hz to 1kHz Allowed voltage between input
and earth (ground)
max. 60Vdc or
42.4Vac
Turn-on voltage
typ. 22.8Vdc The output does not switch on if the input voltage does
not exceed this level. max. 23Vdc Input current **)
typ. 120mA Internal current consumption for the DC-UPS
typ.
max.
2.0A
2.7A
Current consumption for battery charging ***)
External capacitors on the input
No limitation
*) The DC-UPS shows “Check Wiring” with the red LED and buering is not possible. **) The total input current is the sum of the output current,
the current which is required to charge the battery during the
charging process and the current which is need
ed to supply the DC-UPS itself. See also
Fig. 5-2 . This calculation does not apply
in overload situations where the DC-UPS limits the output current, therefore see Fig. 5-3.
***) Please note: This is the input current and not the current which ows into the battery during charging. The battery current can
be found in section 8.
Fig. 5-1 Input voltage range Fig. 5-2 Input current, denitions
A: Rated input voltage range B: Temp. allowed, no harm to the unit C: Absolute max. input voltage D: Buffer mode
V
IN
18 30 35V22.50
AB
C
D
V
OUT
Internal
current
consumption
Current
consumption
for battery
charging
Output Current
Input
Current
Fig. 5-3 Input current and output voltage vs.
output current, typ. (battery fully charged)
Electric output current limitation
The DC-UPS is equipped with an electronic output current limitation. This current limitation works in a switching mode which reduces the power losses and heat generation to a minimum. As a result, the output voltage drops since there is not enough current to support the load. A positive eect of the current limitation in switching mode is that the input current goes down despite an increase in the output current resulting in less stress for the supplying source.
0
0
5
10
15
20A
O
u
t
p
u
t
C
u
r
r
e
n
t
4812
20A
Output Voltage
15
20V
Overload
I
n
p
u
t
C
u
r
r
e
n
t
10
4 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 5
Bulletin 1606 Switched Mode Power Supplies
6. Output in Normal Mode
Output voltage in normal mode
nom. DC 24V The output voltage follows the input voltage reduced by
the input to output voltage drop.
Voltage drop between input and output
max. 0.3V At 10A output current, see Fig. 6-1 for typical values
max. 0.45V At 15A output current, see
Fig. 6-1 for typical values
Ripple and noise voltage
max. 20mVpp 20Hz to 20MHz, 50Ohm *) Output current nom. 15A Continuously allowed Output power nom. 360W Continuo usly allowed Short-circuit current
min. 17.9A Load impedance 100mOhm, see Fig. 6-2 for typical values max. 21A Load impedance 100mOhm, see
Fig. 6-2 for typical values
Capacitive and inductive loads
No limitation
might be higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-1 Input to output voltage drop, typ.
Fig. 6-2
Output voltage vs. output current in
normal mode at 24V input, typ.
Input to Output Voltage drop
0
02 10
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
Ou
t
p
u
t
C
u
r
r
e
n
t
468 121416
Output Voltage
0
05101520
4
8
12
28V
16
20
24
25
A
Output Current
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 5
Page 6
Bulletin 1606 Switched Mode Power Supplies
7. Output in Buer Mode
If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buering without any interruption or voltage dips. Buering is possible even if battery not fully charged.
Output voltage in buer mode
nom. DC 24V Output voltage is stabilized and independent from
battery voltage
22.45V ±1%, at no load,
22.25V ±1%, at 10A output current
Transfer threshold for buering
typ. 80mV higher than the output voltage in buer mode Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm Output current nom. 10A Continuously allowed 15A < 5s with full output voltage *) Short-circuit current
min. 17.9A Load impedance 100mOhm **) max. 21A Load impedance 100mOhm **)
*) If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the
maximal output current to 10A occurs. If the 10A are not suci
ent to maintain the 24V, buering stops after another 5s.
Buering will again be possible as soon as the input voltage recovers.
**) If the nominal output voltage cannot be maintained in buer mode, the DC-UPS switches o after 5s to save battery
capacity.
Fig. 7-1 Buering transition, denitions
Buffer mode
Output voltage
24V
28V
Input voltage
t
t
Transfer
threshold
5
0
0
m
s
/
D
I
V
0
V
O
u
t
p
u
t
V
o
l
t
a
g
e
I
n
p
u
t
V
o
l
t
a
g
e
2
4
V
2
2
.
2
5
V
a
t
1
0
A
2
4
V
Fig. 7-3 Available output current in buer mode
Fig. 7-4 Output voltage vs. output current in buer mode, typ.
Output Current
0
05 Sec.
15A
10A
Time
5A
BonusPower
Output Voltage
A B C
Continuously available Available for 5s then auto switching to curve
Buffering will stop after 5s
D
0
0
5101520
5
10
15
25V
20
25A
Output Current
A B
CD
D
Buffering will stop after 5s
Fig. 7-2 Transfert behavior, typ.
6 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 7
8. Battery Input
The DC-UPS requires one 12V VRLA battery to buer the 24V output.
Battery voltage
nom. DC 12V Use one maintenance-free 12V VRLA lead acid battery or
one battery module which is listed in the Accessories section.
Battery voltage range
9.0 15.0V Continuously allowed, except deep discharge protection
max. 35Vdc Absolute maximum voltage without any damage to the unit
typ. 7.4V Above this voltage level battery charging is possible Allowed battery sizes
min. 17Ah max. 130Ah Internal battery resistance
max. 100mOhm See individual battry data sheets for this value. Battery charging method CC-CV Constant current, constant voltage mode Battery charging current (CC-mode) nom. 3.0A Independent from battery size
max. 3.4A End-of-charge-voltage (CV-mode)
13.0-14.4V See section 15. Battery charging time typ. 9h *) For a 26Ah battery typ. 34h *) For a 100Ah battery Battery discharging current **)
typ. 21A Buer mode, 10A output
current, 11.5V on the battery
terminal of the DC-UPS, see Fig. 8-1 for other parameters
typ. 0.3A Buer mode, 0A output current
max. 50μA At no input, buering had switched o, all LEDs are o typ. 270mA At no input, buering had switched o, yellow LED
shows “buer time expired” (max. 15 minutes)
Deep discharge protection ***)
typ. 10.5V At 0A output current
typ. 9.8V At 10A output current
*) The charging time depends on the duration and load current of the last buer event. The numbers in the table represent a
fully discharged battery.
**) The current between the battery and the DC-UPS is more than twice the output current. This is caused by boosting the 12V
battery voltage to a 24V level. This high current requires large wire gauges and short cable length for the longest possible buer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the battery terminals which increases the discharging current. See also section 26 for more installation instructions.
***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops
buering when the voltage on the battery terminals of the DC-UPS falls below a certain value. The yellow LED will show “buer time expired” for a period of 15 minutes after the unit stopped buering.
Fig. 8-1 Battery discharging current vs. output current, typ.
Battery Current
0
0
10
20
5
15
25
30A
2.5 7.5 10 5.21A515
O
u
t
p
u
t
C
u
r
r
e
n
t
Voltage on battery terminal of the DC-UPS:
A:
10.5V
B:
11V
C:
12V
A B C
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 7
Page 8
Bulletin 1606 Switched Mode Power Supplies
9. Buer Time
The buer time depends on the capacity and performance of the battery as well as the load current. The diagram below shows the typical buer times of the standard battery modules.
Buer time with 26Ah battery (1606-XLSBATASSY2) min. 99’30’’ At 5A output current *) min. 39’ At 10A output current *) typ. 130’ At 5A output current, see
Fig. 9-1
**)
typ. 55’ At 10A output current, see
Fig. 9-1
**) Buer time with 100Ah battery min. 62h 20’ At 0.5A output current *) min. 3h At 10A output current *) typ. 82h 20’ At 0.5A output current, see Fig. 9-1
**)
typ. 4h At 10A output current, see
Fig. 9-1 **)
*) Minimum value includes 20% aging of the battery and a cable length of 1.5m with a cross section of 2.5mm2 between the
battery and the DC-UPS and requires a fully charged (min. 24h) battery.
**) Typical value includes 10% aging of the battery and a cable length of 0.3m with a cross section of 2.5mm
2
between the battery
and the DC-UPS and requires a fully charged (min. 24h) battery.
Fig. 9-1 Buer time vs. output current with a 65Ah and a 100Ah battery
Buffer Current
0
40 50
0.5
1.0
1.5
2A
70 8060 90h30
A
B
A:
65Ah Battery
B:
100Ah Battery
Buffer Time (Hours)
30h
Buffer Current
0
5
2
4
6
8
10A
10 15 20 25
Buffer Time (Hours)
A
B
A:
65Ah Battery
B:
100Ah Battery
5
The battery capacity is usually specied in amp-hours (Ah) for a 20h discharging event. The battery discharge is non­linear (due to the battery chemistry). The higher the discharging current, the lower the appropriate battery capacity. The magnitude of the reduction depends on the discharging current as well as on the type of battery. High current battery types can have up to 50% longer buer times compared to regular batteries when batteries are discharged in less than one hour.
High discharging currents do not necessarily mean high power losses as the appropriate battery capacity is reduced with such currents. When the battery begins to recharge after a discharging event, the process is completed much faster since only the energy removed from the battery needs to be “relled.”
For this reason, the buer time cannot be calculated using the Ah capacity value. The equation “I x t” = capacity in Ah generally leads to incorrect results when the discharging current is higher than C20 (discharging current for 20h).
8 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 9
Bulletin 1606 Switched Mode Power Supplies
10. Eciency and Power Losses
Eciency typ. 97.8% Normal mode, 10A output current, battery fully charged Power losses typ. 2.9W Normal mode, 0A output current, battery fully charged typ. 5.5W Normal mode, 10A output current, battery fully charged typ. 7.2W During battery charging, 0A output current typ. 18.5W Buer mode, 10A output current
Fig. 10-1 Eciency at 24V, typ.
Fig. 10-2 Losses at 24V, typ.
Efciency vs. output current in normal mode
94.5 39
95.5
96.0
97.0
15A
95.0
96.5
97.5
98%
O
u
t
p
u
t
C
u
r
r
e
n
t
57 1113
Power losses versus output current
0
07.5
6
12
15A
3
9
15
18W
O
u
t
p
u
t
C
u
r
r
e
n
t
2.5 5 10 12.5
A
B
A:
Buffer Mode
B:
Charging Mode
C:
Normal Mode
C
11. Functional Diagram
Fig. 11-1 Functional diagram
-
+
-
+
DC- UPS
24V
Power
Supply
Step-up
Converter
Battery
Charger
Electronic
Current
Limiter
Battery
Tester
+
-
12V Battery
+
-
Buffered
Load
Cut-off
Relay
Input Output
Battery
Diagnosis LED
(yellow)
Status LED
(green)
Inhibit +
Controller
Check Wiring LED
(red)
Replace Battery
Buffering Contact
Ready Contact
Battery Temperature
(7)
Inhibit -
(8)
(1) (2)
(3) (4)
(5) (6)
Input Fuse
& Reverse Polarity
Protection
*
Temp.
*) Return current protection: this feature uses a Mosfet instead of a diode to minimize the voltage drop and power losses.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 9
Page 10
Bulletin 1606 Switched Mode Power Supplies
12. Check Wiring and Battery Quality Tests
The DC-UPS is equipped with an automatic “Check Wiring” and “Battery Quality” test.
“Check Wiring” test:
Under normal circumstances, an incorrect or bad connection from the battery to the DC-UPS or a missing (or blown) battery fuse would not be recognized by the UPS when operating in normal mode. Only when backup is required would the unit be unable to buer. Therefore, a “Check Wiring” test is included in the DC-UPS. This connection is tested every 10 seconds by loading the battery and analyzing the response from the battery. If the resistance is too high, or the battery voltage is not in range, the unit displays “Check Wiring” along with the red LED. At the same time, the green “Ready” LED will turn o.
“Battery Quality” or “State of Health” (SoH) test:
The battery has a limited service life and needs to be replaced at xed intervals determined by the specied service life (acc. to the Eurobat guideline), based on the surrounding temperature and the number of charging and discharging cycles. If the battery is used longer than the specied service life, its capacity will degrade. Section 27-1 contains additional information on the topic. The battery quality test cannot identify a gradual loss in capacity. However, it is able to detect a battery failure within the specied service life of the battery. Therefore a battery quality test in included in the DC-UPS. A battery problem is indicated by the yellow LED (replace battery pattern) and the relay contact “Replace Battery.” Please note that it can take up to 170 hours (with the largest battery size) until a battery problem is reported. This should avoid nuisance error messages as any urgent battery problems will be reported by the “Check Wiring” test and create a warning signal. When “Replace Battery” is indicated, we recommend replacing the battery as soon as possible.
13. End-of-Charge Voltage
The end-of-charge voltage depends on the temperature of the battery. An excessively high end-of-charge voltage may damage the battery and shorten its lifetime. Therefore the DC-UPS includes an internal temperature sensor, which regulates the end-of-charge voltage depending on the battery temperature. To achieve the longest lifetime, the battery should be placed at the coldest location.
The temperature dierence between the DC-UPS and the battery requires a correction of the end-of-charge voltage. This can be done with the selector on the front side of the unit. See section 15 for details.
10 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 11
Bulletin 1606 Switched Mode Power Supplies
14. Relay Contacts and Inhibit Input
The DC-UPS is equipped with relay contacts and signal inputs for remote monitoring and controlling of the unit.
Relay contacts:
Ready:
Contact is closed when battery is charged more than 85%, no wiring failure is recognized, input voltage is sucient and inhibit signal is not active.
Buering: Contact is closed when unit is buering. Replace Battery: Contact is closed when the unit is powered from the input and the battery quality test (SOH test)
reports a negative result.
Relay contact ratings max 60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A resistive load min 1mA at 5Vdc min. Isolation voltage max 500Vac, signal port to power port
Signal input:
Inhibit: The inhibit input disables buering. In normal mode, a static signal is
required. In buer mode, a pulse with a minimum length of 250ms is required to stop buering. The inhibit is stored and can be reset by cycling the input voltage. See also section 27.3 for application hints.
7 +
5.1V
3mA
Inhibit
8
-
Signal voltage max. 35Vdc Signal current max. 6mA, current limited Inhibit threshold min. 6Vdc, buering is disabled above this threshold level max. 10Vdc Isolation nom. 500Vac, signal port to power port
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 11
Page 12
Bulletin 1606 Switched Mode Power Supplies
15. Front Side User Elements
A
Power Port
Quick-connect spring-clamp terminals, connection for input voltage,
output voltage and battery
B
Signal Port
Plug connector with sc rew terminals, inserted from the bottom.
Connections for the Ready, Buering, Replace Battery contacts and for the Inhibit input. See details in section 14. .
C
Green Status LED
Ready: Battery is charged > 85%, no wiring failure is recognized, input
voltage is sucient and inhibit signal is not active.
Charging: Battery is charging and the battery capacity is below 85%. Buering: Unit is in buer mode.
Flashing pattern of the green status LED:
Ready
1 0
1 0
Charging
1 0
Buffering
D
Yellow Diagnosis LED
Overload: Output has switched o due to long overload in buer mode
or due to high temperatures.
Replace battery: Indicates a battery that failed the battery quality test (SoH test).
Battery should be replaced soon.
Inhibit active: Indicates that buering is disabled because of an active inhibit signal.
Flashing pattern of the yellow diagnosis LED:
1 0
Overload
1 0
Replace
Battery
1 0
Inhibit
active
E
Red Check Wiring LED
This LED indicates a failure in the installation (e..g. input voltage excessively low), wiring, battery or battery fuse.
F
Battery Temperature Selector
A: Same as this unit Temperature compensated end-of-charge voltage. B: 10°C lower than this unit Temperature compensated end-of-charge voltage with an oset conditional upon tempera
C: 20°C lower than this unit Temperature compensated end-of-charge voltage with an oset conditional upon tempera
D: Battery temperature is 30°C Fixed end of charge voltage for 30°C battery temperature E: Battery temperature is 20°C Fixed end of charge voltage for 20°C battery temperature F: Battery temperature is 10°C Fixed end of charge voltage for 10°C battery temperature
C
D
E
12 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 13
16. Terminals and Wiring
Power terminals Signal terminals
Type Bi-stable, quick-connect spring-
clamp terminals. IP20 Finger­touch-proof. Suitable for eld­and factory installation. Shipped in open position.
Plug connector with screw terminal. Finger-touch-proof construction with captive screws for 3.5mm slotted screwdriver. Suitable for eld and factory installation. Shipped in open position. To meet GL requirements,
unused terminal compartments should be closed. Solid wire 0.5-6mm2 0.2-1.5mm2 Stranded wire 0.5-4mm2 0.2-1.5mm2 AWG 20-10AWG 22-14AWG Ferrules Allowed, but not required Allowed, but not required Pull-out force 10AWG:80N, 12AWG:60N,
14AWG:50N, 16AWG:40N according to UL486E
Not applicable
Tightening torque Not applicable 0.4Nm, 3.5lb.in Wire stripping length 10mm / 0.4inch 6mm / 0.24inch
Fig. 16-1 Spring-clamp terminals, connecting a wire
Insert wire
Close the lever
To disconnect wire, reverse the procedure.
Instructions:
a) Use appropriate copper cables that are designed
for an operating temperature of 60°C. b) Follow national installation codes and regulations! c) Ensure that all strands of a stranded wire are properly inserted in
the terminal connection! d) Up to two stranded wires with the same cross-section are
permitted in one connection point.
17. Reliability
Lifetime expectancy min. 137 400h At 10A output current, 40°C min. > 15 years At 5A output current, 40°C min. > 15 years At 10A output current, 25°C MTBF SN 29500, IEC 61709 886 000h At 10A output current, 40°C 1 482 000h At 10A output current, 25°C MTBF MIL HDBK 217F 397 900 At 10A output current , 40°C, ground benign GB40 545 000 At 10A output current , 25°C, ground benign GB25
The Lifetime expectancy shown in the table indicates the operating hours (service life), and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specied in operational hours. Lifetime expectancy is calculated according to the capacitor’s manufacturing specications. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF stands for Mean Time Between Failures, which is calculated according to statistical device failures and indicates reliability of a device. It is the statistical representation of the likelihood of failure of a specic unit and does not necessarily represent the life of a product.
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 13
Page 14
Bulletin 1606 Switched Mode Power Supplies
18. EMC
The unit is suitable for applications in industrial environments as well as in residencial, commercial and light industry environment without any restrictions. The CE Mark indicates conformance with EMC guideline 89/336/EC, 93/68/EC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EC, 93/68/EC and 2006/95/EC.
A detailed EMC report is avalaible upon request.
EMC Immunity
EN 61000-6-1, EN 61000-6-2 Generic standards
Electrostatic discharge EN 61000-4-2 Contact discharge
Air discharge
8kV 15kV
Criterion A*)
Criterion A*) Electromagnetic RF eld EN 61000-4-3 80MHz-2.7GHz 10V/m Criterion A Fast transients (Burst) EN 61000-4-4 Out- and Input lines
Signal lines **)
2kV 2kV
Criterion A
Criterion A Surge voltage
EN 61000-4-5 + -
500V 500V
Criterion A
Criterion A
+ -
housing
500V
Criterion A
Conducted disturbance EN 61000-4-6 0.15-80MHz 10V Criterion A
*) DIN rail earthed **) Tested with coupling clamp.
EMC Emission
EN 61000-6-3 and EN 61000-6-4 Generic standards
Conducted emission EN 55022 Input lines Class B*)
Class B*) Radiated emission EN 55011, EN 55022 Class B This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
*) Informative measurement with voltage probe
Switching frequency
The DC-UPS has three converters with three different switching frequencies included.
Switching frequency of boost converter 100kHz Constant frequency Switching frequency of electronic output current limitation 78kHz Constant frequency Switching frequency of battery charger 19.5kHz Constant frequency
Output
Input
+
-
EN 55022
Output lines
14 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 15
Bulletin 1606 Switched Mode Power Supplies
19. Environment
Operational temperature -25°C to +50°C Full power, for the DC-UPS control unit.
Keep battery in a cooler environment!
Storage temperature -40 to +85°C Storage and transportation, except battery
Humidity 5 to 95% r.H. IEC 60068-2-30
Do not energize while condensation is present Vibration sinusoidal 2-17.8Hz: ±1 .6mm; 17.8-500Hz: 2g IEC 60068-2-6 Shock 30g 6ms, 20g 11ms IEC 60068-2-27 Altitude 0 to 6000m Approvals apply only up to 2000m Over-voltage category III EN 50178 II EN 50178 above 2000m altitude Degree of pollution 2 EN 50178, not conductive
Fig. 19-1 Output current vs. ambient temperature
Fig. 19-2 Output current vs. ambient temperature
Allowable Output Current in Normal Mode
0
-25 0 20 30
50°C
2.5
5
7.5
10
12.5
15A
4010
Ambient Temperature
Allowable Output Current in Buffer Mode
0
-25 0 20 30
50°C
2.5
5
7.5
10
12.5
15A
10 40
Ambient Temperature
c
o
n
t
i
n
u
o
u
s
f
o
r
t
y
p
.
5
s
The ambient temperature is dened 2cm below the unit.
20. Protection Features
Output protection Electronically protected against overload, no-load and short-circuits Output over-voltage protection
in buer mode
typ. 32Vdc max. 35Vdc
In case of an internal defect, a redundant circuitry limits the maximum output voltage. The output
automatically shuts-down and makes restart attempts. Degree of protection IP20 EN/IEC 60529 Penetration protection > 3.5mm E.g. screws, small parts Reverse battery polarity protection yes Max. –35Vdc; Wrong battery voltage protection yes Max. +35Vdc (e.g. 24V battery instead of 12V battery) Battery deep discharge protection yes The limit is battery current dependent Over temperature protection yes Out put shut-down with automatic restart Input over-voltage protection yes Max. 35Vdc, no harm or defect of the unit Internal input fuse 25A, blade type No user accessible part, no service part
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 15
Page 16
Bulletin 1606 Switched Mode Power Supplies
21. Safety
Output voltage SELV IEC/EN 60950-1 PELV EN 60204-1, EN 50178, IEC 60364-4-41
Max. allowed voltage between any input, output or signal pin and ground:
60Vdc or 42.4Vac Class of protection III PE (Protective Earth) connection is not required. Isolation resistance > 5MOhm Power port to housing, 500Vdc Dielectric strength 500Vac Power port to signal port 500Vac Power port / signal port to housing Touch current (leakage current) The leakage current which is produced by the DC-UPS itself depends on the input
voltage ripple and need to be investigated in the nal application.
For a smooth DC input voltage, the produced leakage current is less than 100
μA.
22. Certications
EC Declaration of Conformity
Complies with:
- CE EMC directive
- CE Low-voltage directive
UL 508
LISTED E56639 for the use in the U.S.A. (UL 508) and Canada (C22.2 No. 14-95). Industrial Control Equipment
ISA 12.12.01, CSA C22.2 No. 213
RECOGNIZED UNDER FILE NUMBER E244404 for use in the U.S.A. (ISA 12.12.01) and Canada (C22.2 No. 213) Hazardous Location Class I, Div. 2 - Groups A, B, C, D
GOST R
GOST R certication is applicable for products intended for sale and use within Russia. See below for link to Certicate.
C-TICK
C-tick compliance is for products intended for sale and use within the Australian market. See below for the link to the C-tick Declaration of Conformity.
Marine GL GL (Germanischer Lloyd) classied for marine and offshore
applications. Environmental category: C, EMC2. See below for link to Certicate.
Marine Rina
RINA (Registro Italiano Navale) certied. See below for the link to the certicate.
UL 60950-1
RECOGNIZED E168663 for use in the U.S.A. (UL 60950-1) and Canada (C22.2 No. 60950) Information Technology Equipment, Level 3
CSA C22.2 No. 213 ISA 12.12.01
CSA Certied under File Number 240020; CERTIFIED for use in the U.S.A. (ISA 12.12.01) and Canada (C22.2 No. 213) Hazardous Location Class I, Div. 2 - Groups A, B, C, D
Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certifications.
16 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 17
Bulletin 1606 Switched Mode Power Supplies
23. Environmental Compliance
The unit does not release any silicone and is suitable for use in paint shops. Electrolytic capacitors included in this unit do not use electrolytes such as Quaternary Ammonium Salt Systems. Plastic housings and other molded plastic materials are free of halogens, wires and cables are not PVC insulated.
The materials used in our production process do not include the following toxic chemicals: Polychlorinated Biphenyl (PCB), Pentachlorophenol (PCP), Polychlorinated naphthalene (PCN), Polybrominated Biphenyl (PBB), Polybrominated Biphenyl Oxide (PBO), Polybrominated Diphenyl Ether (PBDE), Polychlorinated Diphenyl Ether (PCDE), Polybrominated Diphenyl Oxide (PBDO), Cadmium, Asbestos, Mercury, Silica
24. Physical Dimensions and Weight
Width 49mm / 1.93’’ Height 124mm / 4.88’’ Plus height of signal connector plug Depth 117mm / 4.61’’ Plus depth of DIN rail Weight 545g / 1.2lb DIN Rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7.5 or 15mm.
The DIN rail height must be added to the depth (117mm) to calculate the total required installation depth.
Fig. 24-1 Side view
Fig. 24-2 Front view
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 17
Page 18
Bulletin 1606 Switched Mode Power Supplies
25. Installation Notes
Mounting:
The power terminal shall be located on top of the unit. An appropriate electrical and re end-product enclosure should be considered in the end use application.
Cooling:
Convection cooled, no forced air cooling required. Do not obstruct air ow!
Installation clearances:
40mm on top, 20mm on the bottom, 5mm on the left side are recommended when loaded
permanently with more than 5A. Do not place heat sources next to the 1606-XLS240-UPSE since it can inuence the function of rthe internal temperature sensor. Keep a minimum of 15mm from the adjacent device.
Risk of electrical shock, re, personal injury or death!
Turn power o and disconnect battery fuse before working on the DC-UPS. Protect against inadvertently re-powering. Make sure the wiring is correct by following all local and national codes. Do not open, modify or repair the unit. Use caution to prevent any foreign object from penetrating in the housing. Do not use in wet locations or in areas where moisture and condensation can be expected.
Service parts:
The unit does not contain any service parts. The tripping of an internal fuse is caused by an internal fault. If damage or malfunctioning should occur during operation, immediately turn power o and send unit to the factory for inspection.
Wiring and installation instructions:
(1) Connect the power supply to the input terminals of the DC-UPS. (2)
Connect the battery to the battery terminals of the DC-UPS. Do not install the battery in airtight housings or cabinets.
(3) Connect the buered load to the output terminals of the DC-UPS. The output is decoupled from the input allowing load
(4)
Install the fuse upon completion of the wiring.
Fig. 25-1 Typical wiring diagram
24V Power Supply
+
-
NLPE
DC-UPS
1606-XLS240
-UPSE
24V
IN
24V
OUT
12V
BAT
+
-+-+-
12V
Battery
Module
+
-
Buffered
Load
+
-
Non-
buffered
Load
+
-
24V buffered branches
24V Non-bufferd branches
The battery should be installed according to EN50272-2, which includes sucient ventilation. Batteries store energy and must be protected against energy hazards. Use a 30A battery fuse type ATO® 257 30 (Littelfuse) or similar in the battery path. The battery fuse protects the wires between the battery and the DC-UPS. It also allows the disconnection of the battery from the DC-UPS which we recommend when working on the battery or DC-UPS. Disconnect battery fuse before connecting the battery. Please note: Excessively long or short wires between the DC-UPS and battery may shorten the buer time or result in a malfunction of the DC-UPS. Do not use wires smaller than 2.5mm² (or 12AWG) and no longer than 2x1.5m (cord length
1.5m). Avoid voltage drops on this connection.
circuits to be easily split into buered and non-buered sections. Noncritical loads can be connected directly to the| power supply and will not be buered. The energy of the battery can then be used in the circuits that require buering.
18 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 19
Bulletin 1606 Switched Mode Power Supplies
26. Accessories
Battery Modules
One pre-assembled battery module with a single 12V battery is available. As an option, the mounting bracket is also available without battery. This option oers more exibility in selecting an approriate battery or can save shipping and logistics costs. See individual datasheets for detailed information.
1606-XLSBATASSY2
Battery type High current version12V, 26Ah VRLA lead-acid maintenance free battery Service life 10 to 12years According to EUROBAT guideline Dimensions 214x179x158mm Width x height x depth Weight 9.9kg DIN Rail mountable no Order number 1606-XLSBATASSY2 Battery module 1606-XLSBATBR2 Mounting bracket without battery 1606-XLSBAT2 Replacement battery only
Fig. 27-1
1606-XLSBATASSY2
1606-XLB Wall / Panel mounting bracket
Use this bracket to mount the DC UPS units onto a at surface without using a DIN rail. Both the aluminium brackets and the black plastic slider of the DC UPS must be removed so that the two surface brackets may be mounted.
Fig. 26-2 1606-XLB Wall / Panel Mounting Bracket
Fig 26-3 Assembled Wall / Panel Mounting Bracket
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 19
Page 20
Bulletin 1606 Switched Mode Power Supplies
27. Application Notes
27.1. Battery Replacement Intervals
Batteries have a limited lifetime. They degrade slowly beginning from the production and need to be replaced periodically, The design life gures can be found in the indidividual battery datasheets and are usually specied according to the Eurobat guideline or according to the manufacturer’s specications.
The design life is the estimated life based on laboratory condition, and is quoted at 20°C using the manufacturer’s recommended oat voltage condition. According to the Eurobat guideline, design lives have been structured into the following distinct groups:
3 - 5 years:
This group of batteries is very popular in stand-by applications and in small emergency equipment.
This represents a 4 years design life with a production tolerance of ±1 year.
6 - 9 years:
This group of batteries is generally used when an improved life is required.
This represents a 7.5 years design life with a production tolerance of ±1.5 years.
10 - 12 years:
This group of batteries is used in applications for which longest life and highest safety level are
required. This represents a 11 years design life with a production tolerance of ±1 year.
A battery failure within the specied design life of the battery usually results in complete loss of battery function (broken cell, faulty connection, …) and will be detected and reported by the periodical battery tests included in the 1606-XLS240-UPSE DC-UPS control unit.
If the operational parameters dier from those specied for the design life, earlier replacement of the battery may prove necessary. The “real life” is called service life and is dened as the point at which the cell’s actual capacity has reached 80% of its nominal capacity. At the end of the service life, capacity degrades much more rapidly, so that further use of the battery is not recommended.
Temperature eect
Temperature has the greatest impact on service life of a battery. The hotter the temperature, the earlier the wear-out phase of the battery begins. The wear-out results in a degradation of battery capacity. See Fig 27-1 for details.
Eect of discharging cycles
The number as well as the depth of discharging cycles is limited. Replacing the battery may prove necessary earlier than the calculated service life if the battery exceeds the numbers and values in Fig. 27-2.
Other factors shortening service life
Overcharging and deep discharging shortens the service life and should be avoided. Thanks to the single battery concept of the 1606-XLS240-UPSE, the end-of-charge-voltage can be set very precisely to the required value, thereby preventing unnecessary aging eects.
Charge retention is important to achieve the longest battery life. Stored batteries not fully charged age faster than fully charged batteries. Batteries which are not in use should be recharged at least once a year.
Excessive oat charge ripple across the battery has the ect of reducing life and performance. The 1606-XLS240-UPSE does not produce such a ripple voltage. This eect may therefore safely be ignored if you’re charging a battery with
your 1606-XLS240-UPSE.
Guidelines for long battery service life
Place the battery in a cool location, for instance near the bottom of the control cabinet. Do not place the battery near heat generating devices. Do not store discharged batteries. Do not discharge the battery more than necessary. Set buer time limiter to the required buer time. When choosing the battery capacity, always try to get the next higher capacity than the one you require.
The depth of discharge reduces the battery service life and limits the number of cycles. See Fig. 27-2.
20 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 21
Bulletin 1606 Switched Mode Power Supplies
Example for calculating the service life and the required replacement cycle:
Parameters for the example:
A 26Ah battery with a design life of 10-12 years is used.
The average ambient temperature is 30°C. One buer event consumes approx. 25% of the achievable buer time. One buer event every two days
Calculation:
Ambient temperature inuence:
According to Fig. 27-1 curve C, a 5 years service life can be expected for an ambient temperature of 30°C. Number of discharging cycles: 5 years * 182 cycles = 910cycles in 5 years.
According to Fig. 27-2, curve C has to be used (only 25% of battery capacity is required). 910 cycles have only a negligible inuence in a battery degradation and can be ignored.
Result: The battery shall be replaced after 5 years. Please note that the battery degrading begins from the production date (check date code on the battery) which may shorten the replacement intervals.
Fig. 27-1 Service life versus ambient temperatures, typ. *)
Fig. 27-2 Cell capacity degradation vs. discharging cycles *)
20°C
10
30°C 35°C
40°C
45°C
8
6
4
2
Ambient Temperature
25°C
1
3
5
7
9
Service Life in Years
Design Life of Battery
A:
3-5 Years
B:
6-9 Years
C:
10-12 Years
A
B
C
0
120%
100%
40%
20%
Number of Discharging Cycles
200
60%
80%
Cell Capacity
Depth of discharge
A:
100%
B:
50%
C:
30%
400 600 800 1000 1200
A
B
C
*) datasheet gures from battery manufacturer
27.2. Parallel and Serial Use
Do not use the DC-UPS in parallel to increase the output power. However, two units of the DC UPS can be paralleled for 1+1 redundancy to gain higher system reliability.
Do not use batteries in parallel, since the battery quality test might create an error message. Do not connect two or more units in series for higher output voltages. Do not connect two or more units in a row to get longer hold-up times.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 21
Page 22
Bulletin 1606 Switched Mode Power Supplies
27.3. Using the Inhibit Input
The inhibit input disables buering. In normal mode, a static signal is required. In buer mode, a pulse with a minimum length of 250ms is required to stop buering. The inhibit is stored and can be reset by cycling the input voltage.
As long as the inhibit signal is active in normal mode, an internal relay contact will be opened and the battery will no longer be charged.
For service purposes, the inhibit input can also be used to connect a service switch. Therefore, the inhibit signal can be supplied from the output of the DC UPS.
Fig. 28-3 Wiring example for inhibit input
24V
Power
Supply
+
-
DC-UPS
1606­XLS240-UPSE
24V
IN
24V
OUT
12V
BAT
+-+-+
-
Signal Port
Inhibit
+
-
12V Battery Module
+
-
Buffered
Load
+
-
Service Switch
27.4. Troubleshooting
The LEDs on the front of the unit and relay contacts indicate about the actual or elapsed status of the DC-UPS. Please see also section 15
.
The following guidelines provide instructions for xing the most common failures and problems. Always start with the most likely and easiest-to-check condition. Some of the suggestions may require special safety precautions. See notes in section
25
rst.
“Check wiring” LED is on Check correct wiring between the battery and the DC-UPS.
Check battery fuse. Is the battery fuse inserted or blown? Check battery voltage (must be typically between 7.4V and 15.1V). Check input voltage (must be typically between 22.8V and 30V). Check battery polarity.
DC-UPS did not buer
Inhibit input was set.
Battery did not have enough time to be charged and is still below the deep discharge protection limit.
DC-UPS stopped buering Deep discharge protection stopped buering
use a larger battery, or allow
sucient time for ch
arging the battery.
Output was overloaded or short circuit reduce load.
Output has shut down
Cycle the input power to reset the DC UPS.
Let DC UPS cool down, over-temperature protection may have triggered.
DC-UPS constantly switches between normal mode and buer mode
The supplying source on the input is too small and can not deliver sucient current.
Use a larger power supply or reduce the output load.
22 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Page 23
Page 24
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. You can also visit our Knowledgebase at http://
www.rockwellautomation.com/knowledgebase for FAQs, technical information, support chat and forums,
software updates, and to sign up for product notification updates.
, you can find technical manuals, technical and application
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConne ct representative, or visit http://www.rockwellautomation.com/support/
SM
support programs. For more information, contact your local distributor or Rockwell Automation
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada 1.440.646.3434
Outside United States or Canada Use the Wor ldw ide Loc ator at http://www.rockwellautomation.com/rockwellautomation/support/overview.page, or contact your local
Rockwell Automation representative.
New Product Satisfaction Return
Rockwell Automation tests all of its products to help ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your
Outside United States Please contact your local Rockwell Automation representative for the return procedure.
distributor to complete the return process.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002
literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf.
Publication 1606-RM013A-EN-P — March 2014
, available at http://
Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...