Rockwell Automation 1606-XL240-UPSE User Manual

Reference Manual
1.
General Description ............................................1
2. Specication Quick Reference .............................1
3. Catalog Numbers .....................................................1
4. Certication Marks
...................................................1
6. Output in Normal Mode
........................................4
7. Output in Buer Mode
............................................5
8. Battery Input
..............................................................6
9. Buer Time ...............................................................7
10. Eciency and Power Losses .................................8
11. Functional Diagram .............................................8
12. Check Wiring and Battery Quality Tests
............9
13. End-of-Charge Voltage
..........................................9
14. Relay Contacts and Inhibit Input .....................10
15. Front Side User Elements ....................................11
16. Terminals and Wiring
...........................................12
17. Reliability .......................................................... 12
18. EMC ...................................................................... 13
19. Environment ................................................... 14
20. Protection Features .................................... 14
21. Safety .................................................................. 15
22. Certications
..................................................... 15
23. Environmental Compliance ......................... 16
24. Physical Dimensions and Weight
.............. 16
25. Installation Notes ......................................... 17
26. Accessories ........................................................ 18
27. Application Notes ......................................... 19
27.1. Battery Replacement Intervals
...... 19
27.2. Parallel and Serial Use
....................... 20
27.3. Using the Inhibit Input ..................... 21
27.4. Troubleshooting
................................. 21
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLS240-UPSE
Index
Terminology and Abbreviations
•DC UPS—Uninterruptible power supply with DC input.
•Normal mode—Describes a condition where the battery is charged, the input voltage is in range and the output is loaded within the
allowed limits..
Buffer mode—Describes a condition where the input voltage is below the transfer threshold level, the unit is running on battery (buffering) and the output is loaded within the allowed limits.
Charging mode—Describes a condition where the battery is being charged, the input voltage is in range and the output is loaded within the allowed limits.
Inhibit mode—Describes a condition where buffering is disabled intentionally by using the inhibit input of the DC UPS (e.g. for service actions or to save battery capacity).
•Buffer time—Equivalent to the term “hold-up time.”
T.b.d.—To be defined, value or description will follow later.
Bulletin 1606 Switched Mode Power Supplies
1. Description
This uninterruptible power supply (UPS) controller 1606-XLS240-UPSE is an addition to standard 24V power supplies to bridge power failures or emergency systems which must be kept fully in operation for e.g. 72 hours.
The DC-UPS includes an internal temperature sensor and a professional battery management system which charges and monitors the battery to achieve the longest battery service life as well as many diagnostic functions that ensure a reliable operation of the entire system.
A unique feature of the 1606-XLS240-UPSE is that only one 12V battery is required to buer the 24V output. This makes matching batteries unnecessary and allows a precise battery charging and testing.
1606-XLS240-UPS Series
Related products
1606-XLS240-UPS
battery
included
larger
battery sizes
additional
12V output
1606-XLS240-UPSC
1606-XLS240-UPSE
1606-XLS240-UPSD
DC-UPS Control Unit
Requires Only One 12V Battery for a 24V Output
Allows Batteries Between 17Ah and 130Ah
Battery Charging with Temperature Tracking
Stable Output Voltage in Buer Mode
Superior Battery Management for Longest Battery Life
Comprehensive Diagnostic and Monitoring Functions
Replace Battery Signal Included
Electronically Overload and Short Circuit Protected
50% Power Reserves
3 Year Warranty
2. Specication Quick Reference
Input voltage nom. 24Vdc range 22.5-30Vdc Output current min.15A Normal mode min. 10A Buer mode Output voltage typ. 0.23V lower
22.25V Buer mode, 10A Allowed batteries 17Ah to 130Ah VRLA lead acid Temperature range -25 to +50°C Dimensions 49x124x117mm WxHxD Buer time (at 10A) typ. 55 minutes 26Ah battery typ. 4 hours 100Ah battery
Typical setup of a DC-UPS system:
AC
24V Power Supply
e.g.:
as input voltage
24V
DC-UPS
12V
Battery
Normal mode
DC
24V
Load
e.g.: PLC
3. Catalog Numbers
DC UPS
Accessories 1606-XLSBAT2 Battery module 12V 26Ah 1606-XLSBATBR23 Mounting kit w/o battery
1606-XLS240-UPSE Controller
1606-XLB Panel/Wall mount bracket
4. Certication Marks
IND. CONT. EQ.
UL 508
C-Tick
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
2 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
UL 60950-1
UL 508
GOST R
EMC, LVD
Marine RINA
Marine
Bulletin 1606 Switched Mode Power Supplies
Intended Use
This device may only be installed and put into operation by qualified personnel.
This device is designed for installation in an enclosure and is intended for the general professional use such as in industrial control, office,
communication, and instrumentation equipment.
Do not use this power supply in aircraft, trains, nuclear equipment or similar systems where malfunction may cause severe personal injury or threaten human life.
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 3
Bulletin 1606 Switched Mode Power Supplies
5. Input
Input voltage
nom. DC 24V
Input voltage ranges
nom. 22.5 to 30Vdc Continuous operation, see Fig. 5-1
30 to 35Vdc Temporarily allowed, no damage to the DC-UPS *)
35Vdc Absolute maximum input voltage with no damage to the
DC-UPS
0 to 22.5Vdc The DC-UPS switches into buer mode and delivers
output voltage from the battery if the input was above the turn-on level before and all other buer conditions are fullled.
Allowed input voltage ripple
max. 1.5Vpp Bandwidth <400Hz 1Vpp Bandwidth 400Hz to 1kHz Allowed voltage between input
and earth (ground)
max. 60Vdc or
42.4Vac
Turn-on voltage
typ. 22.8Vdc The output does not switch on if the input voltage does
not exceed this level. max. 23Vdc Input current **)
typ. 120mA Internal current consumption for the DC-UPS
typ.
max.
2.0A
2.7A
Current consumption for battery charging ***)
External capacitors on the input
No limitation
*) The DC-UPS shows “Check Wiring” with the red LED and buering is not possible. **) The total input current is the sum of the output current,
the current which is required to charge the battery during the
charging process and the current which is need
ed to supply the DC-UPS itself. See also
Fig. 5-2 . This calculation does not apply
in overload situations where the DC-UPS limits the output current, therefore see Fig. 5-3.
***) Please note: This is the input current and not the current which ows into the battery during charging. The battery current can
be found in section 8.
Fig. 5-1 Input voltage range Fig. 5-2 Input current, denitions
A: Rated input voltage range B: Temp. allowed, no harm to the unit C: Absolute max. input voltage D: Buffer mode
V
IN
18 30 35V22.50
AB
C
D
V
OUT
Internal
current
consumption
Current
consumption
for battery
charging
Output Current
Input
Current
Fig. 5-3 Input current and output voltage vs.
output current, typ. (battery fully charged)
Electric output current limitation
The DC-UPS is equipped with an electronic output current limitation. This current limitation works in a switching mode which reduces the power losses and heat generation to a minimum. As a result, the output voltage drops since there is not enough current to support the load. A positive eect of the current limitation in switching mode is that the input current goes down despite an increase in the output current resulting in less stress for the supplying source.
0
0
5
10
15
20A
O
u
t
p
u
t
C
u
r
r
e
n
t
4812
20A
Output Voltage
15
20V
Overload
I
n
p
u
t
C
u
r
r
e
n
t
10
4 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Bulletin 1606 Switched Mode Power Supplies
6. Output in Normal Mode
Output voltage in normal mode
nom. DC 24V The output voltage follows the input voltage reduced by
the input to output voltage drop.
Voltage drop between input and output
max. 0.3V At 10A output current, see Fig. 6-1 for typical values
max. 0.45V At 15A output current, see
Fig. 6-1 for typical values
Ripple and noise voltage
max. 20mVpp 20Hz to 20MHz, 50Ohm *) Output current nom. 15A Continuously allowed Output power nom. 360W Continuo usly allowed Short-circuit current
min. 17.9A Load impedance 100mOhm, see Fig. 6-2 for typical values max. 21A Load impedance 100mOhm, see
Fig. 6-2 for typical values
Capacitive and inductive loads
No limitation
might be higher if the supplying source has a higher ripple and noise voltage.
Fig. 6-1 Input to output voltage drop, typ.
Fig. 6-2
Output voltage vs. output current in
normal mode at 24V input, typ.
Input to Output Voltage drop
0
02 10
0.1
0.15
0.25
18A
0.05
0.2
0.3
0.35
0.4V
Ou
t
p
u
t
C
u
r
r
e
n
t
468 121416
Output Voltage
0
05101520
4
8
12
28V
16
20
24
25
A
Output Current
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 5
Bulletin 1606 Switched Mode Power Supplies
7. Output in Buer Mode
If the input voltage falls below a certain value (transfer threshold level), the DC-UPS starts buering without any interruption or voltage dips. Buering is possible even if battery not fully charged.
Output voltage in buer mode
nom. DC 24V Output voltage is stabilized and independent from
battery voltage
22.45V ±1%, at no load,
22.25V ±1%, at 10A output current
Transfer threshold for buering
typ. 80mV higher than the output voltage in buer mode Ripple and noise voltage max. 20mVpp 20Hz to 20MHz, 50Ohm Output current nom. 10A Continuously allowed 15A < 5s with full output voltage *) Short-circuit current
min. 17.9A Load impedance 100mOhm **) max. 21A Load impedance 100mOhm **)
*) If the output current is in the range between 10A and 15A for longer than 5s, a hardware controlled reduction of the
maximal output current to 10A occurs. If the 10A are not suci
ent to maintain the 24V, buering stops after another 5s.
Buering will again be possible as soon as the input voltage recovers.
**) If the nominal output voltage cannot be maintained in buer mode, the DC-UPS switches o after 5s to save battery
capacity.
Fig. 7-1 Buering transition, denitions
Buffer mode
Output voltage
24V
28V
Input voltage
t
t
Transfer
threshold
5
0
0
m
s
/
D
I
V
0
V
O
u
t
p
u
t
V
o
l
t
a
g
e
I
n
p
u
t
V
o
l
t
a
g
e
2
4
V
2
2
.
2
5
V
a
t
1
0
A
2
4
V
Fig. 7-3 Available output current in buer mode
Fig. 7-4 Output voltage vs. output current in buer mode, typ.
Output Current
0
05 Sec.
15A
10A
Time
5A
BonusPower
Output Voltage
A B C
Continuously available Available for 5s then auto switching to curve
Buffering will stop after 5s
D
0
0
5101520
5
10
15
25V
20
25A
Output Current
A B
CD
D
Buffering will stop after 5s
Fig. 7-2 Transfert behavior, typ.
6 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
8. Battery Input
The DC-UPS requires one 12V VRLA battery to buer the 24V output.
Battery voltage
nom. DC 12V Use one maintenance-free 12V VRLA lead acid battery or
one battery module which is listed in the Accessories section.
Battery voltage range
9.0 15.0V Continuously allowed, except deep discharge protection
max. 35Vdc Absolute maximum voltage without any damage to the unit
typ. 7.4V Above this voltage level battery charging is possible Allowed battery sizes
min. 17Ah max. 130Ah Internal battery resistance
max. 100mOhm See individual battry data sheets for this value. Battery charging method CC-CV Constant current, constant voltage mode Battery charging current (CC-mode) nom. 3.0A Independent from battery size
max. 3.4A End-of-charge-voltage (CV-mode)
13.0-14.4V See section 15. Battery charging time typ. 9h *) For a 26Ah battery typ. 34h *) For a 100Ah battery Battery discharging current **)
typ. 21A Buer mode, 10A output
current, 11.5V on the battery
terminal of the DC-UPS, see Fig. 8-1 for other parameters
typ. 0.3A Buer mode, 0A output current
max. 50μA At no input, buering had switched o, all LEDs are o typ. 270mA At no input, buering had switched o, yellow LED
shows “buer time expired” (max. 15 minutes)
Deep discharge protection ***)
typ. 10.5V At 0A output current
typ. 9.8V At 10A output current
*) The charging time depends on the duration and load current of the last buer event. The numbers in the table represent a
fully discharged battery.
**) The current between the battery and the DC-UPS is more than twice the output current. This is caused by boosting the 12V
battery voltage to a 24V level. This high current requires large wire gauges and short cable length for the longest possible buer time. The higher the resistance of the connection between the battery and the DC-UPS, the lower the voltage on the battery terminals which increases the discharging current. See also section 26 for more installation instructions.
***) To ensure longest battery lifetime, the DC-UPS has a battery deep discharge protection feature included. The DC-UPS stops
buering when the voltage on the battery terminals of the DC-UPS falls below a certain value. The yellow LED will show “buer time expired” for a period of 15 minutes after the unit stopped buering.
Fig. 8-1 Battery discharging current vs. output current, typ.
Battery Current
0
0
10
20
5
15
25
30A
2.5 7.5 10 5.21A515
O
u
t
p
u
t
C
u
r
r
e
n
t
Voltage on battery terminal of the DC-UPS:
A:
10.5V
B:
11V
C:
12V
A B C
Bulletin 1606 Switched Mode Power Supplies
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Rockwell Automation Publication 1606-RM013A-EN-P — March 2014 7
Bulletin 1606 Switched Mode Power Supplies
9. Buer Time
The buer time depends on the capacity and performance of the battery as well as the load current. The diagram below shows the typical buer times of the standard battery modules.
Buer time with 26Ah battery (1606-XLSBATASSY2) min. 99’30’’ At 5A output current *) min. 39’ At 10A output current *) typ. 130’ At 5A output current, see
Fig. 9-1
**)
typ. 55’ At 10A output current, see
Fig. 9-1
**) Buer time with 100Ah battery min. 62h 20’ At 0.5A output current *) min. 3h At 10A output current *) typ. 82h 20’ At 0.5A output current, see Fig. 9-1
**)
typ. 4h At 10A output current, see
Fig. 9-1 **)
*) Minimum value includes 20% aging of the battery and a cable length of 1.5m with a cross section of 2.5mm2 between the
battery and the DC-UPS and requires a fully charged (min. 24h) battery.
**) Typical value includes 10% aging of the battery and a cable length of 0.3m with a cross section of 2.5mm
2
between the battery
and the DC-UPS and requires a fully charged (min. 24h) battery.
Fig. 9-1 Buer time vs. output current with a 65Ah and a 100Ah battery
Buffer Current
0
40 50
0.5
1.0
1.5
2A
70 8060 90h30
A
B
A:
65Ah Battery
B:
100Ah Battery
Buffer Time (Hours)
30h
Buffer Current
0
5
2
4
6
8
10A
10 15 20 25
Buffer Time (Hours)
A
B
A:
65Ah Battery
B:
100Ah Battery
5
The battery capacity is usually specied in amp-hours (Ah) for a 20h discharging event. The battery discharge is non­linear (due to the battery chemistry). The higher the discharging current, the lower the appropriate battery capacity. The magnitude of the reduction depends on the discharging current as well as on the type of battery. High current battery types can have up to 50% longer buer times compared to regular batteries when batteries are discharged in less than one hour.
High discharging currents do not necessarily mean high power losses as the appropriate battery capacity is reduced with such currents. When the battery begins to recharge after a discharging event, the process is completed much faster since only the energy removed from the battery needs to be “relled.”
For this reason, the buer time cannot be calculated using the Ah capacity value. The equation “I x t” = capacity in Ah generally leads to incorrect results when the discharging current is higher than C20 (discharging current for 20h).
8 Rockwell Automation Publication 1606-RM013A-EN-P — March 2014
All parameters are specified at an input voltage of 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless noted otherwise.
It is assumed that the input power source can deliver a sufficient output current.
Loading...
+ 16 hidden pages