Rockwell Automation 1503VC User Manual

IntelliVAC™ Contactor Control Module
Bulletin 1503VC
User Manual
IMPORTANT
Read this document and the documents listed in the Additional Resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Table of Contents

Product Description Chapter 1
Introduction ..............................................................................1-1
Description ...............................................................................1-1
IntelliVAC Features ......................................................... 1-2
IntelliVAC Versions ......................................................... 1-3
Specifications .......................................................................... 1-4
Mounting and Connections .............................................. 1-4
Configuration ................................................................... 1-4
Firmware .......................................................................... 1-4
Electrical Ratings (Table 1.A) .......................................... 1-5
Mechanical Ratings (Table 1.B) ....................................... 1-6
Altitude Derating (Table 1.C) .......................................... 1-6
Receiving and Storage Chapter 2
Receiving ............................................................................... 2-1
Storage .................................................................................... 2-1
Installation and Wiring Chapter 3
General Precautions ................................................................ 3-1
Safety and Codes .................................................................... 3-1
Arrangements .......................................................................... 3-2
Integral to an Allen-Bradley MV Controller .................... 3-2
OEM ................................................................................. 3-3
Fuse Protection ....................................................................... 3-6
Grounding ............................................................................... 3-6
Connections ............................................................................ 3-7
Control Power .................................................................. 3-7
Status Relays .................................................................... 3-7
Interface Connections ....................................................... 3-8
Wiring Guidelines Electrically Held Contactors .................. 3-10
Two-Wire Control .......................................................... 3-11
Three-Wire Control ........................................................ 3-12
Wiring Guidelines Mechanically Latched Contactors .......... 3-14
Mechanically Latched Contactors ........................................ 3-15
Capacitor Trip ................................................................ 3-14
Motor Jogging Control ......................................................... 3-17
Time Delay Undervoltage ..................................................... 3-18
1503-UM051D-EN-P – June 2013
ii Table of Contents
Setup and Commissioning Chapter 4
IntelliVAC Configuration ....................................................... 4-1
Monitoring & Troubleshooting Chapter 5
Introduction ............................................................................. 5-1
Module Status ......................................................................... 5-1
Contactor Status ...................................................................... 5-2
Series B Design ................................................................ 5-2
Spare Parts Chapter 6
Spare Parts List ....................................................................... 6-1
Optional Equipment ......................................................... 6-1
Appendix A Typical Contactor Drop-out Times
Table A.1 – Contactor Drop-out Times ................................. A-1
1503-UM051D-EN-P – June 2013
Chapter 1

Product Description

Introduction

An IntelliVAC control module may also be provided as a loose
Description IntelliVAC is an efficient and flexible solution for controlling
This document contains information for the Allen-Bradley Bulletin
1503VC IntelliVAC™ control module. The Bulletin 1503VC is used to control the Allen-Bradley Bulletin 1502 vacuum contactors that are a significant component of the Bulletin 1500/1900 Centerline Medium Voltage Motor Controllers offered by Rockwell Automation.
component, for application with a Bulletin 1502 contactor by a third party (OEM).
medium voltage vacuum contactors used in motor starter and feeder applications. IntelliVAC may be used to control both 400 and 800 Amp contactors. Electrically held and mechanically latched contactor types can be controlled with IntelliVAC.
Figure 1.1 – IntelliVAC Contactor Control Module
1503-UM051D-EN-P – June 2013
1-2 Product Description
Description (cont.)
Contactor Coil(s) In t erface
Coil Current Transducer
C C
Feedback
Aux.
CC
Outputs
Status
Vacuum Contactor
Trip Coil
Vacuum Contactor
Close Coil
Vacuum Contactor
Auxiliary
Module
Status
Contactor
Status
External Capacitor (Optional)
Supply
Voltage
110-240
VAC
or
110-250
VDC
Close
Signal
Open
Signal
Altitude
Select
Drop-Out
Select
Contactor
Select TDUV
Time
Select
Power Up
Safety
Coil
Power
Input
Power
Conditioning
Command
Inputs
c
cc
c
c c
c
Configuration
Inputs
(DIP
switches)
c
c c
c
c
c c
Supply
Control
Power
Supply
Micro Controller
Flash EEPROM
Interface
c
Current
Regulator
IGBT Coil Switching
Figure 1.2 – IntelliVAC Block Diagram

IntelliVAC Features

A wide range of supply voltage (110 – 240 V AC 50/60 Hz,
110 - 250 V DC) allows implementation in multiple applications
Consistent vacuum contactor pick-up time (at a given supply
voltage) ensures repeatable performance
Selectable vacuum contactor drop-out time improves
coordination with upstream power fuses
Electronic altitude compensation (400 A only) eliminates
mechanical compensation required for altitudes above 1,000 meters (800 A contactors include a user-friendly altitude adjustment)
Power loss ride-through (TDUV) allows the vacuum contactor
to remain closed during short power loss (may require an optional external capacitor, dependant on ride-through time)
1503-UM051D-EN-P – June 2013
Product Description 1-3
IntelliVAC Features (cont.)
Anti-kiss and anti-pumping protection ensure that the vacuum
contactor close – open sequence occurs as expected, avoiding rapid re-closure due to faulty control devices
Delayed restart protects the vacuum contactor by ensuring that
the rated duty cycle is not exceeded
Temporary jog function (electrically held contactors only)
allows the motor to be positioned for process set-up
IntelliVAC Versions Series A There are two versions of IntelliVAC control. The
first type is used to control vacuum contactors that are electrically held, with a single electrical coil that is economized electronically. The second is used to control mechanically latched vacuum contactors.
Series B There is a single version of IntelliVAC, to control
both electrically held and mechanically latched vacuum contactors.
Refer to Chapter 6, for catalog numbers for each version of IntelliVAC.
A Series B IntelliVAC module can be used to replace a Series A module.
1503-UM051D-EN-P – June 2013
1-4 Product Description

Specifications

Mounting & Connections
The IntelliVAC control modules are mounted using two (2) screws (see Figure 1.3). They are typically located in the low voltage control panel of the medium voltage controller (Bulletin 1500/1900 controllers, in the case of Rockwell Automation).
IntelliVAC is interfaced to the Bulletin 1502 vacuum contactors using a “quick” connector, located at the module, a wire harness and “quick” connector at the contactor. Control power and other control circuit connections are similarly achieved with “quick” connectors.

Configuration

IntelliVAC is easily configured for a wide variety of medium voltage motor and feeder control applications. It is configured using DIP switches, located within the enclosure (front side). Please refer to Chapter 4 for information.
Bulletin 1500/1900 controllers are shipped with IntelliVAC configured for the required application. Please refer to the documents provided with the order.
pre-

Firmware

IntelliVAC has firmware stored in flash EEPROM; therefore, this may be updated in the field (if necessary). The IntelliVAC firmware is updated using the mini-DIN connector, which is accessible inside the enclosure.
board
1503-UM051D-EN-P – June 2013
Product Description 1-5
Table 1.A – Electrical Ratings
Main Input Voltage (L1 to L2/N)
AC – 110 to 240 V rms, +10/-15%, 47 to 63 Hz DC – 110 to 250 V, +10/-15%
Main Input Current (L1 to L2/N)
Command Inputs \
Description
Contactor Ratings
(Amps)
Inrush Current 400/800 120/240
Control Voltage
(AC or DC)
AC Rating DC Rating
25 A peak (1/2 cycle)
25 A peak
Idle Current (Maximum without contactor
400/800 120/240 125 mA 35 mA
coil energized)
Hold Current (maximum) 400/800 120/240 300 mA 100 mA
Close Current
400
(0.2 sec)
800
120 4.6 A 3.6 A
240 3.4 A 3.3 A
120 11.3 A 4.8 A
240 8.9 A 4.5 A
120 7.0 A 3.7 A
400
Trip Current (latch)
(0.2 sec)
240 3.6 A 2.0 A
120 7.0 A 3.3 A
800
240 4.3 A 1.9 A
AC – 100 to 240 V rms DC – 24 to 250 V
Maximum on state current for open or close command:
9mA
@ 250 V AC, 60Hz, TA=60°C
AC
9mA
@ 250 V DC, TA=60°C
DC
Minimum on state current for open or close command:
2mA
@ 100 V AC, 60Hz, TA=60°C
AC
600µA
@ 24 V DC, TA=60°C
DC
Maximum off state current for open or close command:
400µA
@ 11 V AC, 60Hz, TA=60°C
AC
400µA
@ 15 V DC, TA=60°C
DC
Status Output Contacts
Standards and
AC – 250 V rms, 5 A, R load; 2 A (reactive), PF=0.4 DC – 30 V, 5 A, R load; 2 A (reactive), L/R=7 ms
CE , cULus, CSA, IEC pending
Approvals
T
Ambient Temperature
A =
Refer to Chapter 6 for suitable EMC filter needed to meet CE requirements.
Also refer to Chapter 3 for EMC filter installation guidelines.
Please consult Factory for DC input current ratings. Includes idle current.
\ Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors.) Consult factory for assistance, if needed.
1503-UM051D-EN-P – June 2013
1-6 Product Description
Specifications (cont.)
Table 1.B – Mechanical Ratings
Temperature
Altitude -1000 to 5000 meters Pollution Pollution level II (as defined by UL 840 and IEC 60664-1) Humidity Class II
Shock and Vibration (Operational)
X Ambient temperature is derated at altitudes above 1,000 meters (3,300 feet). Please refer to Table 1.C.
Operating: 0° to 60°C ambient at the control module X
Non-Operating: -40° to 85°C
Shock – 15 g peak, 11 milliseconds
Vibration – 10 to 57 Hz, 0.015 inch displacement peak to peak
- 57 to 150 Hz, 2.5 g acceleration
Table 1.C – Altitude Derating
Altitude DIP Switch Setting 1, 2, 3 X
-1000 to 0 000 60
1 to 1000 001 60
1001 to 2000 010 58
2001 to 3000 011 56
3001 to 4000 100 54
4001 to 5000 101 52
X Refer to Chapter 4. Y Derate by 2°C / 1000 m for high altitude operation
Maximum Operating Ambient
at the control module (°C) Y
5.1 (0.20)
5.1 (0.20)
29.7
29.7
(1.17)
(1.17)
165.9 (6.53)
165.9 (6.53)
5.8 (0.228)
5.8 (0.228) 2 places
2 places
174.8
174.8 (6.88)
(6.88)
185.3
185.3 (7.29)
(7.29)
59.4
59.4
(2.34)
(2.34)
Figure 1.3 – Mechanical Dimensions
1503-UM051D-EN-P – June 2013
Dimensions in mm (inches)
Dimensions in mm (inches)
Chapter 2
Receiving and Storage

Receiving Upon receiving the controller, remove the packing and check for

damage that may have occurred during shipping. Report any damage immediately to the claims office of the carrier.
NOTE: If the IntelliVAC module is an integral component of a
complete MV controller (Bulletin 1500/1900), special receiving and handling instructions will apply. For details, refer to the service manual provided with the equipment.

Storage It is important to consider the following storage requirements if you

are not installing your controller immediately after receiving it.
• Store the controller in a clean, dry, dust-free environment.
• Storage temperature should be maintained between -40°C and 85°C (-40°F and 185°F).
• Relative humidity must not exceed 95%, non-condensing.
1503-UM051D-EN-P – June 2013
2-2 Receiving and Storage
(This page is intentionally left blank.)
1503-UM051D-EN-P – June 2013
Installation and Wiring

General Precautions

In addition to the precautions listed throughout this manual, the
following statements, which are general to the system, must be read and understood.
Chapter 3
A T T E N T I O NA T T E N T I O N
The controller contains ESD (electrostatic discharge) sensitive parts and assemblies. Static control precautions are required when installing testing, servicing, or repairing the assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, refer to applicable ESD protection handbooks.
A T T E N T I O NA T T E N T I O N
An incorrectly applied or installed controller can damage components or reduce product life. Wiring or application errors, such as incorrect or inadequate AC supply, or excessive ambient temperatures, may result in malfunction of the system.
A T T E N T I O NA T T E N T I O N
Only personnel familiar with the controller and associated machinery should plan or implement the installation, start-up, and subsequent maintenance of the system. Failure to do this may result in personal injury and/or equipment damage.

Safety and Codes

A T T E N T I O NA T T E N T I O N
The Canadian Electrical Code (CEC), National Electrical Code (NEC), or other local codes outline provisions for safely installing electrical equipment. Installation MUST comply with specifications regarding wire type, conductor sizes, branch circuit protection, interlocking and disconnect devices. Failure to do so may result in personal injury and/or equipment damage.
1503-UM051D-EN-P – June 2013
3-2 Installation and Wiring

Arrangements

Integral to an Allen-Bradley MV Controller

The IntelliVAC is available as a primary component of an Allen-
The IntelliVAC is offered in two arrangements, Integral (part of a
Bulletin 1500/1900 MV controller) or as an OEM component.
Bradley Bulletin 1500/1900 MV controller as shown in Figure 3.1.
Figure 3.1 - Typical IntelliVAC Installation within a Bulletin 1500/1900 MV Controller
(Shown with optional external capacitor)
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-3
OEM
The IntelliVAC may be ordered as an OEM component. This allows the OEM to mount the components in a configuration most suitable to the motor controller equipment layout. Care must be exercised to ensure the IntelliVAC has adequate ventilation provided around it. Refer to Figure 3.2 for mounting the IntelliVAC. It is recommended that a minimum of 1.5 inches (38.1mm) of free air space be provided between the IntelliVAC and any solid barrier above or below.
The OEM is responsible for controller fusing, motor overload
protection, control devices (eg. Start/Stop push buttons), and wiring
between the IntelliVAC and 1502 vacuum contactor (using optional wire harness). Wiring and mounting for optional items, such as TDUV Capacitor are also the OEM’s responsibility. Refer to Figure
3.3 or 3.4 for basic connections.
An optional EMI filter is required to meet CE EMC requirements (refer to Chapter 6 for recommended type).
Minimum top clearance
Minimum top clearance
38.1
38.1
(1.50)
(1.50)
Dimensions in mm (inches)
Dimensions in mm (inches)
38.1
Minimum bottom clearance
Minimum bottom clearance
38.1
(1.50)
(1.50)
6.4 (0.25)
6.4 (0.25)
Additional Modules
Additional Modules
(as required)
(as required)
Figure 3.2 – Typical Mounting Configurations
Note: Adjacent IntelliVAC modules may be mounted with a
minimum separation of 6.4 mm (0.25 inches).
1503-UM051D-EN-P – June 2013
3-4 Installation and Wiring
Arrangements (cont.)
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
OVERLOAD
OVERLOAD
STOP
STOP
START
START
CAPACITOR
CAPACITOR (OPTIONAL)
(OPTIONAL)
M
M
CONTROL POWER
CONTROL POWER
M-INTELLIVAC
M-INTELLIVAC
78
78
+-
+-
OPEN
OPEN
910
910
+-
+-
CLOSE
CLOSE
16
16
15
15
1
1
11
11 12
12
CONTACTOR
CONTACTOR STATUS
STATUS
MODULE
MODULE
STATUS
STATUS
-
-
EC
EC
+
+
AUX CCO
AUX CCO
TCO
TCO
14
14
13
13
4
4 32
32
6
6 5
5
MOV
MOV
M
M
CONFIGURATION
CONFIGURATION
DIP SWITCHES
DIP SWITCHES
INPUT POWER
INPUT POWER
L1 L2/NG
L1 L2/NG
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
Figure 3.3 – IntelliVAC Typical Schematic (Electrically Held Vacuum Contactor)
Without Optional EMC Filter
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-5
CONTROL POWER
CONTROL POWER
M-INTELLIVAC
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
OVERLOAD
OVERLOAD
STOP
STOP
START
START
CAPACITOR
CAPACITOR (OPTIONAL)
(OPTIONAL)
M
M
M-INTELLIVAC
78
78
+-
+-
OPEN
OPEN
910
910
+-
+-
CLOSE
CLOSE
16
16
15
15
1
1
11
11 12
12
CONTACTOR
CONTACTOR STATUS
STATUS
MODULE
MODULE
STATUS
STATUS
-
-
+
+
AUX CCO
AUX CCO
EC
EC
TCO
TCO
14
14
13
13
4
4 32
32
6
6 5
5
MOV
MOV
M
M
CONFIGURATION
CONFIGURATION
DIP SWITCHES
DIP SWITCHES
INPUT POWER
INPUT POWER
L1 L2/NG
L1 L2/NG
N'
N'
N
N
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
P'
P' P
P
EMC FILTER
EMC FILTER
G
G
Figure 3.4 – IntelliVAC Typical Schematic (Electrically Held Vacuum Contactor)
With Optional EMC Filter
1503-UM051D-EN-P – June 2013
3-6 Installation and Wiring

Fuse Protection The IntelliVAC module requires external fuse protection to

coordinate with the power supply and contactor. The fuse ratings shown in Table 3.A allow the passage of inrush currents expected when the contactor is closed, or from recommended external capacitors for the TDUV option. They will also protect the contactor coils in the event of a module malfunction.
The recommended fuses have been tested to ensure reliable
protection of the module. If the supply voltage is DC, the module must be used with an external fuse that is approved for and rated to interrupt the DC voltage supply. The types listed are Ferraz-Shawmut Midget Fuses (1-1/2" X 13/32"). The TRM is a time-delay type, rated 250 VAC. The ATM is a fast-acting type, rated 500 VDC.
Table 3.A – IntelliVAC Fuse Protection
Rated Supply Voltage Contactor Type
400A EH TRM 2 TRM 3.2
110/120 VAC
220/240 VAC
125 VDC
250 VDC
EH = Electrically Held vacuum contactor ML = Mechanically Latched vacuum contactor
800A EH TRM 2 TRM 6.25
400/800A ML TRM 2 TRM 3.2
400A EH TRM 2 TRM 6.25 800A EH TRM 2 TRM 6.25
400/800A ML TRM 2 TRM 6.25
400A EH/ML ATM 3 ATM 3 800A EH/ML ATM 5 ATM 6 400A EH/ML ATM 3 ATM 5 800A EH/ML ATM 5 ATM 6
Recommended Fuse
(minimum) (maximum)

Grounding

The IntelliVAC module must be connected to a common ground
terminal (PE) on the controller panel. The ground terminal is located on top of the module enclosure for Series A design (refer to Figure
3.7), and on the bottom of module enclosure for Series B design, (refer to Figure 3.6)
A T T E N T I O NA T T E N T I O N
It is important that IntelliVAC is properly grounded using the ground connection provided. Failure to do so may result in damage to equipment or personal injury.
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-7

Connections There are three green connectors on the IntelliVAC module for

connections to the control circuitry. Connector plugs are provided with the module. If additional plugs are required, refer to Chapter 6,
Spare parts.

Control Power

Control power is applied to the module with a two-pole connector
In order to meet CE electromagnetic interference requirements, an
The IntelliVAC can accept either AC or DC control power. Refer to Table 1.A for acceptable input power and control signal ratings.
located at the bottom rear portion of the module. Refer to Figures
3.5 and 3.6 for connections. The ‘L1’ connection is intended to be the ‘Hot’ or ‘+’ side of the control power, and the ‘L2/N’ connection is intended to be the ‘Neutral’, ‘Return’, or ‘-’ side of the control power.
external EMC filter must be installed. Refer to Chapter 6 for suitable EMC filter part number and install per Figure 3.4.

Status Relays

Status relay connections are accessed with a four-pole connector
located at the bottom front portion of the module. Refer to Figure
3.5 or 3.6 for connections. There are two status relays, each with one normally-open contact:
Module Status: Terminals 13 and 14 Contactor Status: Terminals 15 and 16
Refer to Chapter 5 Monitoring and Troubleshooting for a description
of operation for the relays.
Refer to Table 1.A for electrical ratings of the status relays.
13 161514
CONTACTOR STATUS OUTPUT (N.O.)
Figure 3.5 – Bottom side connections (Series A)
MODULE STATUS OUTPUT (N.O.)
L2/NL1
POWER INPUT
1503-UM051D-EN-P – June 2013
3-8 Installation and Wiring
Connections (cont.)
Figure 3.6 – Bottom side connections (Series B)

Interface Connections

Ground Connection
Ground Connection
13 161514
13 161514
CONTACTOR STATUS OUTPUT (N.O.)
CONTACTOR STATUS OUTPUT (N.O.)
MODULE STATUS OUTPUT (N.O.)
MODULE STATUS OUTPUT (N.O.)
POWER INPUT
POWER INPUT
Interface Connections
All other control interface connections are made at a twelve-pole connector located on the top of the module. Refer to Figure 3.7 or
3.8 and Table 3.B for connections. Refer to the Wiring Guidelines
section in this chapter for guidance in making connections to the control circuit.
L2/NL1
L2/NL1
11 1289105672341
CONTACTOR INTERFACE
EX. CAP.
CONTACTOR INTERFACE
EX. CAP.
Ground Connection
Ground Connection
11 1289105672341
Figure 3.7 – Top side connections (Series A)
CONTACTOR INTERFACE
EX. CAP.
11 1289105672341
Figure 3.8 – Top side connections (Series B)
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-9
Table 3.B – Terminal Assignments for IntelliVAC Interface Connections X
Terminal No. Terminal Designation Description
1 External capacitor (negative) Y
2 External capacitor (positive) Y
3 Latch trip coil (common) Y
4 Latch trip coil Y
5 Close coil (common)
6 Close coil
7 Open / Jog command Y Z
Power connection for TDUV or capacitor trip options only
Output for mechanical latch contactor trip coil
Output to close coil of electrically held & mechanical latch contactors
Input to open a mechanical latch contactor or jog an electrically held contactor
8 Open / Jog command (common) Y Z
9 Close command Z
10 Close command (common) Z
11 Contactor auxiliary contact Z
(mutually exclusive)
Input to initiate the closure of electrically held & mechanical latch contactors
Input to indicate the state of the contactor (typically wired to a normally closed
12 Contactor auxiliary contact Z
X Refer to Table 1.A for electrical ratings. Y No connection required if option is not used. Z Ensure compatibility of IntelliVAC input ratings with those of circuit components activating these inputs.
Consider means of isolating/loading these signals, as required (using interposing relays or load resistors). Consult factory for assistance, if needed.
auxiliary contact)
1503-UM051D-EN-P – June 2013
3-10 Installation and Wiring
Wiring Guidelines
The IntelliVAC can be applied with two- or three-wire control
Electrically Held Contactors
circuits. The control system utilized will determine the configuration of the input wiring. Consider the following input and output for the type of control used:
• Terminals 9 and 10 Close Contactor
• Terminals 15 and 16 Contactor Status
In either case, the CLOSE input must receive a maintained voltage
high to keep the contactor closed.
Note:
1. When used with electrically held contactors, the IntelliVAC
allows close commands every six seconds. This is to ensure the rated contactor duty cycle is not exceeded.
2. If a contactor close command is applied and then removed in less
than 500 milliseconds the IntelliVAC may fault. To clear the fault, module power has to be removed and reapplied.
3. If IntelliVAC powers up configured for an electrically held
contactor, and the vacuum contactor is detected as being closed, the module will not respond to a close command until the vacuum contactor auxiliary contact input is in the correct (open) state and module power is removed and re-applied. (See Chapter 5). This is true if the power-up safety DIP switch is enabled.
4. In general, a Close command should only be applied 4 seconds
after energizing IntelliVAC.
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-11

Two-Wire Control

Some two-wire control schemes may be configured such that a close
If using two-wire control, the CLOSE contactor input is maintained high using a single contact. Momentarily opening this input will cause the IntelliVAC to open the contactor. Maintaining the contact will provide a CLOSE command to IntelliVAC (given that all permissives are satisfied). If a fault occurs, in addition to cycling control power to the IntelliVAC module, the CLOSE command must be removed for a minimum of 4 seconds, before being re-applied. Refer to Figure 3.9.
command is present when IntelliVAC is energized. In this case, the Power-Up Safety feature may be disabled by setting DIP switch 12 accordingly. (Available with an IntelliVAC using firmware 2.001 (or newer) refer to Table 4.B).
Note: Only disable the Power-Up safety feature when absolutely
necessary. Doing so can create unsafe operating conditions.
CONTROL POWER
CONTROL POWER
CAPACITOR
CAPACITOR (OPTIONAL)
(OPTIONAL)
1
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
OVERLOAD
OVERLOAD
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
M
M
1
+
+
11
11 12
12
L1 L2/NG
L1 L2/NG
P'
P'
P
P
Figure 3.9 – Two-Wire Control
M-IV
M-IV
-
-
EC
EC
AUX CCO
AUX CCO
EMC FILTER
EMC FILTER
G
G
RUN
RUN
TCO
TCO
4
4 32
32
6
6 5
5
N'
N'
N
N
MOV
MOV
M
M
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
1503-UM051D-EN-P – June 2013
3-12 Installation and Wiring

Three-Wire Control

Wiring Guidelines Electrically Held
If using three-wire control, the CLOSE contactor input is maintained
Contactors (cont.)
In this configuration, the STATUS output acts as a seal-in contact. If a
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
high using two contacts. Momentarily opening this input will cause the IntelliVAC to open the contactor. Momentarily closing the START contact will provide a CLOSE command to IntelliVAC (given that all permissives are satisfied).
fault occurs, in addition to cycling control power over to the IntelliVAC module, the CLOSE command must be removed for a minimum of 4 seconds before being re-applied. Refer to Figure 3.10.
CONTROL POWER
CONTROL POWER
CAPACITOR
CAPACITOR (OPTIONAL)
(OPTIONAL)
M
M
11
11 12
12
1
1
M-IV
M-IV
-
-
EC
EC
+
+
AUX CCO
AUX CCO
TCO
TCO
4
4 32
32
6
6 5
5
MOV
MOV
M
M
L1 L2/NG
L1 L2/NG
P'
P'
P
P
OVERLOAD
OVERLOAD
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
STOP
STOP
EMC FILTER
EMC FILTER
G
G
N'
N'
N
N
START
START
M-IV
M-IV
15 16
15 16
CONTACTOR
CONTACTOR
STATUS
STATUS
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
Figure 3.10 – Three-Wire Control
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-13
CLOSE COMMAND
TO MICRO
MICRO OUTPUT TO CLOSE COIL
CLOSE LEVEL OF
CURRENT TO CLOSE
COIL
CONTACTOR STATUS
RELAY OUTPUT
MODULE STATUS
RELAY OUTPUT
CONTACTOR
AUXLIARY
INPUT TO MICRO
15mS
DEBOUNCE
200mS
X
CONTACTOR PICK UP
90mS
(@120VAC)
X
Contact status relay closes on request to close. It will open if the contactor auxiliary contact does not close within 200 milliseconds and
15mS
DEBOUNCE
CLAMP DELAY
5mS
ACKNOWLEDGE
WINDOW
NATURAL
CONTACTOR
DROP OUT
80mS
Y
module will fault (opening module status relay).
Y
For this example, the 130 millisecond drop-out time has been selected. The base drop-out time is 50 milliseconds. The microcontroller delay is 130-50=80 milliseconds.
Figure 3.11 – Timing Diagram 400A (Electrically Held) Contactor
with IntelliVAC Control for three-wire Control
SELECTABLE DROP
OUT TIME
(0 TO 190mS)
60mS
30mS
1503-UM051D-EN-P – June 2013
3-14 Installation and Wiring
IntelliVAC control may be used for mechanically latched contactors.

Wiring Guidelines Mechanically Latched Contactors

A momentary control signal is needed to close the contactor, and a second momentary control signal is needed to open the contactor. The momentary open/close commands must be at least 50 milliseconds in duration.
Refer to Figure 3.12 for a typical mechanical latch control scheme.
Note:
1. A mechanically latched contactor may already be closed when power is applied to the IntelliVAC control module.
2. It is permissible to apply an open command to the IntelliVAC module as power is re-applied.
CONTROL POWER
CONTROL POWER
M
M
MOV
MOV
TC
TC
MOV
MOV
CC
CC
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
M-IV
M-IV
1
1
-
-
EC
EC
+
+
M
M
11
11
AUX CCO
AUX CCO
12
12
TCO
TCO
4
4 32
32
6
6 5
5
L1 L2/NG
L1 L2/NG
P'
P'
P
P
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
EMC FILTER
EMC FILTER
G
G
CLOSE
CLOSE
OPEN
OPEN
OVERLOAD
OVERLOAD
N'
N'
N
N
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
M-IV
M-IV
78
78
+-
+-
OPEN
OPEN
Figure 3.12 – Mechanically Latched Contactor Control
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-15

Mechanically Latched Contactors

The IntelliVAC must receive an ‘OPEN’ command within a few
A separate voltage source is needed to provide the ‘OPEN’ command.
Note: Minimum capacitor voltage ratings
• 120V applications – 200V DC (250V DC preferred)
• 240V applications – 400V DC (450V DC preferred)

Capacitor Trip

The IntelliVAC can be configured to provide capacitor trip functionality with mechanically latched contactors. A capacitor must be connected to the IntelliVAC (terminals #1 and #2) in order to provide this capability. The capacitor provides control power for the IntelliVAC as well as stored energy to trip the contactor. Maximum recommended capacitor size is 1650 µF for 120V control or 330 µF for 240V control. Use of larger capacitors will require a current limiting circuit to prevent opening the control fuse on energization.
seconds of losing AC control power. This time limit depends on voltage and capacitor size as shown in the table below. If the elapsed time exceeds this limit, the contactor cannot be tripped by IntelliVAC.
This may be taken from the external capacitor as shown in Figure
3.13.
Table 3.C – Mechanically Latched Contactor – Capacitor Trip Times
Contactor
Rating
400 Amp
Nominal Voltage
(Vac)
120
240
Actual
V
(Vac)
input
120 3.5
110 2.7
100
240 7.5
200
Ext.
Capacitor
(µF)
1650
330
Max. time
for trip
(sec)
1.7
4.7
1503-UM051D-EN-P – June 2013
3-16 Installation and Wiring
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
OPEN
OPEN
OVERLOAD
OVERLOAD
CONTROL POWER
CONTROL POWER
M-IV
M-IV
78
78
+-
+-
OPEN
OPEN
CAPACITOR
CAPACITOR
M
M
1
1
-
-
EC
EC
+
+
11
11
AUX CCO
AUX CCO
12
12
L1 L2/NG
L1 L2/NG
M-IV
M-IV
TCO
TCO
M
M
MOV
MOV
4
4 32
32
6
6 5
5
TC
TC
MOV
MOV
CC
CC
N'
N' N
N
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
CLOSE
CLOSE
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
P'
P'
P
P
EMC FILTER
EMC FILTER
G
G
Figure 3.13 – Mechanically Latched Contactor with Capacitor Trip Option
1503-UM051D-EN-P – June 2013
Installation and Wiring 3-17

Motor Jogging Control

For motor jogging operations, the second control input, or OPEN
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
When used with electrically held contactors, the IntelliVAC allows close commands every six seconds. This is to ensure the rated contactor duty cycle of 600 operations per hour is not exceeded.
command, will close the contactor for as long as the input is present, and open the contactor when the input is removed. (Refer to Figure
3.14.) This method will bypass the standard six second motor re-
start delay for jogging purposes only.
CONTROL POWER
CONTROL POWER
M-IV
M-IV
4
1
1
-
-
EC
EC
+
+
M
M
11
11
AUX CCO
AUX CCO
12
12
TCO
TCO
4 32
32
6
6 5
5
MOV
MOV
M
M
L1 L2/NG
L1 L2/NG
EMC FILTER
P'
EMC FILTER
P'
P
P
OVERLOAD
OVERLOAD
* Refer to Table 3.A for recommended fuse sizing.
* Refer to Table 3.A for recommended fuse sizing.
STOP
STOP
JOG
JOG
G
G
N'
N'
N
N
START
START
M-IV
M-IV
15 16
15 16
CONTACTOR
CONTACTOR
STATUS
STATUS
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
M-IV
M-IV
78
78
+-
+-
OPEN
OPEN
Figure 3.14 – Motor Jogging Control
1503-UM051D-EN-P – June 2013
3-18 Installation and Wiring

Time Delay Undervoltage The IntelliVAC can be configured to provide time delay undervoltage

(TDUV) protection. The feature is available to keep electrically held contactors closed during a voltage dip or brief power loss. This option may require the addition of a capacitor (see below). Refer to Chapter 6 for typical capacitor sizing. The capacitor is connected to terminals 1(-) and 2(+) of the IntelliVAC. (Refer to Figure 3.15.)
Table 4.B of the “Setup and Commissioning” chapter has the dip
switch settings to provide TDUV from 0.2 to 2 seconds. IntelliVAC can provide TDUV protection without the use of an external capacitor, as shown in Table 3.D.
Table 3.D – Maximum TDUV Time (without Capacitor)
Control Voltage Max. TDUV Time (secs)
110/120 V 0.2 220/240 V 1.0
The following conditions will initiate TDUV protection, regardless
of the supply voltage:
1. If the supply voltage drops below 90 VAC/VDC after the first
200 milliseconds after a contact close request.
2. When the supply voltage drops below 72 VAC/FDC after the
200 millisecond close sequence.
If the undervoltage condition persists beyond the set delay time, the
contactor will be opened and an undervoltage fault condition will occur.
CONTROL POWER
CONTROL POWER
M-IV
CAPACITOR
CAPACITOR
*
*
CONTROL
CONTROL POWER
POWER FUSE
FUSE
OVERLOAD
OVERLOAD
Refer to Table 3.A for recommended fuse sizing.
Refer to Table 3.A for recommended fuse sizing.
M
M
11
11 12
12
P'
P'
STOP
STOP
Figure 3.15 – TDUV Control Circuit
M-IV
1
1
-
-
EC
EC
+
+
AUX CCO
AUX CCO
L1 L2/NG
L1 L2/NG
EMC FILTER
EMC FILTER
P
P
TCO
TCO
G
G
15 16
15 16
CONTACTOR
CONTACTOR
N'
N' N
N
START
START
M-IV
M-IV
STATUS
STATUS
4
4 32
32
6
6 5
5
MOV
MOV
M
M
M-IV
M-IV
910
910
+-
+-
CLOSE
CLOSE
1503-UM051D-EN-P – June 2013
Chapter 4
Setup and Commissioning

IntelliVAC Configuration The IntelliVAC module is configured for a specific application by

setting DIP switches. They are accessed by loosening the two screws on the front of the unit, and removing the cover by sliding it forward. The switches are found on the front edge of the IntelliVAC circuit board (see Figure 4-1). There are 12 switches, with number 1 being at the top next to the mini DIN connector. (Refer to Table 4.B).
I M P O R T A N TI M P O R T A N T
Remove power from the module before removing the cover and before changing the DIP switch settings. The new settings are recognized only on power-up.
Ground Stud (Series A)
Ground Stud (Series A)
Interface Connections
Interface Connections
EEPROM Programming Port
EEPROM Programming Port
(Mini DIN Connector)
(Mini DIN Connector)
DIP Switches
DIP Switches
Status Relay Outputs
Status Relay Outputs
Supply Power Input
Supply Power Input
Internal Control Fuse
Internal Control Fuse
Figure 4.1 – DIP Switch and Connector Locations
Ground Stud (Series B)
Ground Stud (Series B)
An IntelliVAC unit shipped separately from the factory will have a
default configuration per Table 4.A.
Table 4.A – DIP Factory Default Settings
Description 1 2 3 4 5 6 7 8 9 10 11 12
Altitude: 0 – 1000m 0 0 1
Drop-out time: 130 msec 0 1 1
Contactor config.: 400A EH 0 1
TDUV config.: No TDUV 0
Ext. cap TDUV time: 0.2 sec 0 0
*Power-Up Safety: Enable 0
1503-UM051D-EN-P – June 2013
DIP switch
4-2 Setup and Commissioning
IntelliVAC units shipped in a complete MV controller (Bulletin
IntelliVAC Configuration (cont.)
1500/1900) will be configured to suit the installed application (i.e. contactor type). The user should verify the settings before energizing the equipment. Table 4.B defines the settings for each switch.
UP = 1
DOWN = 0
DIP switch SW1
1 2 3 4 5 6 7 8 9 10 11 12
| | | |
Altitude X
-1000 to 0
1 to 1000
1001 to 2000
2001 to 3000
3001 to 4000
4001 to 5000
Not defined
Not defined
1 2 3 12
0 0 0 0
0 0 1 1
0 1 0
0 1 1 10 11
1 0 0 0 0 1 0 1 0 1 1 1 0 1 0 1 1 1 1 1
9
Drop out time Z
50 msec
75 msec
100 msec
130 msec
150 msec
175 msec
200 msec
240 msec
4 5 6 1
0 0 0
0 0 1 7 8
0 1 0 0 0 0 1 1 0 1 1 0 0 1 0 1 0 1 1 1
1 1 0 1 1 1
Power-Up Safety Y
Enable
Disable
Ext. cap. TDUV time
TDUV config.
0
No TDUV
TDUV Enabled
Contactor Config.
400A Mech. Latch
400A Elec. Held
800A Mech. Latch
800A Elec. Held
X The altitude compensation by DIP switch settings applies to Series E 400 amp vacuum contactors only. All 800 amp contactors are adapted
for altitude by altering the return springs. 800 amp contactors are to be set for 1 to 1000m (001 DIP setting).
Y Available with IntelliVAC using version 2.001 firmware or newer. Z By-pass contactors in MV SMC applications must be set for 50 millisecond drop-out time.
Refer to Appendix A for typical drop-out time settings used when power fuses are provided by Rockwell Automation.
0.2 sec
0.5 sec
1.0 sec
2.0 sec
1503-UM051D-EN-P – June 2013
Chapter 5
Monitoring and Troubleshooting

Introduction The IntelliVAC module has two light emitting diodes (LEDs) and

relay outputs to indicate the status of the contactor and the module. The LEDs are visible on the front of the module and the relay outputs are accessed on the bottom front of the module.
Figure 5.1 – IntelliVAC LEDs

Module Status The Module Status is indicated with a Green LED if the module is

functioning properly and has a valid configuration. If the module powers up with an invalid configuration the LED will be Red, indicating a Fault condition which will not allow the contactor to close. If the module powers up properly and experiences an undervoltage condition when attempting to close the contactor or while the contactor is closed, the LED will be Red (Fault). If the contactor does not close properly, a Fault is generated, the LED turns Red, and inputs are inhibited until the module power is removed and reapplied. If the processor has an internal fault, the LED will be Red, the outputs will be cleared, and the processor will be reset. If the reset is successful, the LED will be Green and the module will respond to the control inputs. The input command must be toggled before the module will respond to a new command (rising edge triggered).
Module Status output relay has a normally open contact. The contact
is open during a Fault condition (LED red), and closed during a healthy condition (LED green).
The module states for Series A are summarized in Table 5.A.
Series B Design
Additional module states are indicated with the LED as per Table 5.B.
1503-UM051D-EN-P – June 2013
5-2 Monitoring and Troubleshooting
Contactor Status
Contactor Status output relay has a normally open contact. The
Series B Design
Additional module states are indicated with the LED as per Table 5.B.
The Contactor Status is indicated with a yellow LED that is off until
a CLOSE command is received. The LED will stay on if the contactor closes properly, until the contactor is opened.
contact is open when the contactor is open (LED off), and closed when the contactor has received a close command (for 200 milliseconds) or if it is closed (LED on).
Table 5.A – IntelliVAC Status Indication (Series A design)
Parameter Conditions LED State Relay Contact State
• rated supply voltage and
• valid configuration
Module Status
Y
Contactor
Status
X Applies only to power-up condition. Y Fault is reset by cycling control power. Z If a contactor close command is applied and then removed in less than 500 milliseconds, the
IntelliVAC may fault and the module status LED will turn red. To clear the fault, module power has to be removed and reapplied.
[ For mechanical latch contactors a close command does not need to be maintained for the contactor
to remain closed (resulting in a yellow state for contactor status).
• undervoltage or
• contactor fault or
• invalid configuration X or
• internal fault
• insufficient supply voltage Off Open
• rated supply voltage and
• close command present [ and
• contactor closed
• insufficient supply voltage or
• close command absent [ or
• contactor open
Green Closed
Red Y
Yellow Closed
Off Open
Open
1503-UM051D-EN-P – June 2013
Monitoring and Troubleshooting 5-3
Table 5.B – IntelliVAC Status Indication (Series B design)
Conditions
XY
Description
Normal Healthy Module and Contactor OPEN Green Closed Off Open
Normal Healthy Module and Contactor CLOSED Green Closed Yellow Closed
Warning Invalid Command Present ^ Yellow Closed Off Open
Warning Mechanical Latch Fail to Trip Yellow Open Yellow Closed
Fault Power Up with Contactor CLOSED Red – Flash 2 [ Open Yellow Closed
Fault Contactor Fails to Pick Up Green Open Red – Flash 1 Z Open
Fault Contactor Drop Out During Hold Green Open Red – Flash 2 [ Open
Fault Long Contactor Drop Out Time Green Open Red – Flash 3 Z Open
Fault Microcontroller Malfunction Red Open Red Open
Fault Power Up with Invalid Dip Switch Configuration Red – Flash 1 Open Off Open
Fault Undervoltage with a CLOSE Command Present Red Open Off Open
X Warning = Recoverable Condition – Remove and retry offending signal Y Fault = Non-recoverable condition – Module power must be removed and re-applied. Z Flash 1 = 1 Flash Red LED followed by a pause. [ Flash 2 = 2 Consecutive Red LED flashes followed by a pause. \ Flash 3 = 3 Consecutive Red LED flashes followed by a pause. ] EH = Only for Electrically Held Contactor ^ Invalid Command Types:
1. Close, Jog or Trip commands present during power up sequence.
2. Close or Jog command re-applied too quickly (before contactor opening sequence is verified). Allow at least 60 msec, plus drop out delay time, before re-applying these signals. NOTE: Contactor will only respond to a close command re-applications after the re-start delay timer has expired.
3. Close and Trip commands present simultaneously (valid with Mechanical Latch contactors only).
Module Status Contactor Status
LED Color Relay LED Color Relay
1503-UM051D-EN-P – June 2013
5-4 Monitoring and Troubleshooting
Table 5.C – M
Problem or Trip Indicated Indication of the following conditions Possible Solutions
Contactor does not energize
Contactor closes momentarily and will not reclose.
odule Troubleshooting
• Motor Protection activated
• Both Status LEDs ‘Off’
• Module Status LED ‘Red’ upon power up
• Module Status LED ‘Red’ upon power up
• Module Status ‘Red Flash 1’ upon power up
• Loose connection in control circuit. • Verify contactor auxiliary set up. Reference
• Module status LED ‘Red’ and Contactor
• Module status LED ‘Red’ and Contactor
• Module status LED ‘Green’ and Contactor
• Both status LEDs ‘Off’ • Check internal control fuse. Verify IntelliVAC
(Series A)
(Series A)
(Series B)
Status LED ‘Off’ (Series A)
Status LED ‘Off’ (Series A)
Status LED ‘Red Flash 1’ (Series B)
• Investigate and reset
• Check Control Power
• Loose connections in control circuit
• Verify IntelliVAC power input plug is in place and properly seated
• Verify internal control fuse has not opened (Refer to Figure 4.1 for location)
• IntelliVAC faulted. Cycle control power to reset. Replace IntelliVAC if unsuccessful.
• Improper setting of dip switches. Check settings and cycle control power.
Publication 1502-UM052A-EN-P (400A) or 1502-UM051B-EN-P (800A) – Auxiliary Contact Set-up Procedure.
• Verify circuit continuity (is contactor plug connected properly?)
• Coil damaged or connections are loose. Repair and cycle control power.
• Auxiliary Contact Assembly improperly adjusted. Reference Publication 1502­UM052A-EN-P (400A) or 1502-UM051B-EN-P (800A) – Auxiliary Contact Set-up Procedure. Cycle control power to reset.
• Undervoltage fault (no TDUV), control voltage dipped below trip point. Cycle control power to reset. Verify voltage levels are 110 to 240 VAC, 110 to 250VDC
• Armature Plate obstructed from closing to coil face. Verify no foreign material behind the armature plate. Cycle control power to reset.
operation in test mode before applying Medium Voltage. (Refer to Fig. 4.1 for location.)
1503-UM051D-EN-P – June 2013
Monitoring and Troubleshooting 5-5
Table 5.C – Module Troubleshooting (cont.)
Problem or Trip Indicated Indication of the following conditions Possible Solutions
Contactor opens during operation
Contactor does not open (mechanical latch only)
• Motor Protection activated • Investigate and reset.
• Stop command initiated • Verify circuit
• Module Status LED ‘Red’ • Undervoltage fault (no TDUV), control voltage dipped below trip point. Cycle control power to reset. Verify voltage levels are 110 to 240 VAC, 110 to 250 VDC.
• With external capacitor and TDUV feature activated, undervoltage condition for longer than programmed TDUV time. Undervoltage fault activated. Cycle control power to reset.
• Module Status LED ‘Green’ and Contactor Status LED ‘Red Flash 2’ (Series B only)
• Both status LEDs ‘Off’ • Check control voltage and internal control
• Module Status LED ‘Red’ and Contactor Status LED ‘Yellow’ (Series A, with firmware
2.001 or newer)
• Module Status LED ‘Yellow’ and Contactor Status LED ‘Yellow’ (Series B, with firmware
2.001 or newer)
• Contactor Status feedback between Terminals 11 and 12 on the IntelliVAC has closed. The IntelliVAC will de-energize the coil, thinking the contactor has opened for other reasons.
fuse. (Refer to Figure 4.1 for location.)
• Check control power to ensure that it has not dipped below minimum (see Table 5.D).
• Trip mechanism is damaged. Inspect and replace if needed.
• Check for loose connections in the control circuit.
Refer to Tables 5.A or 5.B for definition of Module LED states.
Table 5.D – Minimum IntelliVAC Operational Supply Voltages
Voltage Level
Pick-Up 400/800 95
Drop-Out 400/800 75
Trip (Mechanical Latch)
Contactor Rating
(Amps)
400 70
800 80
Minimum Voltage
(VAC, 47 to 63 Hz)
1503-UM051D-EN-P – June 2013
5-6 Monitoring and Troubleshooting
(This page is intentionally left blank.)
1503-UM051D-EN-P – June 2013
Chapter 6
Spare Parts

Spare Parts List IntelliVAC (electrically held) Series A 1503VC-BMC1

IntelliVAC (mechanical latch) Series A 1503VC-BMC2 IntelliVAC (electrically held and
mechanical latch) Series B 1503VC-BMC3
Internal Fuse: 6.3 A, 250 V (Littlefuse 21506.3) 80174-902-14-R
Multi-pole connectors: 2 pole (module power) 80174-014-01-R 4 pole (status outputs) 80174-014-03-R 12 pole (coil and I/O connections) 80174-014-11-R
Optional Equipment
TDUV Capacitor* For 110/120V AC control (1650 µF) 80158-779-51-R For 220/240V AC control (330 µF) 80158-779-52-R
EMC Filter
Schnaffer (FN 670-10/06) 80026-430-01-R
*Includes mounting bracket and terminal guards
1503-UM051D-EN-P – June 2013
6-2 Spare Parts
1503-UM051D-EN-P – June 2013
Appendix A
Typical Contactor Drop-out Times
The contactor drop-out times shown in the following table are typical
values used when the power fuses are provided as part of a complete MV controller from Rockwell Automation. The recommendations are based on Ferraz Shawmut power fuses. Other fuse types may require alternate drop-out time settings.
Table A.1 – Contactor Drop-out Times
Fuse Rating Contactor Drop-out Time (msec)
Voltage Current 400A 800A
2R 3R 4R 6R
9R 12R 18R
< 5000
< 5000
Fuse not suitable for use with 400A contactor.
19R 24R 100 32R 240 38R
48X
57X 2 x 24R 2 x 32R 2 x 38R
20E
30E
40E
50E
65E
80E
100E 125E 150E 175E 200E 250E 300E 350E 75 400E 100 450E 130 500E 600E 750E 900E
50
     
50
   
50
75 200 100 240
240 *
50
75 200
240 *
1503-UM051D-EN-P – June 2013
A-2 Typical Contactor Drop-out Times
Table A.1 – Contactor Drop-out Times (cont.)
Fuse Rating Contactor Drop-out Time (msec)
Voltage Current 400A 800A
2R 3R 4R 6R
7200
8250
Fuse not suitable for use with 400A contactor.
9R 12R 18R 75 24R 150
2X18R 2X24R
20E 30E 40E 50E 65E 80E
100E 125E 150E 175E 200E
50
50
 
50 50
130
Note: The drop-out time is chosen to be equal to or greater than the intersection of the rated
contactor interrupting current and the fuse melt time curve (except where noted *)
1503-UM051D-EN-P – June 2013
Medium Voltage Products, 135 Dundas Street, Cambridge, ON, N1R 5X1 Canada, Tel: (1) 519.740.4100, Fax: (1) 519.623.8930, www.ab.com/mvb
Publication 1503-UM051D-EN-P – June 2013
Supersedes Publication 1503-UM0 51C-EN-P – January 2006 Copyright © 2013 Rockwell Automation, Inc. All rights res erved. Printed in Canada.
Loading...