2.1 Unit data.......................................................................................................................................... 9
2.2 Unit dimensions, outdoor unit........................................................................................................ 12
2.3 Unit dimensions, indoor unit.......................................................................................................... 13
3Design and function............................................................................................................................ 14
3.1 Unit description............................................................................................................................. 14
Carefully read the operating manual before commissioning the units or their components for the
first time. It provides useful tips and notes such as
hazard warnings to prevent injury and material
damage. Failure to follow
manual can endanger persons, the environment
and the equipment itself or its components and will
void any claims for liability.
Store this manual and the information required for
the operation of this system (e.g. refrigerant datasheet) in the vicinity of the unit.
The refrigerant used in the system is flammable. If
applicable, observe the local safety conditions.
the directions in this
DANGER!
This combination of symbol and signal word
warns of a situation in which there is immediate
danger
cause serious injury.
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may be fatal or cause
serious injury
, which if not avoided may be fatal or
WARNING!
.
Warning of inflammable substances!
Identification of notes
1.2
This section provides an overview of all important
safety aspects for proper protection of people and
safe and fault-free operation.The instructions and
safety notes contained within this manual must be
observed in order to prevent accidents, personal
injury and material damage.
Notes attached directly to the units must be
observed in their entirety and be kept in a fully
legible condition.
Safety notes in this manual are indicated by symbols. Safety notes are introduced with signal words
which help to highlight the magnitude of the danger
in question.
CAUTION!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause injury or material and environmental damage.
NOTICE!
This combination of symbol and signal word
warns of a potentially hazardous situation,
which if not avoided may cause material and
environmental damage.
This symbol highlights useful tips and recommendations as well as information for efficient
and fault-free operation.
DANGER!
Contact with live parts poses an immediate
danger of death due to electric shock. Damage
to the insulation or individual components may
pose a danger of death.
1.3 Personnel qualifications
Personnel responsible for commissioning, operation, maintenance, inspection and installation must
be able to demonstrate that they hold a qualification which proves their ability to undertake the
work.
Dangers of failure to observe
1.4
the safety notes
Failure to observe the safety notes may pose a risk
to people, the environment and the units. Failure to
observe the safety notes may void any claims for
damages.
5
Page 6
REMKO RVD series
In particular, failure to observe the safety notes
may pose the following risks:
n The failure of important unit functions.
n The failure of prescribed methods of mainte-
nance and repair
n Danger to people on account of electrical and
mechanical effects.
.
1.5 Safety-conscious working
The safety notes contained in this manual, the
existing national regulations concerning accident
prevention as well as any internal company
working, operating and safety regulations must be
observed.
Safety instructions
1.6
for the operator
The operational safety of the units and components is only assured providing they are used as
intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified personnel.
n Protective covers (grills) over moving parts
must not be removed from units that are in
operation.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury
n The units and components must not be
exposed to any mechanical load, extreme
levels of humidity or extreme temperatures.
n Rooms in which refrigerant may escape shall
be adequately aerated and ventilated. Otherwise, a risk of suffocation or fire exists.
n Do not leave children unsupervised when close
to the system.
n Commissioning must be performed by author-
ised specialists exclusively. Deficient commissioning may lead to water leaks, electric
shocks or fire. Commissioning must take place
as described in the user manual.
n Only instruct authorised specialist personnel to
perform maintenance or servicing.
n The system is filled with a flammable refrig-
erant. Never thaw any frozen unit components
independently!
n Do not operate any further devices that pro-
duce high heat or naked flames in the same
room.
.
n All housing parts and unit openings, e.g. air
inlets and outlets, must be kept clear
n The units must be inspected by a service tech-
nician to ensure that they are safe to use and
fully functional at least once yearly. Visual
inspections and cleaning may be performed by
the operator when the units are disconnected
from the mains.
.
1.7 Safety notes for installation,
maintenance and inspection
n The refrigerant R32 used in the system is flam-
mable. If applicable, observe the local safety
conditions.
n Keep the cooling circuit clear of other gases
and foreign substances. Only fill the cooling circuit with the refrigerant R32.
n Only use the accessories, components and
appropriately marked parts provided. The use
of non-standardised components may result in
water leaks, electric shocks and fire.
n Only install and store the units in rooms larger
than 4 m2. With a failure to comply
result in the room filling with a flammable mixture!
The minimum room size of 4 m2 required for
installation and storage pertains to the basic fill
quantity of the unit. This varies according to the
installation type and total fill quantity of the
system. The calculation must take place in
accordance with valid DIN standards. Make
sure that the installation site is suitable for safe
unit operation.
n Only mount the unit components on structurally
suitable brickwork.
n The units must not be installed in rooms in
which further devices that produce heat are
operated (heaters, open hearths).
n Make sure the installation room is sufficiently
ventilated.
n Interventions in the cooling circuit are only pos-
sible after completely draining the refrigerant.
Never solder or grind unit components!
n Note that refrigerant may be odourless.
n Never operate the air conditioning unit in a
humid room, such as a bathroom or laundry
room. If the humidity is too high, this can cause
short circuits on electrical parts.
n The product must be correctly earthed at all
times, otherwise it may induce electric shocks.
n Attach the condensate drain as described in
the operating manual. The inadequate
drainage of condensate can lead to water
damage in your apartment.
n All persons who intervene in the cooling circuit
must hold a valid certificate from the chamber
of industry and commerce, which confirms their
ability to work with refrigerant.
, leaks may
6
Page 7
n Appropriate hazard prevention measures must
be taken to prevent risks to people when performing installation, repair
cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken
in accordance with the usage and operating
conditions stipulated in this manual and comply
with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n Units may only be mounted at the points pro-
vided for this purpose at the factory. The units
may only be secured or mounted on stable
structures, walls or floors.
n The units and components should not be oper-
ated in areas where there is a heightened risk
of damage. Observe the minimum clearances.
n The units and components must be kept at an
adequate distance from flammable, explosive,
combustible, abrasive and dirty areas or
atmospheres.
n Safety devices may not be modified or
bypassed.
n The connection of the indoor unit must be
established as a permanent connection; a
detachable, reusable connection is not permissible.
, maintenance or
1.8 Unauthorised modification
and changes
1.10 Warranty
For warranty claims to be considered, it is essential
that the ordering party or its representative complete and return the "certificate of warranty" to
REMKO GmbH & Co. KG at the time when the
units are purchased and commissioned.
The warranty conditions are detailed in the "General business and delivery conditions". Furthermore, only the parties to a contract can conclude
special agreements beyond these conditions. In
this case, contact your contractual partner in the
first instance.
1.1
1 Transport and packaging
The devices are supplied in a sturdy shipping container. Please check the equipment immediately
upon delivery and note any damage or missing
parts on the delivery and inform the shipper and
your contractual partner. For later complaints can
not be guaranteed.
WARNING!
Plastic films and bags etc. are dangerous
toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to
children!
Modifications or changes to units and components
are not permitted and may cause malfunctions.
Safety devices may not be modified or bypassed.
Original replacement parts and accessories
authorised by the manufactured ensure safety
use of other parts may invalidate liability for
resulting consequences.
. The
1.9 Intended use
Depending on the model, the units and the additional fittings with which they are equipped are only
intended to be used as an air-conditioner for the
purpose of cooling or heating the air in an
enclosed space.
Any different or additional use is a non-intended
use. The manufacturer/supplier assumes no liability for damages arising from a non-intended use.
The user bears the sole risk in such cases.
Intended use also includes working in accordance
with the operating and installation instructions and
complying with the maintenance requirements.
The threshold values specified in the technical
data must not be exceeded.
7
Page 8
REMKO RVD series
1.12 Environmental protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly materials. Make a valuable contribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved
collection points.
Disposal of equipment and components
Only recyclable materials are used in the manufacture of the devices and components. Help protect
the environment by ensuring that the devices or
components (for example batteries) are not disposed in household waste, but only in accordance
with local regulations and in an environmentally
safe manner, e.g. using certified firms and recycling specialists or at collection points.
8
Page 9
2 Technical data
2.1 Unit data
SeriesRVD 355 DCRVD 525 DCRVD 685 DCRVD 1055 DC
Operating mode
Nominal cooling output
Energy efficiency ratio SEER
1)
1)
Rated power consumption, electrical cooling
1)
kW
kW0.851.632.193.95
Rated elec. curr. consump.,
cooling
Power consumption, annual,
QCE
Energy efficiency ratio, cooling
Nominal heat capacity
Energy efficiency ratio SCOP
Rated power consumption, electrical heating
1)
3)
2)
2)
kWh157304402602
1)
kW
4)
kW1.101.462.053.00
Rated elec. curr. consump.,
heating
2)
Inverter ceiling cassette-room air conditioner combination
for cooling and heating
3.5
(1.5-5.3)
5.3
(2.9-5.7)
7.0
(3.2-8.2)
10.5
(4.0-12.0)
7.86.1
A3.87.29.56.6
A++
3.1
(1.0-5.6)
4.2
(2.4-6.1)
5.4
(2.4-8.7)
8.1
(2.6-13.2)
4.64.0
A5.06.48.95.0
Power consumption, annual,
3)
QHE
Energy efficiency ratio, heating
kWh959143518902835
2)
A++A+
Max. power consumptionkW1.81.92.94.8
Max. current consumptionA7.98.512.58.3
EDP no.1623845162385516238651623875
1)
Air inlet temp. TK 27 °C/FK 19 °C, outside temperature TK 35 °C, FK 24 °C, max. air flow volume,
5 m pipe length
2)
Air inlet temp. TK 20 °C, outside temperature TK 7 °C, FK 6 °C, max. air flow volume, 5 m pipe length
3)
The specified value is based on results from standard testing.
The actual consumption depends on the use and location of the unit
4)
The specified value is based on the average heating period
9
Page 10
REMKO RVD series
Associated indoor unit / series
Power supplyV/Ph/Hz230/1~/50
Application area (room
volume), approx.
Adjustment range
room temperature
Operating range°C/r.H.%+17 to +30 / 35-65
Air flow volume per stage
Sound pressure level per
5)
stage
Enclosure classIPX0
Refrigerant connection,
liquid pipe
Refrigerant connection,
suction pipe
Condensate drainage connection
m
°C+17 to +30
m3/h
dB (A)33/36/4136/39/4340/43/4741/47/51
Inches
(mm)
Inches
(mm)
mm2532
RVD 355 DCITRVD 525 DCITRVD 685 DCITRVD 1055 DC
3
110160230320
416/504/
617
1/4 (6.35)3/8 (9.52)
3/8 (9.52)1/2 (12.7)5/8 (15.9)
540/625/
750
1032/1200/
1378
IT
1438/1620/
1775
Condensate pump,
flow rate, max.
Dimensions:
Length/width/depth
Cover dimensions: Length/
width/depth
Weightkg18.728.032.5
EDP no.1623847162385716238671623877
5)
At distance of 1 m in the open air; specified values are maximum values
mm WS500750
mm570/570/260840/840/245
mm647/647/50950/950/55
10
Page 11
Associated outdoor unit / series
RVD 355 DC
A
T
RVD 525 DCATRVD 685 DCATRVD 1055 DC
AT
Power supplyV/Ph/Hz230/1~/50400/3~/50
Operating range, cooling°C
Operating range, heating°C
+5 to +50
+5 to +24
7)
7)
Air flow rate, max.m³/h200027004000
Enclosure classIP24
Sound power level max.dB (A)636468
Sound pressure level
Refrigerant
6)
5)
dB (A)56556264
R32
Refrigerant, basic quantitykg0.871.151.502.40
CO2 equivalent
t0.590.781.011.62
Operating pressure, max.kPa4300/1700
Refrigerant, additional quantity
>5m
g/m1530
Refrigerant piping, max. lengthm25305065
Refrigerant piping, max. heightm10202530
Refrigerant connection,
liquid pipe
Refrigerant connection,
suction pipe
Dimensions:
Height / width / depth
Inches
(mm)
Inches
(mm)
3/8 (9.52)1/2 (12.7)5/8 (15.9)
1/4 (6.35)3/8 (9.52)
mm554/800/333702/845/363810/946/410
Weightkg34.733.749.481.5
EDP no.1623846162385616238661623876
5)
At distance of 1 m in the open air; specified values are maximum values
6)
Contains greenhouse gas per the Kyoto protocol, GWP 675 (for further information, see chapter "Adding refrigerant")
7)
Can be expanded up to -15 °C with optional winter fan speed control
11
Page 12
D
E
B
A
C
REMKO RVD series
2.2 Unit dimensions, outdoor unit
Fig. 1: Dimensions RVD 355-1055 DC AT (all measurements in mm)
Measurements (mm)ABCDE
RVD 355-525 DC800554333514340
RVD 685 DC845702363540350
RVD 1055 DC946810410673403
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
12
Page 13
2.3 Unit dimensions, indoor unit
A
9
6
1
2
600
3
54
7
8
>290
260
>2000
4
545
570
647
523
570
647
B
6
1
2
880
3
54
7
8
>275
245
>2000
94
780
840
950
680
840
950
Fig. 2: Dimensions (all measurements in mm)
A: RVD 355-525 DC
B: RVD 685-1055 DC
1: Ceiling
2: Suspended ceiling
3: Floor
5: Injection pipe connection
6: Ceiling cut-out
7: Unit trim
8: Suction pipe connection
9: Refrigerant piping connections
4: Condensate drainage connection
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
13
Page 14
1
7
8
9
B
A
4
3
5
6
2
3
M
M
TE
PSH
T1
T2
T
3
T5
P
S
L
M1
M3
T2
T3
T4
T5
M2
PSL
PSH
T1
V1
EEV
FLT
1
B
A
REMKO RVD series
3 Design and function
3.1 Unit description
The RVD 355-1055 DC room air conditioners have
a REMKO RVD...AT outdoor unit as well as an
RVD...IT indoor unit.
In cooling mode, the outdoor unit serves to output
the heat extracted by the indoor unit from the room
being cooled. In heating mode, the heat taken up
by the outdoor unit can be discharged by the
indoor unit into the room to be heated. In both
operating modes, the output produced by the compressor precisely matches requirements, and
thereby regulates the nominal temperature with
minimal temperature deviations. This "inverter
technology" results in energy savings over conventional split systems and also reduces noise emissions to a particularly low level. The outdoor unit
can be installed in an outdoor area or, providing
that certain requirements are met, an indoor area.
The outdoor unit consists of a cooling cycle with
compressor, fin condenser, condenser fan,
reversing valve and throttle element. The outdoor
unit is controlled by the regulation of the indoor
unit.
The indoor unit is designed for indoor areas, for
suspended ceilings with Euroraster dimensions.
The cassette is hidden behind the suspended
ceiling, only its cover is visible. It is operated by an
infrared remote control. The indoor unit consists of
a fin evaporator, evaporator fan, regulation system
and condensate tray with condensate pump.
Floor consoles, wall consoles, refrigerant piping
and winter fan speed control are available as
accessories.
Fig. 3: System layout RVD 355-1055 DC
A: Outdoor area
B: Indoor area
1: Indoor units
2: Outdoor unit
3: Condensate drainage line
4: Condenser fan
5: Power supply
6: Shut-off valve
7: Suction pipe
8: Injection pipe
9: Control lines
Refrigerant piping is used to connect the indoor
unit to the outdoor unit.
Fig. 4: Cooling cycle schematic RVD 355-1055 DC
A:Outdoor area
B:Indoor area
1:RVD 355-1055 DC
M1:Condenser fan
M2:Compressor
M3:Evaporator fan IT
V1:Changeover valve C/H
EEV: Elec. Expansion valve
FLT:Filter
OEL: Oil return line
PSH: High pressure switch AT
PSL: Low pressure switch AT
T1:Probe, heat gas AT
T2:Probe, air inlet AT
T3:Probe, condenser AT
T4:Probe, air inlet IT
T5:Probe, evaporator IT
14
Page 15
max. 6 m
4 Operation
4.1 General notes
The indoor unit is easily operated using the
standard infrared remote control. The indoor unit
beeps to acknowledge the correct transmission of
data. If it is not possible to program the indoor unit
with the remote control, then it can also be manually operated. The indoor unit can also be operated via an optional cabled remote control.
Manual mode
The indoor units can be put into operation man-
. Press the MANUAL key on the cover's
ually
receiver unit to first activate automatic mode and
then test mode. Pressing the button a third time
switches the unit off. Pressing the button again
switches back to automatic mode.
The following settings apply for manual operation:
Cooling mode: 24 °C, fan speed: AUTO
Test mode: 30 minutes cooling, high fan speed, the
IR remote control is deactivated, after 30 minutes
the unit changes over to automatic mode
Infrared remote control
The infrared remote control sends the programmed
settings a distance of up to 6 m to the receiver of
the indoor unit. Data will only be received correctly
if the remote control is pointed at the receiver and
no objects are obstructing the transmission path.
Two AAA batteries must be inserted into the
remote control in preparation. To do so, remove
the flap from the battery compartment and insert
the batteries the correct way around (see markings). Removing the batteries causes all stored
data to be lost. The remote control will then access
the default settings, which you are free to customise at any time.
Fig. 5: Maximum distance
NOTICE!
Immediately replace flat batteries with a new
set, otherwise there is a risk of leakage. It is
recommended that the batteries are removed if
the equipment is shut down for longer periods.
15
Page 16
A
B
13 5
2
46
1
3
5
7
2
4
6
FUNC
REMKO RVD series
Wired remote control
Connection of an optional wired remote control
The plug for connection of a wired remote control
is located at the panel of the ceiling cassette (s.
Fig. 6, [A]). The 5-core cable, coming from the display panel, is marked with the designations A-E (s.
Fig. 6, [B]).
4.2 Display on indoor unit
Display on indoor unit RVD 355-525 DC
The LED indicators illuminate to indicate the settings:
OPERA
TIMER LED yellow = timer programmed
DEF/FAN LED red = defrosting active/recirculation
mode
ALARM LED red = alarm present
Fig. 7: Display on the unit RVD 355-525 DC
1: Unit for receiving signals from the remote con-
Activation of the turbo function makes it possible to
reach the setpoint in cooling or heating mode as
fast as possible.
“SELF CLEAN” key (no function)
“ARROW UP” and “ARROW DOWN” keys
“ARROW UP” key
Press the key in order to increase the setpoint in 1
°C steps to a maximum 30°C.
“ARROW DOWN” key
Press the key in order to reduce the setpoint in 1°C
steps to a minimum 17°C.
“SILENCE/FP” key (no function)
Fig. 9: Keys on the remote control
"ON/OFF" key
Press this key to switch the air conditioning unit on
f.
and of
Operating mode selection
This key is used to set the desired operating mode.
The automatic, cooling, dehumidification, heating
and recirculation modes are available.
Fan speed
Use this key to select the desired fan speed. The
automatic, low, medium and high functions are
available. Note: In the dehumidification mode, the
fan speed cannot be set manually.
"SLEEP" key
Activates/deactivates the "SLEEP" function.
Pressing this key will automatically increase or
decrease the target temperature by 1 °C within an
hour in cooling and heating mode respectively
Press this key to maintain the most convenient
temperature and save energy. This function is only
available in "Cooling", "Heating" and "Auto" modes.
If the unit is working in "SLEEP" mode, this activity
is interrupted by pressing the "MODE", "FAN",
"Speed" or "ON/OFF" keys.
"TIMER ON" key
Press this key to activate the unit start delay time.
Each press of this key increases the delay time by
30 minutes. When the set time on the display
exceeds 10.0, each press of the button increases
the set time by 60 minutes. T
o deactivate the delay
time, set the time to 0.0.
"TIMER OFF" key
This key can be used to program the delayed
switch-of
f time. Each press of this key increases
the switch-off time by 30 minutes. When the set
time on the display exceeds 10.0, each press of
the button increases the set time by 60 minutes. To
deactivate the switch-off time, set the time to 0.0.
Swing mode
Press this key to start or stop the swing mode.
With the 2-point key
, you can change the fin set-
tings on the left side. The right key has no function.
Press this key once to change the angle by 6
degrees. Pressing the key for 2 seconds stops the
swing function.
.
17
Page 18
13
14
2
1
4
3
6
9
8
10
5
7
11
1312
REMKO RVD series
"FOLLOW ME" key
This key can be used to activate/deactivate the
FOLLOW ME function. In this mode, the room temperature is measured on the remote control. This
sends a signal to the indoor unit every 3 minutes. If
the remote control does not send a signal to the
indoor unit for 7 minutes, this mode is automatically deactivated.
"LED" key
This activates/deactivates the display on the indoor
unit.
Indicators on the LCD
Fig. 10: Indicators on the LCD
1:Mode indicator - shows the current operating
modes, including Auto ( ), Cooling ( ),
Dehumidification ( ), Heating ( ), Fan ()
and back to Auto ( ) mode.
2:Signal transmission symbol. This symbol
appears when signals are being transmitted
from the remote control to the indoor unit.
3:ON/OFF symbol. This symbol appears when
the "ON/OFF" key is pressed. Pressing this
key again causes the indicator to go out.
4:TIMER ON symbol. This symbol appears
when TIMER ON is switched on.
5:ECO function (not available)
6:TIMER OFF symbol. This symbol appears
when TIMER OFF is switched on.
7:Battery charge status (weak)
8:Sleep symbol. This symbol appears when the
"Sleep" function is activated. Pressing this key
again causes the indicator to go out.
9:Temperature/Timer symbol. Shows the tem-
perature setting (-17°C~30°C). If "F
AN" mode
is selected, the temperature setting is not displayed. In Timer mode, the ON and OFF settings appear for the TIMER.
10: FOLLOW ME symbol. This symbol appears
when the "Follow me" function is activated.
11: Display of ion generator active (optional)
12: Fan speed symbol. This is where the selected
fan speeds are displayed: AUTO (no indicator)
and the three fan speed settings:
(slow),
(medium) and
(fast). The fan speed is set to "Automatic"
when either "Auto" or "Dehumidification" mode
is activated.
13: Silent mode active (optional)
18
Page 19
1
3
2
1
4
2
3
The illustration of the LCD with all of the symbols present is only intended to provide a
clearer overview
. During operation, only those
symbols relevant to the respective functions
appear on the display.
Key functions
A symbol is shown on the display to indicate that
the settings are being transferred.
“Auto” mode (please observe notes!)
Make sure that the indoor unit is connected to the
power supply
, and is switched on.
The operating mode indicator on the display of the
indoor unit begins to flash.
1.Press the "MODE" key to select "Auto"
mode.
2.Press the "Arrow up/down" key to set the
desired temperature. The temperature can
be set between 17 and 30°C, in increments
of 1°C.
3.Press the "ON/OFF" key to switch on the air
conditioning unit.
"Cooling", "Heating" and "Recirculation" mode
Make sure that the indoor unit is connected to the
power supply
, and is switched on.
1.Press the "MODE" key to select from operating modes "Cooling", "Heating" or "Recirculation".
2.Press the "Arrow up/down" key to set the
desired temperature. The temperature can
be set between 17 and 30°C, in increments
of 1°C.
3.Press the "F
AN" key to select from the four
fan speeds (Auto, slow, medium and fast).
4.Press the "ON/OFF" key to switch on the air
conditioning unit.
Fig. 11: "Auto" mode
Fig. 12: "Cooling", "Heating" and "Recirculation"
mode
19
Page 20
1
3
2
2
1
REMKO RVD series
"Dehumidification" mode
Make sure that the indoor unit is connected to the
power supply
The operating mode indicator on the display of the
indoor unit begins to flash.
1.Press the "MODE" key to select "Dehumidification" mode.
2.The temperature setting on the remote control has no ef
3.Press the "ON/OFF" key to switch on the air
conditioning unit.
, and is switched on.
fect on unit operation.
"Timer" mode
Press the "TIMER ON" key to set the "switch-on
time" and the "TIMER OFF" key to set the "switchof
f" time for the unit.
Setting the “switch-on time”
1.Press the "TIMER ON" key
trol shows "TIMER ON", the last "switch-on
time" setting and the symbol "H" appear on
the display. The unit is now ready to reset the
"switch-on time" and to start "TIMER ON"
mode.
2.Press the "TIMER ON" key again to set the
desired "switch-on time". Each time the key
is pressed, the time is increased by half an
hour between 0 and 10 hours, and by an
hour between 10 and 24 hours.
3.Once these settings have been made, there
is a one second delay before the remote control transmits the signal to the indoor unit.
Then, after approx. two seconds, the "H"
symbol disappears from the LCD display
the set temperature appears again on the
display.
. The remote con-
, and
Fig. 13: "Dehumidification" mode
In the “Dehumidification” mode, manual selection of the fan speed is not possible! Please
note that temperature pre-selection is not possible and the dehumidified room can cool dramatically!
Fig. 14: "Timer" mode
20
Page 21
Start
Off
2 hours laterSet time
Stop
On
4 hours laterSet time
Setting the “switch-off time”
1.Press the "TIMER OFF" key
. The remote
control shows "TIMER OFF", the last "switchoff time" setting and the symbol "H" appear
on the display. The unit is now ready to reset
the "switch-off time" and to stop "TIMER
OFF" mode.
2.Press the "TIMER OFF" key again to set the
desired "switch-of
f time". Each time the key
is pressed, the time is increased by half an
hour between 0 and 10 hours, and by an
hour between 10 and 24 hours.
3.Once these settings have been made, there
is a one second delay before the remote control transmits the signal to the indoor unit.
Then, after approx. two seconds, the "H"
symbol disappears from the LCD display
, and
the set temperature appears again on the
display.
–When T
imer mode is selected, the remote
control automatically transfers the timer
signal to the indoor unit for the specified
period of time. Therefore, you should hold
the remote control in a location where it can
transfer the signal to the indoor unit without
interference.
–The effective operation for the time settings
by the remote control for the timer function
is restricted to the following settings:
. The last operating time setting for the timer, and the "H"
symbols, appear on the display.
2.Press the "TIMER ON" key until the desired
start time is shown in the "TIMER ON" area
on the remote control.
3.W
ait for 3 seconds and the temperature
appears again in this area of the digital display. The "TIMER ON" indicator stays lit, and
this function is activated.
Fig. 15: "TIMER ON" example
"TIMER OFF" (Auto off mode)
Example:
ou want the air conditioning unit to switch off 4
Y
hours from the time it was programmed.
1.Press the "TIMER OFF" key
. The last operating time setting for the timer, and the "H"
symbols, appear on the display.
2.Press the "TIMER OFF" key until "10H" is
shown in the "TIMER OFF" area on the
remote control.
3.W
ait for 3 seconds and the temperature
appears again in this area of the digital display. The "TIMER OFF" indicator stays lit,
and this function is activated.
Fig. 16: "TIMER OFF" example
21
Page 22
On
Set time
Stop
Start
2 hours later
after setting
10 hours later
after setting
Off
Set time
Stop
Start
2 hours later
after setting
5 hours later
after setting
REMKO RVD series
Combined TIMER (setting "TIMER ON" and
"TIMER OFF" at the same time)
"TIMER OFF ð "TIMER ON"
(On ð Stop ð Start)
Example:
Y
ou want the air conditioning unit to switch off in
two hours from the time it was programmed, and
switch back on ten hours later.
1.Press the "TIMER OFF" key.
2.Press the "TIMER OFF" key again until the
desired stop time is shown in the "TIMER
OFF" area on the remote control.
3.Press the "TIMER ON" key.
4.Press the "TIMER ON" key again until "10H"
is shown in the "TIMER ON" area on the
remote control.
5.Wait for 3 seconds and the temperature
appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF"
indicators stay lit, and this function is activated.
"TIMER ON ð
"TIMER OFF"
(Off ð Start ð Stop)
Example:
You want the air conditioning unit to switch on in
two hours from the time it was programmed, and
switch back off five hours later.
1.Press the "TIMER ON" key.
2.Press the "TIMER ON" key again until "2.0H"
is shown in the "TIMER ON" area on the
remote control.
3.Press the "TIMER OFF" key.
4.Press the "TIMER OFF" key again until
"5.0H" is shown in the "TIMER OFF" area on
the remote control.
5.Wait for 3 seconds and the temperature
appears again in this area of the digital display. The "TIMER ON" and "TIMER OFF"
indicators stay lit, and this function is activated.
Fig. 17: "TIMER OFF" / "TIMER ON" example
Fig. 18: "TIMER ON" / "TIMER OFF" example
22
Page 23
5 Installation instructions for qualified personnel
215
34
5.1 Important notes prior to installation
ransport the unit in its original packaging as
n T
close as possible to the installation location.
You avoid transport damage by doing so.
n Check the contents of the packaging for com-
pleteness and check the unit for visible transport damage. Report any damage immediately
to your contractual partner and the shipping
company.
n Lift the unit on the corners and not on the
refrigerant or condensate drainage connections.
n The refrigerant piping (injection and suction
pipe), valves and connections must be insulated against vapour density. If necessary also
insulate the condensate drainage line.
n Select an installation location which allows air
to freely flow through the air inlet and outlet
(see section "Minimum clearances").
n Do not install the unit in the immediate vicinity
of devices which generate intensive thermal
radiation. Installation in the vicinity of thermal
radiation reduces the unit output.
n Only open the shut-off valves on the refrigerant
piping after installation is complete.
n Seal off open refrigerant piping with suitable
caps or adhesive strips to prevent the infiltration of moisture and never kink or compress
the refrigerant piping.
n Avoid unnecessary bends. This minimises the
pressure loss in the refrigerant piping and
ensures that the compressor oil can flow back
without obstruction.
n Use the fastening materials provided in the
scope of supply for the units. .
n Use four supports and the associated hooks to
attach the ceiling cassette.
n Use the insulated condensate hose in the
scope of delivery as a junction piece to the
continuing condensate drain. Secure the condensate drain with the supplied clamps.
5.2 Wall openings
n A wall opening of at least 70mm diameter and
10mm incline from the inside to the outside
must be created.
o prevent damage to the lines, the interior of
n T
the wall opening should be padded or, for
example, lined with PVC pipe (see figure).
n After installation has been completed, use a
suitable sealing compound to close off the wall
opening, taking account of fire protection regulations (responsibility of customer). Do not use
cement or lime containing substances!
Fig. 19: Wall opening
1: Liquid line
2: Control line
3: Condensate drainage line
4: Suction pipe
5: PVC pipe
5.3 Installation materials
The indoor unit is attached using 4 threaded rods
provided by the customer
The outdoor unit is attached by 4 screws and a
wall bracket to the wall or fixed by a floor bracket to
the ground.
.
23
Page 24
1
20 cm
1
REMKO RVD series
5.4 Selection of installation
location
Indoor unit
The indoor unit is designed for horizontal ceiling
installation. The minimum distance from the floor
should be 2 metres.
Outdoor unit
The outdoor unit is designed for horizontal installation on a base in outdoor areas. The installation
site must be level, flat and firm. The unit should
also be secured to prevent it from tipping over
outdoor unit can be set up outside as well as inside
a building. For external installation, please observe
the following notes to protect the unit from the
influence of the weather.
Rain
The unit should be at least 10 cm off the ground
when mounted on the roof or ground. A floor
bracket is available as an accessory.
Sun
The condenser on the outdoor unit emits heat.
Exposure to sunlight further increases the temperature of the fins and reduces the heat released by
the finned heat exchanger. The outdoor unit should
be installed on to the north side of the building
whenever possible. If necessary, take measures to
provide sufficient shade (responsibility of customer). This could be a small roof. However, the
discharging warm air flow must not be affected by
the measures.
. The
Wind
If the unit is being installed in windy areas, ensure
that the warm outlet air is discharged in the prevailing wind direction. If this is not the possible, it
may be necessary to install a windbreak (to be provided by the customer). Ensure that the windbreak
does not adversely affect the air intake to the unit.
Additional stabilisation is recommended. This can
be realised with wire ropes or other constructions.
Fig. 20: Windbreak
1: Wind
Snow
The unit should be wall-mounted in areas of heavy
snowfall. Installation should be at least 20 cm
above the expected level of snow to prevent snow
from entering the outdoor unit. An optional wall
bracket is available as an accessory
.
Fig. 21: Minimum clearance to snow
1: Snow
24
Page 25
2
1
K
3
W
3
1000
1000
E
C
B
A
D
2
1
1000
1000
1000
ITAT
Installation inside buildings
n Ensure that heat can dissipate adequately
when placing the outdoor unit in cellars, lofts,
adjoining rooms or halls (
Fig. 22).
n Install an additional fan with a rated flow com-
parative to that of the outdoor unit being
installed in the room and which can compensate any additional pressure loss in ventilation
ducts (Fig. 22).
n Comply with any regulations and conditions
fecting the statics of the building. If neces-
af
sary, fit acoustic installation.
Fig. 22: Installation inside buildings
K: Cold fresh air
W: Warm air
2: Additional fan
3: Air shaft
1: Outdoor unit
5.5 Minimum clearances
Observe the minimum clearances to allow access for maintenance and repair work and facilitate optimum air
distribution.
Fig. 23: Minimum clearances, indoor unit and outdoor unit (all measurements in mm)
AT: Outdoor unit / IT: Indoor unit1:Air inlet / 2: Air outlet
ABCDE
RVD 355-1055 DC3002000600300600
25
Page 26
1
A
B
2
A
B
REMKO RVD series
5.6 Oil return measures
If the outdoor unit is installed at a higher level than
the indoor unit, suitable oil return measures must
be taken. Usually
every 7 metres of height difference.
Fig. 24: Oil return measures
AT: Outdoor unit
IT: Indoor unit
1:1 x oil pump bend in suction pipe to outdoor
unit every 7 metres of height dif
radius: 50 mm
2:Max. 10-15 m
, an oil pump bend is installed for
ference,
6 Installation
6.1
Unit installation
NOTICE!
Installation should only be performed by authorised specialists.
The unit is mounted with the cover facing down on
four threaded rods. T
grid and any other installations.
1.Use the dimensions of the ceiling cassette to
mark the fixing points for the threaded rods
on structural parts approved to support the
static load above the suspended ceiling
(Fig. 25).
2.Fit the indoor unit onto the threaded rods and
use the lower nuts to level the unit (
3.Adhere to a ceiling clearance of at least 30
mm. Connect the refrigerant piping, electrical
cables and condensate drainage line to the
indoor unit as described below
4.Check again that the unit is level.
5.The final task is to tighten the counternuts
and attach the cover
ake into account the ceiling
Fig. 26).
.
.
Fig. 25: Hooking in the unit
Indoor units
(all dimensions in mm)
RVD 355-525 DC545523
RVD 685-1055 DC780680
Measure-
ment A
Measure-
ment B
26
Page 27
1
1
A
A
1
2
3
1
Fig. 26: Hooking in the unit
1: Structural component
Distance A
RVD 355 DC IT290 mm
Indoor units
Distance
A
Suspended
unit
RVD 355-525 DC IT23 mm545x523 mm
RVD 685-1055 DC IT
10-18
mm
780x680 mm
Fresh air connection
The unit is prepared for the intake of fresh air.
Fig. 28: Fresh air connection
1: Fresh air connection
RVD 525 DC IT290 mm
RVD 685 DC IT275 mm
NOTICE!
Only use one fresh air connection
RVD 1055 DC IT275 mm
NOTICE!
The unit is factory filled with dry nitrogen for
leak testing purposes. The pressurised nitrogen
is released when the union nuts are undone.
Fresh air connection
The unit can also be employed to suck in and regulate the temperature of fresh air (outdoor air), in
addition to room air
. This is the preferred option for
rooms with a high rate of air consumption.
n Observe the regional regulations concerning
air treatment.
Fig. 27: Fastening the unit
n Fit a collar with a nominal diameter of 65 mm
to the fresh air connection (Fig. 29
).
A: Distance A
1: Ceiling
2: Suspended ceiling
3: Unit housing
27
Page 28
AB
1
1
REMKO RVD series
Fig. 29: Fresh air connection
1: Outdoor air intake
A: Outside
B: Inside
n The fresh air content should not exceed 10% of
the nominal air flow rate for the unit. The fresh
air supply should be controlled by an additional
speed-regulated fan.
n The air at the outdoor air intake should be
sucked in through a dust filter at a maximum
rate of 2.5 m/s to prevent the ingress of rain
.
water
n The fan should be connected to a separately
protected electrical supply that is to be provided by the customer.
6.2 Connection of
refrigerant piping
The refrigerant piping connection provided by the
customer takes place on one corner of the unit,
inside the suspended ceiling. Once installed, the
connections should be insulated to make them
vapour dif
Use only tools which are approved for use in an
HV
tubing cutters, de-burrers and flaring tools). Do
not cut refrigerant pipes with a saw.
All work must be carried out in a way that prevents dirt, particles, water etc. from entering,
refrigerant lines!
A detachable connection may only be established outside the room. To connect the indoor
units, use only the supplied, non-detachable
union nuts or provide a firm connection.
fusion proof.
NOTICE!
AC environment. (z. B.: bending pliers, pipe/
NOTICE!
NOTICE!
Fig. 30: Fresh air inlet
1: Fresh air inlet
Connection of the unit panel
The unit panel is bolted onto the ceiling cassette
with the 4 screws supplied. Connect the connection cables between the unit panel and ceiling cassette together
nection cable of the swing motors must be
connected directly to the control board of the
ceiling cassette at contact CN14 (swing). A cable
with connecting plug may have been plugged in at
the factory. This must be removed for installation.
. When doing so, note that the con-
28
Page 29
The following instructions describe the installation
2
1
1
of the cooling cycle and the assembly of the indoor
unit and the outdoor unit:
1.The required pipe diameters are given in the
table "T
2.Install the indoor unit and connect the refrigerant piping as described in the operating
manual for the indoor unit.
3.Use the wall or floor brackets to fit the outdoor unit against structural parts approved to
support the static load (refer to the installation instructions for the brackets).
4.Ensure that structure-borne sound is not
transferred to parts of the building. Use vibration dampers to reduce the ef
ture-borne sound!
5.Lay the refrigerant piping from the indoor unit
to the outdoor unit. Ensure that the fastenings are adequate and if necessary
appropriate oil return measures!
6.Remove the factory-fitted protective caps and
union nuts on the connections. These should
be used later in the installation process.
7.Before flanging the refrigerant piping, ensure
that the union nut is fitted on the pipe.
8.Prepare the laid refrigerant piping as shown
below (
9.V
(Fig. 33).
10.First connect and hand-tighten the refrigerant
piping to ensure it is correctly seated.
11.Then tighten the fittings with 2 appropriatelysized open-ended spanners. Use a spanner
to counter the force when tightening the fitting (Fig. 34).
12.Use insulation hoses which are designed for
this temperature range and are dif
proof.
13.Observe the permitted bending radius for the
refrigerant piping during installation. Never
bend a pipe twice in the same place. Brittleness and cracking can result.
14.Apply appropriate heat insulation to the
installed refrigerant piping, including connector
15.T
for all subsequent refrigerant piping.
echnical data".
fects of struc-
, take
Fig. 31 and Fig. 32).
erify that the shape of the flange is correct
fusion
.
ake the same action at the shut-off valves
Fig. 31: Deburring the refrigerant piping
1: Refrigerant piping /2: Deburrer
Fig. 32: Flanging the refrigerant piping
1: Flanging tool
Fig. 33: Correct flange shape
29
Page 30
2
1
REMKO RVD series
6.3 Leak testing
Once all the connections have been established,
the pressure gauge station is attached to the corresponding Schrader valve connection as follows:
blue = large valve = suction pressure
Once the connection has been made successfully
the leak test is carried out with dry nitrogen.
Leak testing involves spraying a leak detection
spray onto the connections. If bubbles are visible,
the connections have not been made properly. In
that case, tighten the connection or, if necessary,
create a new flange.
After completing a successful leak test, the excess
pressure in the refrigerant piping is removed and a
vacuum pump with an absolute final partial pressure of min. 10 mbar is used to remove all of the
air and empty the pipes. Any moisture present in
the pipes will also be removed.
,
Fig. 34: Tightening the fitting
1: Tighten with the first open-ended spanner
2: Counter with the second open-ended spanner
Pipe dimension in
inches
1/4"15-20
3/8"33-40
1/2"50-60
5/8"65-75
3/4"95-105
Tightening torque in Nm
NOTICE!
A vacuum of at least 20 mbar must be produced!
The time required to generate the vacuum is
dependent on the final pressure pipe volume of the
indoor units and the length of the refrigerant piping.
However
minutes. Once any foreign gases and humidity
have been completely extracted from the system,
the valves on the pressure gauge station are
closed and the valves on the outdoor unit are
opened as described in the "Commissioning" section.
, the process will take at least 60
30
Page 31
6.4 Adding refrigerant
The units contain a basic quantity of refrigerant. In
addition, an additional amount of refrigerant must
be added for refrigerant piping lengths exceeding 5
metres per circuit. Refer to the following chart:
Up to and
incl. 5m
RVD 355 DC
RVD 525 DC
RVD 685 DC
RVD 1055 DC
CAUTION!
ear protective clothing when handling refrig-
W
erant.
DANGER!
Only refrigerant in a liquid state may be used to
fill the cooling cycle!
NOTICE!
Check the overheating to determine the refrigerant fill quantity
NOTICE!
The escape of refrigerant contributes to climatic
change. In the event of escape, refrigerant with
a low greenhouse potential has a lesser impact
on global warming than those with a high
greenhouse potential.
This unit contains refrigerant
potential of 675. That means the escape of 1 kg
of this refrigerant has an effect on global
warming that is 675 times greater than 1 kg
CO2, based on 100 years. Do not conduct any
work on the refrigerant circuit or dismantle the
unit - always enlist the help of qualified experts.
0 g/m
.
From 5m to
max. length
15 g/m
30 g/m
with a greenhouse
7 Condensate drainage
connection and safe
drainage
Condensate drainage connection
If the temperature falls below the dew point, condensate will form on the cooling fins during cooling
mode. A collection tray together with a condensate
pump and liquid level switch are fitted as standard
below the cooling fins. If the liquid level switch trips
a protective shutdown due to inadequate removal
of the condensate, the pump will switch on immediately and run on for approx. three minutes.
n The condensate drainage line should have an
incline of min. 2%. This is the responsibility of
the customer
proof insulation.
n If the level of the condensate drainage line on
the unit is above that of the outlet, route the
pipe vertically upwards and then with an incline
to the drain.
n Route the unit's condensate drainage line
freely into the drain line. If the condensate runs
directly into a sewer pipe, fit a trap to prevent
any unpleasant odours.
n When operating the unit at outside tempera-
tures below 4 °C, ensure the condensate
drainage line is laid to protect it against frost. If
necessary, fit a pipe heater.
n Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
Safe drainage in the event of leakages
Local regulations or environmental laws, for
example the German W
can require suitable precautions to protect against
uncontrolled drainage in case of leakage to provide
for safe disposal of escaping air conditioning fluid
or hazardous media.
NOTICE!
The max. pump pressure of the condensate
pump is 500/750 mmWS. Capacity reductions
can result from external influences such as airside counter-pressure, soiling or wear. In order
to guarantee safe functional operation, we recommend observing a maximum delivery height
of 450/700 mm!
. If necessary, fit vapour-diffusion-
ater Resource Act (WHG),
31
Page 32
A
C
B
D
16-20 mm
min. 2%
max.
500 mmWS
REMKO RVD series
NOTICE!
If condensate is removed via a duct in accordance with DIN EN 1717, ensure that any microbiological contamination present on the wastewater side (bacteria, fungi, viruses) cannot
enter the unit connected to it.
A protected power supply cable is to be connected
to the outdoor unit and a four-core control line with
a minimum cross-section of 1.5mm2. T
interference, only use shielded cable for this purpose and connect the shielding on both sides.
DANGER!
All electrical installation work is to be performed
by specialist companies. Disconnect the power
supply when connecting the electrical terminals.
NOTICE!
The electrical connection for the units must be
made at a separate feedpoint with a residual
current device in accordance with local regulations and should be laid out by an electrician.
o avoid EMC
8.2 Connecting the indoor unit
Make the connection as follows:
1.Open the air inlet grill.
2.Loosen the switch cabinet's cover (
3.Feed the voltage-free cable through the edge
protection rings on the control box and clamp
the cable in the strain relief.
4.Then connect the cable in accordance with
the wiring diagram (see chapter “Electrical
wiring diagram”).
5.Connect the electrical plugs on the cover to
the mating connectors on the cassette. It is
not possible to incorrectly connect these.
6.Re-install all disassembled parts.
Fig. 38).
e recommend using shielded wires for the
W
control lines.
e recommend that a mains/repair switch be
n W
installed near the outdoor unit.
n The terminal blocks for establishing the con-
nections are located on the side of the unit.
When the unit is installed, measurements can
be made from the front by removing the cover.
n If an optional condensate pump is used as an
accessory in conjunction with the unit, it may
be necessary to install an additional relay with
a higher contact rating after the switch-off contact on the pump to switch off the compressor.
n The control lines used should comprise
shielded wire, if laid in areas exposed to strong
magnetic fields.
Check all plugged and clamped terminals to verify that they are seated correctly and make permanent
contact. T
ighten as required.
8.3 Outdoor unit connection
Proceed as follows to connect the line:
5: Communication line to outdoor unit
6: Plastic cover
7: Cable fastening possibility
1.Remove the unit cover
2.Remove the side panel at the connection.
3.Choose the cable cross-section in accord-
ance with the relevant specifications.
4.Feed both cables through the edge protection rings on the fixed connection panel.
5.Connect the lines as shown on the electrical
connection diagram.
6.Fix the line in the strain relief and reassemble the unit.
.
34
Page 35
8.4 Electrical wiring diagram
230V/1~/50 Hz
S
PE
2(N) 1(L) W L N S
PE
2(N) 1(L) W
PE
1
A
2
B
Connection RVD 355 DC
Fig. 39: Electrical wiring diagram RVD 355 DC
A: Outdoor unit RVD 355 DC AT
B: Indoor unit RVD 355 DC IT
1Power supply
2: Communication lines
35
Page 36
AB
230V/1~/50 Hz
L N 1(L) 2(N) S L N PE
PE
S
PE
1
2
REMKO RVD series
Connection RVD 525 DC
Fig. 40: Electrical wiring diagram RVD 525 DC
A: Outdoor unit RVD 525 DC AT
B: Indoor unit RVD 525 DC IT
1Power supply
2: Communication lines
36
Page 37
Connection RVD 685 DC
230V/1~/50 Hz
L N S1
PE
S2
PE
1(L) 2(N) L N
PE
S1
S2
PE
1
A
2
B
2
Fig. 41: Electrical wiring diagram RVD 685 DC
A: Outdoor unit RVD 685 DC AT
B: Indoor unit RVD 685 DC IT
1Power supply
2: Communication lines
37
Page 38
400V/3~/50 Hz
L N S1
PE
S2
PE
L1 L2 L3 N
S1
S2
PE
(1)L
(2)N
PE
PE
1
A
2
B
2
REMKO RVD series
Connection RVD 1055 DC
Fig. 42: Electrical wiring diagram RVD 1055 DC
A: Outdoor unit RVD 1055 DC AT
B: Indoor unit RVD 1055 DC IT
1Power supply
2: Communication lines
38
Page 39
8.5 Electrical drawings
rot (braun)
blau (schwarz)
gelb
schwarz
weiss
rot
rot
braun
schwarz
CN16
CN14
XS9
XP9
CN13
10
T2
T1
CN6
4
CN8
M
CN10A
M
2
CN40
5
CN23
ON - OFF
CN33
ALARM
CN13
CN3
3
CN15
M
5
M
CN1
CN5
E Y X
CN7
T2B
P1
CN3
JR6
JR6
P3
P2
6
CN4
2
H
CH
P4
4
CN110
P5
rot
W
1(L) 2(N)
S
A
B
2
1
4
3
5
6
7
8
9
10
11
12
13
14
15
16
17
Indoor unit RVD 355 DC IT
Fig. 43: Electrical drawings RVD 355 DC IT
A: Control board
B: Display circuit board
1:DC fan motor (alternative)
2:Optional wired remote control
3:Connection of optional wired remote control
4:Potential-free alarm contact
5:External on/off
6:Connection possibility for fan motor provided by
the customer
7:Transformer
8:Temperature probe, suction pipe
9:Temperature probe, evaporator
10: Temperature probe, indoor air
11: Swing motor
12: Connecting line to the outdoor unit
13: MCC-1 controller connection
14: DC fan motor
15: Condensate pump
16: Condensate pump liquid level switch
17: AC fan motor
39
Page 40
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
ON
1
ON
1
ON
1
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
REMKO RVD series
DIP switch setting possibilities
Address assignment MCC-1 (S2+S1)
Switch
S2 + S1
Address0~1516~31
Factory
setting
3
S2 + S1
Address32~4748~63
Factory
setting
Anti-cold air function (SW1)
SwitchSW1
Factory
setting
Automatic restart after power failure (SW3)
SwitchSW3Value
Factory
setting
Automatic
restart in
ON
Setting
last oper-
ating
mode
3
No auto-
matic
restart
Mode priority (SW5)
SwitchSW5
ON
Setting
ValueHeating Heating Cooling Cooling
Factory
setting
3
Fan motor
stop temperature
24
15
8
After EEPROM
programming
Fan behaviour without demand (SW2)
SwitchSW2Value
Fan OFF
ON
Setting
Fan ON
3
Factory
setting
3
Temperature compensation (SW6)
SwitchSW6
ON
Setting
Value642
Factory
setting
3
40
Page 41
Indoor units RVD 525-1055 DC
CN16
CN14
XS9
XS10
CN55
CN66
XS2
XP2
XS2
XP2
CN13
10
CN6
4
CN8
M
CN10(CN10A)
M
2
CN40
4
CN23
ON - OFF
CN33
ALARM
CN13
CN3
3
CN15
M
5
5
M
CN1
L
N
CN5
CN2
Q E P
CN7
P1
CN3
JR6
JR6
FAN1
CAP1
P3
CH
P2
H
4
6
CN4
S2
S1
N
P4
E Y X
CN1
SWING
MOTOR
XP9
XP10
T2
T1
T2B
5
SWING
MOTOR
schwarz
weiss
rot (braun)
blau (schwarz)
schwarz
braun
rot
rot
A
B
2
1
4
3
5
6
7
8
9
10
11
12
13
14
15
16
17
19
3
Fig. 44: Electrical drawings RVD 525-1055 DC
A: Control board
B: Display circuit board
1:DC fan motor (alternative)
2:Connection of optional wired remote control
3:Swing motors
4:Connection possibility for fan motor provided by
the customer
5:Condensate pump
6:Optional wired remote control
7:Temperature probe, suction pipe
8:Temperature probe, evaporator
9:Temperature probe, indoor air
10: Condensate pump liquid level switch
11: Power supply
12: Communication line to outdoor unit
13: MCC-1 controller connection possibility
14: DC fan motor
15: Transformer
16: External on/off
17: Potential-free alarm contact
41
Page 42
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
0
8
4
1
2
3
5
6
7
C
9
A
B
D
E
F
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
ON
1
ON
1
ON
1
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
ON
1
2
REMKO RVD series
DIP switch setting possibilities
Address assignment MCC-1 (S2+S1)
Switch
S2 + S1
Address0~1516~31
Factory
setting
3
S2 + S1
Address32~4748~63
Factory
setting
Anti-cold air function (SW1)
SwitchSW1
Fan motor
stop temperature
Factory
setting
Automatic restart after power failure (SW3)
SwitchSW3Value
Factory
setting
Automatic
restart in
ON
Setting
last oper-
ating
mode
3
No auto-
matic
restart
Main / slave setting (SW5)
SwitchSW5
ON
Setting
ValueMAIN
MAINMAINSLAVE
NO
SLA
VE
setting
Factory
3
24
15
8
After EEPROM
programming
Fan behaviour without demand (SW2)
SwitchSW2Value
Fan OFF
ON
Setting
Fan ON
3
Factory
setting
3
Temperature compensation (SW6)
SwitchSW6
ON
Setting
Value642
Factory
setting
3
Power setting (ENC1)
ENC1
Switch
no.
Power [W]Switch
no.
Power [W]
44000-530089100-10500
55400-7100912000-14000
6-A14500-16000
77500-9000
42
Page 43
Outdoor unit RVD 355 DC AT
A
2
1
4
3
5
6
7
8
9
10
111213
gelb o. schwarz
blau
braun
grün/gelb
blau o. schwarz
rot
grün/gelb grün/gelb
grün/gelb
grün/gelb
blau
rot
schwarz
CN 7
3
5/6
CN 31
5
3
CN 25
CN 15
CN 60
CN 17
2(N)
1(L)
CN 21
CN 1A
CN 50
3
U
V
W
SLN
W
Fig. 45: Electrical drawings RVD 355 DC AT
A: Control board
1:Compressor
2:To indoor unit
3:Power supply
4:4-way reversing valve
5:Crankcase heating
6:Condensate tray heating
7:Condenser
8:AC fan motor
9:Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line
43
Page 44
CN 7
3
5/6
CN 31
CN 15
CN 60
CN 17
L
S
N
CN 21
CN 1A
CN 50
3
U
V
W
5
3
CN 25
S(2)
N(B)
CN 2
CN 7
CN 1-3
CN 1-1
CN 1-2
VALVE-B
N
L
L(B)
S(1)
N(A)
L(A)
S(A)
S(B)
schwarz
blau
braun
grün/gelb
grün/gelb
grün/gelb
grün/gelb
blauschwarz
rot
A
B
2
1
4
3
5
6
7
8
9
10
111213
REMKO RVD series
Outdoor unit RVD 525 DC AT
Fig. 46: Electrical drawings RVD 525 DC AT
A: Control board
B: Auxiliary circuit board
1:Compressor
2:Communication line to indoor unit
3:Supply line to indoor unit
4:Power supply
5:4-way reversing valve
6:Crankcase heating
7:Condensate tray heating
8:AC fan motor
9:Electronic E-valve
10: DC fan motor
11: Air inlet temperature probe
12: Temperature probe for condenser outlet
13: Temperature probe for heat gas line
44
Page 45
Outdoor unit RVD 685 DC AT
CN1
U(R)
V(S)
W(C)
U
V
W
CN7
VALVE-A
CN17
T4
T3
P-1
CN18
COM(3)
RY2
ON(4)
CN29
CN21
CN14
CN12
4
CN4
CN5
~
~
5
L-OUT
CN6
CN5
HEAT1
CN1
CN2
4-WAY
CN9
CN8
HEAT2
CN2
CN3
P2
P1
CN14
3
3
6
L-IN
N-IN
CN28
CN3
CN4
XT2
S1
S2
XT1
L
N
L
N
2)(1
( )
grün/gelb
grün/gelb
rot
schwarz
rot
schwarz
gelbgrau
rot
gelb
rot (braun)
blau
blaublau
A
B
2
1
4
3
5
6
78
9
10
1112
13
14
15
Fig. 47: Electrical drawings RVD 685 DC AT
A: Control board
B: Inverter board
1:Klixon
2:Low pressure switch
3:High pressure switch
4:Air inlet temperature probe
5:Temperature probe for condenser outlet
6:Temperature probe for heat gas line
7:Condensate tray heating
8:Crankcase heating
9:4-way reversing valve
10: Communication line to indoor unit
11: Power supply
12: Supply line to indoor unit
13: DC fan motor
14: Compressor
15: Transformer
45
Page 46
U
V
W
SV
L-PRO
T3
T4
H-PRO
TP
~
HEAT_D
HEAT_Y
PE3
CAP1
CN5
CN5 CN6 CN7
M
CN1
CN3
CN4
CN2
CN8CN6
PE1
6
5
N
L1
L2
L3
PE2
CN4CN1
L1’
L2’ L3’
CN2
CN3
CN20CN43
CN30
CN31
5
CN17
CN28
CN16
CN27
CN16
CN15
CN26
CN25
CN24
CN22
2
2
CN10
CN9
CN8
CN21
FM1
CN13
CN3
3
7
2
CN11
CN7
CN4CN1
6
XT1
XT2
Y/G
2
L3L2L1N
S1
S2
(
(
1
L
(
(
2
N
CN35
CN34
V
U
W
CH5
weiss
blau
rot
blau
rot
schwarz
blau
rot
schwarz
blau
blau
blau
blau
blau
weiss
blau
rot
weiss
blau
rot
grün/gelbgrün/gelb
schwarz
rot
weiss
blau
schwarz
blau
weiss
rot
blau
rot
grau
gelb
gelb
blau
blau
rot
orange
orange
orange
orange
schwarz
schwarz
A
B
2
1
4
3
5
6
7
8
9
10
11
12
13
14
15
1617
C
1
1
1
2
2
REMKO RVD series
Outdoor unit RVD 1055 DC AT
Fig. 48: Electrical drawings RVD 1055 DC AT
A: Control board
B: Inverter board
C: Control board DC fan motor
1:Transformer
2:Magnetic ring
3:Compressor
4:DC fan motor
5:AC fan motor
6:Crankcase heating
7:Condensate tray heating
8:4-way reversing valve
9:Electronic E-valve
10: Temperature probe for heat gas line
11: Temperature probe for condenser outlet
12: Air inlet temperature probe
13: Low pressure switch
14: High pressure switch
15: Communication line to indoor unit
16: Supply line to indoor unit
17: Power supply
46
Page 47
ON OFF
JR6
ON OFF
JR6
1
2
ON OFF
JR6
8.6 Connection of a superordinate
controller provided by the customer
Units of type RVD can be switched on and off by a
superordinate controller
potential-free contact for externally switching the
unit on and off, it is first necessary to remove the
jumper (JR6) at the indoor unit control board. The
contacts are then available.
Fig. 49: Removing the jumper
The building controller is now connected via the
two outer contacts of the plug labelled ON - OFF
the connection between the two contacts is open,
the system is in stand-by mode. The “Operation
LED” and the “Timer LED” blink alternately. The
unit can no longer be switched on using the remote
control.
. In order to utilise the
. If
If the connection between the two contacts is
closed, the unit is reactivated and switches to the
last operating mode used.
Fig. 51: Closed contact
2: Operation
Fig. 50: Open contact
1: Stand-By
47
Page 48
REMKO RVD series
9 Before commissioning
After leak testing has been successfully completed, connect the vacuum pump via the pressure
gauge station to the valve connections on the outdoor unit (see chapter "Leak testing") and create a
vacuum.
Perform the following checks prior to putting the
unit into operation for the first time and after any
work on the cooling cycle. Record the results in the
commissioning report:
n Check all refrigerant piping and valves for leak-
tightness using leak detection spray or soapy
water
.
n Check the refrigerant piping and insulation for
damage.
n Check the electrical connection between the
indoor unit and the outdoor unit for correct
polarity.
n Check that all fastenings, mountings, etc. are
firm and at the correct level.
10 Commissioning
NOTICE!
Commissioning should only be performed by
specially trained personnel and documented
after the certificate has been issued. Observe
the operating manuals for the indoor unit and
outdoor unit when commissioning the entire
system.
Once all the components have been connected
and tested, the system can be put into operation. A
functional check should be performed to verify its
correct function and identify any unusual operating
behaviour prior to handing it over to the operator
NOTICE!
Check that the shut-of
are tight after carrying out any work on the
cooling cycle. Use appropriate sealant products
as necessary.
Functional checks and test run
Check the following points:
f valves and valve caps
.
n Leak-tightness of the refrigerant piping.
n Compressor and fan running smoothly.
n In cooling mode, cold air output by the indoor
unit, and warm air output by the outdoor unit.
n Function test of the indoor unit and all program
sequences.
n Check of the surface temperature of the suc-
tion pipe and that the vaporiser is not overheating. To measure the temperature, hold the
thermometer to the suction pipe and subtract
the boiling point temperature reading on the
pressure gauge from the measured temperature.
n Record the measured temperatures in the
commissioning report.
48
Page 49
Function test of the cooling and heating modes
1.Remove the protective caps from the valves.
2.Start the commissioning procedure by briefly
opening the shut-of
unit until the pressure gauge indicates a
pressure of approx. 2 bar.
3.Check all connections for leaks with leak
detection spray and suitable leak detectors.
4.If no leaks are found, fully open the shut-of
valves by turning them anti-clockwise using a
spanner. If leaks are found, remedy the faulty
connection. It is imperative that the vacuum
creation and drying steps are repeated.
5.Activate the main circuit breaker or fuse.
6.Use the remote control to switch on the unit
and select the cooling mode, maximum fan
speed and lowest target temperature.
7.Check the overheating, outside, inside, outlet
and vaporisation temperatures and record
the measured values in the commissioning
report. Check the correct function and settings of all regulation, control and safety
devices.
8.Check the unit control system using the func-
tions described in the chapter "Operation".
T
imer, temperature setting, fan speeds and
switching to ventilation or dehumidification
mode.
9.Check the correct function of the condensate
drainage line by pouring distilled water into
the condensate tray
recommended for pouring the water into the
condensate tray.
10.Switch the indoor unit to heating mode.
11.During the test run, check the functionality of
all of the previously described safety devices.
12.Record the measured values into the commissioning report and familiarise the operator
with the system.
13.Remove the pressure gauge. Check that
seals have been fitted in the sealing caps.
14.Re-install all disassembled parts.
f valves on the outdoor
f
. A bottle with a spout is
11 Shutdown
Temporary shutdown
1.Let the indoor unit run for 2 to 3 hours in
recirculation mode, or in cooling mode at
maximum temperature, to extract any
residual humidity from the unit.
2.Shut down the system using the remote control.
3.Switch of
unit.
4.Cover the unit as far as possible with plastic
foil in order to protect it from the influences of
weather
Permanent shutdown
Ensure that units and components are disposed of
in accordance with local regulations, e.g. through
authorised disposal and recycling specialists or at
collection points.
REMKO GmbH & Co. KG or your contractual
partner will be pleased to provide a list of certified
firms in your area.
f the electrical power supply to the
.
49
Page 50
REMKO RVD series
12 Troubleshooting, customer service and fault analysis
12.1 Troubleshooting and customer service
The unit and components are manufactured using state-of-the-art production methods and tested several
times to verify their correct function. However
detailed in the list below. For systems with an indoor unit and outdoor unit, refer to the chapter "Troubleshooting and customer service" in both operating manuals. Please inform your dealer if the unit is still not
working correctly after all function checks have been performed!
Operational malfunctions
MalfunctionPossible causesChecksRemedial measures
, if malfunctions should occur, please check the functions as
The unit does not start or
switches itself of
f
Power failure, undervoltage, defective mains
fuse / main switch in
OFF position
Damaged power supplyDoes all other elec.
Wait time after switching
on is too short
Temperature outside
operating range
Electrical surges caused
by thunderstorms
Malfunction of the
external condensate
pump
High-pressure / low-pressure switches have triggered
Does all other electrical
equipment function correctly?
equipment function correctly?
Have approx. 5 minutes
elapsed since the
restart?
Are the fans in the indoor
unit and outdoor unit
working correctly?
Have there been lightning strikes in the area
recently?
Has the pump shut down
due to a malfunction?
Check refrigerant pressure and look for leaks if
necessary
Check the voltage and if
necessary
come back on
Repair by specialist firm
Schedule longer wait
times
Observe temperature
ranges of indoor unit and
outdoor unit
Switch off the mains
breaker and switch it
back on. Have it
inspected by a specialist
Check and if necessary
clean the pump
Rectify leakage and restart
, wait for it to
The unit does not
respond to the remote
control
Transmission distance
too far / receiver af
by interference
Defective remote controlIs the unit running in
Receiver or transmitter
unit exposed to excessive solar radiation
Electromagnetic fields
are interfering with transmission
Key in remote control
jammed / two buttons
pressed at same time
Batteries in remote control are flat
fected
Does the indoor unit
beep when pressing a
key?
manual mode?
Does it function correctly
in the shade?
Does it function after
removing potential
sources of interference?
Does the “Transmitting”
symbol appear on the
display?
Have new batteries been
inserted? Is the display
incomplete?
Reduce the distance to
less than 6 m or change
position
Replace the remote control
Place the receiver and/or
transmitter unit in the
shade
Signal is not transmitted
when interference
sources are operational
Release the key / only
press one key
Insert new batteries
50
Page 51
MalfunctionPossible causesChecksRemedial measures
The unit is running but
only provides reduced or
no cooling or heating
capacity
Filter is dirty / air inlet /
outlet opening is blocked
by debris
Windows and doors
open. Heating / cooling
load has increased
Neither cooling nor
heating mode has been
set
Fins on outdoor unit
blocked by foreign
objects
Leaking cooling cycleAre there signs of frost
Outdoor unit iced upCheck outdoor unit. Has
Drainage pipe on collection container clogged /
damaged
Have the filters been
cleaned?
Have structural / usage
modifications been
made?
Does the cooling symbol
appear on the display?
Is the fan on the outdoor
component running? Are
the fins unobstructed?
on the exchanger fins of
the indoor unit?
the cassette probe on
the outdoor unit been
correctly positioned?
Can the condensate
drain of
obstruction?
f without any
Clean the filters
Close windows and
doors / install additional
units
Correct the settings for
the unit
Check the fan or winter
fan speed control,
reduce the air resistance
Repair by specialist
De-ice and fit the probe
at the point where the
most ice forms
Clean the drainage pipe
and collection container
Condensate discharge
on unit
NOTE
Faulty external condensate pump or float
Condensate has not
drained away and has
collected in the condensate drainage line
Condensate does not
drain of
Float is stuck or jammed
due to excessive dirt
f
Is the collection tray full
of water and the pump
not running?
Is there an incline on the
condensate drainage
line? Check there is no
blockage in the pipe.
Are the condensate
drainage lines unblocked
and is there a steady
incline? Are the condensate pump and liquid
level switch functioning
correctly?
Are the LEDs on the
receiver unit of the
indoor unit flashing?
Call out a specialist to
replace the pump
Route the condensate
drainage line with an
incline and clean it.
Route the condensate
drainage line with an
incline and clean it. If the
liquid level switch or the
condensate pump is
defective, have them
replaced
Should be cleaned by
specialist firm
If the outdoor unit makes noises at low outside temperatures, even although it is switched off, this is not a
malfunction. This is the winding of the compressor being run briefly in order to heat up the oil within it and
also to guarantee the viscosity at low ambient temperatures. If you do not use the unit in the winter then
you can switch off the breaker
will be required!
51
. Switch it back on again at least 12 hours before the next time that the unit
Page 52
2
1
REMKO RVD series
Malfunction indicated by flashing code RVD 355-525 DC
Number
Error description
of flashes
per
second)
EEPROM error, indoor unit1OFFE0
Communication error between indoor unit and outdoor unit2OFFE1
Safety shut-down due to low outside temperature4FLASHESP3
Compressor control faulty5FLASHESP4
Mode conflict6FLASHESP5
Low pressure alarm7FLASHESP6
1)
LED [1] in the bottom figure
2)
LED [2] in the bottom figure
3)
LED [3] in the bottom figure
Fig. 53: Malfunction indicated by flashing code RVD 685-1055 DC
53
Page 54
YES
REMKO RVD series
12.2 Indoor unit fault analysis
Error code:E0 / F4
Reason:The control board of the outdoor unit or indoor unit cannot read the unit memory
(EEPROM)
Cause:
Switch off voltage, switch on again 2 minutes
later
Replace the circuit boards of the outdoor unit
and indoor unit in turn, in order to locate the
n Installation error
n Control boards of outdoor unit or indoor unit defective
. Is the error still present?
defective EEPROM
54
Page 55
Error code:E1
YES
NO
YES YES
YES
NO
NO
YES
NO
Reason:The indoor unit does not receive a signal from the outdoor unit within 110 seconds.
Cause:
Switch off voltage, switch on again 2 minutes
later
Measure the voltage between the “S” and “N”
terminals of the outdoor unit. Is the measured
Check electrical connections in the outdoor
n Electrical connection not configured correctly
n Control boards outdoor unit or indoor unit defective
. Is the error still present?
value positive?
unit. Are they OK?
Is the transformer OK?
Check electrical connections in the indoor unit.
Are they OK?
Replace the control boards of the indoor unit. Is
the fault remedied?
Replace the control boards of the outdoor unit
Replace the transformer
Replace the control boards of the outdoor unit.
Is the fault remedied?
Replace the control boards of the indoor unit
55
Page 56
NO
YES
NO
YES
NO
YES
NO
YES
NO
REMKO RVD series
Error code:E3 / F5
Reason:If the fan speed of the indoor unit/outdoor unit falls below 300 rpm, the unit switches off
and the display shows error code E3 or E5
Cause:
Switch off voltage, switch on again 2
minutes later
De-energise the unit and attempt to
turn the fan wheel by hand. Does it
Check the electrical connections.
Are these correctly implemented?
Measure the voltage at the corre-
sponding connector plug on the con-
trol board (see section
dure’ on page 57). Does the
measured voltage lie within the toler-
n Electrical connection faulty
n Evaporator fan wheel defective
n Evaporator fan motor defective
n Control board faulty
. Is the error still
present?
rotate freely?
Ä
‘Proce-
ance range?
The unit operates normally.
Check the motor and the fan
wheel bearing, and replace the
defective parts.
Correctly establish the electrical
connection
Replace the control board.
Replace the fan motor. Is the fault
remedied?
56
Page 57
Procedure
13 4 56
DC fan motor of the indoor unit (control chip is installed in the motor):
Switch on the voltage to the unit. In standby mode, measure the unit between terminals 1-3 and 4-3 of the
connector plug. Check the measured values against those listed in the table below
problem with the control board and it must be replaced.
. If these differ, there is a
Fig. 54: Motor measurements
TerminalColourVoltage
1Red280V~380 V
2------
3Black0 V
4White17-17.5V
5Yellow0~5.6V
6Blue17-17.5V
DC fan motor of the outdoor unit (control chip is installed in the motor):
Measure the resistance between terminals 1-3 and 4-3. This should be roughly identical. If the resistance
deviates significantly, assume that the motor is defective and must be replaced.
57
Page 58
YES
YES
NO YES
YES
NO
REMKO RVD series
Error code:EC
Reason:The evaporator probe T2 measures the actual value with the compressor start and takes
this as the reference value T
has not dropped by 2 °C for at least 4 seconds then the system assumes that the refrig-
erant is low
error code "EC".
. The measurement is performed a total of 3 times before the display shows the
. If, 5 minutes after the compressor start, the value T
Start
Start
Cause:
Switch off voltage, switch on again 2 minutes
later. Is the error still present?
Check whether the indoor unit blows out cold
Check the cooling circuit for leaks. Leaks
Check the cooling circuit for any blockages. Are
the shut-of
n Refrigerant low or cooling circuit blocked
n Evaporator probe T2 defective
n Indoor unit control board defective
.
air
found?
f valves on the outdoor unit open?
Check the position and function of the evapo-
rator probe T2. Is it correctly seated and with
the correct resistance?
Exchange the control boards of the indoor unit.
Remedy leaks and put the unit back into opera-
tion.
58
Page 59
Error code:E4 / E5 / F1 / F2 / F3
NO
YES
NO
YES
Reason:If the test voltage of the probes is lower than 0.06 V or higher than 4.94 V then the display
shows the error code of the corresponding probe.
Cause:
Check the connecting cable between the control board and the temperature probe. Is it OK
Check the probe for correct resistance,
depending on the temperature (see resistance
Replace the corresponding control board.
n Electrical connection faulty
n T
emperature probe defective
n Control board defective
and correctly connected?
table)
Establish a proper connection.
Replace the probe.
Fig. 55: Check the probes
59
Page 60
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RVD series
Error code:F0
Reason:Safety shutdown due to overly high current consumption of individual unit components
Cause:
Check the supply voltage. Is this correct?
Check the cooling circuit for any blockages. Is
Check the winding resistances of the com-
Check the electrical connections. Are these cor-
n Faulty power supply
n Cooling circuit blocked
n Faulty control board
n Electrical connections faulty
n Compressor defective
the cooling circuit OK?
pressor
. Are they OK?
rectly implemented?
Switch the unit off and ensure correct supply
voltage.
Remove the blockage (shut-off valve open?)
Replace the compressor.
Replace or correct the electrical connections.
Does the transformer operate fault-free?
Replace the outdoor unit.
Replace the transformer or control boards of
the outdoor unit.
60
Page 61
Error code:P0
YES
NO
YES
NO
NO
YES
NO
YES
NO
YES
Reason:If the power supply to the compressor controller is faulty, the display shows the error code
“P0” and the unit switches of
f
Cause:
Check the external enabling contact CN23 and
the jumper JR6. Are both contacts open? (See
Ä
Chapter 8.6 ‘Connection of a superordinate
controller provided by the customer ’
Check the connecting cables between the con-
trol board and compressor? Are they faulty?
Check the inverter controller (see section
Ä
‘Check the inverter controller’ on page 62).
n External enabling contact open
n Electrical connection faulty
n Faulty control board
n Condenser fan motor defective or blocked
n Compressor defective
on page 47)
Fault eliminated?
Close the external enabling contact CN23 or
the jumper JR6.
Establish a correct connection between the
control board and compressor
Replace the control board.
.
Check the condenser fan motor. Is it working
correctly?
Check the winding resistances of the com-
pressor
Exchange the control boards of the outdoor
. Are they OK?
unit.
See troubleshooting fault F5
Replace the compressor.
61
Page 62
NO
YES
NO
YES
NO
YES
NO
YES
REMKO RVD series
Check the inverter controller
Switch off the power supply to the unit. Wait until the capacitors are fully discharged and disconnect the compressor from the control board.
Check the resistances at the outputs of the control board with the aid of a digital voltmeter as follows:
VoltmeterNormal resistance
(+) Red(-) Black
U
V
W
(+) Red
Error code:P1
Reason:Overvoltage or undervoltage protection has tripped
Cause:
Check the power supply. Is the supply voltage
Check the electrical connections. Are they OK?
n Faulty supply voltage
n Refrigerant low or cooling circuit blocked
n Faulty control board
correct?
N
Switch the unit off and have the power supply
¥
(multiple MW)
checked/corrected.
Replace the electrical connections.
Switch the power on and put the unit into
standby mode. Measure the voltage on the
board, at contacts "P" and "N". This should be
approx. 310 V
the unit. The voltage between "P" and "N"
should now be between 220-400V. Is the cor-
Check the transformer. Is a defect present?
, 340 V or 380 V DC. Now start
rect voltage applied?
Replace the transformer.
Replace the control board.
Replace the control board.
62
Page 63
Error code:P2 (with units with a thermal contact)
YES
NO
YES
NO
YES
NO
YES
YES
NO
YES
Reason:If the test voltage of the thermal contact does not lie at 5 V, then the display shows the
error message “P2”
Cause:
Check the air flow
volumes of the
indoor unit and out-
door unit. Are they
blocked or dirty?
Switch off the power
supply to the unit
and switch it on
again after 10 mins.
Does the unit start
up?
Check the tempera-
ture of the com-
pressor
heated up?
n Faulty supply voltage
n Refrigerant low or cooling circuit blocked
n Faulty control board
. Has it
Clean the filter or heat exchanger and ensure a sufficient air flow volume.
Check the thermal contact. Is it correctly connected?
Measure the resistance of the thermal contact.
Is it 0?
Connect it correctly.
Check the cooling
circuit. Is it OK?
Replace the thermal
contact.
Replace the control board of the outdoor unit.
63
Page 64
YES
NO
NO
YES
NO
YES
NO
YES
1
REMKO RVD series
Error code:P4
Reason:Safety shutdown of inverter controller. Internal system monitoring triggered (e.g. communi-
cation problem between board and compressor
, the compressor speed is not OK)
Cause:
Check the electrical connection between the
control board and compressor
Check the inverter controller. Is this functional?
Check the condenser fan motor. Is it OK?
Check the winding resistances of the com-
n Faulty electrical connections
n Inverter regulation on board defective
n Condenser fan motor defective
n Compressor defective
n Control board defective
. Are these cor-
rectly implemented?
pressor
. Are they OK?
Establish a proper connection.
Replace the control board.
Follow the instructions for troubleshooting fault
F5
Replace the compressor
Replace the control boards of the outdoor unit.
Check individual components
Check the temperature probes
Disconnect the temperature probe from the control board and measure the resistance on the plug's contacts.
1: Multimeter
Error code:dF
Reason:The unit is in heating mode and the outdoor unit is being defrosted. After the defrost phase,
the indoor unit automatically switches back to the last operating mode.
64
Page 65
12.3 Resistances of the
temperature probes
Probe T1, T2, T3 and T4
Temp.
(°C)
-20115.271218.72
-19108.151317.80
-18101.521416.93
-1796.341516.12
-1689.591615.34
-1584.221714.62
-1479.311813.92
-1374.541913.26
-1270.172012.64
-1166.092112.06
-1062.282211.50
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
444.39791.21
454.21801.17
464.05811.14
473.89821.10
483.73831.06
493.59841.03
503.45851.00
513.32860.97
523.19870.94
533.07880.91
542.96890.88
552.84900.85
562.74910.83
572.64920.80
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
-958.712310.97
-856.372410.47
-752.242510.00
-649.32269.55
-546.57279.12
-444.00288.72
-341.59298.34
-239.82307.97
-137.20317.62
035.20327.29
133.33336.98
231.56346.68
329.91356.40
428.35366.13
526.88375.87
625.50385.63
582.54930.78
592.45940.75
602.36950.73
612.27960.71
622.19970.69
632.11980.67
642.04990.65
651.971000.63
661.901010.61
671.831020.59
681.771030.58
691.711040.56
701.651050.54
711.591060.53
721.541070.51
731.481080.50
724.19395.40
822.57405.18
921.81414.96
1020.72424.76
1119.69434.57
65
741.431090.48
751.391100.47
761.341110.46
771.291120.45
781.251130.43
Page 66
REMKO RVD series
Temp.
(°C)
1140.421270.30
1150.411280.29
1160.401290.28
1170.391300.28
1180.381310.27
1190.371320.26
1200.361330.26
1210.351340.25
1220.341350.25
1230.331360.24
1240.321370.23
1250.321380.23
1260.311390.22
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Temp.
(°C)
1682.545118.96
1778.795218.26
1875.245317.58
1971.865416.94
2068.665516.32
2165.625615.73
2262.735715.16
2359.985814.62
2457.375914.09
2554.896013.59
2652.536113.11
2750.286212.65
2848.146312.21
2946.116411.79
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
Probe T5
Temp.
(°C)
-20542.7-2200.7
-19511.9-1190.5
-18483.00180.9
-17455.91171.9
-16430.52163.3
-15406.73155.2
-14384.34147.6
-13363.35140.4
-12343.66133.5
-11325.17127.1
-10307.78121.0
-9291.39115.2
-8275.910109.8
-7261.411104.6
-6247.81299.69
-5234.91395.05
-4222.81490.66
-3211.41586.49
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
3044.176511.38
3142.336610.99
3240.576710.61
3338.896810.25
3437.30699.90
3535.78709.57
3634.32719.25
3732.94728.94
3831.62738.64
3930.36748.36
4029.15758.08
4128.00767.82
4226.90777.57
4325.86787.32
4424.85797.09
4523.89806.86
4622.89816.64
4722.10826.43
4821.26836.23
4920.46846.03
5019.69855.84
66
Page 67
Temp.
(°C)
865.661092.86
875.491102.78
885.321112.70
895.161122.63
905.001132.56
914.851142.49
924.701152.42
934.561162.36
944.431172.29
954.291182.23
964.171192.17
974.051202.12
983.931212.06
993.811222.01
Resistance
(kW)
Temp.
(°C)
Resistance
(kW)
1003.701231.96
1013.601241.91
1023.491251.86
1033.391261.81
1043.301271.76
1053.201281.72
1063.111291.67
1073.031301.63
1082.94
67
Page 68
REMKO RVD series
13 Care and maintenance
Regular care and observation of some basic points
will ensure trouble-free operation and a long
service life.
DANGER!
Prior to performing any work, ensure the equipment is disconnected from the voltage supply
and secured to prevent accidental switch-on!
Contact Remko GmbH & Co. KG to sign up for
a maintenance contract
Care
n Ensure that the indoor unit and outdoor unit are
free of dirt, mould and other deposits.
Type of task
Checks / maintenance / inspection
n Only clean the units with a damp cloth. Do not
use any caustic, abrasive or solvent-based
cleaning products. Do not use a jet of water
n Clean the fins on the indoor unit and outdoor
unit prior to long shutdown periods.
Maintenance
n It is recommended that you take out a mainte-
nance contract with an annual service from an
appropriate specialist firm.
n For systems which operate year-round (e.g. in
server rooms), the maintenance intervals must
be reduced accordingly
This enables you to ensure the operational reliability of the plant at all times!
Commis-
sioning
MonthlyHalf-
.
yearly
.
Yearly
General
Check voltage and current
Check function of compressor / fans
Dirt on condenser / evaporator
Check the refrigerant volume
Check condensate drainage
Check insulation
Check moving parts
Sealing test for cooling cycle
1)
see note below
Cleaning the cover on the indoor unit
1.Disconnect the power supply to the unit.
2.Open and fold down the air inlet guard on the
cover
. The filter is held in place by the flaps
screwed in at the side of the guard (Fig. 56).
3.Clean the grill and cover with a soft, damp
cloth.
4.Switch the power supply back on.
l
l
l
ll
l
l
l
l
l
Air filter for indoor unit
We recommend cleaning the air filter at intervals of
no more than 2 weeks. Reduce this interval if the
air is especially dirty
NOTICE!
Statutory regulations require an annual leak test
for the cooling cycle dependant on the refrigerant quantity. Inspection and documentation of
the work performed is to be carried out by specialist technicians.
.
l
l
l
l
l
l
l
1)
l
68
Page 69
Cleaning the filter
1.Disconnect the power supply to the unit.
2.Open and fold down the air inlet guard on the
cover
. The filter is held in place by the flaps
screwed in at the side of the guard (Fig. 56).
3.T
4.Clean the filter with a commercially available
5.Dirt can also be removed by carefully
6.If water is used, let the filter dry out properly
7.Carefully insert the filter
8.Close the cover as described above but in
9.Switch the power supply back on.
10.Switch the unit back on.
ilt the filter and lift it out (Fig. 56).
vacuum cleaner (
dirty side so it is facing upwards.
cleaning with lukewarm water and mild
cleaning agents. The dirty side should be
face down (
in the air before fitting it back into the unit.
locates correctly.
reverse order
Fig. 57). To do so, turn the
Fig. 58).
. Ensure that it
.
Fig. 57: Cleaning with a vacuum cleaner
Cleaning the condensate pump
The indoor unit includes a built-in condensate
pump for pumping the condensate to a drain at a
higher level.
The pump is more or less maintenance-free. The
condensate drainage lines should be checked for
dirt at regular intervals. Clean them as required.
If an external pump is also used, observe the
maintenance and care instructions in the separate
operating instructions.
Fig. 56: Pull out the filter
Fig. 58: Cleaning with lukewarm water
69
Page 70
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
REMKO RVD series
14 Exploded view and spare parts lists
14.1 Exploded view - Indoor unit RVD 355-525 DC
Fig. 59: Exploded view of the unit RVD 355-525 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
70
Page 71
14.2 Spare parts list - Indoor unit RVD 355-525 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Infrared remote control
2Condensate pump liquid level switch
3Condensate pump
4Condensate pump mounting plate
5Condensate hose
6Condensate connection
7Unit trim
8Display board
9Condensate tray
10Temperature probe, evaporator
11Evaporator
12Evaporator housing
TANT!
13Unit housing
14Terminal block cover
15Control board
16Temperature probe, indoor air
17Air inlet nozzle
18Fan wheel
19Fan motor
20Fan motor mounting plate
71
Page 72
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
REMKO RVD series
14.3 Exploded view - Indoor unit RVD 685-1055 DC
Fig. 60: Exploded view of the unit RVD 685-1055 DC IT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
72
Page 73
14.4 Spare parts list - Indoor unit RVD 685-1055 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Infrared remote control
2Condensate pump liquid level switch
3Condensate pump
4Condensate pump mounting plate
5Condensate hose
6Condensate connection
7Unit trim
8Display board
9Air filter
10Liquid level switch mounting plate
11Condensate tray
12Evaporator
TANT!
13Casing part, left
14Unit housing
15Casing part, front
16Temperature probe, indoor air
17Condensate tray sealing cap
18Temperature probe, evaporator
19Casing part, rear
20Casing part, right
21Control board
22Transformer
23Air inlet nozzle
24Fan wheel
25Fan motor
26Housing floor
73
Page 74
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
REMKO RVD series
15 Exploded view - Outdoor unit RVD 355 DC
Fig. 61: Exploded view of the unit RVD 355 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
74
Page 75
16 Spare parts list - Outdoor unit RVD 355 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Corner panel, left
8Condenser
9Air inlet temperature probe
10Electronic injection valve
11Shut-off valve, injection pipe
124-way reversing valve
TANT!
13Shut-off valve, suction pipe
14Partitioning panel
15Temperature probe for heat gas line
16Compressor
17Floor panel
18Side panel, right
19Refrigerant connections cover
20Terminal block cover
21Control board
22Temperature probe for condenser outlet
23Condensate tray heating
24Crankcase heating
25Mounting plate for refrigerant connections
75
Page 76
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
REMKO RVD series
17 Exploded view - Outdoor unit RVD 525 DC
Fig. 62: Exploded view of the unit RVD 525 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
76
Page 77
18 Spare parts list - Outdoor unit RVD 525 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Corner panel, left
8Condenser
9Air inlet temperature probe
10Electronic injection valve
11Shut-off valve, injection pipe
124-way reversing valve
TANT!
13Shut-off valve, suction pipe
14Partitioning panel
15Temperature probe for heat gas line
16Compressor
17Floor panel
18Side panel, right
19Refrigerant connections cover
20Control board
21Auxiliary circuit board
22Temperature probe for condenser outlet
23Condensate tray heating
24Crankcase heating
77
Page 78
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
REMKO RVD series
19 Exploded view - Outdoor unit RVD 685 DC
Fig. 63: Exploded view of the unit RVD 685 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
78
Page 79
20 Spare parts list - Outdoor unit RVD 685 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)
No. Designation
1Cover panel
2Protection grid, front wall
3Front panel
4Fan blade
5Fan motor
6Fan motor mounting plate
7Corner panel, left
8Condenser
9Air inlet temperature probe
10Electronic injection valve
11Shut-off valve, injection pipe
124-way reversing valve
TANT!
13Shut-off valve, suction pipe
14Partitioning panel
15Temperature probe for heat gas line
16Compressor
17Floor panel
18Side panel, right
19Refrigerant connections cover
20Terminal block cover
21Control board
22Inverter board
23Cooling fins
24Temperature probe for condenser outlet
25Mounting plate for refrigerant connections
26Transformer
27Condensate tray heating
28Crankcase heating
79
Page 80
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
REMKO RVD series
21 Exploded view - Outdoor unit RVD 1055 DC
Fig. 64: Exploded view of the unit RVD 1055 DC AT
We reserve the right to modify the dimensions and design as part of the ongoing technical development
process.
80
Page 81
22 Spare parts list - Outdoor unit RVD 1055 DC
IMPOR
To ensure the correct delivery of spare parts, please always the device type with the corresponding serial
number (see type plate)