Inverter ceiling-mounted air conditioner in split design
Operation · Technology · Spare parts
Issue D – V03
Contents
Safety notes
Environmental protection and recycling
warranty
Transport and packaging
Description of the equipment
Operation
Shutdown
Care and maintenance
Troubleshooting and customer service
Installation instructions for qualified personnel
Installation
Tightness check
Condensate drain
4
4
4
5
5
6-12
13
13-14
15-16
16-19
19-21
21
21
Electrical connection
Before start up
Add refrigerant
Commissioning
Electrical connection diagram
Electrical circuit diagram
Unit dimensions
Exploded view
Spare parts list
Technical data
22
22
23
23-24
25
25-26
27
28-29
28-29
30
Made by REMKO
These operating instructions should be read carefully
prior to commissioning / operation of the equipment!
These instructions are part of the equipment and must always
be kept in the vicinity of the installation or on the equipment.
Subject to modifications; No liability accepted for errors or misprints!
3
REMKO RVD...DC
Safety notes
Carefully read this manual before
starting the unit for the first time. It
contains useful tips, information as
well as hazard warnings to prevent
injury or material damage. Nonobservance of this manual may
endanger persons, the environment
as well as the equipment itself and
will void any claims for liability.
■ Store this manual as well as
the refrigerant datasheet in the
vicinity of the unit.
■ The unit should only be set up
and installed by qualified personnel.
■ The setup, connection and
operation of the unit and its
components must be in accordance with the operating conditions stipulated in this manual
and comply with all applicable
local regulations.
■ Units designed for mobile use
should be safely set up on a
suitable floor and in a vertical position. Units designed for
stationary use should only be
operated in their permanently
installed state.
■ It is prohibited to make modi-
fications or changes to equipment or components supplied
by REMKO as this may cause
malfunctions.
■ Equipment and components
should not be operated in areas
where there is a heightened
damage risk. Observe the minimum clearances.
■ The electrical supply should be
adapted to fulfil the requirements of the unit.
■ The operational safety of equip-
ment and components is only
assured providing they are used
as intended and in a fully assembled state. Safety devices should
not be modified or bypassed.
■ Do not operate equipment or
components with obvious defects or signs of damage.
■ All housing parts and openings,
e.g. air inlets and outlets, must
not be blocked by foreign items,
fluids or gases.
■ The equipment and components
must be kept in a safe distance
from inflammable, explosive,
combustible, aggressive and
dirty areas or atmospheres.
■ Persons coming into contact
with equipment parts may suffer
burns or injury.
■ Installation, repair and mainte-
nance work should only be carried out by authorised specialists. Inspection and cleaning can
be performed by the operator
providing the equipment is not
under voltage.
■ Take appropriate hazard preven-
tion measures when performing
installation, repair or maintenance work or cleaning the
equipment.
■ The equipment or components
should not be exposed to any
mechanical stresses, extreme
levels of humidity or direct exposure to sunlight.
Environmental
protection
and recycling
Disposal of packaging
All products are packed for transport in environmentally friendly
materials. Make a valuable contribution to reducing waste and
sustaining raw materials. Only
dispose of packaging at approved
collection points.
Disposal of units and
components
For the manufacture of the units
and components, only recyclable
materials have been used.
Help protect the environment by
ensuring that the units or components (for example batteries) are
not disposed in household waste,
but only in accordance with local
regulations and in an environmentally safe manner, e.g. through
authorised disposal and recycling
specialists or at collection points.
Warranty
Prerequisite for any warranty claims
is that the purchaser or his client
has completely filled out the "warranty registration card" included
with any unit within the relevant
time period of sale and initial operation and returned it to
REMKO GmbH & Co. KG.
The warranty conditions are listed
in the "General business and delivery conditions. The contractual parties can also agree additional terms
beyond the scope of the above.
For this reason please contact your
direct contracting partner first.
4
Transport and
Packaging
The equipment is shipped in sturdy
transport packaging. Immediately
check the equipment on delivery and
make a note of any damage or missing parts on the delivery note. Inform
the forwarding agent and contractual
partner. Warranty claims at a later
date will not be accepted.
Description of the
equipment
The RVD 351-521DC room air
conditioning units have a REMKO
RVD...AT outdoor component as
well as an indoor unit RVD...IT.
The outdoor unit serves to output
the heat extracted by the indoor
unit from the room being cooled.
In heating operation, the heat
absorbed by the outdoor component can be discharged through
the indoor unit into the room being
heated.SFlbIn both operating modes,
the performance of the compressor
precisely adjusts itself to the demand, thereby regulating the target
temperature with minimal temperature variations. This "inverter-technology" enables power saving over
conventional split systems and also
reduces noise emissions to a particularly low level.
The outdoor component is mounted
outdoors or under the observation of certain requirements it may
be installed indoors. The outdoor
component consists of a refrigerant
circuit with compressor, fin liquefier,
liquefier fan, reverse flow valve and
flow regulator. The outdoor unit is
controlled via the regulation of the
indoor unit.
Schematic of outdoor refrigerant circuit
Liquefier fan
Liquefier
Schematic of refrigerant circuit in indoor unit - cooling
Vaporiser
System layout
Indoor area
Interior unit
M
Condensation line
Reverse flow valve
M
Filter dryerRestrictor element exp. or capillary tube
Vaporiser fan
Compressor
Connection
Manometer
Connection
valve
Suction pipe
Connection
valve
Injection pipe
Connection to suction pipe
Connection to injection line
The indoor unit is designed for
indoor installation in suspended
ceilings with Euroraster dimensions.
The cassette is hidden behind the
suspended ceiling, only its cover is
visible. Operation is undertaken via
an infrared remote control unit. The
indoor unit consists of a fin vaporiser, vaporiser fan, regulation system
and condensation pan.
Floor consoles, wall consoles, refrigerant pipes and a winter control
program are available as accessories.
Outdoor area
Exterior unit
Condensation line
Control line
Mains cable
Injection pipe
Stop valve
Liquefier fan
Suction pipe
The connection between the indoor unit and the outdoor component is
made with refrigerant pipes.
5
REMKO RVD...DC
Operation
The indoor unit is easy to operate using an infrared remote control. This is supplied as standard. The indoor unit
beeps to acknowledge the correct transmission of data. If it is not possible to program
the indoor unit using the remote control, it can also be manually operated.
Manual operation
The indoor units can be started
manually. Press the RESET button
on the receiver unit of the cover to
activate automatic mode. In manual
operation, the following settings
apply:
Cooling mode: 24 °C,
Fan speed AUTO
Heating mode: 26 °C,
Fan speed AUTO
Pressing any button on the infrared remote control interrupts
manual operation
Display on indoor unit
The lit display LEDs indicate the settings.
LED H red = high fan speed
LED M yellow = medium fan speed
LED L green = low fan speed
Display on indoor unit
Unit for receiving signals
from the remote control
Operation-
screen
Timerscreen
fan
Defrost
Alarm display
infrared remote control
The infrared remote control sends
the programmed settings over a
distance of up to 6 m to the receiver of the indoor unit. Data will
only be received correctly if the
remote control is pointed at the receiver and no objects are obstructing the transmission path.
First insert the supplied batteries
(2 x type AAA) into the remote
control. To do so, pull off the flap
of the battery compartment and
insert the batteries according to
their polarization (see marks).
Maximum distance
max. 6 m
CAUTION
Problems are
shown in code
(see chapter Troubleshooting
and Customer service).
NOTE
Immediately replace flat batteries with a new set, otherwise
there is a risk of leakage. It is
recommended that the batteries
are removed if the equipment is
shut down for long periods.
6
Buttons on the remote control
Buttons on the remote control
"ON/OFF" Button
Press this button
to start the unit.
"MODE" button
Press this button
to select the operating mode.
The
indoor unit has 5 modes:
1. Automatic mode
In this mode, the unit works in
cooling or in heating mode.
2. Cooling mode
In this mode, the warm room
air is cooled to the
desired temperature.
3. Dehumidification mode
In this mode
the room is mainly dehumidified, the adjusted temperature is
retained.
4. Heating mode
In this mode, the warm air in
the room is warmed up to the
desired temperature.
5. Circulation mode
In this mode, the air in the room
is recirculated.
Temperature selection is not
possible.
Button "Temp ▲ ▼ "
This button is used to
select the desired temperature
between 17 - 30°C.
"FAN SPEED" button
Press this button to set the
required fan speed. 4 settings
are available: automatic, high,
medium and low fan speed.
"ECONOMIC RUNNING" button
Pressing this button will auto-
matically increase or decrease
the target temperature by 1
°C within an hour in cooling
and heating mode respectively.
"AIR DIRECTION" Button
With this button, the desired
fin position can be set. There
are 5 positions and an oscillating function available.
"SWING" Button
This button directly activates
the oscillating function of the
fins for better air distribution
in the room.
"TIMER ON/OFF" button
This button serves to program
the automatic activation time
for the device within the next
24 hours.
"CLOCK" button
This button opens the time
program.
"OK" button
This button transfers the pro-
grammed data to the indoor
unit.
"CANCEL" button
This button stops the set timer
program.
"LOCK / RESET" button (flush buttons
The left LOCK button pre-
vents subsequent operation,
the right RESET button resets
the display.
7
REMKO RVD...DC
Button functions
A symbol is shown on the display to indicate that the settings are being transferred.
ON/OFF Button
COOL
TEMP
20
C
°
SPEED
pq
Buttons
COOL
TEMP
20
C
°
SPEED
CLOCK
LOW
CLOCK
LOW
10:49
10:49
By pressing the ON / OFF button, you can activate or deactivate your
unit. The programmed settings and adjustment values before the unit
was turned off will appear on the display.
The
TEMP
20
SPEED
p/q
COOL
C
°
ON/OFFON/OFF
CLOCK
10:49
LOW
buttons can be used to reduce and increase the desired nominal
COOL
TEMP
CLOCK
10:49
20
C
°
LOW
SPEED
temperature.
10:49
p
COOL
TEMP
CLOCK
2i
C
°
LOW
SPEED
COOL
TEMP
CLOCK
20
C
°
LOW
SPEED
10:49
q
COOL
TEMP
CLOCK
10:49
20
C
°
LOW
SPEED
MODE Button
COOL
TEMP
20
SPEED
CLOCK
C
°
LOW
AUTOMATIC MODE
AUTO
TEMP
20
SPEED
CLOCK
C
°
AUTO
10:49
10:49
Use the MODE button to select between the individual operating modes.
A total of 5 modes are available:
1. Automaticautomatic selection of cooling or heating operation
2. Coolingpredominantly summer operating mode
3. DehumidificationSummer or winter operating mode
4. Heatingpredominantly winter operating mode
5. Air circulation only for circulation of air SFlb
AutomaticCoolingDehumidificationHeating
AUTO
TEMP
2i
°
SPEED
MODE
CLOCK
10:49
C
LOW
COOL
TEMP
2i
°
SPEED
MODEMODEMODEMODE
CLOCK
10:49
C
LOW
DRY
TEMP
CLOCK
10:49
2i
C
°
LOW
SPEED
TEMP
CLOCK
2i
C
°
LOW
SPEED
HEAT
10:49
Air circulation
TEMP
2i
FAN
CLOCK
10:49
C
°
LOW
SPEED
In automatic mode, the control system autonomously selects between
heating, cooling and circulating modes. The nominal temperature can
be preselected and is then applied in automatic mode. The fan speed is
automatically adapted to the given circumstances.
The nominal temperature is
below the room temperature
The nominal temperature is
above the room temperature
AUTOAUTO
TEMPTEMP
CLOCKCLOCK
2i23
C
°
AUTOAUTO
SPEEDSPEED
▲
10:4910:49
OR
▼
COOLING
or
C
°
HEATING
or
AIR CIRCULATION
8
COOLING mode
COOL
TEMP
20
C
°
SPEED
CLOCK
LOW
10:49
In cooling mode, the air in the room is cooled down to the set target
temperature. The desired room temperature is set with the ▲/▼buttons
in 1 °C increments. If the room temperature is 1 °C above the selected
nominal temperature, the indoor unit starts to cool the air in the room.
The inverter controller checks the difference between the adjusted target
temperature and the actual room temperature. If there is a large difference, the cooling output is very high. If the difference is smaller, a lower
cooling output is produced. This serves to maintain extremely even air
discharge temperature and room temperature.If the adjusted room temperature is lower than approx. 2 °C, then the control system turns the
cooling function off. To protect the compressor, the regulation only turns
the cooling on again after a waiting period of 3 minutes.
DEHUMIDIFICATION MODE
DRY
TEMP
20
CLOCK
10:49
C
°
AUTO
TEMP
CLOCK
10:49
2i
C
°
SPEED
MODE
LOW
COOL
TEMP
CLOCK
2i
C
°
LOW
SPEED
10:49
▲
and
▼
FAN
TEMP
CLOCK
2i
C
°
LOW
SPEED
10:49
TEMP
22
FAN
CLOCK
C
°
LOW
SPEED
COOLING
10:49
OPERATION
Functional diagram
Nominal temperature
Nominal temperature -2°C
Compressor operation AT
Fan operation AT
Fan operation IT
Actual temperature
> 6 Min.
30 sec.30 sec.
> 6 Min.> 3 Min.
Start cooling mode
Cooling mode
Stop cooling mode
Operation
Stop
In dehumidification mode, the room temperature is set to 24 °C. Due to
the low temperature of the refrigerant, the dew point of the air on the
vaporiser is lower. The excess moisture in the air is condensed by the
vaporiser, the room is dehumidified. The fan speed should be set to automatic in order to achieve a maximum level of dehumidification. The fan
speed is automatically adapted to the given circumstances.
SPEED
AUTO
COOL
TEMP
CLOCK
MODE
10:49
2i
C
°
LOW
SPEED
2i
Functional diagram
Nominal temperature
Nominal temperature -2°C
Compressor operation AT
Fan operation AT
Fan operation IT
DRY
TEMP
CLOCK
10:49
C
°
AUTO
SPEED
Actual temperature
▲
AND
▼
DRY
TEMP
CLOCK
24
C
°
AUTO
SPEED
Low fan speed
10:49
ON/OFF
DRY
TEMP
CLOCK
24
C
°
AUTO
SPEED
DE-
10:49
HUMIDIFICATIONMODE
Start
Dehumidifying mode
Dehumidifying mode
Stop
Dehumidifying mode
30 sec.
Operation
Stop
9
REMKO RVD...DC
HEATING Mode
TEMP
20
C
°
SPEED
CLOCK
LOW
HEAT
10:49
In the heating mode, you can heat the room in spring or fall. The desired
room temperature is set with the ▲/▼ buttons in 1 °C increments. If the
room temperature is 1 °C below the selected target temperature, the indoor unit starts to heat the air in the room. The inverter controller checks
the difference between the adjusted target temperature and the actual
room temperature.
In the event of a greater difference, a higher cooling performance is created.
In the event of a smaller difference, a lower cooling performance is created.
This serves to maintain the air discharge temperature and the room temperature.
If the adjusted room temperature is still exceeded by approx. 2 °C, then
the control system turns the heating function off. To protect the compressor, the regulation only turns the heater on again after a waiting
period of 3 minutes.
In heating mode, the indoor unit fan motor is switched on after a delay,
in order to prevent the discharge of cold air.
The fins on the outdoor unit could crack at low outdoor temperatures.
Regular reversal of the cooling circuit results in a defrosting action. The
display shows "H1" during the defrosting period.
Heating mode operational sequence
DRY
TEMP
CLOCK
10:49
2i
°
AUTO
SPEED
MODE
C
HEAT
TEMP
CLOCK
▲
10:49
2i
C
°
SPEED
AND
LOW
▼
HEAT
TEMP
CLOCK
10:49
23
°
SPEED
FAN
C
LOW
HEAT
TEMP
CLOCK
10:49
23
C
°
MED
SPEED
HEATINGMODE
Functional diagram
Stop heating
operation
Heating mode
Start heating
mode
Operation
Stop
Nominal temperature +5 ℃
Nominal temperature +2 ℃
Compressor operation AT
Fan operation AT
Fan operation IT
Reverse flow valve
Actual temperature
> 6 Min.
30 sec.30 sec.
> 6 Min.> 3 Min.
30 sec.30 sec.
During the defrosting cycle, the indoor unit vaporiser fan and the outdoor unit liquefier fan are switched off.
After the cycle is concluded, the fans are switched to their
previous settings.
Reverse flow valve
Compressor operation AT
Fan operation AT
Fan operation IT
Defrost period
30 sec.
< 7 Min.
15 sec.
30 sec.
60 sec.
30 sec.
3 Min.
Operation
Stop
10
AIR CIRCULATION Mode
TEMP
20
SPEED
CLOCK
C
°
LOW
FAN
10:49
In ventilation mode, the air in the room is only circulated.
The room temperature cannot be changed in this mode.
The cooling or heating operation is not activated.
HEAT
TEMP
CLOCK
10:49
2i
C
°
LOW
SPEED
MODE
TEMP
2i
C
°
SPEED
FAN
FAN
CLOCK
10:49
SPEED
LOW
2i
FAN
TEMP
CLOCK
10:49
C
°
MED
SPEED
AIR CIRCULATION
FAN SPEED button
FAN
TEMP
20
SPEED
CLOCK
10:49
C
°
LOW
ECONOMIC RUNNING button
FAN
TEMP
20
SPEED
CLOCK
10:49
C
°
LOW
The fan speed can be adjusted with this button. A selection can be made
between low, medium, high and automatic fan speed.
TEMP
CLOCK
10:49
2i
C
°
AUTO
SPEED
SPEED
TEMP
CLOCK
2i
C
°
LOW
SPEED
FAN
HEAT
FAN
HEAT
10:49
SPEED
TEMP
2i
C
°
SPEED
FAN
HEAT
CLOCK
10:49
MED
SPEED
TEMP
2i
C
°
SPEED
FAN
HEAT
CLOCK
10:49
SPEED
HIGH
This button activates a programming function, which causes the
target temperature in cooling mode to increase after one hour by 1°C
and after two hours by 2 °C. In heating mode, the target temperature is
decreased after one hour by 1 °C and after 2 hours by 2 °C.
The display on the indoor unit goes out.
The TURBO function is used to activate the maximum fan speed
TEMP
CLOCK
10:49
2i
C
°
AUTO
SPEED
RUNNING
TEMP
2i
°
AUTO
SPEED
ECONOMIC
HEAT
C
HEAT
CLOCK
ECONOMIC
10:49
RUNNING
HEAT
C
°
AUTO
CLOCK
deactivated
10:49
TEMP
2i
SPEED
SWING and AIR DIRECTION Buttons
FAN
TEMP
20
SPEED
CLOCK
10:49
C
°
LOW
The oscillating function of the air discharge fins can be adjusted with
this button. The air distribution in the room is improved with the swing
function. In order to adjust the aim of the air discharge fins to a particular
direction, the AIR DIRECTION button must be pressed briefly. In order to
activate the automatic swing function, the AIR DIRECTION button must
be pressed for longer than 2 seconds.
deactivated
HEAT
▲▲
TEMP
2i
C
°
AUTO
SPEED
SWING
CLOCK
10:49
HEAT
TEMP
2i
C
°
AUTO
SPEED
SWING
CLOCK
10:49
11
REMKO RVD...DC
TIMER button TIMER ON / OFF
FAN
TEMP
20
SPEED
C
°
CLOCK
TIMER ON
TIMER OFF
LOW
10:49
18:45
22:30
The activation and switch-off time can be programmed with this button. The timer is activated/deactivated by means of pressing the timer
on and the timer off button. The timer symbol ON TIMER or OFF TIMER
appears. The desired turn on or turn off time is set by pressing the TIME
ADJUST button. Pressing a TIME ADJUST arrow button serves to adjust
the time in 10 min. intervals. Pressing both TIME ADJUST arrow buttons
enables the time to be set more quickly.
When the programmed time has been reached, the device is automatically turned on or off. If the indoor unit is automatically switched on, then
the mode, temperature and fan speed for the last setting is reactivated.
Pressing the OK button serves to store the selected TIMER setting.
The prior deletion of the on and off time can be achieved by pressing the
CANCEL button. The timer display on the indoor unit goes out.
TIMER ON button - activation delay
HEAT
TEMP
2i
°
SPEED
TIMER
CLOCK
10:49
C
ON
LOW
HEAT
CLOCK
TIMER ON
LOW
10:49
18:45
TIMER
ADJUST
TEMP
2i
C
°
SPEED
HEAT
TEMP
CLOCK
10:49
TIMER ON
06:30
2i
C
°
LOW
SPEED
Activationdelay
TIMER OFF button - switch-off delay
TEMP
2i
C
°
SPEED
CLOCK
TIMER ON
LOW
10:49
06:30
OFF
TIMER
HEAT
HEAT
TEMP
2i
C
°
SPEED
TIMER
CLOCK
10:49
ADJUST
TIMER ONTIMER ON
06:3006:30
TIMER OFFTIMER OFF
12:3017:30
LOW
HEAT
TEMP
CLOCK
10:49
2i
C
°
LOW
SPEED
Switch-off
delay
CLOCK button
TEMP
20
SPEED
C
°
CLOCK
TIMER ON
TIMER OFF
LOW
FAN
10:49
18:45
22:30
CANCEL - delete timer program
HEAT
TEMP
CLOCK
10:49
CANCEL
TIMER ON
06:30
2i
C
°
TIMER OFF
17:30
LOW
SPEED
HEAT
TEMP
CLOCK
10:49
2i
C
°
LOW
SPEED
The current time can be adjusted with this button. If the clock button is
pressed for longer than 3s, the time can be set with the TIME ADJUST
button. Store
HEAT
TEMP
CLOCK
i0:49
2i
C
°
SPEED
CLOCK
LOW
HEAT
TEMP
2i
C
°
SPEED
TIMER
CLOCK
i0:49
ADJUST
LOW
HEAT
TEMP
CLOCK
i5:50
2i
C
°
LOW
SPEED
OK
HEAT
TEMP
CLOCK
i5:50
2i
C
°
LOW
SPEED
Time
stored
12
Shutdown
Care and maintenance
Temporary shutdown
1. Allow the indoor unit to run for
2 to 3 hours in air circulation
mode or in cooling mode at the
maximum temperature setting
in order to remove any residual
moisture from the unit.
2. Shut down the unit using the
remote control.
3. Switch off the voltage supply to
the unit.
4. Cover the unit as far as possible with plastic foil in order to
protect it from the influences of
weather.
Permanent
Shutdown
Ensure that equipment and components are disposed of in accordance with local regulations, e.g.
through authorised disposal
and recycling specialists or at collection points.
Contact REMKO GmbH & Co. KG
or your contract partner for a list
of specialist companies near you.
Regular care and maintenance
serves to ensure trouble-free operation and long service life of the
unit.
CAUTION
Prior to performing any work,
ensure the equipment is isolated from the voltage supply
and secured to prevent accidental switch-on!
NOTE
The statutory regulations
require an annual sealing test
for the refrigerant circuit in
relation to the refrigerant
filling level. The inspection
and documentation is to be
carried out by corresponding
specialist engineers.
Care
■
Ensure the indoor unit and outdoor component are protected
against dirt, mould and other
deposits.
Type of task
Checks/Maintenance/Inspections
■
Clean the equipment using a
damp cloth. Do not use any
caustic, abrasive or solventbased cleaning products. Do
not use a jet of water.
■
Clean the fins on the indoor
unit and outdoor component
prior to long shutdown periods.
Maintenance
■
It is recommended that
you take out a maintenance
contract with an annual service
from an appropriate specialist
firm.
TIP
This ensures the operational
reliability of your
equipment!
Commissioning
Monthly
Six-monthly
Yearly
General
Measure voltage and current
Check compressor/fans are functioning correctly
Check fan is functioning correctly
Dirt on liquefier/vaporiser
Check refrigerant fill quantity
Check condensation drain
Test insulation
Check moving parts
Sealing test for refrigerant circuit
1) see note
••
••
••
••
••
••
••
••
••
• •
1)
13
REMKO RVD...DC
Cleaning the cover
of the indoor unit
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Fig. 1).
3. Clean the guard using a soft,
damp cloth.
4. Switch the supply voltage back
on.
Air filter for indoor unit
Clean the air filter at intervals of
no more than 2 weeks.
Reduce this interval in case of
heavily soiled air.
5. Any dirt can be cleaned off using lukewarm water and mild
cleaning agents.
To do so, turn the dirty side
downward (Fig. 3).
6. When using water, allow
the filter dry out properly in air
before replacing it in the unit.
7. Carefully insert the filter. Make
sure it is seated correctly.
8. Close the cover as described
above but in reverse order.
9. Switch the supply voltage back
on.
10.
Switch the unit back on.
Cleaning the
condensation pump
The indoor unit includes a built-in
condensation pump,
for pumping the condensation to a
drain at a higher level.
1 Guard on cover
2 Clean with a vacuum cleaner
3
Cleaning with lukewarm water
Cleaning the filter
1. Disconnect the supply voltage
to the equipment.
2. Open and fold down the air
inlet guard on the cover. The
filter is held in place by the flaps
screwed in at the side of the
guard (Fig. 1).
3. Tilt the filter and lift it out.
4. Clean the filter using a normal
vacuum cleaner (Fig. 2).
Turn the dirty side until it faces
up.
The pump is more or less maintenance free. The condensation
pipes should be checked for dirt
at regular intervals. Clean them as
required.
If an external pump is also used,
observe the maintenance and care
instructions given in the separate
operating manual.
14
Troubleshooting and customer service
The equipment and components are manufactured using state-of-the-art production methods and tested several times
to verify their correct function. If malfunctions should occur, please check the functions as detailed in the list below.
Please inform your dealer if the unit is still not working correctly after all the functional checks have been performed!
Malfunction
FaultPossible causeChecksRemedial measures
The unit does not start
or switches itself off
The unit does not respond
to the remote control
The unit is running with
reduced or without
reduced cooling / heating
performance
Condensation discharge
on unit
Power outage, undervoltage,
defective mains fuse / main circuit
breaker switched off
Damaged mains cable
Waiting time after switch-on too
short
Temperature outside operating
range.
Overvoltages caused by thunder
storms
Fault in external condensation
pump
High-pressure / low-pressure
monitors have triggered
Transmission distance too far /
receiver affected by interference
Defective remote control
Receiver or transmitter unit exposed to excessive solar radiation
Electromagnetic fields are interfering with transmission
Button in remote control jammed
/ two buttons pressed at same
time
Batteries in remote control are flat
Filter is unclean / air inlet / outlet
blocked by foreign items
Windows and doors open. Heating/cooling output increases
Neither cooling nor heating mode
has been set
Fins on outdoor component
blocked by foreign items
Leaking refrigerant circuit
Outdoor component iced up
Drainage pipe on collection container clogged / damaged
Faulty external condensation
pump or float
Condensation has not drained
away and has collected in the
condensation line
Condensation does not drain off
Float is stuck or jammed due to
excessive dirt.
Are all other
electrical installations functioning
correctly?
Are all other
electrical installations functioning
correctly?
Have approx. 5 minutes
elapsed since the restart?
Are the fans in the indoor unit
and outdoor component working
correctly?
Has there recently been lightning?
Did the pump shut down due to
a fault?
Check refrigerant pressure and
look for leaks if necessary
Does the indoor unit beep when
pressing a button?
Is the unit running in manual
mode?
Does it function correctly in the
shade?
Does it function when switching off
possible sources of interference?
Does the “Send”
symbol appear on the display?
Have new batteries been inserted?
Is the display incomplete?
Have the filters been cleaned?Clean the filters
Have there been any constructional /
application-related
changes?
Does the cooling symbol appear
on the display?
Is the fan on the outdoor component running? Are the fins
unobstructed?
Are there signs of frost on the fins
of the indoor unit?
Check outdoor component. Has
the cassette sensor on the outdoor
component been correctly positioned?
Can the condensation drain off
without any obstruction?
Is the collection tray full of water
and the pump not running?
Is there a steady fall on the condensation pipe? Check there is no
blockage in the pipe.
Are the condensation lines unblocked and is there a steady fall?
Are the condensation pump and
float switch functioning correctly?
Are the LEDs on the receiver unit
of the indoor unit flashing?
Check voltage
possible wait until turned on
again.
Repair by
a specialist
Schedule longer waiting
periods
Take into account the temperature range for the indoor unit and
outdoor component
Switch off the mains breaker and
switch it back on. Have it checked
by a specialist
Check and if necessary clean the
pump
Rectify leakage and re-start
Reduce the distance to less than 6
m or change position
Replace the remote control
Place the receiver&transmitter unit
in the shade
Signal is not transmitted when interference sources are operational
Release the button / only press
one button
Insert new batteries
Close windows and doors / install
additional units
Correct the settings for the unit
Check the fan or winter controller,
reduce the air resistance
Repair by specialist
De-ice and fit the sensor at the
point where the most ice forms
Clean the drainage pipe and collection container
Call out a specialist to replace the
pump
Ensure there is a fall when laying
the condensation pipe and clean
the pipe.
The condensation line must have
a fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.
Should be cleaned by specialist firm
15
REMKO RVD...DC
Problem display by blinker code
LED
Operation
flashes
rapidly
flashes
slowly
LED
Timer
flashes
rapidly
flashes
slowly
LED
Defrost
flashes
rapidly
flashes
slowly
LED
Alarm
flashes
slowly
flashes
rapidly
Display
outdoor
unit
E0EEPROM errorCheck EEPROM
E2
E3
E4
E5Overvoltage compressorCheck compressor voltage
P0Excessive temperature compressorAllow compressor to cool
P1High pressure sensor has triggeredCheck refrigerant pressure
P2Low pressure sensor has respondedCheck refrigerant pressure
P3
P4Compressor discharge gas over 105°C
P5Liquefier temperature over 65°C
P6
CauseRequired action
Communication error between PCBs
outdoor unit & indoor unit
Communication error between outdoor unit main board & outdoor unit
inverter board
Outdoor temp sensor on outdoor component tripped
Compressor power consumption too
high
Voltage protection main board outdoor
unit
Sensor air circulation / sensor liquefier
tripped
Communication error between outdoor
unit & indoor unit
Mode malfunction
Sensor liquefier / outdoor temp faulty
or not correctly connected
Read off error code on
outdoor unit
Check sensors
Check condensate pump
and float switch
Installation instructions for qualified personnel
Important points prior to installation
■
Transport the unit in its original
packaging as close as possible
to the installation location to
avoid transport damage.
■
Check the contents of the
packaging for completeness
and check the unit for visible
transport damage. Report any
damage immediately to your
contracting party and the shipping company.
■
Lift the unit at the corners and
not by the refrigerant or condensation connections.
16
■
The refrigerant pipes
(injection and suction pipe),
valves and connections must be
insulated impervious to vapour
diffusion. If necessary, also insulate the condensation pipe.
■
Select an installation location
which allows air to freely flow
through the inlet and outlet.
(See section "Minimum clearances").
■
Do not install the unit in the
immediate vicinity of devices
with intensive thermal radiation. Installation near sources of
thermal radiation reduces the
output of the unit.
■
Open the blocking valves of the
refrigerant pipes only after the
installation is complete.
■
Seal off open refrigerant pipes
with suitable caps or adhesive
strips to avoid infiltration of
moisture
and never kink or compress the
refrigerant pipes.
■
Avoid unnecessary
bends. This minimises the pressure loss in the refrigerant pipes
and ensures that the compressor oil can flow back without
obstruction.
■
Make special preparations
regarding the oil return if the
outdoor component is located
above the indoor unit. (See section "Oil return flow measures").
■
Add refrigerant if the basic
length of the refrigerant pipe
exceeds 5 metres.
The quantity of additional refrigerant is given in chapter "Add
refrigerant".
■
Only use the union nuts for the
refrigerant pipes included in
the delivery, and remove them
shortly before connecting the
refrigerant pipes.
■
Establish all electrical connections
in accordance with the relevant
DIN- and VDE standards.
■
See electrical connection diagram
Always properly insert electrical
cables into the electrical terminals. Otherwise a fire could
result.
Wall openings
■
A wall opening of at least 70
mm diameter and 10 mm slope
from the inside to the outside
must be made for each indoor
unit.
■
We recommend that the inside
of the hole is padded or lined,
e.g. using a PVC tube, to prevent the pipes being damaged.
■
After installation, the wall
opening should be closed off on
the building side with a suitable
sealant. Do not use materials
containing cement or lime!
Pipes and cables in wall breakthrough
Control line
PVC tube
Suction pipe
Condensation line
Injection pipe
Installation material
The indoor unit is fastened
using a wall bracket and 4 threaded
screws (provided by the customer).
The outdoor component is attached with 4 screws and a wall
bracket to the wall or fixed by a
floor bracket to the ground.
Selection of the installation
location
Interior unit
The indoor unit is designed for
horizontal wall installation above
doors. However, it can also be
used on the upper wall area
(min. 1.75 m from upper edge of
floor).
Exterior unit
The outdoor component is designed for horizontal base installation in outdoor areas. It should
be placed on level, flat and firm
ground. The unit should also
be secured to prevent toppling.
The outdoor component can be
set up outside as well as inside a
building. For external installation,
please observe the following notes
to protect the unit from weather
conditions.
Rain
The unit should be at least 10 cm
off the ground when mounted on
the roof or ground. A floor bracket
is optionally available.
Sun
The liquefier on the outdoor unit
radiates heat.
Exposure to direct sunlight will
further increase the temperature of
the fins and reduce the heat output of the finned heat exchanger.
The outdoor unit should therefore
be installed as near as possible to
the north side of the building. If
necessary, take measures to provide sufficient shade (responsibility
of customer). One possible solution is to build a small roof. These
measures should not affect the
flow of warm outlet air.
Wind
If the unit is being installed in
windy areas, ensure that the warm
outlet air discharges in the main
wind direction. If this is not the
case it may be necessary to install
a windbreak (provided by the customer). Ensure that the windbreak
does not adversely affect the air
intake to the unit.
Windbreak
Wind
17
REMKO RVD...DC
■
Snow
The unit should be wall-mounted
in areas of heavy snowfall.
Installation should be at least 20
cm above the expected level of
snow to prevent snow from entering the outdoor component. An
optional wall bracket is available as
an accessory.
Minimum clearance to snow
Comply with any regulations
and conditions affecting the
statics of the building. If necessary, fit acoustic installation.
5 Installation inside buildings
Warm air
Cold
Fresh air
Additional
fan
Snow
20 cm
Installation inside buildings
■
Ensure there is adequate heat
dissipation when placing the
outdoor component in cellars,
attics, adjoining rooms or halls
(Fig 5).
■
Install an additional fan with a
rated flow comparative to that
of the outdoor unit being installed in the room. This is used
in conjunction with ventilation
ducts to compensate any pressure losses
(Figure 5).
Light
well
Warm air
Exterior unit
Light
well
Minimum clearances
Observe the minimum clearances to allow access for maintenance and
repair work and facilitate optimum air distribution.
Minimum clearances
1000
1000
Air intake
1000
D
1000
A
500
E
Air outlet
B
All values in mm
C
■
Ensure a continuous and unobstructed air flow from outside,
preferably using sufficiently
large air intakes placed opposite
each other
(Figure 5).
18
RVD 351DC ATRVD 521DC AT
A150 mm
B900 mm
C500 mm
D150 mm
E500 mm
Oil return measures
If the outdoor component is
installed at a higher level than
the indoor unit, suitable oil return
measures must be taken. Usually
an oil pump bend is installed for
every 2.5 metres of height difference.
Oil return measures
Exterior unit
Oil pump bend
in suction pipe to
outdoor unit
1 x every 5
metres of rising
pipe
Radius:
50 mm
max. 5/10 m
Interior unit
a second room or a fresh air
intake.
3. Fit the indoor unit onto the
threaded rods and use the
lower nuts to level the unit
(Fig. 9).This ensures that the
condensate drains into the collection tray.
4. Make sure that clearance A,
(Fig. 10) as specified in the table below, is provided between
the underside of the suspended
unit and the underside of the
fastening surface.
5. Connect the refrigerant pipes,
electrical cables and condensation line to the indoor unit as
described below.
6. Check that the unit is level.
7. The final task is to tighten the
counternuts and attach the
cover.
8 Mounting the unit
400
All dimensions in mm
Dimensions in mm
RVD 351-
521DC
Distance A35 mm
Distance B25 mm
Mounting the unit
620 mm
x400- mm
620
Installation
NOTE
Installation should only be
performed by authorised specialists.
Unit installation
The indoor unit is mounted face
down on four threaded rods. Take
into account the ceiling grid and
any other installations.
1. Use the dimensions of the ceiling cassette (Fig. 8) to mark the
fixing points for the threaded
rods on structural parts approved to support the static
load above the suspended ceiling.
2. Fit any connection nozzles
before installing the unit if connections to a second room or a
fresh air intake are required.
See section - Connections to
9 Hooking in the unit
Structural component
10 Fastening the unit
Structural component
A
B
19
REMKO RVD...DC
Connection of
refrigerant pipes
The on-site connection of the
refrigerant pipes is made at the
rear of the unit.
It may be necessary to fit a reducer
or flared adapter to the indoor
unit. These fittings are included
as standard with the indoor unit.
Once installed, the connections
should be made tight against vapour diffusion.
CAUTION
The units are factory filled with
dry nitrogen to check for leaks.
The pressurised nitrogen is
released when loosening the
union nuts.
The following instructions describe
the installation of the refrigerant circuit and the assembly of
the indoor unit and the outdoor
component.
5. Verify that the shape of the
flange is correct(Figure 8).
6. First connect and hand-tighten
the refrigerant connections
to ensure they are correctly
seated.
7. Now fully tighten the fittings
using 2 suitably sized openended spanners. Use one spanner to counter the force when
tightening the fitting (Figure
9).
8. Use insulation hoses which are
designed for this temperature
range and diffusion tight.
9. Lay the refrigerant pipes from
the indoor unit to the outdoor
component. In doing so, ensure
6 Deburring the refrigerant pipe
Refrigerant pipe
that they are sufficiently at-
tached and take measures for
the oil return, if necessary!
10.
Observe the permitted bending radius for the refrigerant
pipes during installation. Never
bend a pipe twice in the same
place. Brittle pipes and potential
cracking are the consequences.
NOTE
Only employ tools and components suitable for refrigeration applications.
11.
Use the wall or floor brackets
to fit the outdoor component
against structural parts approved to support the static
load (refer to the installation
instructions for the brackets).
7 Flanging the refrigerant pipe
Flanging tool
1.
The required pipe diameters are
given in the table "Technical
data".
2. Remove the factory-fitted protective caps and union nuts on
the connections. These should
be used during installation.
3. Before flanging the refrigerant
pipes, ensure that the union nut
is fitted on the pipe.
4. Prepare the laid refrigerant
pipes as shown below
(Fig. 6+7).
Deburrer
8 Correct flange shape
9 Tighten the fitting
Tighten 1. spanner
Counter
2. spanner
Tightening
torque:
“
15-20 Nm
“
33-40 Nm
“
50-60 Nm
“
65-75 Nm
“
95-105 Nm
20
Tightness check
Condensate drain
Once all the connections have
been established, the pressure
gauge station is attached as follows to the Schrader valve (if
fitted):
red = small valve
= injection pressure
blue = large valve
= suction pressure
Once connected, perform a tightness test using dried nitrogen.
The tightness test involves spraying a leak detection spray onto
the connections. If bubbles are
visible, the connections have not
been properly made. Re-tighten
the connection or prepare a new
flange.
If the tightness test is successfully completed, depressurise
the refrigerant pipes and start a
vacuum pump with an absolute
final partial pressure of min. 10
mbar to remove the air in the pipe.
Any humidity present in the pipes
is also removed.
CAUTION
A vacuum of min. 20 mbar
must be created!
If the temperature falls below the
dew point, condensation will form
on the cooling fins during cooling
mode.
A collection tray together with
a condensation pump and float
switch are fitted as standard below
the cooling fins. Should the float
switch trip a protective shutdown
due to inadequate removal of
the condensation, the pump will
switch on immediately and run on
for approx. three minutes.
■
The condensation pipe should
have a fall of min. 2 %. This is
the responsibility of the customer. If necessary, fit vapour
diffusion proof insulation.
■
If the level of the condensation
pipe on the unit is above that
of the outlet, route the pipe
vertically upwards (max. 1000
mm from the lower edge of the
unit) and then with a fall to the
drain.
■
The condensation line from the
unit should run freely into the
drainage pipe. If the condensation runs directly into a sewer
pipe, fit a trap to prevent any
unpleasant odours.
Condensation connection - Wrong!
Riser pipe too far away
No fall
Condensation pipe too large/small
Cannot freely drain away
Condensation connection - Correct!
min. 2% fall
12-20 mm
A
The time required to generate the
vacuum is dependent on the pipework volume of the indoor unit
and the length of the refrigerant
pipes. This always takes at least
60 minutes.
Once any foreign gases and
humidity have been completely
extracted from the system, the
valves on the pressure gauge station are closed and the valves on
the outdoor unit are opened as
described in the chapter on "Commissioning".
■
When operating the unit at
outdoor temperatures below 4,
ensure the condensation pipe is
laid to protect it against frost.
If necessary, fit supplementary
pipe heating.
■
Once the pipe has been laid,
check the condensation drains
off and permanently seal it.
max. 100 mm
RVD 351 ITRVD 521 IT
A500 mm750 mm
21
REMKO RVD...DC
Electrical connection
A protected mains supply cable
and control cable should be connected to the outdoor component
RVD 351-521DC and indoor unit
respectively.
NOTE
We recommend realising the
control lines with shielded
cable.
CAUTION
All electrical installation work
should be performed by specialist contractors. Isolate the
voltage supply when connecting the electrical terminals.
■
We recommend that customers install a main/repair switch
in the vicinity of the outdoor
component.
■
The terminal blocks for making
the connections are located at
the rear of the unit. When the
unit is installed, measurements
can be made from the front by
removing the cover.
■
If an optional condensation
pump is used in conjunction
with the unit, it may be necessary to install an additional relay
with a higher contact rating
after the switch-off contact
on the pump to switch off the
compressor.
■
Control cables should be
screened if laid in areas exposed
to strong magnetic fields.
Connecting the indoor unit
Make the connection as follows:
1. Open the air intake grill.
2. Unfasten the cover on the right
side and at the bottom right
rear side.
(Fig. 12).
3. Connect the unit to the control
cable on the outdoor component. See electrical connection
diagram.
4. Re-assemble the unit.
12
Connecting the indoor unit
Control line
from the outdoor unit
Terminal block
Control line
Cover
Connecting the outdoor component
Proceed as follows to connect the
cable:
1. Remove the cover from the
unit.
according to the relevant standards.
4. Feed both cables through the
edge protection rings on the
fixed connection panel.
5. Terminate the cables as shown
on the electrical connection
diagram.
6. Support the cable in the strain
relief and re-assemble the unit.
Before
Commissioning
After the tightness check has been
successfully completed,
connect the vacuum pump via the
pressure gauge station to the valve
connections on the outdoor unit
(see chapter "Tightness check")
and create a vacuum.
Perform the following checks prior
to commissioning the unit for the
first time and after any interventions affecting the refrigerant
circuit. Record the results in the
commissioning report:
■
Check of all refrigerant
pipes and valves with
leak detection spray or soapy
water for leaks and for inadvertent mix up of suction and
injection pipe, with the unit at a
standstill.
■
Check of all refrigerant
pipes and insulation for damage.
■
Check of all electrical
connections between
indoor unit and outdoor unit
for correct polarity.
■
Details concerning the electrical
protection
of the system are given in the
section on technical data.
22
2. Remove the side panel next to
the terminals.
3. Select the cable cross-section
■
Check that all fastenings,
mountings etc.
are firm and at the correct level.
Add refrigerant
The equipment contains a basic
quantity of refrigerant. Beyond
these conditions, for refrigerant
pipe lengths of more than 5 meters
per circuit, an additional amount of
refrigerant must be added, according to the following chart:
CAUTION
Note that the employed refrigerant is always filled in liquid
form!
NOTE
Check the overheating to
determine the refrigerant fill
quantity
CAUTION
Wear protective clothing when
handling refrigerant.
RVD 351DC RVD 521DC
Up to and
incl. 5m
5m to
max. 15m
5m to
max. 20m
0 g/m
25
g/m
-25 g/m
-
Commissioning
NOTE
Commissioning should only be
performed and documented by
specially trained personnel.
The system can be commissioned
once all the components have
been connected and tested. A
functional check should be performed to verify its correct function and identify any unusual
operational behaviour prior to
handing it over to the operator.
NOTE
Check that the stop valves and
valve caps are tight after carrying
out any work on the refrigerant
circuit. If necessary, use appropriate sealant products.
Function test and
test run
Check the following points:
■
Leak tightness of refrigerant
pipes.
■
Compressor and fan running
smoothly.
■
In cooling mode, cold air should
be output by the indoor unit,
and warm air should be output
by the outdoor component.
■
Functional test of the indoor
unit and all program
sequences.
■
Check of the surface temperature of the suction pipe and
determination of vaporiser
overheating. To measure the
temperature, hold the thermometer to the suction pipe
and subtract the boiling point
temperature reading on the
pressure gauge from the measured temperature.
■
Record the measured temperatures in the commissioning
report.
Functional test for cooling
and heating modes
1. Remove the caps
from the valves.
2. Begin the commissioning
process by briefly opening the
blocking valves of the external
section until the manometer
displays a pressure of approx. 2
bar.
3. Use leak detection spray or suitable devices to check that all
the connections are tight.
4. If no leaks are found, fully open
the stop valves by turning them
anti-clockwise using a spanner.
If leaks are found, repair the
faulty connection. It is imperative that the vacuum creation
and drying steps are repeated.
5. Switch off the main circuit
breaker or remove the fuse
(provided by the customer).
6 Press the test knob on the
outdoor unit and wait until
a frequency of min. 50 Hz is
established (only RVD521).
6. Use the remote control to
switch on the unit and select
the cooling mode, maximum
fan speed and lowest target
temperature.
7. Check the overheating, outdoor, indoor, outlet and vaporisation temperatures and record
the measured values in the
commissioning report. Check
the correct function and settings of all regulation, control
and safety devices.
8. Check the indoor unit control
system using the functions
described in the chapter "Operation". Timer, temperature setting, fan speeds and switching
to ventilation or dehumidifying
mode.
9. Check the correct function
of the condensation pipe by
pouring distilled water into the
condensation tray.
A bottle with a spout is recommended for pouring the water
into the condensation tray.
10.
Switch the indoor unit to heating mode.
23
REMKO RVD...DC
1.
Check all the previously
described safety devices and
functions during the test run.
12.
Enter the measured data in
the commissioning report.
in the commissioning report
and familiarize the operator
with the system.
13.
Remove the pressure gauge.
Check that seals have been
fitted in the sealing caps.
NOTE
Press the TEST knob on the
outdoor unit board. This
serves to set the inverter to
max. refrigerating capacity.
14. Reinstall all parts which were
removed.
Functional test and
test run for RVD 521 DC
During operation of the plant
operating parameters can be called
up on the outdoor unit display.
The following parameters are displayed successively:
RVD 521 DC
- Frequency of the compressor
- Operating mode
- Level fan
- Current cooling/heating perforance
- Temperature sensor liquefier
- Temperature sensor hot gas
- Temperature sensor air inlet
- Power consumption outdoor unit
- Degree of opening for electronic
Expansion valve only RVD 521 DC
- error code
Proceed as follows to call up the
operating parameters:
1. Remove the cover from the
outdoor unit.
2. Switch all indoor units on and
select cooling mode and the
highest fan speed.
Display RVD 521 DC
The display on the outdoor unit
PCB can call up the operating parameters of the plant in the above
order. In order to do so, press the
check button located next to the
display on the AT board.
446.0 A
466.2 A
547.4 A
557.6 A
587.8 A
628.0 A
668.6 A
678.8 A
689.0 A
709.2 A
729.5 A
7610.0 A
7810.2 A
8010.4 A
8210.6 A
8411.0 A
8811.6 A
9212.0 A
9412.2 A
Power consump-
tion
24
Electrical connection diagram
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11CN5CN7CN9
Weiß
C5
Weiß Schwarz
Rot
CN3
CN2
T1T2
T2 T1
CN14CN10CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
C
YEX
E
F M
CN12
CN1
zum Außengerät
Steuerleiter
zum CCN
Steuerleiter
DM
Display
Y/G
c
Blau
Y/G
CN5
GM
P1
Lila
Weiß
Netzzuleitung Innenteil
Rot
Weiß
CN4
CN11CN5CN7CN9
Weiß
C5
Weiß Schwarz
Rot
CN3
CN2
T1T2
T2T1
CN14CN10CN15
(E)
Y
X
Schwarz
Grau
Gelb
Schwarz
Blau
Weiß
(E)
P
C
YEX
E
F M
CN12
CN1
zum Außengerät
Steuerleiter
zum CCN
Steuerleiter
DM
Display
Y/G
c
Blau
Y/G
CN5
RVD 351-521
Interior unit
L
N
P
Control conductor
Q
Control conductor
E
Control conductor
PEPE
Electrical circuit diagram
RVD 351 DC IT
Exterior unit
Phase conductor
L
N
Neutral conductor
P
Q
E
Earth conductor
Mains cable
L
N
PE
230 V~,
50 Hz,
L / N / PE
RVD 521 DC IT
Q
E
Q
EPP
25
Blau
Blau
Blau
Blau
Blau
Blau
Blau
Kompressor
Rot
Schwarz
Gelb
Gelb
Schwarz
Rot
Weiß
Rot
RotRot
Schwarz
Gelb
Grau
Filter
Schwarz
Rot
Rot
Schwarz
Schwarz
Yellow/Green
Yellow/Green
Yellow/Green
Schwarz
Rot
Schwarz
Braun
Braun
Weiß
Weiß
Weiß
Weiß
Rot
Rot
Rot
Rot
Rot
Orange
Rot
Schwarz
UWV
U
V
W
P
N
IPM
10PIN
W V
U
L202
IPM
EEW
T5
CN4
CN12
CN5CN5
CN16
CN11
CN1
CN2
Trans.Trans.
CN20
CN27
CN28
CN9
Hochdruckschalter
Niedrigdruckschalter
R2503
P-3
P-4
P-5
P-6
P-2
3
CN3
R1815B
R1325C
CN14
CN15
CN13
CN12
CN7
CN5
CN6
CN4
CN8
CN10
CN9
Blau
Ventilator
CN1 CN2
L
N
L
N
P-1
L
H
Sensor Heißgas
Sensor Außentemperatur
Sensor Austritt
Verflüssiger
Elektronisches
Expansionsventil
Leistungsplatine
zum Innengerät
Steuerleiter
Hauptplatine
Steckverbinder
Steckverbinder
A
U
V
W
Y/G
U
V
W
RY3
4
CN6
CN7
CN5
CN4
CN2 8
CN26
C
N
1
0
N
-
B
B
C
N
3
C
N
2
C
N
1
CN15
CN14
CN16
N-A
Zum Innengerät
Y/G
WHITE
REACTOR2 R6025C
REACTOR1 R1310K
Kurbelwannenhei z ung
Heizung
5
CN31
CN33
CN34
CN32
B
L
A
C
K
Y/G
T3
Sensor Umgebung
T5
Sensor Verflüssiger Sensor Heißgas
Sensor Öl
Kompressor
Ventilatormotor
Umkehrventil
Blau
Schwarz
Rot
Schwarz
Rot
Rot
Hauptplatine
Grau
Optional
Orange
Gelb
Rot
Orange
Gelb
Gelb
Orange
Rot
Blau
Stromüberwachung
Gelb
Blau
Braun
REMKO RVD...DC
RVD 351 DC AT
RVD 521 DC AT
26
Unit dimensions
RVD 351-521 DC IT
650
RVD 351-521 DC AT
650
400
580
610
28
A
We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.
B
E
C
D
RVD 351 DCRVD 521 DC
A760840
B270310
C590700
D530560
E290335
All values in mm
27
REMKO RVD...DC
Device illustration RVD 351DC IT to RVD 521DC IT
5
1
2
14
6
3
9
8
10
7
the dimensions and constructional design as part of the ongoing
11
12
13
We reserve the right to modify
technical development process.
Spare parts list
No.Designation RVD 351DC ITRVD 521DC IT
1Air inlet guard11109501110950
2air filter11109511110951
3Cover11109521110952
4Fin motor11109531110953
5Air inlet, condensate pan module11109541110954
6Outlet fins, set of 411109551110956
7Vaporiser11109571110958
8Condensation pump cpl. 11109591110959