REMKO ELT Series, ELT 3-2, ELT 3-2 E, ELT 10-6, ELT 10-6 E Operating And Installation Instructions

...
Operating and installation instructions
REMKO ELT series
Electric heaters
ELT 3-2 (E), ELT 10-6 (E), ELT 18-9 (E)
This product is suitable only for well-insulated rooms or for occasional use.
Edition EN - Q03 Read the instructions prior to performing any task!
Contents
Unit description 4
Shutdown 6
Care and maintenance 7
Troubleshooting 7
Intended use 8
Customer service and guarantee
Environmental protection and recycling 8
Electrical wiring diagram
Exploded view of ELT 3-2 10
Spare parts list for ELT 3-2 10
Exploded view of ELT 10-6 11
Spare parts list for ELT 10-6 11
Exploded view of ELT 18-9 12
Spare parts list for ELT 18-9 13
Maintenance protocol 14
Technical data 15
9
8
Carefully read this operating manual prior to commissioning / using the units! This operating manual is a translation of the German original.
These instructions are an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO ELT series
Safety notes Unit description
Always observe the respective local building code and fire prevention guidelines as well as the guidelines of the accident prevention and insurance associations when using the units.
The units have been subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can arise from the units if they are used improperly or not as intended by untrained personnel!
Please observe the following notes:
The personnel tasked with operating the units must check the units for visible defects on the operating and safety devices as well as the presence and function of the protective devices prior to starting work
Inform the supervisor if defects are discovered!
In the event of defects that endanger the operational safety of the unit, operation must be discontinued immediately
Observe the respective local regulations and the relevant electrical safety measures when using the units
Maintain safety distances to combustible materials
An unobstructed air inlet and air outlet must be guaranteed at all times
Never insert foreign objects into the units
The units must not be covered during operation
Safety devices must not be
bypassed or disabled
■ The units must not be operated
in the vicinity of bathtubs, showers, swimming pools etc.
The units must not be operated directly below a wall socket
The units must not be exposed to direct jets of water e.g. pressure washers etc.
■ Never allow water to enter the
units
The units must not be installed
or operated in potentially flammable or explosive environments
The units must not be installed
or operated in atmospheres containing oil, sulphur or salt
■ All electrical cables for the
units must be protected against damage, even damage caused by animals
The units are portable electric heating units for industrial applications. The units are operated exclusively with electric power and have been designed in such a way that they can be used fully automatically, universally and in a straightforward manner.
The units are equipped with specially enclosed electric heating resistors, low noise and low­maintenance axial fans, safety and aftercooler thermostats, a room thermostat socket and power cable with protective contact plug.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations.
The units are dependable and offer ease of operation.
The units may be used among other things for the following:
Drying newly completed
buildings
Spot heating outdoor
workspaces or fire-proof manufacturing facilities and halls
Continuous or temporary room
heating
The air outlet must not be constricted or equipped with pipe or hose lines
4
The units must be set up in a stable, horizontal position
CAUTION
Safety devices must not be
bypassed or disabled.
De-icing machines, vehicles and
non-combustible warehoused goods while adhering to the relevant safety distances
Commissioning
Operating sequence
The units can be used in the respective operating modes for air heating and air circulation purposes (not ELT 3-2).
The units ELT 3-2 can be operated exclusively in 2 heating stages (2.2 or 3.2 kW). They have a 3-stage operating switch with the functions: Heat (I) / Off (0) / Heat (II).
The units ELT 10-6 and ELT 18-9 can be operated with three heating settings and one fan setting. They have a 5-stage operating switch with the functions: Off (0) / Fan (1) / Heat (2-4).
All units can be equipped with a plug-in ready room thermostat (accessory) to ensure that the room temperature is constant. Once the desired temperature has been reached, the thermostat switches the heating operation off. If the room temperature falls below the set temperature, the thermostat starts up the heating operation again.
!
CAUTION
After switching off the units via the operating switch or the room thermostats, the supply air fan runs to cool the heating resistors for a certain time and then switches off automatically.
NOTE
For optimum operation the units should not be operated above an ambient temperature of 25 °C.
One person, who has been adequately trained in the handling of the units, should be tasked with the operation and monitoring of the units.
The units must be in the intended horizontal position on their supports at all times during operation.
The units are equipped with the following operating switches:
Operating switch ELT 3-2
Heating 1st stage; 2.2 kW
Off
Heating 2nd stage; 3.2 kW
Operating switch ELT 10-6 and ELT 18-9
Off
Fan
1st heating stage
2nd heating stage
3rd heating stage
1. Check the customer’s mains voltage and ensure sufficient fuse protection for the unit type in use.
Power supplies:
ELT 3-2 230V/1~/50 Hz ELT 10-6 400/3~N/50 Hz ELT 18-9 400/3~N/50 Hz
2. Move the operating switch to the "0" (Off) position.
ELT 3-2
ELT 10-6 / 18-9
3. Connect the unit's power plug to a properly installed mains socket.
ELT 3-2
ELT 10-6 ELT 18-9
NOTE
The electrical connection for the units must be made at a separate feed point with a residual current device in accordance with VDE 0100, Section 55.
CAUTION
Extensions to the connection cable must only be conducted by authorised specialist electricians, taking into consideration the unit capacity, cable length and local use.
s
s
s
5
REMKO ELT series
s
s
s
Shutdown
Operating settings
The operating settings can be selected via a switch or a cam switch.
However, a room thermostat is always required for operation.
ELT 3-2
1st stage
2nd stage
ELT 10-6 and ELT 18-9
1st stage
Fan
Only the supply air fan operates in this setting. Thermostatic regulation and heating operation are not possible in this operating mode.
2nd stage
3rd stage
Heating with room thermostat
(Accessories)
The units operate fully automatically and according to the respective room temperature.
1. Pull out the strapping plug [2].
2. Connect the plug [3] of the room thermostat [4] with the thermostat socket [1] on the unit.
1
3
3. Place the room thermostat [4] at a suitable location in the room. The thermostat sensor must not be located directly in the warm air flow and must not be placed directly on the cold floor.
1. Move the operating switch to the “0” position.
ELT 3-2
The supply air fan runs on to cool the units and only switches off after the cooling down phase is complete. The fan can switch on and run several times before the final shutdown.
2. If the units are inactive for long
periods, disconnect them from the mains power supply.
ELT 10-6 / 18-9
ELT 3-2
Move the operating switch to the
desired position 1.
ELT 10-6 / 18-9
!
CAUTION
There is no separate ventilation function for this ELT 3-2.
4. Set the desired room temperature on the room thermostat [4].
4
5. Select the desired power
position on the respective operating switch.
ELT 10-6 ELT 18-9
CAUTION
Never interrupt the power supply prior to the completion of the follow-up cooling phase. There is no warranty claim for damage to the units from overheating.
6
Care and maintenance
Troubleshooting
NOTE
Regular care and maintenance, at the latest after every heating period, is the basic requirement for a long service life and malfunction-free operation of the units.
Observe the regular care and
maintenance intervals
CAUTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
In accordance with the
operating conditions, the units must, if necessary, be checked at least yearly by a specialist to ensure that they are in a condition that is safe to use
Keep the units free of dust and
other debris
Only clean the units with a dry
or lightly moistened cloth
Never subject to direct jets of
water.
e.g. pressure washers etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
Check the inlet and outlet grille
for contamination on a regular basis
Check the safety equipment
and protective devices on a regular basis
Be careful not to damage the
probe or capillary tube of the temperature limiter when removing or mounting the protective outlet grille
NOTE
Setting and maintenance work may only be carried out by authorised and qualified technicians.
CAUTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
NOTE
Replace defective or damaged parts immediately and exclusively with original spare parts.
Checking
The strapping plug supplied with the device is used for maintenance or testing according to VDE 0701. Follow the steps below to check.
1. Connect the supplied strapping plug [2] to the thermostat socket [1] on the unit.
1
The unit (fan) does not start.
1.
Check the mains fuses on site.
2. Check the power plug.
3. Check the operating switch.
4. Check that the fan can move freely.
The unit does not heat up.
1.
Check the operating switch.
2. Check that the contactor is functioning correctly.
3.
Check that the temperature
limiter or capillary tube are functioning correctly and check for damage.
4.
Check whether the thermostat
or strapping plug are plugged in.
5.
In case of unit operation
with a room thermostat, set the thermostat to a value that is higher than the room temperature.
If all of the functional checks have been carried out without any findings, please contact an authorised service station.
2
2. Check the device.
3. Remove the strapping plug
7
REMKO ELT series
Intended use
Customer service and Guarantee
Environmental protection and recycling
The units (not ELT 3-2) are designed exclusively for heating and ventilation purposes in industrial or commercial use (no living space heating) on the basis of their structural design and equipment. Any different or additional use is a non-intended use. The manufacturer/supplier assumes no liability for damages arising from non-intended use.
The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any manufacturer liability or guarantee claims are voided.
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative complete and return the “certificate of guarantee” to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units are tested several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
NOTE
Setting and maintenance work may only be carried out by authorised and qualified technicians.
Disposing of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in sturdy transport packaging made from cardboard and polystyrene. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
Disposal of the old unit
The manufacturing process for the units is subject to continuous quality control. Only high-grade materials are processed, the majority of which are recyclable. You also contribute to environmental protection by ensuring that your used equipment is only disposed of in an environment friendly manner.
CAUTION
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended is strictly prohibited without the written authorisation of
REMKO GmbH & Co. KG
8
Therefore, only bring the old unit to an authorised recycling business or to an appropriate collection point.
.
Electrical wiring diagram
ELT 3-2; 2-stage ELT 10-6
230V/1~/50Hz
L1NPE
4
KL
6
5
4321
M
1~
6
5
L1 L2 L3 N PE
L1 L2 L3 N
KL
1 2 3 4 5
STB
TB
RT
1
2
3
HW 2
HW 1
1,0 kW
2,2 kW
B
9 7
6 4
1 2
RT
3
Legend:
= Auxiliary relay
HR
HW = Heating resistor
K1 = Contactor 1
HR
TB
M
A2
1A
4B
I
5B
6B
A
S
2A
3A
II
A1
1~
K1
NK
x
H M
1
V1
L1 V2 L2
V3 V4 L3
V5 V6
HW 1-6
NK
08.2018
S
08.2018
ELT 18-9
L1 L2 L3 N PE
RT
1
3
2
L1 L2 L3 N
KL
1 2 3 4 5
STB
TB
NK
K2 = Contactor 2
KL = Connection terminal strip
M = Fan motor
NK = Aftercooler thermostat
RT = Thermostat socket
S = Operating switch
STB = Temperature limiter with
probe
= Temperature limiter
TB
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
A2
A1
HW 1-9
M 1~
A2
K1K2
A1
H
x
M
1
L1
V1 V2
L2
V3 V4 L3
V5 V6
S
08.2018
9
REMKO ELT series
Exploded view of ELT 3-2 (E)
20 21
19
18
17
23
14
13
12
24
1
2
6
7
3
4
16
15
11
8
9
5
10
Spare parts list
No. Designation EDP no. No. Designation EDP no.
1 Transport handle 1101142 13 Fan motor 1103820 2 Exterior cladding ELT 3-2 1103905 14 Back wall 1103913
2a Exterior cladding ELT 3-2 E 1103940 15 Mains cable with plug 1103901
3 Aftercooler thermostat 1104065 16 Strain relief 1101267 4 Temperature limiter 1101161 17 Strapping plug 1101019 5 Inner casing 1103907 18 Thermostat socket, cpl. 1101018 6 Heating resistor 1.0 kW 1103908 19 Operating switch cpl. 1101188 7 Heating resistor 2.2 kW 1103909 20 Contactor 1108038 8 Front wall 1103910 21 Terminal block 1101366
9 Protective outlet grille 1103803 23 Mounting plate 1101067 10 Floor panel 1103911 24 Grommet, small 1101304 11 Fan blade 1103902 12 Drive clutch 1108455
When ordering spare parts, in addition to the EDP no. please always also quote the unit number and unit type (see name plate)!
Not shown
Thermostat plug 1101020
10
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Exploded view of ELT 10-6 (E)
1
2
16
15
19
24
13
12
18
Spare parts list
25
14
17
10
11
21
20
22
23
5
3
4
9
8
6
7
8
No. Designation EDP no. No. Designation EDP no.
1 Transport handle 1101142 13 Back wall 1103954 2 Exterior cladding ELT 10-6 1107910 14 Strain relief 1107944
2a Exterior cladding ELT 10-6 E 1107909 15 Strapping plug 1101019
3 Inner casing 1103951 16 Thermostat socket, cpl. 1101018 4 Protective outlet grille 1103952 17 Operating switch cpl. 1107993 5 Front wall 1103953 18 Terminal block 5er 1107952 6 Floor panel 1107913 19 Contactor 1101096 7 Support 1107914 20 Grommet 1101304 8 Temperature limiter
9 Protective hose 1107915 22 Temperature limiter 1101161 10 Fan blade 1103950 23 Aftercooler thermostat 1104065 11 Drive clutch 1103956 24 Mounting angle 1101031 12 Fan motor 230 V 1101254 25 Mains cable with plug 1101026
When ordering spare parts, in addition to the EDP no. please always also quote the unit number and unit type (see name plate)!
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
with probe
1107960 21 Heating resistor 1103955
11
REMKO ELT series
Exploded view of ELT 18-9 (E)
18
1
2
17
16
14
26
15
19
13
10
12
11
20
8
21
21
22
24
23
9
7
3
8
4
25
5
6
12
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Spare parts list
No. Designation EDP no.
1 Transport handle 1101142
2 Exterior cladding ELT 18-9 1107920
2a Exterior cladding ELT 18-9 E 1107919
3 Interior cladding with blow-out cone 1107953
4 Seal for blow-out cone 1107954
5 Protective outlet grille 1101353
6 Front wall 1107921
7 Floor panel 1107950
8 Temperature limiter
9 Support 1107922
10 Protective hose 1107915
11 Fan blade 1101153
12 Drive clutch 1103956
13 Fan motor 230 V 1101254
with probe
1107960
14 Back wall 1107923
15 Strain relief 1107961
16 Thermostat socket, cpl. 1101018
17 Strapping plug 1101019
18 Protective intake grille 1107947
19 Grommet 1101304
20 Operating switch cpl. 1107993
21 Contactor 1101096
22 Terminal block 5er 1107952
23 Aftercooler thermostat 1104065
24 Temperature limiter 1101161
25 Heating resistor 1107998
26 Mains cable with plug 1107962
Not shown
Thermostat plug 1101020
When ordering spare parts, in addition to the EDP no. please always also quote the unit number and unit type (see name plate)!
13
REMKO ELT series
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Protection grid cleaned
Safety equipment checked
Safety devices checked
Unit checked for damage
All fastening screws checked
Electrical safety check
Test run
Comments:......................................................................................................................................................
............................................................................................................................................................................
............................................................................................................................................................................
1. Date: ..............
..............................
Signature
6. Date: ..............
..............................
Signature
11. Date: ............
..............................
Signature
2. Date: ..............
..............................
Signature
7. Date: ..............
..............................
Signature
12. Date: ............
..............................
Signature
3. Date: ..............
..............................
Signature
8. Date: ..............
..............................
Signature
13. Date: ............
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: ..............
..............................
Signature
14. Date: ............
..............................
Signature
5. Date: ..............
..............................
Signature
10. Date: ............
..............................
Signature
15. Date: ............
..............................
Signature
16. Date: ............
..............................
Signature
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
14
17. Date: ............
..............................
Signature
18. Date: ............
..............................
Signature
19. Date: ............
..............................
Signature
20. Date: ............
..............................
Signature
Technical data
Series
Nominal heating capacity P
Minimum heating power P
Maximum continuous heating power
Symbol
nom
min
P
max,c
Unit ELT 3-2 (E) ELT 10-6 (E) ELT 18-9 (E)
kW 3.2 10.5 18
kW 2.2 3.5 6
kW 3.2 10.5 18
Switchable heating capacity kW 2.2 or 3.2 3 x 3.5 3 x 6
3
Air volume m
/h 350 750 1,000
Power supply V/Hz 230/1~/50 400/3~N / 50 400/3~N / 50
Max. rated current A 13.9 14.9 27.5
Max. power consumption kW 2.25 / 3.25 10.65 18.2
Auxiliary current consumption at nominal heating power
Auxiliary current consumption at minimum heating power
Auxiliary current consumption in standby condition
Electrical protection (provided by the customer - slow)
el
max
el
min
el
SB
kW 3.250 10.650 18.150
kW 2.250 3.650 6.150
kW 0.000 0.000 0.000
A 16 16 32
Sound pressure level L
1m 1) dB (A) 46 53 57
pA
Dimensions: L/W/H mm 400/200/335 675/300/455 740/335/500
Type of room temperature control with elecrical room temperature control (external)
Weight kg 6.8 20.0 27.4
EDP no.: 114155 (114165) 114255 (114265) 114305 (114315)
1) Noise level measurement DIN 45635 - 01 - KL 3 ( ) INOX design
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
15
REMKO QUALITY WITH SYSTEMS
Air-Conditioning | Heating | New Energies
REMKO GmbH & Co. KG Klima- und Wärmetechnik
Im Seelenkamp 12 32791 Lage
Telephone +49 (0) 5232 606-0 Telefax +49 (0) 5232 606-260
E-mail info@remko.de URL www.remko.de
Hotline within Germany
+49 (0) 5232 6 06-0
Hotline International
+49 (0) 5232 606-130
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
Loading...