REMKO ELT 10-HT Operation,technology,spare Parts

REMKO ELT 10-HT
High temperature Electric heater
Operation · Technology · Spare parts
Edition GB – J08
Contents
Unit description 4
Safety notes 4
Commissioning 5-6
Shutdown 6
Operation with a warm air hose 6
Care and maintenance 6
Troubleshooting 7
Intended use 7
Customer service and guarantee 7
Environmental protection and recycling 7
Electrical wiring diagram 8
Maintenance protocol 9
Exploded view of the unit 10
Spare parts list 11
Technical data 11
Carefully read this operating manual prior to commissioning/using the units! This operating manual is a translation of the German original.
This manual is an integral part of the unit and must always be kept in the vicinity of the installation location or on the unit itself.
Subject to modifications; no liability accepted for errors or misprints!
3
REMKO ELT 10-HT
Safety notesUnit description
The units are portable electric heating units for industrial applications at various locations. The units are operated exclusively with electric power and have been designed for high-temperature applications with an air outlet temperature of up to 120°C. The air outlet temperature is altered by manually adjusting the fan speed.
The units can be operated using no more than one high-temperature hose (accessory) with a ø of 205 mm and a length of 7.6 m.
The units are equipped with special-purpose, highly efficient electrical heating coils for immediate and consistent heat generation, low-maintenance axial fans, a safety thermostat, a room thermostat socket and a mains cable with earthed safety plug.
The units conform to the fundamental health and safety requirements of the appropriate EU stipulations.
The units are dependable and offer ease of operation.
The units may be used among other things for the following:
Drying heat-resistant materials
Generating process heat for
industrial applications
Hardening plastics
Pest control
Drying out construction work/
heating
The units have been subjected to extensive material, functional and quality inspections prior to delivery. However, dangers can arise from the units if they are used improperly or not as intended by untrained personnel!
Please observe the following notes:
■ In the event of defects that
endanger the operational safety of the unit, operation must be discontinued immediately
■ Observe the respective local
electrical regulations and the necessary safety measures when using the units
■ Maintain safety distances to
combustible materials
0.5 m at the side of the unit and on the air inlet side
2.0 m on the air outlet side
■ An unobstructed air inlet and air
outlet must be guaranteed at all times
■ The units must not be covered
during operation
■ Never insert foreign objects into
the units
■ The units must not be operated
in the vicinity of bathtubs, showers, swimming pools etc.
■ The units must not be operated
directly below a wall socket
■ The units may not be exposed to
direct jets of water
The units must not be installed or
operated in potentially flammable or explosive environments
The units must not be operated
in locations where:
Combustible gaseous, air or dust-air mixtures could be produced; flammable small parts could be sucked in, set alight on the heating coil and blown out in a glowing state
Flooring and ceilings must be
fire retardant
The air inlet and outlet must not
be constricted
The relevant safety guidelines
of the Employer's Liability Insurance Association or property insurer must be observed
The units must be installed
in a stable position and must not topple over or slide out of position during operation
The units must not be left
unattended during operation
The units must not be operated
in an environment with an ambient temperature of over 60°C
■ All electrical cables for the
units must be protected against damage, even damage caused by animals
CAUTION
Extensions to the connection cable must only be conducted by authorised specialist electricians, taking into consideration the unit capacity, cable length and local use.
4
Commissioning
One person, who has been adequately trained in the handling of the units, should be tasked with the operation and monitoring of the units.
The units are equipped with a 3-stage operating switch.
1. Move the operating switch to the “0” position.
2. Connect the unit's power plug to a properly installed 16 A mains socket.
NOTE
The electrical connection for the units must be made at a separate feed point with a residual current device in accordance with VDE 0100, Section 55.
Heating without room thermostat
The units are operating in permanent operating mode.
1. Connect the supplied strapping plug [2] to the thermostat socket [1] on the unit.
1
2
Heating with a special purpose HT room thermostat or duct thermostat (accessories)
The units operate fully automatically and according to the air outlet/room temperature.
1. Pull out the strapping plug [2].
2. Connect the plug [3] of the relevant thermostat to the thermostat socket [1] on the unit.
1
3
3. Place the probe in a suitable position according to the type of thermostat used. The thermostat probe must not be located directly in the warm air flow and must not be placed directly on the cold floor.
4. On the room thermostat, set the temperature required for the application at hand.
5. Move the operating switch to the “2” (Heating) position.
GREEN indicator light on!
Operating lights
1 2 3
Adjust the air outlet temperature
Upon start-up, set the fan speed to the maximum setting.
If the
YELLOW
light up after an operating time of approx. 5 minutes, please decrease the fan speed by approx. 10%.
If the
yellow
up after another 5 minutes, repeat the previous procedure until the
YELLOW HT operating light
continuously lit.
The unit has now been optimally adapted to the ambient conditions and is operating in high­temperature mode at approx. 100-120°C.
Safety in the event of excessive temperature
If the operating conditions change in permanent operating mode and the temperature at the air outlet exceeds 120°C, the unit reverts to a heating capacity of 7 kW automatically. The
GREEN indicator light
the
YELLOW
In this case, we recommend checking the operating conditions or increasing the speed by 10% until the max. heating capacity is reactivated.
light does not
light has still not lit
is
goes out,
one remains lit.
GREEN indicator light on!
2. Move the operating switch to the “2” (Heating) position.
GREEN indicator light on!
1 = HT mode 2 = max. heating capacity 3 = STB fault
YELLOW
GREEN RED
In the event of serious heat build-up caused by, for example, a constricted air outlet, a lack of unrestricted air intake or the fan being at a standstill, the safety thermostat switches the unit off. This needs to be manually unlocked once the fault has been rectified and the unit has cooled down.
5
REMKO ELT 10-HT
Ventilation only operation
Only the supply air fan operates in this setting. Thermostatic regulation and heating operation are not possible in this operating mode.
Move the operating switch to the “1” position.
The fan speed can likewise be changed in this mode.
Operation with a warm air hose
The units are equipped with a special-purpose high performance axial fan.
This opens up the possibility of operating the unit with an HT warm air hose with a Ø of 205 mm and a length of 7.6 m to transport the heated air efficiently and effectively to the place where it is required.
Care and maintenance
Regular care and observation of some basic requirements will ensure trouble-free operation and a long service life of the units.
!
CAUTION
Before undertaking any work on the units, the power plug must be removed from the mains socket.
In accordance with the
operating conditions, the units must, if necessary, be checked at least yearly by a specialist to ensure that they are in a condition that is safe to use
Keep the units free of dust and
other debris
Only clean the units with a dry
or moistened cloth
Shutdown
1. Move the operating switch to the “0” position.
2. If the units are inactive for long
periods, disconnect them from the mains power supply.
3. The supply air fan may run
on to cool the units and only switch off after the cooling down phase is complete.
4. If the units need to be stored, clean them and, if necessary, cover them with a plastic sheet/ film or cotton cloth and store in a sheltered and dry storage location.
Only warm air hoses (accessories) that have been approved by Remko may be used as these have been designed specifically for these high temperature units.
Note about the assembly of the warm air hose
Only special-purpose high-
temperature hoses may be used
Make sure that the unit’s outlet
nozzle is securely fastened
There should be no kinks or
bends in the hose lines in order to prevent hot-spots forming
Make sure that the air outlet at
the end of the hose is clear at all times
Never subject to direct jets of
water.
e.g. pressure washers etc.
Never use abrasive or solvent-
based cleaners
Use only suitable cleaners, even
for heavy contamination
Check the inlet and outlet grille
for contamination on a regular basis
Check the safety equipment
and protective devices on a regular basis
Be careful not to damage
the temperature controllers’ probes or capillary tubes when removing or mounting the protective exhaust grid
!
CAUTION
An electrical safety check must be carried out in accordance with VDE 0701 after any work on the units.
6
Troubleshooting
The unit (fan) does not start.
Intended use
Customer service and guarantee
1. Check the mains fuses on site.
2. Check the control fuse on the rear panel of the unit.
3. Check the power plug.
4. Check the operating switch.
5. Check that the air circulating fan can move freely.
The unit does not heat up.
1. Check the operating switch.
2. Check that the contactors are functioning correctly.
3. Check that the temperature controller is functioning correctly and check the capillary tube for damage.
4. Check whether the safety thermostat has triggered or check the capillary tube for damage.
5. Check that the thermostat and the strapping plug are in place.
6. When operating the unit with a room thermostat, set the thermostat to a temperature that is above the room temperature.
If all of the functional checks have been carried out without any findings, please contact an authorised service station.
NOTE
Adjustment and maintenance work may only be carried out
by authorised and qualified
technicians.
The units are designed exclusively for heating and ventilation purposes in industrial or commercial use (not for living space heating in private use) on the basis of their structural design and equipment. The units must only be operated by appropriately instructed personnel.
With non-observance of the manufacturer's specifications, the respective local legal requirements or after arbitrary alterations to the units, the manufacturer shall not be liable for resulting damages.
NOTE
Operation other than the types listed in this operating manual is prohibited. With non-observance, any manufacturer liability or guarantee claims are voided.
!
CAUTION
Safety devices
must not be bypassed or
disabled.
!
CAUTION
Copyright The redistribution, even in part, or the use of this documentation for purposes other than intended is prohibited without the written authorisation of
Co. KG
.
REMKO GmbH &
As a prerequisite for any guarantee claims to be considered, it is essential that the ordering party or its representative completes and returns the “Certificate of guarantee” to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The units were tested at the factory several times to verify their correct function. However, if malfunctions should arise that cannot be remedied by the operator with the assistance of the troubleshooting section, please contact your specialist dealer or contractual partner.
Environmental protection and recycling
Disposal of packaging
When disposing of packaging material, please consider our environment. Our units are carefully packed and delivered in sturdy transport packaging made from cardboard and polystyrene. The packaging materials are environmentally-friendly and can be recycled. By recycling packaging materials, you make a valuable contribution to the reduction of waste and conservation of raw materials.
Therefore, only dispose of packaging material at appropriate collection points.
7
REMKO ELT 10-HT
C1
H1
Grün
Black
X2:3
X2:4
KL:L1
4
1
4
2
TH
dT/120°C
C
TL
dT/80°C
F1
6.3Amp
N
N
N
H2
Gelb
N
H3
Rot
3
1
2
M
Braun
Blau
Blau
U2
U1
X2:2
1
4
2
STB
dT/100°C
Z
Braun
Fuse
13
14
X2:1
STB 100°C
HT-Betrieb ab 80°C
Grünlicht an = 10,5 kW Power ab 120°C Grünlicht aus = 7 kW Power
HW1
HW2
400 V / 3 ~ N/50H z
1 2 4 53
L1 L2 L3 N PE
7 kW 3,5 kW
EMV Filter
Poti 150kW
Leistungsregler
13
A2
A1
A2
A1
14
1
3
5
2 4 6 2 4 6
1
3
5
1 0 2
S1
2
1
1 2
A1
A2
A1
A2
1
2
NK
dT/37°C
5 6 3 4
1 2
X3
X3
~
KL
K2K1
K2K1
K2
K1
RT
h
N
Betriebs-
stundenzähler
optional
Fuse
1 = Ventilation 2 = Heating
HT mode from 80°C
Operating hours
counter
Power controller
EMC lter
Green light on = 10.5 kW power
From 120°C, green light o󰀨 = 7 kW power
optional
Yellow Red
Green
Blue
Blue
Brown
Black
Brown
6×2.5 mm
2
Electrical wiring diagram
Legend:
C1 = Condenser HW = Special-purpose heating insert KL = Connection terminal strip K1 = Contactor 1 K2 = Contactor 2 M = Fan motor NK = Aftercooler thermostat RT = Thermostat receptacle S1 = Operating switch STB = Safety thermostat TH = Temperature controller TL = Temperature controller
8
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
Maintenance protocol
Unit type: .................................. Unit number: ...................................
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
Unit cleaned - outside -
Unit cleaned - inside -
Fan blade cleaned
Protection grid cleaned
Safety equipment checked
Safety devices checked
Unit checked for damage
All fastening screws checked
Electrical safety check
Test run
Comments:.....................................................................................................................................................
............................................................................................................................................................................
............................................................................................................................................................................
1. Date: .................
..............................
Signature
6. Date: .................
..............................
Signature
11. Date: .................
..............................
Signature
2. Date: .................
..............................
Signature
7. Date: .................
..............................
Signature
12. Date: ................
..............................
Signature
3. Date: .................
..............................
Signature
8. Date: .................
..............................
Signature
13. Date: ................
..............................
Signature
4. Date: ..............
..............................
Signature
9. Date: .................
..............................
Signature
14. Date: ................
..............................
Signature
5. Date: .................
..............................
Signature
10. Date:
.................
..............................
Signature
15. Date: ...............
..............................
Signature
16. Date: .................
..............................
Signature
Unit to be maintained only by authorised specialists in accordance with the statutory regulations.
17. Date: ................
..............................
Signature
18. Date: ................
..............................
Signature
19. Date: ................
..............................
Signature
20. Date: ...............
..............................
Signature
9
REMKO ELT 10-HT
Exploded view of the unit
1
2
3 (3a)
2
36
4
8
34
14
15
13
16
11
17
6
33
2312
22
9
24
25
26
27
30
28
29
32
35
31
21
10
18
5
10
2019
We reserve the right to modify the dimensions and design as part of the ongoing technical development process.
7
Spare parts list
No. Designation EDP
1 Transport handle 2 Reinforcement plate 3 Outer casing ELT 10-HT 3a Outer casing ELT 10-HT INOX 4 Front panel with outlet nozzle 5 Floor panel 6 Front plate of floor panel 7 Support plate, right 8 Heating insert assembly 9 Back wall 10 Support plate, left 11 Inner casing with outlet cone
EDP no. on
request
12 Cover plate for STB 13 Mounting plate 14 Terminal block 6er (6 mm²) 15 Contactor 16 Aftercooler thermostat 17 Control thermostat with probe
18 Safety clamp for mains cable 19 EMC filter 20 Terminal block 5er (16mm²)
No. Designation EDP
21 Grommet for mains cable
Fan with motor and protection
22
grid
23 Condenser 24 “RED” light (STB fault) 25
“GREEN” light (max. heating capacity) 26 “YELLOW” light (HT mode) 27 Thermostat receptacle assembly 28 6.3 A control fuse 29 Speed controller adjusting knob 30 Operating switch 1-0-2 31 Speed control film
EDP no. on
32 Mains cable with plug 33 M012 speed control 34 Terminal block 6er (1.5 mm²) 35 Speed controller 36 Safety thermostat STB
Not
illustrated
Not
illustrated
Not
illustrated
Thermostat plug
Strapping plug
Operating hours counter
request
When ordering spare parts, please state the EDP no., unit number and type (see name plate)!
Technical data
Series ELT 10-HT
Nominal heat capacity kW 10.5
Switchable heating capacity kW Thermodynamic
Air volume m3/h 400-900
Air outlet temperature °C up to 120
Maximum ambient temperature °C 60
Power supply V/Hz 400/3~N / 50
Max. rated current A 15.9
Max. power consumption kW 11
Electrical protection (provided by the customer) A (slow) 16
Sound pressure level LpA 1m
Dimensions: Length mm 750
Width mm 305
Height mm 500
Weight kg 18.0
1)
dB (A) 70
1)
Noise level measurement DIN 45635 - 01 - KL 3
11
REMKO INTERNATIONAL
... and also right in your neighbourhood! Take advantage of our experience and advice
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Fax +49 5232 606-260 E-mail info@remko.de Internet www.remko.de
Consulting
Thanks to intensive training,
our consultants are always
completely up-to-date when
it comes to technical expertise.
This has given us the reputation
of being more than just
an excellent, reliable supplier:
REMKO, a partner who helps
to solve problems.
Sales
REMKO offers not just a well
established sales network both
nationally and internationally, but
also has exceptionally highly-
qualified sales specialists.
REMKO employees in the
field are more than just sales
people: above all, they must
be advisers to our customers
in air conditioning and heating
technology.
Customer service
Our units operate precisely and
reliably. However, in the event of
a malfunction REMKO customer
service is quickly on the scene. Our
extensive network of experienced
dealers guarantees quick and
reliable service.
We reserve the right to make technical changes and provide no warranty as to the accuracy of this data!