REMKO EFS 25 User Manual

Assembly and operating instructions
REMKO fresh water station EFS 25
Instructions for user and specialist
0039-2013-04 Edition 1, en_GB
Read the instructions prior to performing any task!
Read these operating instructions carefully before commis­sioning / using this device!
These instructions are an integral part of the system and must always be kept near or on the device.
Subject to modifications; No liability accepted for errors or mis­prints!
Installation and operating instructions (translation of the orig­inal)

Table of contents

1 Safety and usage instructions............................................................................................................. 4
1.1 General safety notes....................................................................................................................... 4
1.2 Identification of notes...................................................................................................................... 4
1.3 Personnel qualifications.................................................................................................................. 4
1.4 Dangers of failure to observe the safety notes................................................................................ 4
1.5 Safety-conscious working............................................................................................................... 4
1.6 Safety instructions for the operator................................................................................................. 5
1.7 Safety notes for installation and inspection tasks........................................................................... 5
1.8 Unauthorised modification and changes......................................................................................... 5
1.9 Intended use................................................................................................................................... 6
1.10 Safety-conscious working............................................................................................................. 4
1.11 Warranty........................................................................................................................................ 6
1.12 Transportation and packaging....................................................................................................... 6
1.13 Environmental protection and recycling........................................................................................ 6
2 Technical data....................................................................................................................................... 7
2.1 Unit data.......................................................................................................................................... 7
2.2 Pressure loss characteristic curve.................................................................................................. 8
3 Unit description..................................................................................................................................... 9
4
Design and planning........................................................................................................................... 10
4.1 General Information...................................................................................................................... 10
4.2 Design of the storage tank............................................................................................................ 11
5 Circulation operation.......................................................................................................................... 12
6 Assembly and installation (Specialist).............................................................................................. 12
7 Commissioning (specialist)............................................................................................................... 14
7.1 General Information...................................................................................................................... 14
7.2 Filling the primary circuit............................................................................................................... 14
7.3 Commissioning the controller........................................................................................................ 15
7.4 Maximum dispensing medium flow rate........................................................................................ 16
7.5 Setting the Temperature............................................................................................................... 18
7.6 Commissioning report................................................................................................................... 19
8 Maintenance........................................................................................................................................ 19
9 Depiction of spare parts (specialist)................................................................................................. 20
10 Index..................................................................................................................................................... 22
3
REMKO fresh water station
1
1.1
Carefully read the operating manual before com­missioning the units for the first time. It contains useful tips and notes such as hazard warnings to prevent personal injury and material damage. Failure to follow the directions in this manual not only presents a danger to people, the environment and the system itself, but will void any claims for liability.
Keep this operating manual and the refrigerant data sheet near to the units.
1.2
This section provides an overview of all important safety aspects for proper protection of people and safe and fault-free operation.The instructions and safety notes contained within this manual must be observed in order to prevent accidents, personal injury and material damage.
Notes attached directly to the units must be observed in their entirety and be kept in a fully legible condition.
Safety notes in this manual are indicated by sym­bols. Safety notes are introduced with signal words which help to highlight the magnitude of the danger in question.

Safety and usage instructions

General safety notes

Identification of notes

DANGER!
CAUTION!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause injury or mate­rial and environmental damage.
NOTICE!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may cause material and environmental damage.
This symbol highlights useful tips and recom­mendations as well as information for efficient and fault-free operation.
1.3

Personnel qualifications

Personnel responsible for commissioning, opera­tion, maintenance, inspection and installation must be able to demonstrate that they hold a qualifica­tion which proves their ability to undertake the work.
Contact with live parts poses an immediate danger of death due to electric shock. Damage to the insulation or individual components may pose a danger of death.
DANGER!
This combination of symbol and signal word warns of a situation in which there is immediate danger, which if not avoided may be fatal or cause serious injury.
WARNING!
This combination of symbol and signal word warns of a potentially hazardous situation, which if not avoided may be fatal or cause serious injury.
Dangers of failure to observe
1.4 the safety notes
Failure to observe the safety notes may pose a risk to people, the environment and the units. Failure to observe the safety notes may void any claims for damages.
In particular, failure to observe the safety notes may pose the following risks:
n The failure of important unit functions. n The failure of prescribed methods of mainte-
nance and repair.
n Danger to people on account of electrical and
mechanical effects.
1.5

Safety-conscious working

The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.
4
Safety instructions for the oper-
1.6 ator
The operational safety of the units and compo­nents is only assured providing they are used as intended and in a fully assembled state.
n The units and components may only be set up,
installed and maintained by qualified per­sonnel.
n The existing regulations concerning accident
prevention must be adhered to.
n Do not operate units or components with
obvious defects or signs of damage.
n Contact with equipment parts or components
can lead to burns or injury.
n Ensure that electrical energy does not pose a
risk.
n Regulations of the VDE and the local energy
supply company must be adhered to.
NOTICE!
Material damage due to mineral oils!
Mineral oil products permanently damage EPDM seal elements; the sealing properties may therefore be lost. We do not take respon­sibility or provide warranty replacements for damage caused by seals that are damaged in this way.
It is essential that you prevent EPDM from
coming into contact with mineral oil sub­stances.
Use a lubricant that is free of mineral oil
and has a silicone or polyalkylene basis, such as Unisilkon L250L and Syntheso Glep 1 made by Klüber, or a silicon spray.
Safety notes for installation and
1.7 inspection tasks
n The operator must ensure that all inspection
and installation work is carried out by author­ised and qualified personnel who have thor­oughly read the operating manual.
n Works on the pump/system may only be car-
ried out whilst at a standstill as a matter of prin­ciple.
n Appropriate hazard prevention measures must
be taken to prevent risks to people when per­forming installation, repair, maintenance or cleaning work on the units.
n The setup, connection and operation of the
units and its components must be undertaken in accordance with the usage and operating conditions stipulated in this manual and comply with all applicable regional regulations.
n Regional regulations and laws as well as the
Water Ecology Act must be observed.
n The power supply should be adapted to the
requirements of the units.
n The units and components must be kept at an
adequate distance from flammable, explosive, combustible, abrasive and dirty areas or atmospheres.
n Safety devices may not be modified or
bypassed.
NOTICE!
Malfunction!
The fresh water module must be integrated into the equipotential bonding system of the elec­trical installation. If this is not ensured by the pipe network, set up an approved potential equalisation connection to the main potential connection.
Unauthorised modification and
1.8 changes
The operational safety of the fresh water module that was delivered is guaranteed only with intended use in accordance with section 1.8 of the operating instructions. Under no circumstances should the threshold values specified in the data­sheet be exceeded.
Modifications or changes to units and components are not permitted and may cause malfunctions. Safety devices may not be modified or bypassed. Original replacement parts and accessories authorised by the manufacturer ensure safety. The use of other parts may invalidate liability for resulting consequences.
5
REMKO fresh water station
1.9

Intended use

The fresh water module is only permitted to be installed in heating systems between the buffer tank and the domestic water circuit. Depending on the design, it may only be installed and operated vertically!
Use only REMKO accessories in conjunction with the fresh water module.
Any different or additional use is a non-intended use. The manufacturer/supplier assumes no lia­bility for damages arising from a non-intended use. The user bears the sole risk in such cases. Intended use also includes working in accordance with the operating and installation instructions and complying with the maintenance requirements.
The threshold values specified in the technical data must not be exceeded.
1.10
The safety notes contained in this manual, the existing national regulations concerning accident prevention as well as any internal company working, operating and safety regulations must be observed.

Safety-conscious working

WARNING!
Plastic films and bags etc. are dangerous toys for children!
Why:
- Leave packaging material are not around.
- Packaging material may not be accessible to children!
1.13
Disposing of packaging
All products are packed for transport in environ­mentally friendly materials. Make a valuable contri­bution to reducing waste and sustaining raw mate­rials. Only dispose of packaging at approved collection points.

Environmental protection and recycling

1.11
For warranty claims to be considered, it is essential that the ordering party or its representative com­plete and return the "certificate of warranty" to REMKO GmbH & Co. KG at the time when the units are purchased and commissioned.
The warranty conditions are detailed in the "Gen­eral business and delivery conditions". Further­more, only the parties to a contract can conclude special agreements beyond these conditions. In this case, contact your contractual partner in the first instance.
1.12

Warranty

Transportation and pack­aging
The units are shipped in sturdy transport pack­aging or within the heat pump housing. Immedi­ately check the units on delivery and make a note of any damage or missing parts on the delivery note. Inform the forwarding agent and contractual partner. Claims under guarantee made at a later date will not be accepted.
Disposing of the units and their components
For the manufacture of the units and components, only recyclable materials have been used. Help protect the environment by ensuring that the units or components (for example batteries) are not dis­posed of in household waste, but only in accord­ance with local regulations and in an environmen­tally safe manner, e.g. using authorised disposal and recycling specialists or council collection points.
6
2
2.1
Series EFS 25
Operating data
Maximum permitted pressure, primary bar 3
Maximum permitted pressure, secondary bar 10
Operating temperature °C 2-95
Pipe connections
Primary circuit (tank circuit) Inches 3/4" inside thread
Secondary circuit (domestic water circuit) Inches 3/4" outside thread, flat-sealing
Equipment
Gravity brake mmWS 200
Primary pump
Secondary pump

Technical data

Unit data

HE pump with
PWM control, 5-63 watts
(optional) HE pump with
PWM control, 5-63 watts
Heat exchanger 30 Plates
Medium flow rate probe 1 x VFS 2.40
Temperature probe Pt 1000, fast
Materials
Valves Brass
Seals: O-rings EPDM
Flat seals AFM 34, asbestos-free
Plate heat exchanger
Insulation EPP
Gravity brake Hostaform
Stainless steel 1.4400/solder:
99.99% Cu
7
A
B
C
[mWS]
[kPa]
]h/l[
0,0
4,9
9,8
14,7
19,6
24,5
29,4
34,3
39,2
44,1
49,0
53,9
58,8
63,7
68,6
73,5
78,4
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
5,5
6,0
6,5
7,0
7,5
8,0
0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300
Sekundär
kvs = 2,27
Primär
kvs = 2,65
Grundfos UPM2 15-75 CIL
REMKO fresh water station
Unit data (continued)
Series EFS 25
Dimensions
Height (with insulation) mm 645
Width (with insulation) mm 344
Depth (with insulation) mm 249
Top axis-centre distance mm 86
Bottom axis-centre distance mm 47
Height (with circulation, vertical installation) mm 1115
Height (with circulation, horizontal installation) mm 943
Pressure loss characteristic
2.2 curve
Fig. 1: Pressure loss characteristic curve
A: Pressure [mWS] B: Medium flow rate [l/h] C: Pressure [kPa]
8
A
B
C
D
1
2
3
4
7
6
8
9
10
11
5
3
The fresh water station is a pre-installed valve group that was checked for leak tightness; it is used to transfer heat between the buffer tank and the domestic water circuit. It contains a pre-set controller and important valves for operating the system:
n Ball valves in the primary circuit n Piston valves in the secondary circuit n Safety valve in the secondary circuit n Pre-installed controller n Temperature probe on the cold water supply n Temperature probe on the heating supply n Ultrasonic flow rate meter on the domestic hot
n Primary pump that can be shut off n Ball valve for filling/drainage, for bleeding the

Unit description

water outlet
heat exchanger and the pump
NOTICE!
A check for pressure and leak tightness after successful installation must always be per­formed before commissioning
Fig. 2: Product description
A: Secondary side: Hot water outlet B: Primary side: Inlet from the buffer tank C: Primary side: Return flow to the buffer tank D: Secondary side: Cold water inlet 1: Piston valve (hot water outlet) 2: Fill/drain valve 3: Safety valve, 10 bar 4: Temperature probe, fast 5: Primary pump 6: Ball valve 7: Ball valve with gravity brake 8: Analogue medium flow rate temperature probe
VFS 2-40 9: Heat exchanger 10: Temperature probe, fast 11: Piston valve (cold water inlet)
9
D
A B C
EFS HGU
RES
M
AB
A
B
A42
REMKO fresh water station
4
4.1
The fresh water station is a fresh water module that heats domestic water according to the contin­uous flow heater principle. In order to ensure fault­free operation of the fresh water station, the system must fulfil certain prerequisites. Before installation, take some time for planning.
Installation example
The operating mode can be bivalent alternative.
This hydraulic diagram serves merely to assist in planning activities; the hydraulic system on site must be planned and laid out by the installer! Subject to technical changes!

Design and planning

General Information

CAUTION!
Danger of scalding due to hot water!
Due to external circulation in the primary cir­cuit, water with a temperature of up to 90 °C can leak out at the dispensing connection.
No external pumps are permitted to be
installed between the fresh water module and the buffer tank.
The fresh water module is not permitted to
be connected to a heating cycle distributor.
Fig. 3: Fresh water station with optional circulation set and optional return distribution
A: Cold water B: Hot water
C: Heater heating cycle D: Circulation
10
4.2

Design of the storage tank

You can use the following table to calculate the approximate required volume of the buffer tank.
Temperature in buffer tank [°C] HW temperature [°C]
50 45 1.5
60
70
80
Sample calculation for the design of the buffer tank:
Temperature of buffer tank: 60 °C, required dispensing medium flow rate at water valve: 20 l/min DHW temperature set on the controller: 45 °C How large must the Storage tank be if a 20-minute dispensing operation is to take place without reheating? 20 l/min x 20 min = 400 l
set in controller
45 0.9
50 1.2
55 1.6
45 0.7
50 0.9
55 1.0
45 0.6
50 0.7
55 0.8
Reqd. Storage tank volume per
litre of HW [Litre]
400 l x 0,9 = 360 l ð The heated part of the buffer tank must be 360 litres in size.
The hot water volume depends on the position of the installed S 08 probe (Smart Control hot water probe). The higher this is installed on the buffer tank, the lower the hot water volume.
11
REMKO fresh water station
5
The fresh water station is (optionally) equipped with a circulation pump. Three possible operating modes are stored in the controller to operate the circulation pump (also see the operating instruc­tions of the controller).
n Pulse-controlled operation (as necessary /
n Time-dependent operation:
n Temperature-dependent operation:
Any of the operating modes can be combined, e.g. time-dependent and temperature-dependent oper­ation. In this case, circulation is only active if the temperature falls below the temperature on the cir­culation temperature probe and the time window is active. Outside this time window, the circulation pump can be activated via a dispensing pulse if pulse-controlled operation is also activated.

Circulation operation

requirement): Actuating a hot water dispensing connection
for a short time (dispensing impulse: ~2 sec­onds) starts the circulation pump. The circula­tion pump then runs for a few minutes (adjust­able).
Operation of the circulation pump can be adjusted on a weekly timer within a freely­selectable period. In this operating mode, cir­culation begins at the start of the period that is set. Circulation is deactivated after the set period expires.
In this operating mode, circulation is only started if the temperature falls below the min­imum temperature that can be set on the circu­lation temperature probe within the operation period. Circulation is deactivated after the adjustable target temperature is reached or after the set period expires.
NOTICE!
In the delivered state, circulation is not acti­vated (see the operating instructions of the controller). If the REMKO circulation pump is installed, the operating mode must be activated urgently. The speed of the circulation pump must be specified via the PWM signal. ( Fac­tory setting: 0 % ).
6
If the fresh water station is not installed directly on the storage tank, note the following points:
1. Determine the installation location of the
2. Transfer the dimensions for the holes to the
3. Drill the holes and insert the enclosed wall
4. Turn the screws into the wall plugs until
5. Remove the front insulation jacket.
Assembly and installa­tion (Specialist)
DANGER!
Danger due to electric shock!
Remove the power plug before carrying out
electrical work on the controller!
Plug the power plug of the controller back
in to a socket only after completing all installation works. In this way, you can pre­vent the motors from starting up acciden­tally.
NOTICE!
To avoid damage to the system, the installation location must be dry, capable of carrying the load and frost-free.
fresh water module near to the buffer tank. On the heating side, the pipes must not exceed a length of 4 m for DN 20.
wall. A corresponding drilling template is pro­vided on the board under the fresh water module
plugs.
around 40 mm is sticking out of the wall.
12
A
B
Fig. 4: Distance between the holes
6. Hang the fresh water module onto the screws. Tighten the screws so that the insu­lation on the sides is flush to the wall.
7. Connect the pipes of the fresh water module to the system in accordance with Fig. 5.
1. Secondary side: Hot water outlet, Connection ¾" AG, flat-sealing
2. Primary side: Inlet from buffer tank, ¾" IG, Piping at least DN 20 22 x 1 mm, recommended DN 25 28 x 1.5 mm
3. Primary side: Return flow to buffer tank, ¾" IG, Piping at least DN 20 22 x 1 mm, recommended DN 25 28 x 1.5 mm
4. Secondary side: Cold water inlet, Connection ¾" AG, flat-sealing
Fig. 5: Piping of the fresh water station
A: Pipe distance from the wall
(secondary) = 107 mm
B: Pipe distance from the wall (primary) = 67 mm
13
B
A
C
45°
90°
14
REMKO fresh water station
7
7.1
NOTE:
Open the valves in the pipes and the fresh water station slowly, in order to prevent pressure shocks.
Function of the gravity brake
The primary circuit is equipped with a gravity brake in the ball valve, in order to prevent undesired gravity circulation.
The gravity brake must be opened to bleed and clean the system. To do this, turn the ball valve to the 45° position. The gravity brake is out of opera­tion.
All ball valves and valves must be opened com-
pletely (0°) in order to operate the system.

Commissioning (specialist)

General Information

7.2

Filling the primary circuit

If the storage tank is (partially) filled
CAUTION!
Danger of scalding due to hot water!
The system is under pressure. By opening the ball valve for filling/drainage, water of up to 90 °C can leak out of the ball valve for filling/ drainage, which may cause bodily injury.
Open the ball valve for filling/drainage
slowly and from a safe distance.
1. Open the ball valve (F) by turning it to the position.
2. Fill the storage tank using the filling valves provided by the customer until you reach an operating pressure of 1.5 bar*. Use the heating water in accordance with VDI 2035 / ÖNorm H5195-1.
3. Connect a hose to the ball valve for filling/ drainage (B). Carefully actuate the ball valve for filling/drainage (B) and allow the air to bleed out.
4. Connect the ball valve for filling/drainage (B).
5. Close the ball valve (F) by turning it to the 90° position.
6. Open the ball valve (G) slowly by turning it to the 45° position.
7. Carefully actuate the ball valve for filling/
drainage (B) and allow the air to bleed out.
8. Connect the ball valve for filling/drainage (B).
9. After bleeding, check the operating pressure
of the storage tank and increase it if neces­sary.
10. Open the ball valves (F) and (G) completely by turning them to the position.
Fig. 6: Setting the gravity brake
A: 0° position - Gravity brake in Operation, only
flowing in flow direction.
B: 45° position - Gravity brake out of Operation,
flowing in both directions.
C: 90° position - Ball valve closed, no flow.
1.5 bar in the primary circuit = recommended
minimum value. The system pressures that depend on the design
and the components of the heating system are also crucial for the pressure
14
B
AL
F
G
7.3

Commissioning the controller

DANGER!
Danger due to electric shock!
Check whether the probes and pumps to the controller are connected and whether the con­troller housing is closed. Only then should you insert the power plug into the socket.
1. Remove the controller's front panel (see the controller instructions).
2. In the selection menu of the controller, select manual operation ("H1"). Switch the PWM signal of the pump on ("100 %").
3. Allow the pump to run for a few minutes in order to bleed the FriwaMini.
4. If you continue to hear air noises after this, connect a hose to the ball valve for filling/ drainage (B). Carefully actuate the ball valve for filling/drainage (B) while the pump is still running and allow the air to bleed out.
5. If you no longer hear any air noises, switch the pump off. To do this, select manual oper­ation ("H1") in the selection menu of the con­troller.
6. Set the pump to automatic operation ("A").
7. Slowly open the piston valves on the secon-
dary side (A and L).
8. Open a domestic hot water dispensing con­nection (e.g. water valve) with a flow of at least 10 l per minute and allow the water to run for around 2 minutes, in order to bleed the secondary circuit. Then close all dis­pensing connections in the secondary circuit.
9. Use the pre-assembled power supply cable to connect the fresh water station to the mains (230 V, 50 Hz).
10. Ensure that the fresh water station is cor­rectly included in the equipotential bonding of the system.
11. Set the required domestic hot water tempera­ture on the controller (see the following page).
12. The fresh water station is now ready for oper­ation.
Fig. 7: Commissioning the controller
15
B
[kW]
Friwa EFS 25
0
10
20
30
40
50
60
A
[l/min]
0
20
40
60
80
100
120
140
REMKO fresh water station
7.4

Maximum dispensing medium flow rate

The following diagram shows the maximum dispensing medium flow rate depending on the storage tank temperature; this assumes a pre-set hot water temperature of 45 °C at the dispensing connection. The inte­grated controller prevents the temperature from decreasing as long as the maximum medium flow rate is not exceeded.
Fig. 8: Maximum dispensing medium flow rate
A: Dispensing medium flow rate [l/min] B: Power [kW]
Boundary conditions: Cold water temperature: 10 °C, Maximum pressure loss on the domestic water
side of the fresh water station: 1000 mbar The following examples explain the relationships
between the individual variables of the hot water temperature, the dispensing medium flow rate and the buffer tank temperature, and show how these affect the transmission capacity of the fresh water station.
The hot water temperature that is set in the Smart Control controller (S 08 probe) is the ref­erence temperature for the buffer tank. Factory setting: 45 °C.
Example 1
Hot water temperature at the dispensing connec­tion: 45 °C
Temperature in the buffer tank: 50 °C ð Maximum dispensing medium flow rate: 18 l/
min, transmission capacity: 44 kW
Example 2
Hot water temperature at the dispensing connec­tion: 45 °C
Maximum dispensing medium flow rate: 25 l/min ð Temperature in the buffer tank: 60 °C, transmis-
sion capacity: 62 kW
16
The following diagram shows the maximum dispensing medium flow rate if the hot water temperature is 45
A
B
[l/min]
[kW]
Friwa EFS 25
°C at the dispensing connection, after being mixed with cold water with a temperature of 10 °C. The hot water temperature set on the controller is 60 °C.
Fig. 9: Maximum dispensing medium flow rate
A: Dispensing medium flow rate [l/min] B: Power [kW]
Boundary conditions: Cold water temperature: 10 °C,
Example 1
Hot water temperature on the controller: 60 °C Temperature in the buffer tank: 70 °C ð Maximum dispensing medium flow rate: 31 l/
min, transmission capacity: 74 kW
Example 2
Hot water temperature on the controller: 60 °C Maximum dispensing medium flow rate: 25 l/min ð Temperature in the buffer tank: ~65 °C, trans-
mission capacity: 60 kW
17
REMKO fresh water station
7.5

Setting the Temperature

Set the required (maximum) domestic hot water temperature on the controller under "Para". To ensure that scalding cannot occur at the water valve, the maximum hot water temperature must not
exceed 60 °C.
Primary side
The temperature required in the buffer tank on the primary side depends on the desired hot water tempera­ture and the required dispensing quantity. The temperature in the buffer tank must be at least 5 K above the required hot water temperature.
Secondary side
The possible dispensing medium flow rate [l/min] on the water valve depends on the hot water temperature that is set in the controller and the temperature that is available in the storage tank.
The recommended maximum domestic water medium flow rate through the fresh water module is 25 l/min. The following table shows the relationship between the storage tank temperature and the maximum dis-
pensing medium flow rate that is connected when the temperature on the valve is 45°C (e.g. single-lever mixer). If the hot water temperature that is set on the Controller is higher than 45 °C, the dispensing medium flow rate consists of a mixture of hot and cold water.
The transmission capacity that is specified for this is required to warm the water quantity of the dispensing medium flow rate [l/min] from 10 °C to 45 °C.
Temperature in
buffer tank probe
S08
[°C]
HW temperature
set on the con-
troller
[°C]
Maximum medium
flow rate from the
fresh water sta-
tion with the set
HW temperature
[l/min]
Maximum dis-
pensing medium
flow rate at the
water valve for an
HW Temperature
of 45 °C
[l/min]
Transmission
capacity of the
fresh water sta-
tion
[kW]
50 45 18 18 44
45 30 30 73
60
70
80
Reheating is not considered if the cold water tem­perature is 10 °C
50 23 27 64
55 17 22 52
45 38* 38 92
50 33 37 91
55 27 34 84
60 22 31 74
45 38* 38 92
50 38* 43 105
55 35 45 109
60 30 42 102
* maximum medium flow rate: 25 l/min, pressure loss of the fresh water station is 1000 mbar in this case (higher values are possible in a limited way hydraulically).
18
7.6

Commissioning report

System operator
System location
Serial numbers
REMKO EFS25
- Medium flow rate probes
- Controller
- Software version
Primary piping Ø = mm l = m
Secondary piping Ø = mm l = m
Other installations
Are both circuits cleaned and bled properly? (no air noises in the pump)
Are all shut-off valves in the cold water supply opened?
Circulation set
q
Miscellaneous:
q
Return distribution set
q
Bled
q
Opened
q
Is pressure of at least 1.5 bar present on the primary side?
Is pressure of at least 2.5 bar present on the secondary side?
Is an error message shown on the display?
Installation operation
8
After each retroactive structural modification to the primary side (e.g. installing a dirt separator, a dirt trap or a mixing valve), you must start a new com­missioning procedure in the controller to ensure optimum regulation.
You should also carry out commissioning again after adjusting the mixing valve temperature.
A specialist must check that the safety valve is functioning correctly when commissioning and at least once per year.

Maintenance

Checked
q
Checked
q
No message
q
Date, Signature
19
2
3
7
1
3
4
7
4
5
6
8
REMKO fresh water station
9
Depiction of spare parts EFS 25

Depiction of spare parts (specialist)

Fig. 10: Spare parts EFS 25
We reserve the right to modify the dimensions and design as part of the ongoing technical development process
When ordering spare parts, please always state the EDP no., unit number and unit type (see name plate)!
20
Spare parts list EFS 25
2
1
A
No. Description EFS 25
1 Controller 260156-9
2 Grundfoss circulation pump UPM 2-15/75 CIL 2 260155-2
3 Screw-in probe 15 mm G 1/4 260155-3
4 Piston valve DN 15 260155-6
5 Safety valve (1/2" x 3/4") 10 bar 260155-5
6 Medium flow rate probe (analogue) 260155-1
7 Thermo ball valve DN 20 (3/4") 260155-4
8 Plate heat exchanger 260155-8
When ordering spare parts, please always state the EDP number, unit number and unit type (see name plate)!
Depiction of circulation pump spare parts
Fig. 11: Circulation pump spare parts
Circulation pump spare parts list
No. Description Circulation
pump
A Circulation pump (complete with pipe assembly) 259052
1 Circulation pump 260155-9
2 Piston valve 260155-6
Spare parts not illustrated
Control cable 260155-10
Powerline cable 260155-11
When ordering spare parts, please always state the EDP number, unit number and unit type (see name plate)!
21
REMKO fresh water station
10
C
Circulation operation.......................................... 12
Commissioning the controller............................. 15
Controller, commissioning ................................. 15
D
Design of the storage tank................................. 11
Dimensions.......................................................... 8
Dispensing medium flow rate, maximum .......... 16
E
Environmental protection..................................... 6
Equipment............................................................ 8
F
Filling the primary circuit.................................... 14
Function of the gravity brake.............................. 14
G
Gravity brake, function ...................................... 14
I
Intended use........................................................ 6
M
Maintenance...................................................... 19
Materials.............................................................. 8
Maximum dispensing medium flow rate............. 16
O
Operating data..................................................... 8
Ordering spare parts.......................................... 21
P
Packaging, disposal............................................. 6
Pipe connections.................................................. 8

Index

Pressure loss characteristic curve....................... 8
R
Recycling............................................................. 6
S
Safety
Dangers of failure to observe the safety
notes............................................................... 4
General........................................................... 4
Identification of notes...................................... 4
Instructions for the operator............................ 5
Note for inspection work................................. 5
Note for installation work
Personnel qualifications.................................. 4
Safety-conscious working........................... 4, 6
Unauthorised modification ............................. 5
Unauthorised replacement part manufacture.. 5
Set the temperature .......................................... 18
Setting the Temperature.................................... 18
Spare parts........................................................ 20
Storage tank, design.......................................... 11
U
Unit disposal........................................................ 6
W
Warranty.............................................................. 6
................................. 5
22
Consulting
Thanks to intensive training, our consultants are always completely up-to-date in terms of technical knowledge. This has given us the reputation of being more than just an excellent, reliable supplier: REMKO, a partner helping you find solutions to your problems.
Distribution
REMKO offers not just a well established sales network both nationally and internationally, but also has exceptionally highly­qualified sales specialists. REMKO field staff are more than just sales representatives: above all, they must act as advisers to our customers in air conditioning and heating technology.
SFlbCustomer Service
Our equipment operates precisely and reliably. However, in the event of a fault, REMKO customer service is quickly at the scene. Our comprehensive network of experienced dealers always guarantees quick and reliable service.
REMKO INTERNATIONAL
… and also right in your neighbourhood! Make use of our experience and advice
We reserve the right to make technical changes, and provide no guarantee as to the accuracy of this data!
REMKO GmbH & Co. KG Air conditioning and heating technology
Im Seelenkamp 12 D-32791 Lage Postfach 1827 D-32777 Lage Telephone +49 5232 606-0 Telefax +49 52 32 606-2 60 E-mail info@remko.de Website www.remko.de
Loading...