REMKO CMF, CMT Installation Manual

REMKO CMF / CMT
Installation Manual
INVERTER HEAT PUMPS
Edition D – V02/09 2-3
Contents
Carefully read these installation instructions prior to commissioning using the equipment!
These instructions are part of the unit and must always be stored in immediate vicinity of the placement location or on the unit.
Subject to modifi cations; No liability accepted for errors or misprints!
Safety notes
4
Heat pump general
5-9
Installation instructions
10-13
Hydraulic connection
14-15
Electrical connection
15-22
Connection of refrigerant lines
23
Commissioning
24-31
Care and maintenance
32
Troubleshooting
33-35
Unit dimensions
36-37
Characteristic curves
38-40
General terms
41-42
Technical data
43
Made by REMKO
3
REMKO CMF / CMT
Safety notes
These instructions are to be read through carefully before installing the device. They contain useful tips and information, which are designated by. Warning information designed to prevent risks to persons and property are highlighted by
Non-observance of this manual may endanger persons, the envi­ronment as well as the equipment itself and will void any claims for liability.
These instructions must be stored in the immediate vicinity of the device.
The unit and components may only be set up and installed by qualified personnel.
The setup, connection and operation of the unit and its components must be undertaken in accordance with the operat­ing conditions stipulated in this manual and comply with all ap­plicable local regulations.
It is prohibited to make modi­fications or changes to equip­ment or components supplied by REMKO as this may cause mal­functions and will lead to loss of any possible claims for liability.
The equipment and components should not be operated in areas where there is a heightened risk of damage. Observe the mini­mum clearances.
The electrical supply should be adapted to fulfil the require­ments of the unit.
The operational safety of the equipment and components is only assured providing they are used as intended and in a fully assembled state. Safety devices may not be modified or deacti­vated.
Operate of equipment or com­ponents with obvious defects or signs of damage is prohibited.
All housing parts and device openings, e.g. air inlets and outlets, may not be blocked by foreign items, fluids or gases.
The equipment and components must be kept at a safe distance to inflammable, explosive, com­bustible, aggressive and dirty areas or atmospheres.
Contact with equipment parts or components can lead to burns or injury.
Installation, repair and mainte­nance work should only be car­ried out by authorised specialists. Inspection and cleaning can be performed by the operator pro­viding the equipment is not live.
Appropriate hazard prevention measures are to be taken when performing installation, repair or maintenance, or cleaning work on the equipment.
The room must be properly ventilated before re-starting the equipment in the event that refrigerant leaks out from the indoor unit. Otherwise there is danger of suffocation.
Tripped circuit breakers may only be replaced by similarly con­structed models.
The units must be inspected by a service technician at least once annually.
In case of defects that endanger the operational safety of the unit, operation must be discon­tinued.
The units may only be installed at the points provided for this purpose on site.
The devices may only be at­tached to load-bearing struc­tures or walls.
Regulations such as the regional building regulations and the Water Ecology Act must be maintained.
4
Economical and environmen­tally-conscious heating
The burning of fossil-based energy sources in order to generate power creates severe consequences for the environment. A high percentage of fossil fuels is also problematic due to the limited resources of oil and gas and the price increases result­ing from this. For this reason, many people today are thinking both economically and environmentally­consciously in terms of heating.
The application of heat pump technology enables both of these concepts to be combined. It makes use of the energy which is perma­nently available in the air, water and soil and converts it into usable heating energy by means of input­ting electrical energy.
Heat pump general
Arguments for REMKO
Low heating costs in comparison to oil and gas
Heat pumps represent a contri­bution to environmental protec­tion
Lower CO2 emissions in com­parison to oil and gas heating
Numerous models are able to cool as well as heat
Low noise level of the outdoor unit
Flexible erection due to split system design
Negligible maintenance costs
Heat sources
There are essentially three heat sources that heat pumps can derive energy from. These are air, soil and groundwater. The air heat pumps have the advantage that the air source is available everywhere are in unlimited amounts an that it can be utilised free-of-charge. A disad­vantage is that the outside air is at its coldest when the heat require­ment is greatest. Brine heat pumps extract energy from the soil.
However, in order to generate a heat content of 4kW, it is only necessary to input approximately 1kW of electricity. The rest is made available free-of-charge by the environment.
This is undertaken in serpentine pipe networks which are laid ap­prox. 1m deep or placed by means of drilling. The disadvantage is the large space requirements for the serpentine pipe networks or the high cost of drilling. A permanent cooling of the soil is also possible.
Water heat pumps require two wells in order to obtain heat from the groundwater, one supply well and one dry well. The development of this source is not possible every­where, it is expensive and requires planning permission.
5
REMKO CMF / CMT
A heat pump is a device which makes use of a working medium to absorb ambient heat under low temperatures and transports this heat to a place where it can be of use for heating purposes. Heat pumps work according to the same principles as a refrigerator. The dif­ference is that the "waste product" of the refrigerator, the heat, is the goal in this case.
The main components of the refrigeration circuit consist of an evaporator, compressor, liquefier and expansion valve. Finned evaporators serve to evapo­rate the refrigerant at low pressure even at low heat source tem­peratures, thereby absorbing the ambient energy. In the compres­sor, the refrigerant is compressed to a higher pressure by means of applying electrical energy, thereby increasing it up the correct tem­perature level.Afterwards the hot refrigerant gas reaches the liquefier, a plate heat exchanger. Here the hot gas condenses and releases its heat to the heating system.The liquefied refrigerant is
Heat pump modes
Heat pumps can work in various operating modes.
Monovalent The heat pump is the sole heating appliance in the build­ing all year round.This mode is par­ticularly suitable for heating plants with low supply water temperatures and is primarily used in combina­tion with brine/water and water/ water heat pumps.
Single energy sourceThe heating system does not require a second­ary heating boiler. The heat pump covers a large proportion of the re­quired heating power. Occasionally, when it is extremely cold outside, an electrical booster heating system switches on in order to support the heat pump as required.
Bivalent parallel modeThe heat pump provides the entire heating energy down to a predetermined outdoor temperature. If the out­door temperature falls below this value, a secondary heating appli­ance switches on in order to sup­port the heat pump. This may take the form of alterna- tive operation with oil or gas-fired heating or regenerative operation utilising solar energy or wood fuel heating. This mode is possible for all heating systems.
then decompressed and cooled in a flow regulator, the expansion valve. Subsequently, the refrigerant flows back into the evaporator and the circuit is completed.
A heat pump manager is used in or­der to control the process, which in addition to all safety functions also provides fully automatic operation. The water circuit for the CMF Series indoor units includes a circulation pump, a plate heat exchanger, dirt trap, safety valve, manometer, filling and drain valve, automatic deaerator and flow monitor.The CMT Series is additionally equipped with a diaphragm expansion vessel, a three-way switching valve and a storage tank.
Wall and fl oor-mounted units, con­densation pans, condensate trough heating, 3-way switching valves, overfl ow valves and additional sensors are available as accessories.
Evaporation Liquefaction
Condensing
Decompression
Functional diagram heating inverter heat pump
Heat pump outdoor unit
Outdoor area
Heat pump indoor unit
Indoor area
6
Layout
Building type
Specifi c heating output in W/m
2
Passive energy house
approx. 10
Low-energy house built in 2002
approx. 40
according to energy conservation order regarding heat insulation 1995
approx. 60
Modern building constructed around 1984
approx. 80
Partially renovated old building constructed pre-1977
approx. 100
Non-renovated old building constructed pre-1977
approx. 200
The diagram with the heating ca­pacity characteristics shows a sim­plified linear heating requirement. A connecting line is drawn from the desired room temperature (20°C) and the point where the average low outdoor temperature (local low for the year) and the heat require­ment meets (in this case: -14°C and
7.4kW). The intersection of the two curves are plotted on the X axis and the temperature of the balance point is read off. In this case it is
-5°C.
The size of the submersion tube heater is the difference between the maximum heat requirement on the coldest days of the year and the heating output on these days. In the example, the required output is
7.4kW – 4.7kW = 2.7kW.
A residential home comprised of 160m² living-space and a heat requirement of 40 W/m² has been selected for the example design. A total of five persons live in the house. The heating load amounts to 160m
2
40W/m2=6,400W. Add­ing a drinking water allowance of 1 kW results in a required heating power of 7.4kW.
The dimensioning of the heat pump is given graphically on the diagram below together with the outdoor­temperature-dependent building heat requirements and the heating capacity characteristics for the heat pump.
A precise calculation of the build­ing's heating load according to EN 12831 is required for the design and dimensioning of a heating system. However, approximate require­ments can be determined based on the year of construction and the type of building. The adjacent table shows the approximate spe­cific heating loads for a number of building types. The required heat­ing system output can be calcu­lated by multiplying the area to be heated with the given values.
Various factors have to be consid­ered in order to achieve a precise calculation.The transmission heat requirement, the infiltration heat loss and an allowance for water heating comprise the total heating output which has to be provided by the heating system.
The total area of the floor surfaces, exterior wall windows, doors and roofing is required in order to determine the transmission heat requirement. In addition, informa­tion about the materials used in the building is required, as these lead to extremely varied thermal trans­mission coefficients (the so called K value). Also required is the room temperature and the average low, the lowest average outdoor tem­perature of the year. The formula for determining the transmission heat requirement isQ=A U (t
R-TA) and this must be
calculated individually for the areas surrounding all rooms.
The infiltration heat requirement takes into consideration how often the heated room air is exchanged for cold external air. The room vol­ume V, the air exchange frequency n and the specific heat capacity of the air is also required in addition to the room temperature and average
low temperature. The formula for this is Q=V n c (t
R-tA).
An approximate allowance for wa­ter heating per person amounts to
0.2 kW according to VDI 2067.
Temperature in °C
Bivalence point
Necessary additional power
Heating capacity in kW
7
REMKO CMF / CMT
Characteristics of REMKO inverter heat pumps
Heat source outdoor air
An air/water heat pump absorbs energy from the outdoor air as its heat source and transmits this to the heating system.They have the following advantages over a brine/ water and water/water heat pump system:
Split AC unit
The REMKO
inverter heat pump is a so called split AC unit. This means that is consists of an outdoor unit and an indoor unit, both of which are connected via refrigerant-carry­ing copper pipes. This means that there are no water-carrying pipes laid from the indoors to outdoors which need to be made frost proof. The outdoor unit contains only the condenser, the evaporator and the expansion valve. This means that the outdoor unit is considerably smaller. The indoor module contains the liquefier for the circuit and the con­nections for the heating network.
The heat pump's condenser is equipped with a requirement-de­pendent speed control system. The power control on conventional heat pumps provides only two states, either on (full power) or off (no power). The heat pump switches on when the temperature drops below a certain level and switches off again when this temperature has been reached. This type of power control is extremely inefficient.The power control on REMKO'S
inverter heat pumps is continuously modified to the actual heat requirement.
The electronics system has an integrated frequency converter which serves to modify the con­denser speed and the speed of the evaporator fan as required. The condenser works at a higher speed when under full load as when it is under partial load. The lower speeds ensure a longer operational lifetime for the components, im­proved coefficient of performance and lower noise. Lower speeds also result in lower energy consumption (electricity).
Can be used everywhereAir is available everywhere in unlim­ited quantities. For example, no wells are required.
No excavation work requiredNo large areas are required for soil collectors.
EconomicalExpensive drilling is not required.
Excellent value for money and simple installation
Particularly suitable for low­energy houses with low inlet temperatures
Ideal for bivalent operation, in order to save energy
8
Minimal temperature deviations
means savings in energy
Time T
Temperature °C
1/3
The inverter requires 1/3 of the time of conventional systems to start up
Conventional
Inverter
Defrost by circulation reversal
At temperatures under approx. 5°C atmospheric moisture freezes on the evaporator which can lead to the formation of an ice layer. This can cause the heat transfer from the air to the refrigerant and the air flow to be reduced. In this case, the ice must be removed. A four-way valve serves to reverse the refrigerant circuit, so that the hot gas from the compressor flows through the original evaporator and the ice that has formed there can melt. The defrost process is not initiated after a predetermined time, rather it is carried out as required in order to save energy.
Cooling mode with models CMF 90, CMF 150, CMT 100 and CMT 150
Due to the circulation reversal sys­tem, a number of REMKO inverter heat pump models also offer cool­ing operation. Cooling mode utilises the refriger­ant components in order to produce cold water, in order that heat can be removed from the building. This can either take the form of dynamic cooling or passive cooling.
Under dynamic cooling the re­frigerating capacity is actively transferred to the indoor air. This is undertaken by means of water­based fan convectors. In doing so, it is desirable that the inlet temper­atures are under the dewpoint, in order to transfer a higher refrigerat­ing capacity and to dehumidify the indoor air.
Passive cooling refers to the ab­sorption of heat via cooled floors, walls or ceiling surfaces. In doing so, water-carrying pipes make the structural sections into thermi­cally effective heat exchangers. In order to achieve this, the refriger­ant temperature has to lie above the dewpoint, in order to avoid the formation of condensation. Dew­point monitoring is required for this purpose.
We recommend dynamic cooling with fan convectors, in order to achieve increased thermal perform­ance and in order to dehumidify the air on muggy summer days. The advantage here is that dewpoint monitoring is not required.
Versions
We offer two different indoor unit designs. The wall-mounted CMF Series is equipped with a circulation pump and a safety module on the up­stream face. In addition, an electri­cal heating coil can be integrated. The CMT Series of indoor modules is additionally equipped with a stor­age tank and an expansion vessel. The storage tank has a capacity of 150 litres. We recommend an external storage tank for the CMF Series in order to avoid short operating times for the heat pump and in order to ensure that sufficient energy is available to bridge off-periods.
The comfort zone shows which values for temperature and humidity are considered comfortable for people. This range should ideally be met when heating or air-conditioning buildings.
Relative air humidity in %
Uneasily humid
Uneasily dry
Still comfy
Comfy
Room air temperature in °C
9
REMKO CMF / CMT
Installation instructions
The indoor and outdoor modules have to be connected with refrigerant lines of dimensions
3
/8" and 5/8".
System design
Outdoor unit
Indoor
module CMT
Series
fan
Outdoor area
Refrigerant lines 3/8" and 5/8"
Mains cable
Interior 3x
Draining pan
Indoor area
Condensate drain
(must be designed to be frost proof!)
* Mains supply
3x230V/1~/50Hz 25A
electrical connection
4x
Domestic water 1"
Hot water 1"
Outdoor unit
fan Condensate drain (must be designed to be frost proof!)
electrical connection
4x
Indoor module CMF Series
Mains cable
Interior 3x
Condensation line
Hot water 1"
A four-wire control cable has to be laid between the two modules.
Both the indoor and outdoor modules require a separate power supply.
* Mains supply
3x230V/1~/50Hz 25A
Refrigerant lines 3/8" and 5/8"
* Mains power supply 5x for outdoor modules CMF 140, CMF 150 and CMT 150: 400V/3~N/50Hz 16A
optional mains
power line
Electric heating
230V or 400V
Mains cable
Electric heating
230V or 400V
Domestic water 1"
10
These instructions are to be observed when installing the entire system.
The device should be delivered as near as possible to the site of installation in its original pack­aging in order to avoid trans­port damage.
The device is to be checked for visible signs of transport dam­age.
Possible faults are to be report-
ed immediately to the contrac­tualpartner and the haulage company.
Suitable sites for installation are to be selected.
The stops valves for the refrig­erant lines may only be opened immediately before commis­sioning of the system.
General Information
All electrical installation work should be performed by spe­cialist contractors.
CAUTION
The installation of refrigerant plants may only be undertaken by trained specialist personnel.
CAUTION
Open refrigerant pipes must be protected against the intro­duction of moisture by means of suitable caps or adhesive strips Refrigerant pipes may not be kinked or depressed.
CAUTION
Special precautions relating to the oil return are to be met if the outdoor component is located above the indoor unit (please refer to the "Connec­tion of Refrigerant Lines" sec­tion).
Add refrigerant if the basic length of the refrigerant pipe exceeds 30 meters.
Establish all electrical connec­tions in accordance with the rel­evant DIN and VDE standards.
The electrical power cables must be fastened in a proper manner with electrical termi­nals.Otherwise there is a risk of fi re.
Wall breakthroughs
A wall breakthrough of at least 70 mm diameter and 10 mm slope from the inside to the outside must be created.
The interior of the break­through is to be padded, e.g. with a cladding PVC pipe in order to avoid damage (see fi gure).
After installation has been
completed, use a suitable sealing compound to close off the wall breakthrough under observation of fi re protection regulations (responsibility of customer).
Control line
Hot gas line
Liquid line
Supply
11
REMKO CMF / CMT
The wall bracket is to be fastened to the wall with the supplied fastening materials and the indoor module hooked on.
The wall must possess suffi cient load-bearing capacity for the weight of the indoor module.
Ensure that the wall bracket is installed level.
The indoor module can be aligned precisely by means of the adjustment screws on the rear side of the housing.
The indoor module is to be mounted in such a way that all of the sides have suffi cient space for purposes of instal­lation and maintenance.It is equally important that there is suffi cient space above the device for installing the safety module.
Only fi xing materials which are suitable for the given ap­plication may be used.
NOTE
Installation of the indoor unit
Indoor module CMF Series Indoor module CMT Series
The indoor module must be installed on a fi rm, level surface.
The surface must possess suf­fi cient load-bearing capacity for the weight of the indoor module.
The height-adjustable feet can be used to precisely align the indoor module.
The indoor module is to be mounted in such a way that all of the sides have suffi cient space for purposes of instal­lation and maintenance.It is equally important that there is also suffi cient space above the device for installing the pipes and safety module.
12
Pre-cut recesses
The device may only be at­tached to a load-bearing con­struction or wall.
Install the device on fl oor con­soles with vibration dampers to minimise noise.
The specifi ed minimum clear­ances should be maintained when carrying out the instal­lation. These protective zones serve to ensure unrestricted air inlet and outlet. It must be ensured that there is suffi cient space available for installation, maintenance and repairs.
The site of installation should be well ventilated.
Installation of the outdoor module
Wind
20 cm
Snow
CMF 80 / CMF 90 / CMT 100 CMF 140 / CMF 150 / CMT 150
A min. 50 mm min. 50 mm
B min. 750 mm min. 1,000 mm
C min. 150 mm min. 150 mm
D min. 250 mm min. 500 mm
E min. 100 mm min. 100 mm
If the outdoor module is erected in an area where there is strong wind, then the device must be protected from the wind. The snow line is to be ob­served during installation (see fi gures).
It is to be ensured that the outdoor module is only installed vertically.
The outdoor module is at­tached by means of 4 screws with vibration dampers on fl oor consoles.
Vibration dampers must also
be used when installing the equipment with a wall bracket. The vibration dampers serve to reduce the noise transmittance.
The Water Ecology Act is to be observed.
A number of sides must have greater clearance that the mini­mum specified clearance.
CAUTION
A heatable condensate catch pan ensures that condensation from the pan is able to drain off.It must be ensured that the condensation water is frost-pro­tected in order that it can drain off (gravel, drainage).
The right-hand side wall of the device is to be removed before installing the electrical cables and the refrigerant line to the outdoor module. In order to do so, release the three screws on the side wall and pull the panel downwards. If there is insuffi cient room under­neath the device for the refrigerant lines, then the precut recesses can be removed from the lower enclo­sure panel and the pipes can be guided in through these openings.
Air intake
Air outlet
13
REMKO CMF / CMT
Safety valve
Automatic deaerator
Manometer
Indoor unit
Hydraulic connection
Turning the thermometer heads serves to close or open the stop valves!
CAUTION
For models CMF 80, CMF 90 and CMT 100 it must be en­sured that the condenser pump fl ow rate always amounts to 1
,
400
l/h
. For models CMF 140, CMF 150 and CMT 150 the fl ow rate must amount to 2,200 l/h. The indoor module com­ponents are designed for these fl ow rates.
A hydraulic splitter or storage tank is to be used in order to separate the system circuits.
A pipeline network connection must be undertaken before installing the heat pump.
Floor heating systems must be protected against excessively high and low inlet tempera­tures.
The pipe diameters for the supply and return connections of the heat pump may not be reduced before the connection of a system separation.
Air bleed valves and drain-off taps must be planned for in suitable areas.
The complete pipe network for the system must be fl ushed be­fore connecting the heat pump.
The safety module contained in the scope of delivery comprises of a manometer, air vent and safety valve. It is to be mounted on the pipe connection for the indoor module.
An expansion vessel must be designed for the entire hy­draulic system. The expansion vessel for the CMT range has a volume of 12 litres and is only intended to protect the stor­age tank and not for the entire pipe network of the hydraulic system.
The system pressure of the entire pipe network is to be matched to the hydraulic sys­tem and must be checked when the heat pump is in a non-oper­ative state.
In order to reduce the heating cycles to a minimum, it must be ensured that the heating load from the heat pump is fully transferred to the heating system.
The supplied stop cocks are to be positioned directly at the connections for the heat pump inlet and return lines.
The shut-off valves each contain a thermometer with gauge.
The dirt traps should be in­stalled outside of the heat pump in the return line.
A separate installation must be carried out for every system.
NOTE
Manual­deaerator
Expansion-
vessel
14
It is to be ensured that a gate valve is positioned upstream and downstream of the dirt traps. This ensures that the dirt traps can be checked at any time without loosing water.
The dirt traps must be checked during every service of the sys­tem.
The indoor module contains a ventilation connection in the inlet line in order to enable ad­ditional venting.
It must be ensured that a suffi cient fl ow-rate is given.
CAUTION
Manual­deaerator
All visible metallic surfaces must be additionally insulated.
Cooling mode via the heating circuit requires a completely vapour diffusion tight insulation along the entire length of the pipework.
All outgoing heating circuits including the connections for water heating are to be secured against circulating water by means of fl ap valves.
The system must be fl ushed before commissioning the sys­tem. The entire system must be subjected to a tightness check and a thorough venting.
Electrical connection
For the CMF and CMT devices, a mains cable must be laid for both the outdoor and indoor modules. In some cases it may also be pos­sible to feed the power supply for the indoor module from the outdoor module. The outdoor modules of Series CMF 80, CMF 90, CMT 100 require a 230V mains supply. The outdoor mod­ules of Series CMF 140, CMF 150 and CMT 150 have to be provided with a 400 V supply. The electrical connection between the modules is realised with a 4-wire control cable.
A clockwise rotating field must be ensured for 400 V power supplies.
CAUTION
The following diagram provides an overview of the required connec­tions. The diameters for the leads and the connection cables are to be selected according to local regula­tions. The fusing level is to be taken from the technical data. It is possible that the energy sup­ply company will provide a special power supply tariff for the opera­tion of heat pumps. Individual tariff options should be agreed with the local energy sup­ply company.
Check all plugged and clamped terminals to verify they are seated correctly and making a permanent contact. Re-tighten as required.
CAUTION
15
REMKO CMF / CMT
Connection diagram
Electrical
heater
Sub-distribution by customers
Connection outdoor unit
Connection indoor unit
Power plant clearing contact
Connection electrical heating
* 5-wire (example NYM-I 5x2,5 mm²)
3-wire (example NYM-I 3x4 mm²)
3-wire (example NYM-I 3x1,5 mm²)
* 5-wire (example NYM-I 5x2,5 mm²)
2-wire (example NYM-I 2x1 mm²)
4-wire (example NYM-I 4x1mm²)
Pump heating circuit 1
Pump heating circuit 2
Charge pump / U-valve
Mixer heating circuit 2
Pump cooling
Circulation pump
Reversing valve cooling
(not at CMF 80 and 140)
Clearance 2nd. heater.
The clamp confi guration depends on
the model!
Connection
Pilot wire
Outdoor unit
Indoor unit
Return
Collector
Tank
Intake heating circuit 1
Intake heating circuit 2
Process water
Collector
* The outdoor units of CMF 80, CMF 90 and CMT 100 have to be supplied by a 3-wire power cable!
The outdoor units of CMF 140, CMF 150 and CMT 250 have to be supplied by a 5-wire power cable!
The cross section indicated have to be complied with the pipe length and kind of construction in order to the VDE
0900 and technical data!
Outdoor temperature
16
Mains cable
Control line
Electrical connection of the outdoor module
The side wall of the the unit is to be removed by means of loosening the screws in order to connect the mains supply (see "Installation of the Outdoor Module").
Details concerning the electri­cal protection of the system are given in the technical data.
The required diameters are to
be observed!
The supply cable must be con­nected under consideration of the correct polarity.
The electrical connection dia­gram is to be observed.
The four-wire control cable is to be connected to terminals S1, S2, S3 and the earth terminal.
The correct polarity must be ensured when connecting the connection cables.
If the outdoor module is in­stalled on a roof, then it must be protected against lightening strikes.
The cables are to be secured with the cord grips.
Electrical connection of the indoor module
The following points refer to the fi gures shown below. The CMF Series indoor module is shown in the example. The connection for the CMT Series is established cor­respondingly.
1. The lower housing cover is folded down and removed.
2. The front of the housing is fi xed in position with two screws and can be taken out in an upward direction after the screws are released.
3. The cover of the switching cabi­net can be folded down and removed after the two screws have been removed.
4. After the screws have been released, the switching cabinet can be folded down in order to facilitate installation.
Ensure correct polarity when connecting the electrical leads.
CAUTION
5. The cable passages serve to en­able the supply lines to be fed in for the indoor unit as well as the connection cable between the indoor and outdoor mod­ules and the leads for the exter­nal devices and sensors into the indoor module.
In doing so, it is to be ensured
that the cable passages for the CMT Series are at the top.
The number of lines and the sensors is dependent on the confi guration of the heating system and the components.
The leads are to be connected in accordance with the terminal assignment diagram.
Cable passage
1. 2. 3.
4.
5.
17
REMKO CMF / CMT
Circuit diagram for models CMF 80 and CMF 140
Heat pump -
temperature
Clearance
compressor
Switch board heat pump manager
Internal fuse
Flow
control
Outlet
yellow
Condenser
pump
Clearance exter-
nal heater 2
open close
Mixer heating
circuit 2
Charge pump
/ U-valve
Pump
heating
circuit 2
Pump
heating
circuit 1
Power
plant
contact
Contact closed
means clearance
Switch board sensor connector
Switch board outdoor unit
Switch board heat pump manager
Outdoor unit
red
18
If an electricity tariff has been selected without energy supply company shut-off, then a bridge is to be cre­ated between terminals X1.5 and X1.6.
If an electricity tariff with energy supply company shut-off is selected, then the customer is to arrange for an on-site starter contact for terminals X1.5 and X1.6. Likewise, the supply line for the outdoor mod­ule requires an interruption mechanism installed by the customer in accordance with the energy supply company's off-periods. In this case it is necessary to have a separate supply line for the indoor unit! The booster heating system requires a separate supply line with fuse protection in the switching cabinet con­nected to contactor terminal K1.
Terminal assignment diagram for models CMF 80 and CMF 140
Terminal Connection
X1.1 Supply line L
X1.2 Supply line N
X1.3 Supply line PE
X1.4 Live phase L
X1.5 Energy supply company release contact
X1.6 Energy supply company release contact
X1.7 Flow monitor
X1.8 Flow monitor
X1.9 Connection cable PE
X1.10 Connection cable S3
X1.11 Connection cable S2
X1.12 Connection cable S1
X1.13 Pump heating circuit 1 L
X1.14 Pump heating circuit 1 N
X1.15 Pump heating circuit 1 PE
X1.16 Pump heating circuit 2 L
X1.17 Pump heating circuit 2 N
X1.18 Pump heating circuit 2 PE
X1.19 Charging pump / switching valve L
X1.20 Charging pump / switching valve N
X1.21 Charging pump / switching valve PE
X1.22 Mixer heating circuit 2 open
X1.23 Mixer heating circuit 2 N
X1.24 Mixer heating circuit 2 PE
X1.25 Mixer heating circuit 2 close
X1.26
X1.27
X1.28 Release heating appliance 2 com
X1.29 Release heating appliance 2 NC
X1.30 Release heating appliance 2 NO
X1.31 Circulating pump (collector pump) L
X1.32 Circulating pump (collector pump) N
X1.33 Circulating pump (collector pump) PE
X1.34 Condenser pump L
X1.35 Condenser pump N
X1.36 Condenser pump PE
Terminal Connection
X2.1 BUS H
X2.2 BUS +
X2.3 BUS L
X2.4 BUS -
X2.5 0 - 10 V -
X2.6 0 - 10 V +
X2.7 Return sensor / F17
X2.8 Switch input / F15
X2.9 Collector sensor / F 14 (PT 1000)
X2.10 F 13
X2.11 Storage tank sensor lower / F 12
X2.12 Supply sensor heating circuit 1 / F11
X2.13 F 1
X2.14 F 2
X2.15 F 3
X2.16 Supply sensor heating circuit 2 / F5
X2.17 Domestic water sensor / F6
X2.18 Collector sensor / F8
X2.19 External sensor / F9
X2.20 Sensor liquid line
X2.21 Sensor liquid line
X2. Earth contact sensor
19
REMKO CMF / CMT
20
21
24
25
26
27
28
X1.1
X1.13
X1.16
X1.19 X1.22
X1.25
A2
A1 A3 A4
A5
Pumpe Pumpe Ladepumpe/
MischerHK2
auf zu
N L
HK1
HK2
U.Ventil
PlatineWärmepumpenmanager
gelb
rot
31
30
29
34
33
32
36
35
38
37
11
14
K3
21
24
K3
A2
K3
A2
K4
11
14
K4
A2
K5
A2
A1
K7
A2
K8
A2
K9
A2
K1
X1.7
X1.28
X1.37
X1.40
X1.8
X1.26
X1.41
X1.6
X1.27
H1
H3
A1
K2
B1
15
K2
A6
A7
A8
A9
Flußwächter
E.-Heizstab
Brücke
PumpeKühlen
Kondensator-
Freigabe
extern
pumpe
A2
A2
22
A1
A1
A1
A1
A1
A1
A1
12
12
18
weiß
K6
X1.4
X1.5
H2
EVU-
Kontakt
A10
39
40
41
X1.31X1.34
A12
U.Ventil
MF4
int.Sicherung
Kühlen
Freigabe
Heizen/Kühlen
Kompressor
0-10V
11
14
K6
11
14
K7
11
14
K8
11
14
K9
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19
X1.12
X1.11
X1.9X1.10
TB61.1
TB61.2
TB61.3 TB61.4
TB62.3 TB62.4
TB142.1
TB142.2
TB142.3
TB141.4
TB141.3
TB6.PE
TB6.S1
TB6.S2
R1
X2-1
X2-2
X2-3
X2-4
X2-5
X2-6
X2-7
X2-8
X2-9
X2-10
X2-11
X2-12
X2-13
X2-14
X2-15
X2-16
X2-17
X2-18
X2-19
X2-20
X2-21
F9 F8 F6 F5 F3 F2 F1
F11 F12 F13 F14 F15 F17
eBUS+ eBUS-
CANH CANL CAN-
PlatineWärmepumpenmanager
PlatineAußenmodul
12
12
TB142.4
TB6.S3
Außenmodul
12
12
CAN+
PlatineFühleranschlüsse
WE2
Ausgang
C1
X1.2
X1.14
X1.17
X1.20
X1.23
X1.29
X1.38
X1.32
X1.35
X1.42
11
14
K5
12
X2-
*
X2-
X2-
X2-
X2-
X2-
X2-
X2-
X2-
X2-
X2-
X2-
X2-
Flüssigkeitstemp.-Fühler
Sammelstörung
Lufttemp.-Fühler(2,6kOhm)
5min
Störung
Kompressor
Pumpennachlauf
E-Heizung
Freigabe
Kompressor
Pumpe
Kühlen
Umschaltung
Kühlen/Heizen
EVU
Abschaltung
Freigabe
Wärmeerzeuger
Freigabe2.
Wärmeerzeuger
Circuit diagram for models CMF 90, CMT 100, CMF150 and CMT 150
Switch board outdoor unit
Switch board sensor connector
Outdoor unit
Outlet
Clearance
heater 2
U-Valve
cooling
Condenser
pump
Bridge
electrical
heater
Pump external
cooling
Flow control
Power
plant
contact
Heat pump -
temperature
Clearance
compressor
Heating /
cooling
switch board heat pump manager
Switch board heat pump manager
internal fuse
open close
Mixer heating
circuit 2
Charge pump
/ U-valve
Pump
heating
circuit 1
Pump
heating
circuit 2
yellow
red
white
20
Terminal assignment diagram for models CMF 90, CMT 100, CMF150 and CMT 150
Terminal Connection
X1.L Live phase
X1.L Live phase
X1.L Live phase
X1.1 Supply line L
X1.2 Supply line N
X1.3 Supply line PE
X1.4 Energy supply company release contact
X1.5 Energy supply company release contact
X1.6 K1 A2 (N)
X1.7 Flow monitor
X1.8 Flow monitor
X1.9 Connection cable PE
X1.10 Connection cable S3
X1.11 Connection cable S2
X1.12 Connection cable S1
X1.13 Pump heating circuit 1 L
X1.14 Pump heating circuit 1 N
X1.15 Pump heating circuit 1 PE
X1.16 Pump heating circuit 2 L
X1.17 Pump heating circuit 2 N
X1.18 Pump heating circuit 2 PE
X1.19 Charging pump / switching valve L
X1.20 Charging pump / switching valve N
X1.21 Charging pump / switching valve PE
X1.22 Mixer heating circuit 2 open
X1.23 Mixer heating circuit 2 N
X1.24 Mixer heating circuit 2 PE
X1.25 Mixer heating circuit 2 close
X1.26 Bridge electrical heating coil
X1.27 Bridge electrical heating coil
X1.28 Pump cooling external L
X1.29 Pump cooling external N
X1.30 Pump cooling external PE
X1.31 Circulating pump (collector pump) L
X1.32 Circulating pump (collector pump) N
X1.33 Circulating pump (collector pump) PE
X1.34 Switching valve cooling L
X1.35 Switching valve cooling N
X1.36 Switching valve cooling PE
X1.37 Condenser pump L
X1.38 Condenser pump N
X1.39 Condenser pump PE
X1.40 Release heating appliance 2 com
X1.41 Release heating appliance 2 NC
X1.42 Release heating appliance 2 NO
Terminal Connection
X2.1 BUS H
X2.2 BUS +
X2.3 BUS L
X2.4 BUS -
X2.5 0 - 10 V -
X2.6 0 - 10 V +
X2.7 Return sensor / F17
X2.8 Switch input / F15
X2.9 Collector sensor / F 14 (PT 1000)
X2.10 F 13
X2.11 Storage tank sensor lower / F 12
X2.12 Supply sensor heating circuit 1 / F11
X2.13 F 1
X2.14 F 2
X2.15 F 3
X2.16 Supply sensor heating circuit 2 / F5
X2.17 Domestic water sensor / F6
X2.18 Collector sensor / F8
X2.19 External sensor / F9
X2.20 Sensor liquid line
X2.21 Sensor liquid line
X2. Earth contact sensor
If an electricity tariff has been selected without energy supply company shut-off, then a bridge is to be cre­ated between terminals X1.4 and X1.5.
If an electricity tariff with energy supply company shut-off is selected, then the customer is to arrange for an on-site starter contact for terminals X1.4 and X1.5. Likewise, the supply line for the outdoor mod­ule requires an interruption mechanism installed by the customer in accordance with the energy supply company's off-periods. In this case it is necessary to have a separate supply line for the indoor unit! The booster heating system requires a separate supply line with fuse protection in the switching cabinet con­nected to contactor terminal K1.
21
REMKO CMF / CMT
Temperature sensors
External sensorThe number of sensors required
can vary with the type of system.
The indoor module contains the collector sensor, the return sensor and the sensor for the liquid line. The scope of delivery contains the external sensor and immersion sensor.
When connecting a solar collector, the PT-1000 sensor has to be used for measuring the collector tem­perature! All other sensors have to be NTC-sensors with a reference resistance of 5 kilo Ohms.
All sensors are to be connected to the indoor module switching cabinet in accordance with the terminal assignment diagram.
The connection of an outdoor sen­sor is always required for the heat pump manager.
The outdoor sensor is to be mounted in a north-easterly direction approx. 2.5 metres above the ground. It may not be subjected to direct sunlight and is to be protected against excessive wind. Installation above windows or air ducts is to be avoided.
In order to carry out installa­tion, the cover is to be removed and the sensor is to be fastened with the screws included.
A cable with wire diameters of
1.0 mm² is recommended for connecting the sensor.
Contact sensor
Contact sensors can be mounted on the pipes in order to measure e.g. the heating circuit tempera­tures.
The contact sensors are fi xed in position with the enclosed trapezoidal brackets and the retaining strap is fi xed to a pipe.
The corresponding site must be cleaned. Subsequently a ther­mal compound (A) is applied and the sensor is fi xed in posi­tion.
In the event of insuffi cient cable length, the sensor cables can be extended up to a maximum of 100 m with 1.5 m² diameter wire.
NOTE
22
The outdoor module and the indoor module are connected with two copper pipes of di­mensions “ and “.
All work must be excluded which could cause soiling or the infiltration of chips into the refrigerant pipes!
CAUTION
Outdoor unit
Oil pump bend
in suction pipe to
outdoor module1
every 2.5 metres of
rising pipe
Radius: min 50 mm
up to 20 m
Indoor unit
The connection of refriger­ant pipes and the handling of refrigerant may only be carried out by authorised specialist personnel.
CAUTION
Connection of refrigerant lines
Only suitable tools may be used.
Observe the permitted bending radius for the refrigerant pipes during installation in order to prevent kinks. Never bend a pipe twice in the same place in order to prevent embrittlement or crack formation.
Suitable fastening and insula­tion is to be ensured when laying the refrigerant pipes.
The outdoor sections of the refrigerant pipes should be fi t­ted with additional pipe insula­tion by the customer in order to minimise performance loss.
The copper pipes are to be fl anged in order to make the connections to the modules.In doing so, check that the fl ange has the correct shape and suit­able union nuts.
If the outdoor unit is installed at a higher level than the indoor unit, suitable oil return measures must be taken. This is generally achieved by an oil pump bend installed for every
2.5 metres of height difference.
Unit connector
The enclosure panel is to be removed from the outdoor module. It may be necessary to remove the pre-cut bushings.
The connection of the refriger­ant pipes to the device connec­tions are to initially be made by hand, in order to ensure a good fi t.
Subsequently the threaded assemblies are to be fastened with two adjustable spanners. One of the spanners is to be used to counter the rotation.
The installed refrigerant pipes including the connectors must be provided with suitable ther­mal insulation.
Tightness check
Connect the manometer station to at least one Schrader valve on the stop valves of the out­door module.
The tightness test is to be un­dertaken with dried nitrogen at a test pressure of 40 bar.
The connections and connec­tors of the pipelines must be checked with a suitable leak detector and any leaking areas are to be rectifi ed.
Pumping down to vacuum
The positive pressure must be removed from the refrigerant pipes.
The vacuum pump should have an absolute fi nal partial pres­sure of 10 mbar in order to remove all foreign gasses in the pipelines.
Add refrigerant
The outdoor module contains a suffi cient refrigerant fi lling for a pipe length of up to 30 metres.
If the length of any of the pipe­lines exceeds 30 metres, then an additional fi lling of 60g per additional metre of pipe length (single length) is required.
Before start up
The stop valves are to be fully opened in an anticlockwise di­rection with a hexagon wrench.
23
REMKO CMF / CMT
Commissioning
The commissioning and pro­gramming of the heat pump manager may only be car­ried out by trained specialist engineers.
NOTE
End
Installation
OK
An intensive visual inspection is to be carried out before the actual commissioning.
It is to be checked exactly which components belong to the heating system. The follow­ing is an example of a hydraulic diagram with the corresponding parameters indicated.
Switch the electrical supply on.
The following screen appears on the Multitalent display.
In order to begin installation / confi guration of the system, press the OK button.
C
B
A
The heat pump manager is con­trolled by means of the following buttons.
The rotary knob (A) can be used to toggle between the displayed menu points or to change the set values.
Pressing the Home but­ton (B) always brings you back to the default screen.
Each of the four function keys (C) represent one of the four lines of the display. A menu point or value can be selected by pressing the F key.
Home
The operation and control of the complete system is undertaken by the Multitalent heat pump man­ager. The operation of the heat pump manager is carried out from the control console. The control con­sole is supplied connected to the basic device and is located behind the fl ap on the indoor module.
The system has to be matched­to the customer's personal values (e.g. heating characteris­tics).
The supplied brief instructions give an overview of how to set the most important values.
After confi guration, the system is to be run-in and the meas­ured values are to be entered into the commissioning report.
The confi guration in the insta­lation level for the selected hydraulics has to be completely programmed with the param­eters shown adjacently.
The confi guration can be ac­cepted after a power failure, etc. by pressing the F key next to
End
.
NOTE
24
System example 1: Heat pump CMF 80, CMF 140 in single energy source mode
Designation
Range of values System example 1
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 01 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On Off
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Storage
system (tank)
M
RadiatorFloor heating
M
M
Buffer tank
Indoor unit CMF
TS
Chilled water
Flow
control
Circulation
pump
Filling station
0000
Electrical
support heating
- optional
The quantity of necessary sensors have to be controlled!
1)
2)
2)
1) Proposed position for the heat meter (2,5m³/h)
2) Proposal: Use of energy efficiency pumps
Outdoor unit
F 17
F 8
F 9
F 11
F 5
F 6
A
B
AB
intake
Designation
Range of values System example 1
Output/level 00 – 9950 kW
WE 1 level 1 = 1
(WE 2 level 1 = 1)
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10°C – 90°C --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 10 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 02 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 02 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
25
REMKO CMF / CMT
System example 2: Heat pump CMF 80, CMF 140 in bivalent mode with gas / oil condensing
boiler
Designation
Range of values System example 2
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 01 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On Off
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 2
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 2 level 1 = 1
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 10 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 02 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 02 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
26
System example 3: Heat pump CMF 80, CMF 140 in bivalent mode with gas / oil condensing
boiler
Gas / oil boiler
Storage
system (tank)
M
RadiatorFloor heating
M
M
Buffer tank
TS
Chilled water
Flow
control
Circulation
pump
Filling station
Indoor unit CMF
0000
1)
2)
2)
Outdoor unit
AB
The quantity of necessary sensors have to be controlled!
1) Proposed position for the heat meter (2,5m³/h)
2) Proposal: Use of energy efficiency pumps
F 17
F 8
F 11
F 6
F 9
F 5
A
B
intake
Designation
Range of values System example 3
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 01 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On Off
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 3
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 2 level 1 = 1
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 10 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 02 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 02 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
27
REMKO CMF / CMT
System example 4: Heat pump CMF 80, CMF 140 in bivalent mode with solid fuel boiler
Designation
Range of values System example 4
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 20 Gradient On / Off Off WE2 Type 00 – 22 01 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On Off
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 4
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 2 level 1 = 1
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 10 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 22 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 02 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
M
Heating circuit
M
M
Buffer tank
Solid fuel
boiler
Storage
system (tank)
TS
Chilled water
Flow
control
Circulation
pump
Filling station
Indoor unit CMF
1)
0000
2)
3) The circulation pump have to be controlled separately
3)
Outdoor unit
The quantity of necessary sensors have to be controlled!
1) Proposed position for the heat meter (2,5m³/h)
2) Proposal: Use of energy efficiency pumps
F 8
F 6
F 17
F 9
AB
A
B
F 11
F 5
intake
28
System example 5: Heat pump CMF 80, CMF 140 in single energy source mode with solar
connection
Designation
Range of values System example 5
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 01 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On Off
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 5
Output/level 00 – 9950 kW
WE 1 level 1 = 50
(WE 2 level 1 = 1)
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 10 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 23 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 02 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
29
REMKO CMF / CMT
System example 6: Heat pump CMF 90, CMF 150, CMT 100, CMT 150 in single energy
source mode
Storage
system (tank)
M
RadiatorFloor heating
M
M
Buffer tank
TS
Chilled water
Flow
control
Circulation
pump
Filling station
M
Cooling - indoor unit
chilled water
Buffer tank
Steam protected isolation
0000
Mode heating and cooling have to be adjusted manual!
The air-conditioners WLT and KWD are unsuitable for heating!
1)
2)
2)
1)
3)
Outdoor unit
3) The circulation pump have to be controlled separately
The quantity of necessary sensors have to be controlled!
1) Proposed position for the heat meter (2,5m³/h)
2) Proposal: Use of energy efficiency pumps
AB
AB
F 9
F 11
F 5
F 6
A
B
A
B
Indoor unit CMF
F 17
F 8
intake
Designation
Range of values System example 6
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 08 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On On
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 6
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 34 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 02 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 00 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
30
System example 7: Heat pump CMF 90, CMF 150, CMT 100, CMT 150 in single energy source
mode with solar connection
Indoor unit CMF
Storage
system (tank)
TS
Chilled water
Flow
control
Circulation
pump
Filling station
Steam protected isolation
0000
1)
3)
Outdoor unit
M
RadiatorFloor heating
M
M
Buffer tank
M
Cooling - indoor unit
chilled water
Buffer tank
2)
2)
AB
F 11
F 5
F 6
AB
F 17
F 9
F 8
F 14
A
B
A
B
intake
Mode heating and cooling have to be adjusted manual!
The air-conditioners WLT and KWD are unsuitable for heating!
3) The circulation pump have to be controlled separately
The quantity of necessary sensors have to be controlled!
1) Proposed position for the heat meter (2,5m³/h)
2) Proposal: Use of energy efficiency pumps
Designation
Range of values System example 7
Language D/GB/F/NL/E/I D - German
Time 0 - 24 hours Set time
Date Year, month, day Set date
BUS code BM Off, 01-15 Off
Terminal address Off, 01 - 30 01 Regulator address 01 - 16 01 Bus code 1 00 - 15 01 Bus code 2 00 - 15 02
System selection ----, 01 - 13 12
Regulator type 00 – 06 06 WE1 Type 00 – 07 07 WE1 BUS 00 – 05 05 Gradient On / Off Off WE2 Type 00 – 22 08 WE2 storage 00 - 03 00 WE3 Type 00 – 09 01 WE4 Type 00 – 09 00 Buffer type 00, 01, 02 00 Cooling mode Off/ On On
HK1 function
Standard,T-feed
const, swimming
pool, WW,
return
Standard
HK2 function See HK1 Standard
Designation
Range of values System example 7
Output/level 00 – 9950 kW
WE 1 level 1 = 50
WE 3 level 1 = 1
Continue with key next to "end" MF1 function 00 - 34 00 T-MF1 setpoint 10° – 90° ---
MF1 Hyst 2K – 10K --­MF1 Hyst off 2K – 10K --­MF2 function 00 - 34 05 T-MF2 setpoint 10° – 90° --­MF2 Hyst 2K – 10K --­MF2 Hyst off 2K – 10K --­MF3 function 00 - 34 34 T-MF3 setpoint 10° – 90° --­MF3 Hyst 2K – 10K --­MF3 Hyst off 2K – 10K --­MF4 function 00 - 34 23 T-MF4 setpoint 10° – 90° --­MF4 Hyst 2K – 10K --­MF4 Hyst off 2K – 10K --­F15 function 00 - 08 07 E1 function 00 - 03 00 E2 function 00 - 03 00 5K sensors 5K, 1K 5 K
31
REMKO CMF / CMT
Care and maintenance
Regular care and maintenance ensuretrouble-free operation and a long service life.
Care
The indoor and outdoor mod­ules must be kept free of soiling, vegetation and other deposits.
The device is to be cleaned with a damp cloth. In doing so, it is to be ensured that no caus­tic, abrasive or solvent-based cleaning products are used. Use of powerful water jets is to be avoided.
The fi ns on the outdoor module are to be cleaned after long standstill periods.
Prior to performing any work, ensure the equipment is iso­lated from the voltage supply and secured to prevent acci­dental switch-on!
CAUTION
Maintenance
It is necessary to arrange a maintenance contract on an annual basis with a respective specialist fi rm.
As the refrigerant fi ll quantity exceeds 3kg, an
annual
tight­ness check has to be carried out on the refrigerant circuit by a specialist fi rm.
NOTE
Temporary decommis­sioning
The system may not be switched off at the mains power supply even if the heating system is not used for heating purposes over an extended
period (e.g. holidays)!
The system is to be switched to "Stand-by" mode during tem­porary shut-down periods.
Heating phases can be pro­grammed for the duration of the period of absence.
The previous operating mode has to be switched back on when the shut-down phase is over.
Instructions on how to change the mode is described in the corresponding chapter of the configuration manual.
Disposal of packaging
All products are packed for trans­port in environmentally friendly materials. Make a valuable con­tribution to reducing waste and sustaining raw materials. Only dispose of packaging at approved collection points.
In order to make warranty claims, it is essential that the ordering party or their representative complete and return the "certificate of war­ranty" and commissioning report to REMKO GmbH & Co. KG at the time when the equipment is pur­chased and commissioned. The warranty conditions are listed in the "General business and deliv­ery conditions. The contractual par­ties can also agree additional terms beyond the scope of the above. In this case,first contact the contrac­tual partner.
Environmental protection and recycling
Warranty
In "Standby" mode, the heat pump is "switched off". However, the frost protection function of the entire plant remains active.
NOTE
Disposal of units and compo­nents
For the manufacture of the units and components, only recyclable materials have been used. Help protect the environment by ensuring that the units or compo­nents (for example batteries) are not disposed in household waste, but only in accordance with local regulations and in an environmen­tally safe manner, e.g. through authorised disposal and recycling specialists or at collection points.
32
Troubleshooting
The unit has been manufactured using state-of-the-art production methods and tested several times to ensure its correct function. If malfunctions should occur, please check the unit as detailed in the list below. Please in­form your dealer if the unit is still not working correctly after all of the functional checks have been performed.
Control lamp Meaning Remedial measures
red Heat pump fault
Briefl y switch the system off and wait for re­start / inform dealer or installation engineer
yellow Flow monitor fault
Check the function of the condenser pump or fl ow monitor / check system pressure and fl ow
white Energy supply company off-period
The heat pump can be confi gured to switch on automatically as required according to a con­tractually regulated power off period.
Fault Possible causes Remedial measures
The heat pump does not start or switches itself off
Power outage, under voltage
Check the voltage and, if necessary, wait for it to come back on
Defective mains fuse Main circuit breaker is open
Exchange circuit breaker, switch on master switch
Damaged mains cable Repair by specialist fi rm
Energy supply company off-period
Wait until the off-period is over and the heat pump starts up as required
Operational temperature range too low or exceeded
Observe temperature ranges
Setpoint temperature exceeded incorrect mode
The setpoint temperature has to be higher than the heating appliance temperature, check mode
Heating circuit pump fails to switch off
Incorrect pump switching
Have the pump switching system checked in
expert mode "heating circuit"
Heating circuit pumps fail to switch on
Incorrect mode set Check mode
Control PCB fuse in indoor module switching cabinet faulty
Exchange the fuse on the left side of the control PCB
Incorrect heating program set Check heating program
Temperature overlapping, e.g. out­door temperature greater than room temperature
Observe temperature ranges
33
REMKO CMF / CMT
General
In the event of system malfunc­tions, fi rst check the control system cabling and components for cor­rectness.
Sensors
All of the sensors can be checked
from the "General/ Service/Sensor test" screen. All of the connected sensors have to appear here with plausible measured values.
Actuators (mixers, pumps)
All of the actuators can be checked from the "General/ Service/relay test" screen. This screen enables all of the relays to be checked indi­vidually. This enables the correct connection of these components to be easily checked (e.g. mixer direction of rotation).
Communication
The bus and sensor cables should be checked in the event of com­munication faults. The cables are to be spatially separated from power lines. The polarity is also to be checked.
Troubleshooting
A corresponding error code ap­pears on the heat pump manager display in the event of a fault on the heating system. The meaning of the displayed error codes can be
taken from the following table. The system should be restarted after a brief shut-down after the fault has been rectifi ed (mains switch). Subsequently the heat
Display Fault description
E 54 Heat pump fault
E 69 Failure or short in supply sensor HK2
E 70
Failure or short in supply sensor HK1, Multifunction sensor 1
E 71 Failure or short in lower buffer sensor
E 72 Failure or short in top buffer sensor
E 75 Failure or short external sensor
E 76 Failure or short domestic water sensor
E 78 Failure or short collector sensor
E 80 Failure or short room sensor heating circuit 1
E 81
EEPROM error. The invalid value has been replaced by the default value. Check parameter values!
E 83 Failure or short room sensor heating circuit 2
E 84 Fault humidity sensor
E 90
Address 0 and 1 on bus. Bus codes 0 and 1 may not be used simultaneously.
E 91
Bus code assigned. The set bus code is already being used by another device.
E 135
Failure or short lower WW buffer sensor, Multifunction sensor 2
E 136
Failure or short heating appliance sensor 2, collector sensor 2, Multifunction sensor 3
E 137
Failure or short in collector sensor 1, Multifunction sensor 4
E 140 Failure or short in return line sensor cooling mode
E 200 - E 207 Communication heating appliance 1 to WE 7
E 220 - E 253 Communication BM 0 to BM 15
E 240 Communication Manager
E 241 Communication (individual) heating appliances
E 242 Communication mixer
E 243 Communication Solar
Info 51 * Information: Maintenance required
Info 55 Information: Heat pump cut off
* Customer Service appears on the display.
The "Info 55" display (heat pump cut-off) appears during each energy supply company off-period.
NOTE
pump manager will re-start, auto­matically reconfi gure and continue to operate with the set values.
34
LEDs
LEDs on outdoor module
In the event that the red con­trol lamp lights up on the indoor module, then the fault is on the outdoor module. Two LEDs are vis­ible after removing the enclosure panel which light up in green and red during normal operation (see adjacent fi gure). If the LEDs fl ash, then there is a fault. Causes and measures for their remedy can be taken from the following table.
green LED red LED Meaning Remedial measures
fl ashes 1 time
fl ashes 1 time
Phase error: The supply cable to the out­door module or the connection between the indoor and outdoor modules is not correct.
Check the electrical connection (swapped phases)Check connection cable
fl ashes 2 time
One of the connectors has been removed from the PCB or has intermittent contact
Check all connectors on the PCB, check high and low pressure sensors
fl ashes 3 time Fault on PCB Exchange PCB
fl ashes 2 time
fl ashes 1 time
Wiring error between indoor and outdoor modules
Check connection cable for correct polar­ity and proper contact
fl ashes 2 time
Data transfer error between indoor and outdoor modules
Check if the connection cable has been improperly extended or incorrectly con­nected
fl ashes 3 time
fl ashes 1 time
Hot gas temperature in refrigerant circuit too high or hot gas heating too low
Check refrigerant; check hot gas tempera­ture sensor; check expansion valve
fl ashes 2 time
High pressure valve has tripped
Open any closed spherical valves, check refrigerant fi lling
Low pressure cut-off switch has tripped
Open any closed spherical valves, check refrigerant fault
No voltage on condenser Check power supply to the condenser
fl ashes 3 time
Overheating protection tripped, excessive liquid temperature in refrigerant circuit
Clean dirty heat exchanger on outdoor module; rectify possible pneumatic short circuit on the outdoor device.
fl ashes 4 time
Overcurrent circuit breaker on condenser (overload) has tripped, or no operating voltage on condenser
Open any closed spherical valves; check supply voltage; exchange faulty PCBs
fl ashes 5 time
Fault in hot gas temperature sensor or fi n temperature sensor (cable breakage or short circuit)
Check PCB connector for fi rm connection, check functionality of the sensor
fl ashes 6 time
Temperature fault on inverter cooling block
Rectify obstruction to fl ow in outdoor module
fl ashes 7 time Fault in power supply Check and repair power supply
fl ashes 4 time
fl ashes 1 time
Fault on liquid line sensor (cable breakage or short circuit)
Check PCB connector for fi rm connection, check functionality of the sensor
fl ashes 4 time
Temperature of liquid line too high / too low
Check refrigerant line or lack of refriger­ant
Flashing code on outdoor module
35
REMKO CMF / CMT
Unit dimensions
Device dimensions outdoor module
Plan viewFront view Side view
Dimensions outdoor module CMF 140, CMF 150, CMT 150
v
Plan viewFront view Side view
Dimensions outdoor module CMF 80, CMF 90, CMT 100
Air intake
rear
Air intake
side
Air outlet
Air intake
rear
Air intake
side
Air outlet
36
Plan viewFront view Side view
Device dimensions indoor module
Dimensions indoor module CMF
Plan viewFront view Side view
Dimensions indoor module CMT
37
REMKO CMF / CMT
Characteristic curves
Coeffi cient of performance for models CMF 80, CMF 90, CMT 100
Coeffi cient of performance
0,0
0,5
1,0
1,5
2,0
2,5
3,0
3,5
4,0
4,5
5,0
-10 -8 -6 -4 -2 0 2 4 6 8 10
Lufteintrittstemperatur in °C
Leistungszahl
35 °C VL
45 °C VL
55 °C VL
Coeffi cient of performance for models CMF 140, CMF 150, CMT 150
Air intake temperature in °C
Performance factor
Outdoor temperature in °C
Performance factor
38
Performance charts
Heating output and electrical power consumption for models CMF 80, CMF 90, CMT 100
Heating output and electrical power consumption for models CMF 140, CMF 150, CMT 150
Performance factor in W
Outdoor temperature in °C
Power consumption
Heating capacity
Performance factor in W
Heating capacity
Power consumption
Outdoor temperature in °C
39
REMKO CMF / CMT
Pump characteristic curves
Pump characteristic curves for models CMF 80, CMF 90, CMT 100
Level Output in W Current in A
I 39 0,17
II 62 0,27
III 80 0,35
Pump characteristic curves for models CMF 140, CMF 150, CMT 150
Sound pressure level
Noise levels for outdoor modules CMF 80, CMF 90, CMT 100 Noise levels for outdoor modules CMF 140, CMF 150, CMT 150
Level Output in W Current in A
I 122 0,53
II 129 0,69
III 172 0,75
5
4
3
2
1
0
0
1
2
3
4
6
Förderhöhe in m
Durchuss in m/h
Förderhöhe in kPa
50
40
30
20
10
0
60
Förderhöhe in m
Durchuss in m/h
7
8
6
5
4
3
2
1
0
0
1
2
3
4
5
6
7
Förderhöhe in kPa
70
80
60
50
40
30
20
10
0
Supply height in m
Supply height in m
Supply height in kPa
Supply height in kPa
Flow in m³/h
Flow in m³/h
Frequency band
Frequency band
Noise level in dB
Noise level in dB
Cooling
Cooling
Heating
Heating
40
General terms
Defrosting
At outdoor temperatures below 5°C it is possible that ice may form on the evaporators of air/water heat pumps. The removal of this ice is referred to as defrosting and is undertaken by supplying heat, either regularly or as requirements dictate. Air/water heat pumps with circuit reversal are distinguished by their requirements-based, quick and energy-efficient defrosting system.
Bivalent mode
The heat pump provides the entire heating energy down to a pre­determined outdoor temperature (e.g. 0°C). If the temperature drops below this value, the heat pump switches off and the secondary heating appliance takes over the heating, e.g. a heating boiler.
Sealing test
System operators are obliged to ensure the prevention of refriger­ant leakage in accordance with the directive on substances that deplete the ozone layer (EC 2037/2000) and the Regulation on Certain Fluorinated Greenhouse Gases (EC 842/2006). In addition, a minimum of one annual service and inspec­tion must be carried out, as well as a sealing test for refrigerating plants with a refrigerant filling weight over 3 kg.
Energy supply company switching
Certain energy supply companies offer special tariffs for the operation of heat pumps.
Expansion valve
Heat pump component for lower­ing the condensing pressure on
the vapour tension. In addition, the expansion valve regulates the quantity of injected refrigerant in relation to the evaporator load.
Sponsorship
The German Reconstruction Loan Corporation supports ecologically sound construction and modernisa­tion of domestic buildings for pri­vate individuals. This includes heat pumps which can be supported in the form of loans. The German Federal Office of Economics and Export Control (BAFA) subsidises the installation of effective heat pumps (please refer to: www.kfw. de und www.bafa.de).
Limit temperature / balance point
Outdoor temperature where the secondary heating appliance cuts in under bivalent operation.
Heating output
Flow of heat emitted from the liquefier to the environment. The heating output is the sum of the electrical power consumed by the condenser and the heat flux ob­tained from the environment.
Inverter
Power regulator which serves to match the speed of the compressor motor and the speed of the evapo­rator fans to the heating require­ment.
Seasonal performance factor
The seasonal performance factor relates to the ratio of heat content delivered by the heat pump system to the supplied electrical energy in
one year. This is not the same as the coefficient of performance.The seasonal performance factor cor­responds to the reciprocal value of the annual power input factor.
Annual power input factor
The annual power input factor indicates the power input (e.g. electrical energy) required in order to achieve a certain benefit (e.g. heating energy). The annual power input factor includes the energy required for auxiliary drives. Cal­culation of the annual power input factor is undertaken according to VDI – Directive 4650.
Refrigerating capacity
Heat flux extracted from the en­vironment by the evaporator (air, water or soil).
Refrigerant
The working medium used in a refrigerant plant, e.g. heat pump, is referred to as the refrigerant. The refrigerant is a liquid which is used for thermal transfer in a refrigeration plant and which is able to absorb heat by changing its state at low temperatures and low pressures. A further change of state at higher temperatures and higher pressure serves to dissipate this heat.
Compressor (condenser)
Unit designed for the mechanical conveyance and compression of gasses. Compression serves to sig­nificantly increase the pressure and temperature of the medium.
41
REMKO CMF / CMT
Coefficient of performance
The current ratio of thermal out­put produced by the heat pump to the consumed electrical power is referred to as the coefficient of performance, as measured under standardised boundary conditions according to EN 255 / EN 14511. A coefficient of performance of 4 means that a usable thermal output amounting to 4-times the electrical power consumption is available.
Single energy source mode
The heat pump covers a large proportion of the required heating power. On a few days per year an electrical heating coil supplements the heat pump under extremely low outdoor temperatures. Dimension­ing of the heat pump for air/water heat pumps is generally based on a limit temperature (also known as balance point) of approx. -5 °C.
Monovalent mode
In this mode, the heat pump is the sole heating appliance in the building all year round. Monovalent mode is primarily used in combina­tion with brine/water and water/ water heat pumps.
Storage tank
The installation of a hot-water stor­age tank is generally recommended in order to extend the running time of the heat pump under low heat requirements. A storage tank is required for air/water heat pumps in order to bridge off-periods.
Noise
Noise is transmitted in media such as air or water. Essentially there are two types of noise, airborne sound and solid-borne sound. Airborne sound is transmitted entirely via the air. Solid-borne sound is transmit­ted in solid materials or liquids and is only partially radiated as airborne sound. The audible range of sound lies between 20 and 20,000 Hz.
Sound pressure level
The sound pressure level is a comparable characteristic quantity for the radiated acoustic output of a machine, for example, a heat pump. The noise emission level at certain distances and acoustic environments can be measured. The standard is based on a sound pressure level given as a nominal noise level.
Split AC unit
Design where one part of the de­vice is positioned outdoors and the other inside the building. Both units are connected to each other by a refrigerant pipe.
Evaporator
Heat exchanger on a refrigerant plant which uses the evaporation of a working medium in order to ex­tract heat from its environment at low temperatures (e.g. the outdoor air).
Liquefier
Heat exchanger on a refrigerant plant which liquefies a working medium in order to transmit heat to its environment (e.g. the heating system).
Regulations and guidelines
The erection, installation and com­missioning of heat pumps has to be undertaken by qualified special­ist engineers. In doing so, various standards and directives are to be observed.
Heat requirement assessment
A precise dimensioning of the system must be carried out for heat pump systems in order to maximise efficiency. Calculation of the heat requirement is undertaken accord­ing to national standards. However, approximate requirements can be determined based on the W/m² tables multiplied by living space to be heated. The result of this is the overall heat requirement, which includes the transmission heat re­quirement and the infiltration heat loss.
Heat pump system
A heat pump system consists of a heat pump and a heat source system. For brine and water/water heat pumps, the heat source system must be made available separately.
Heat source
Medium from which the heat pump derives heat, in other words, soil, air and water.
Heat carrier
Liquid or gas medium (e.g. water, brine or air), in which heat is trans­ported.
42
Technical data
Range CMF 80 CMF 90 CMT 100 CMF 140 CMF 150 CMT 150
confi guration Heating only
Heating / cool­ing
Heating / cool­ing
Heating only
Heating / cool­ing
Heating / cool­ing
Inverter technology
REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec REMKO SuperTec
System Air / water Air / water Air / water Air / water Air / water Air / water
Heat pump manager Multitalent Multitalent Multitalent Multitalent Multitalent Multitalent
Storage tank for hydraulic decou­pling of volumetric fl ows
optional optional 150 l optional optional 150 l
Electric booster heating 6 kW optional optional Series optional optional Series
Water heating optional optional optional optional optional optional
Heating output min / max kW 3,5 - 10,2 3,5 - 10,2 3,5 - 10,2 5,0 - 16,0 5,0 - 16,0 5,0 - 16,0
Cooling performance min / max kW 3,3 - 8,1 3,3 - 8,1 5,5 - 14,0 5,5 - 14,0
Heating output for A7/W35 kW/COP1)8,1 / 4,5 8,1 / 4,5 8,1 / 4,5 14,2 / 4,5 14,2 / 4,5 14,2 / 4,5
Heating output for A2/W35 kW/COP1)7,0 / 3,9 7,0 / 3,9 7,0 / 3,9 13,4 / 4,2 13,4 / 4,2 13,4 / 4,2
Heating output for A7/W45 kW/COP1)7,3 / 3,2 7,3 / 3,2 7,3 / 3,2 13,1 /3,4 13,1 /3,4 13,1 /3,4
Heating output for A2/W45 kW/COP1)6,3 / 2,8 6,3 / 2,8 6,3 / 2,8 12,7 / 3,2 12,7 / 3,2 12,7 / 3,2
Heating output for A7/W55 kW/COP1)7,0 / 2,3 7,0 / 2,3 7,0 / 2,3 12,1 / 2,6 12,1 / 2,6 12,1 / 2,6
Heating output for A7/W55 kW/COP1)6,0 / 2,1 6,0 / 2,1 6,0 / 2,1 11,6 / 2,4 11,6 / 2,4 11,6 / 2,4
Functional range heating
2)
°C -20 to +34 -20 to +34 -20 to +34 -20 to +34 -20 to +34 -20 to +34
Functional range cooling
2)
°C +15 to +46 +15 to +46 +15 to +46 +15 to +46 +15 to +46 +15 to +46
Max. supply temperature heating water
°C up to +55 up to +55 up to +55 up to +55 up to +55 up to +55
Refrigerant / basic fi lling -- / kg R 410A3) / 3,5 R 410A3) / 3,5 R 410A3) / 3,5 R 410A3) / 5.0 R 410A3) / 5,0 R 410A3) / 5,0
Refrigerant, additional quantity
30-50m
g/m 60 60 60 60 60 60
Power supply V / Hz 230/1~ / 50 230/1~ / 50 230/1~ / 50 400/3~N/50 400/3~N/50 400/3~N/50
Starting current
A 12,5 12,5 12,5 8 8 8
Rated current
A 13 13 13 13 13 13
Rated capacity
kW 3,0 3,0 3,0 9,0 9,0 9,0
Customer's fuse protection (outdoor
unit)Tripping characteristic B
A 25 25 25 3x16 3x16 3x16
Volumetric fl ow water hot water at
∆t 5 K
m³/h 1,4 1,4 1,4 2,2 2,2 2,2
Pressure loss on liquefi er
at t 5 K
kPa 5,4 5,4 5,4 8,1 8,1 8,1
Pressure loss on indoor module kPa 11,1 11,1 22,7 22,7
max. airfl ow volume outdoor
module
m³/h 1.900 1.900 1.900 3.530 3.530 3.530
Max. permissible operating pres-
sure hot water
bar 3,0 3,0 3,0 3,0 3,0 3,0
Hydraulic connection supply /
return fl ow
Inches 1“ AG 1“ AG 1“ AG 1“ AG 1“ AG 1“ AG
Noise output LpA 1m (outdoor
unit)
dB(A) 46/38
4)
46/38
4)
46/38
4)
50/42
4)
50/42
4)
50/42
4)
Dimension indoor unit Height /
width / depth
mm 800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550 800 / 550 / 550 800 / 550 / 550 1800 / 550 / 550
Dimension outdoor unit Height /
width / depth
mm 945 / 950 / 330 945 / 950 / 330 945 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330 1350 / 950 / 330
Weight indoor module kg 52 52 135 55 55 138
Weight outdoor module kg 75 75 75 130 130 130
1) COP=coeffi cient of performance according to EN 14511
2) Based on the outdoor temperature
3) Contains greenhouse gas according to Kyoto protocol
4) Distance 5 m clear fi eld.
43
Subject to technical modifi cations, no responsibility taken for the correctness of information!
Consulting
We keep the specialist knowl-
edge of our advisers continu-
ously up-to-date with intensive
training. This has earned us a
reputation as more than just a
good, reliable supplier: REMKO,
a partner who helps solve prob-
lems.
Sales
REMKO provides not only a
well-developed distribution
network in Germany and abroad,
but also unusually highly skilled
professionals in distribution.
REMKO staff in the fi eld are
more than mere salespeople:
above all, they must advise our
clients in the areas of air condi-
tioning and heating technology.
Customer service
Our units work precisely and
dependably. Should a failure
occur, however, REMKO cus-
tomer service will rapidly be at
your side. Our comprehensive
network of experienced dealers
guarantees quick and reliable
service.
REMKO INTERNATIONAL
… Always nearby! Take advantage of our experience and advice
REMKO GmbH & Co. KG
Air conditioning and heating technology
Im Seelenkamp 12 · D-32791 Lage
P.O. Box 1827 ·D-32777Lage
Phone +49 5232 606-0
Fax +49 5232 6 06-2 60
E-mail info@remko.de
Internet www.remko.de
Hotline
Germany
+49 5232 606-0
International
+49 5232 606-130
Loading...