Pilz PNOZ XV3.1 Data Sheet

Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2.6V
Technical Details PNOZ X2.6V
Electrical data
Supply voltage DC: 24 V Tolerance 85 ... 110 % Power consumption Approx. 3.5 W Voltage and current at input circuit Single channel: 24 V DC/120 mA
Dual channel: 24 V DC/50 mA Switching capability in accordance with EN 60947-4-1, 02/01 AC1: 240 V/6 A/1500 VA
DC1: 24 V/6 A/100 W EN 60947-5-1, 11/97 AC15: 230 V/5 A; DC13: 24 V/5 A (DC13: 6 switching cycles/min) Output contacts 4 safety contacts (N/O), delay-off Contact fuse protection 6 A quick or 4 A slow in accordance with EN 60947-5-1, 08/00
Emergency stop relay and safety gate monitor in accordance with VDE 0113 part 1, 11/98, EN 60204-1, 12/97
Features
Dual-channel operation which detects shorts across the input contacts
Supply voltage: 24 VDC
2 delay-off safety contacts
1 semiconductor output for
variable frequency inverter or PLC
Approvals
Semiconductor output 24 VDC/100 mA, NPN short-circuit
protected
External voltage supply 24 VDC ±20 %
Times
Switch-on delay Automatic reset: max. 200 ms
Manual reset: max. 50 ms Delay-on de-energisation 1 s ±20 % (switched off)/max. 40 ms Recovery time Approx. 1 s Simultaneity channel 1/2 µ Supply interruption before de-energisation Approx. 10 ms
Mechanical data
Maximum cross section of external 2 x 1.5 mm2 or 1 x 2.5 mm conductor Single-core or multi-core
with crimp connector Dimensions (H x W x D) 87 x 45 x 121 mm Weight 370 g
Description
Operating modes
1
2
PNOZ X2.6V
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
45 mm P-97 housing, DIN-Rail mounting
Positive-guided relay outputs: 4 safety contacts (N/O)
Semiconductor for variable frequency inverter
Delay-on de-energisation can be
switched off
Connections for – Emergency stop button or
safety gate limit switch
– Reset button
Detects shorts across the input contacts
LED indicators for power consumption, switching status, channel 1/2 and semiconductor output
Increase in the number of safety contacts available by connecting expander modules
Single-channel operation
Dual-channel operation
Automatic reset
Manual reset
NSG-D-2-306-02/02
1-1
Emergency Stop Relays, Safety Gate Monitors
Category 4, EN 954-1
PNOZ X2.6V
1
Internal wiring diagram
Y55
&
Y11 (+24 V)
Y12
Y10 (0 V)
A1 (L+) A2 (L-)
External wiring
Example 1 Single-channel E-stop wiring with automatic reset
S21
S22
S33
S34
S11
S31
S1
S12
S32
S11
Input­circuit
S11
Reset circuit/ Feedback control loop
S12
S34
Start Unit
Delay Control
S33
K1
S22
Input circuit
S32
Input-­circuit
S31
Start Unit
Delay Control
S21
Safety contacts
37
27
K2
38
28
Example 4
Dual-channel safety gate control with automatic reset
S33
S11
S21
S1S1
S22 S31
S2
S32
S12
S34
- Key
S1/S2: E-STOP or safety gate
57
47
S3: Reset button
switch
Switch operated
Gate open
Gate closed
58
48
Increase in safety contacts The number of output contacts can be increased by using expander modules or relays/contactors with positive-guided contacts.
L1
K3 K4
S33
N
S34
27
28
K3
K4
Example 2 Single-channel E-stop wiring with manual reset
S21
S22
S33
S3
S34
S11
S31
S1
S12
S32
Example 3 Dual-channel E-stop wiring with manual reset
S33
S11
S21
S31
S1
S32
S22
S12
S3
S34
Example 5 Variable frequency inverter
L1 L2 L3
1L+
K3
K4
N
A1 S33 S34
Y55 S11 S11 S12
S21 S22 Y10
A2 S31 S32
K4
27
28
37
Y11 S57
Y12 58
38
47
48
K3
STOPP
M
Drehzahlregler Speed Regulator
n
Pilz GmbH & Co., Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone +49 (7 11) 34 09-0, Telefax +49 (7 11) 34 09-1 33, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-306-02/02
Loading...
+ 1 hidden pages