Parr Instrument Primary Temp Meter User Manual

No. 558M
I
n
s
t
a
l
l
a
t
i
o
n
I
n
s
t
r
u
c
t
i
o
n
s
f
o
r
I
n
s
t
a
l
l
a
t
i
o
n
I
n
s
t
r
u
c
t
i
o
n
u
u
u
s
t
i
o
n
s
r
e
M
r
e
M
r
e
M
I
n
s
t
a
l
l
a
t
i
o
n
I
n
s
t
r
u
c
m
P
P
P
1. Unplug the power cord of the 4848 controller. Remove the (2) screws located on the top/front cover at the rear corners of the controller. Gently lift the cover forward, which is hinged at the bottom, taking care not to apply tension on any internal wiring.
3. If replacing an existing meter, make a note of where the wires are installed on the existing primary temperature meter. The pin numbers are printed on the back of the meter itself. They should match the Pin Out table on the next page. Using tape to designate each wire, record the pin number each wire is attached to. If not replacing an existing meter move on to step 6.
4. Using a Phillips screwdriver, remove the wires from the back of the primary temperature meter.
5. Using a Phillips screwdriver, remove the two screws on the top and bottom mounting brackets. Pull the meter out.
6. Insert the new meter through the panel cutout, from outside in, making sure the rubber gasket is on the outside of the controller front panel. Slide the mounting brackets onto the meter with the mounting screws pointing towards the front panel. Slide the mounting bracket forward until it touches the controller panel. The clasps on the mounting brackets should align with the grooves on the meter. Gently tighten the screws until the meter is held into place.
7. If applicable, connect the free wires (disconnected
in step 3) to the new meter. Check the positions carefully. If a wiring kit was included the wires may be attached to the Primary Temperature Controller. Reference the Pin Out Table for proper wiring connections.
a
r
r
r
i
i
r
y
T
e
m
p
e
r
a
m
a
r
y
T
e
m
m
a
r
i
y
T

Meter installation in 4848 Reactor Controller

e
m
p
p
e
e
t
r
a
t
r
a
t
f
o
r
f
o
r
e
t
e
r
i
n
4
8
4
e
t
e
r
i
n
e
t
e
r
i
n
Back of Primary Temperature Meter
8
4
8
4
4
8
4
8
8
n
t
C
C
C
r
o
o
n
t
r
o
o
t
r
o
o
n
Back Blank Plate
l
l
e
r
l
l
e
r
l
l
e
r
- 1 -
PTM Installation in a 4848

Pin Out Table:

2083E Meter Color/Wire#: Attaches to:
Pin 1 Violet/Wire#8 SSR 4/A2-
Pin 2 Red/Wire#7
Red (RTD Only)
**Red (Type – J, Type – K, Type – T), White (RTD)

Wiring Schematic:

Pin 3
Pin 4 White* Thermocouple + Pin 5 Red** Thermocouple - 1G Pin 6 Pin 7 Brown/Wire#6 Cooling fuse (End) Pin 8 Yellow/Wire#5 Terminal Block 1 Pin 9 Black/Wire#10 Terminal Block 3 Pin 10 White/Wire#9 Terminal Block 4 Pin 11 Black/Wire#4 Terminal Block 5 Pin 12 White/Wire#3 Terminal Block 2 Pin 13 Pin 14 Orange/Wire#1 Terminal Block 6 Pin 15 Blue/Wire#2 Terminal Block 7
*White (Type – J), Yellow (Type – K), Blue (Type – T), Black (RTD)
SSR +3/A1 or ETLM Meter Pin 9 (When used with an ETLM Module)
Thermocouple -
- 2 -
PTM Installation in a 4848

Final Steps:

Close the controller and replace the two screws on the top plate. Plug the 4848 Controller back in and turn it on. The display should show room temperature with the thermocouple connected. It is useful to check that the settings on the display are set correctly. Check these against the Factory Default Settings.
- 3 -
PTM Installation in a 4848

Factory Default Settings for Primary Temperature Module

Keys command:
1. Press “SET” to select
2. Press return key move to next operation mode
3. Up/Down arrow keys to adjust value or select type
Press return key and release
Operation
Select type/value Comment Mode r-S Run Run/Stop SP 0** Decimal point position AL1H 375 Upper alarm setting AL1L 0 Lower alarm setting LoC OFF Lock mode(lock all keys or only up/down arrow
Out1 - (read-only) Heater output % Out2 - (read-only) Cooling output %
** If using a type-J or type-K thermocouple, SV = 0 If using an RTD, SV = 1
Press and hold down “SET” for 5-sec
Operation
Select type/value Comment Mode InPt J** Input type tPUn C Temperature unit tP-H 800** Upper-limit range tP-L 0 Lower-limit temperature range CTRL PID Control mode (ON/OFF, MANUAL, PID and PID
S-HC H1C2 Output 1 is Heating and output 2 is Cooling ALA1 6 Alarm operates when PV value is higher than AL1H
SALA OFF System alarm CoSH ON Communication write function that able to use set
C-Sl ASCII Format type C-no 1 Communication address bPS 9600 Communication baud rate Len 7 Data length setting PrtY Even Parity bit setting StoP 1 Stop bit setting
** If using a type-J thermocouple, InPt = J, tP-H = 800 If using a type-K thermocouple, InPt = K, tP-H = 800 If using an RTD, InPt = Pt, tP-H = 600
able to use)
PROG)
setting or PV value is lower than AL1L setting
point from software
- 4 -
PTM Installation in a 4848
Primary Temperature Module (continued)
Press “SET” and release
Operation
Select type/value Comment Mode At OFF Auto Tuning ON/OFF PID0 0 The 0th PID Parameter SV 0 The 0th SV P0 11.8 Proportional control I0 375 Integral control D0 93 Derivative control IoF0 0 Integral value offset HtPd 5 Heat cycle control HcPd 5 Cool cycle control CoEF 10 1 & 2 value output group during dual loop output
dEAd 0 Dead band tPoF 0 Inaccuracy adjustment
control
- 5 -
PTM Installation in a 4848
This page left blank intentionally.
- 6 -
PTM Installation in a 4848
This page left blank intentionally.
- 7 -
Parr Instrument Company
211 53rd Street • Moline, Illinois 61265 USA
1-309-762-7716 • 1-800-872-7720 • Fax: 1-309-762-9453
E-mail: parr@parrinst.com • http://www.parrinst.com
Revision 09/18/09
Loading...