Mitsubishi LGH-15RX5, LGH-25RX5, LGH-35RX5, LGH-50RX5, LGH-65RX5 Service Manual

...
0 (0)

 

January 2009 No. U155

LOSSNAY

 

HAND BOOK

 

(For HONG KONG)

FOR DEALERS

Model:

LGH-15RX5-E

 

LGH-25RX5-E

 

LGH-35RX5-E

 

LGH-50RX5-E

 

LGH-65RX5-E

 

Nameplate

 

LGH-80RX5-E

 

LGH-100RX5-E

 

LGH-150RX5-E

 

LGH-200RX5-E

Nameplate

Remote controller (Parts number is not set.)

Model: PZ-60DR-E

Filter (Parts number is not set.)

Model: PZ-25RF8-E PZ-50RF8-E PZ-80RF8-E

PZ-35RF8-E PZ-65RF8-E PZ-100RF8-E

Repair work should be performed by the manufacturer, its service agent or similarly qualified person in order to avoid hazards.

Contents

1.

Safety precautions....................................................................

3

2.

Specifications.......................................................................

4-8

3.

Outside dimensions............................................................

9-18

4.

Electrical wiring diagrams ................................................

19-20

5.

Basic circuit diagram .............................................................

21

6.

Fundamentals of operation ..............................................

22-44

7.

Troubleshooting ...............................................................

45-65

8.

Disassembly and assembly..............................................

66-68

9.

Parts catalog ..................................................................

69-123

 

LGH-15RX5-E ...............................................................

70-75

 

LGH-25RX5-E ...............................................................

76-81

 

LGH-35RX5-E ...............................................................

82-87

 

LGH-50RX5-E ...............................................................

88-93

 

LGH-65RX5-E ...............................................................

94-99

 

LGH-80RX5-E ...........................................................

100-105

 

LGH-100RX5-E..........................................................

106-111

 

LGH-150RX5-E..........................................................

112-117

 

LGH-200RX5-E..........................................................

118-123

1. Safety precautions

Please be sure to read the following safety precautions thoroughly before commencing with the maintenance work, and conduct the inspection and repair of the product in a safe manner.

The types and levels of danger that may arise if the product is handled incorrectly are described by using the warning symbols shown below.

 

Warning

orIncorrectdeath. handling of the product may result in serious injury

 

Electric

 

 

 

 

 

 

shock

 

Turn off the power supply

 

If you must inspect the circuitry while the

 

Be sure to shut off the power supply isolator

 

power is on, do not touch the live parts.

 

before disassembling the unit for repair.

 

(Failure to heed this warning may result in elec-

Caution for

(Failure to heed this warning may result in elec-

Be sure to follow

tric shock.)

tric shock.)

electric shock

this instruction.

 

 

 

 

Modification is prohibited

 

Use proper parts and tools

 

Do not modify the unit.

 

For repair, be sure to use the parts listed in the service

 

 

 

 

parts list of the applicable unit model and

 

(Failure to heed this warning may result in elec-

 

use the proper tools.

 

 

 

tric shock, fire and/or bodily injury.)

 

 

 

 

 

 

 

(Failure to heed this warning may result in elec-

Be sure to follow

 

 

 

 

tric shock, fire and/or bodily injury.)

 

 

 

Prohibited

this instruction.

 

 

 

Proper electric work

 

Replace damaged and/or degraded parts

Use the electric wires designated for electric work, and

Be sure to replace the power-supply cord and lead wire

conduct electric work in accordance with the "Electric

in the event that they are damaged and/or

 

Installation Engineering Standard," the "Indoor Wiring

degraded.

 

Regulations," and the Installation Work

 

 

 

Guide.

 

(Failure to heed this warning may result in elec-

Be sure to follow

 

 

 

 

tric shock and/or fire.)

 

 

 

 

this instruction.

(Incomplete connection or wiring installation may Be sure to follow

 

 

Check insulation

 

result in electric shock and/or fire.)

this instruction.

Be sure to measure the insulation resistance once the

 

 

 

 

repair work is complete, and turn on the power supply

 

 

 

 

after verifying that an insulation resistance

 

 

 

 

 

of at least 10MΩ is obtained.

 

 

 

 

 

(If an insulation problem exists, it may result in

Be sure to follow

 

 

 

 

electric shock.)

 

 

 

 

this instruction.

 

 

 

 

 

 

Incorrect handling of the product may result in serious injury Caution or damage to properties including buildings and equipment.

 

 

 

 

Caution for bodily injury

 

Wear gloves

Do not conduct any work at a location

 

Wear gloves when conducting work.

where you do not have a sure footing.

 

 

 

 

 

(Failure to heed this caution may result in injury

(Failure to heed this caution may result in a fall.)

 

to your hands from sharp metal or other edges.)

 

 

Prohibited

 

 

 

 

 

Be sure to follow this instruction.

Request during repair

•Inspect the grounding, and repair it if incomplete. Make sure that a power supply isolator is being installed, if not, install one.

●Make sure that the product operates correctly upon completion of repair. Clean the product as well as the surrounding area, and then notify the customer of the completion of repair.

—3—

2. Specifications

—4—

—5—

Mitsubishi LGH-15RX5, LGH-25RX5, LGH-35RX5, LGH-50RX5, LGH-65RX5 Service Manual

—6—

—7—

—8—

3. Outside dimensions

LGH-15RX5-E

Unit (mm)

—9—

LGH-25RX5-E

Unit (mm)

—10—

LGH-35RX5-E

Unit (mm)

—11—

LGH-50RX5-E

Unit (mm)

—12—

LGH-65RX5-E

Unit (mm)

—13—

LGH-80RX5-E

Unit (mm)

—14—

LGH-100RX5-E

Unit (mm)

—15—

LGH-150RX5-E

Unit (mm)

—16—

LGH-200RX5-E

Unit (mm)

—17—

PZ-60DR-E

Unit (mm)

PZ-25RF8-E, PZ-35RF8-E, PZ-50RF8-E, PZ-65RF8-E, PZ-80RF8-E, PZ-100RF8-E

Unit (mm)

—18—

4. Electrical wiring diagrams

LGH-15RX5-E, LGH-25RX5-E, LGH-35RX5-E, LGH-50RX5-E, LGH-65RX5-E, LGH-80RX5-E, LGH-100RX5-E

 

 

 

GREEN/YELLOW

POWER SUPPLY

 

 

BROWN

 

 

220-240V

50Hz

 

 

RED

 

 

 

 

 

 

 

 

 

 

TM1

Isolator

 

 

 

TAB3

TAB5

 

L

L

 

 

BLACK

BLUE

 

 

 

 

 

TAB1

N

N

 

 

GREY

CN10

 

 

 

 

 

 

 

 

M2

YELLOW

TAB2

 

 

 

 

 

BROWN

PE

 

 

 

 

C

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR

(*2)

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

CN1

RED

 

 

 

 

ORANGE

 

 

TR

 

 

 

 

 

 

 

 

 

BLUE

CN9

 

 

 

 

 

M1

WHITE

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

C

CN7

YELLOW

 

GM

FAN MOTOR

(*2)

 

 

RED

 

 

 

 

 

 

LS

 

 

 

 

 

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

 

 

CN32

CN16

 

 

SW2

 

CN2

BROWN

 

 

 

 

 

 

 

 

TH1 (OA)

 

 

 

 

 

 

SW1

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

CN6

 

 

 

 

 

 

 

 

 

CN5

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW5

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

TM4

Operation or Delay1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

monitor output

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SA1 SA2

X10

MAX 240VAC 2A MIN 220VAC 100mA

 

 

 

TH2 (RA)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

24VDC

2A

5VDC

100mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X12 X11

 

 

 

 

 

 

 

2

PZ-

(*1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

60DR-E

 

 

 

 

 

 

TM3

 

 

TM2

 

 

TB5

 

 

 

 

 

2nd remote controller (Max. two remote controllers installable)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

7

8

1

2

3

A

B

S

 

 

 

 

 

 

 

 

 

 

2nd LOSSNAY unit (Up to max 15 units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmission

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shield Wire

cable

 

 

 

 

 

 

 

 

By-pass or Delay2

 

12V or 24V

DC

 

 

M-NET

 

(non-polar)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

monitor output 6 , 7

Mr.Slim

 

 

 

transmission

 

 

 

 

 

 

 

 

 

 

Malfunction monitor

(non-polar)

MELANS

cable

 

*When the optional Remote Controller PZ-60DR-E

(*2) LGH-100RX5 has two

output 7 , 8

 

 

 

 

 

 

 

 

 

 

capacitors per motor

 

 

 

 

 

 

 

 

 

 

is used as the M-NET System, connect it to 1

MAX 240VAC 1A

 

External control input

 

 

 

 

as following drawing.

 

 

 

 

 

2 of TM4 terminal block, and connect M-NET

24VDC

1A

 

1

 

3

 

 

 

 

 

M

 

 

MIN 220VAC 100mA

 

 

 

 

 

 

transmission wire to A , B on TB5 terminal

 

 

5VDC

100mA

 

 

 

 

 

 

 

 

block.

 

 

(*1)

 

 

 

C

C

 

 

 

 

 

 

 

 

 

 

TM4

 

 

 

 

 

 

 

 

Unchanged a-contact

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Optional Remote controller

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(PZ-60DR-E)

 

 

 

 

NOTE 1.TM1, TM2, TM3, TM4, TB5 shown

 

 

 

 

 

 

 

 

 

 

 

CN16

 

 

 

 

 

 

 

 

 

1

 

 

2nd remote controller

 

 

in dotted lines are field work.

 

 

 

 

 

 

 

 

 

 

 

 

(Unchanged a-contact)

 

 

 

 

 

 

 

 

 

 

 

 

 

(Max. two remote controllers

 

BROWN

2.Isolator should be provided by the customer.

 

 

TB5 (M-NET)

 

 

installable)

 

HI

RED

 

3.Be sure to connect the grounding wire.

 

 

M-NET

A

B

S

 

 

 

 

 

LO

ORANGE

*Attention

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXTRA-LO

YELLOW

 

 

 

 

 

 

transmission

 

Shield Wire

 

(*1)PZ-41SLB-E and PZ-52SF-E cannot

 

 

 

 

 

 

 

 

BY-PASS

GREEN

With this product, the wiring installation method will

 

cable

 

 

 

be used when using PZ-60DR-E.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

vary according to the design of the system.

 

 

 

 

 

2nd or later main units

 

 

 

 

 

 

 

 

Perform electrical installation to meet local electrical regulations.

 

 

 

 

 

 

 

 

 

 

 

.Always use double insulated PVC cable for the transmission cables.

 

 

 

 

 

 

 

 

 

 

.Wiring work must be performed by qualified professionals.

 

 

 

 

 

 

 

 

 

 

 

 

.All supply circuits must be disconnected before obtaining access to the terminal devices.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Specifications may be subject to change without notice.

Definition of Symbols

M1:

Motor for exhaust fan

CN1:

Connector (Transformer primary)

M2:

Motor for supply fan

CN2:

Connector (Transformer secondary)

C:

Capacitor

CN5:

Connector (Thermistor)

GM:

Motor for By-pass operation

CN6:

Connector (Microswitch)

LS:

Microswitch

CN7:

Connector (Motor for By-pass operation)

TH1:

Thermistor for outside air

TAB3:

Tab connector(Fan motor)

TH2:

Thermistor for return air

TAB5:

Tab connector (Fan motor)

SW1:

Switch (Main/Sub change)

CN9:

Connector (Fan motor)

SW2, 5:

Switch (Function selection)

CN10:

Connector (Fan motor)

TM1:

Terminal block (Power supply)

CN16:

Connector (High/Low/Extra Low/By-pass switch)

TM2:

Terminal block (External control input)

CN32:

Connector (Remote control selection)

TM3:

Terminal block (Monitor output)

SA1:

Address setting rotary switch (10 digit)

TM4 :

Terminal block (Transmission cable and monitor output)

SA2:

Address setting rotary switch (1 digit)

TB5 :

Terminal block (M-NET Transmission cable)

SYMBOL

: Indicates terminal block.

TAB1,TAB2:

Connector (Power supply)

 

: Connector.

TR:

Control circuit transformer

 

: Board insertion connector or fastening

 

connector of control board.

X10,X11,X12:

Relay contact

 

 

 

—19—

LGH-150RX

5

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-E, LGH-200RX -E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GREEN/YELLOW

 

 

 

 

 

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220-240V

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TM1

Isolator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BROWN

 

 

 

 

 

L

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

N

N

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x103

 

 

 

 

 

 

TAB3

TAB5

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

BLACK

 

 

 

 

BLUE

 

PE

 

 

 

 

 

 

 

GREY

 

 

 

x103

 

 

 

 

 

 

TAB1

 

 

 

 

 

 

 

M2

YELLOW

 

 

 

GREY

 

CN10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x102

YELLOW

 

 

 

 

 

TAB2

 

 

 

 

 

 

 

 

 

 

 

x102

 

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*2)

 

 

 

x101

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAN MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x101

 

 

 

 

 

 

 

 

 

 

 

TR1

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CN1

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

BLUE

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x203

 

x203

 

 

 

 

 

 

 

RED

 

BLACK

 

 

 

 

 

 

M1

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

CN9

 

 

 

 

 

 

 

LS

 

 

 

 

 

 

 

 

 

 

 

WHITE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

C

 

 

 

x202

 

 

 

 

 

 

CN7

 

WHITE

 

BLACK

 

 

 

 

FAN MOTOR

(*2)

x202

 

 

 

 

 

 

 

 

 

 

TR2

 

 

GM MG

 

 

 

 

 

x201

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x201

 

 

 

 

 

 

 

 

 

 

 

WHITE TR3

 

BLACK

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

 

 

 

 

 

 

 

 

BROWN

 

 

 

 

 

 

 

 

 

GREY

 

 

 

CN32

CN16

 

 

 

 

 

CN2

BROWN

 

 

LS

 

 

 

 

 

M2

YELLOW

 

 

 

 

 

SW2

 

 

 

 

 

 

 

 

 

 

 

TH1 (OA)

 

 

 

 

 

 

SW1

 

 

 

 

GM MG

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

ORANGE

CN5

 

 

 

 

 

 

 

 

 

BLACK

 

 

 

 

FAN MOTOR

(*2)

 

 

ORANGE

 

 

SW5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

TM4

 

Operation or Delay1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

 

 

 

 

 

 

 

 

 

10

monitor output

 

 

 

 

 

 

 

 

TH2 (RA)

 

 

 

 

SA1 SA2

 

X10

 

MAX 240VAC 2A MIN 220VAC 100mA

 

 

 

 

ORANGE

 

 

 

 

 

 

 

 

9

 

24VDC

2A

5VDC

100mA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLUE

 

X12 X11

 

 

 

 

 

 

 

 

 

 

(*1)

 

 

 

 

 

 

 

M1

WHITE

 

 

 

 

 

 

 

 

2

 

PZ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXHAUST

C

 

 

 

 

 

 

 

 

 

 

 

1

 

60DR-E

 

 

 

 

 

 

 

TM3

 

 

TM2

 

TB5

 

 

 

2nd remote controller (Max. two remote controllers installable)

 

FAN MOTOR

(*2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

7

8

1

2

3

A

B

S

 

 

 

2nd LOSSNAY unit (Up to max 15 units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shield Wire

 

Transmission

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cable

 

 

 

 

 

 

 

 

CN16

 

By-pass or Delay2

12V or 24V

DC

 

 

 

M-NET

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(non-polar)

 

 

 

 

 

 

 

 

(Unchanged a-contact)

monitor output

6 , 7

Mr.Slim

 

 

 

 

transmission

 

 

 

 

 

 

 

 

 

 

BROWN

Malfunction monitor

(non-polar)

 

MELANS

cable

 

 

 

 

 

 

 

 

 

 

HI

RED

output 7 , 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAX 240VAC 1A

 

External control input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LO

ORANGE

 

 

 

 

 

 

 

 

 

 

 

(*2) LGH-200RX5 has two

 

 

24VDC

1A

 

1

 

3

 

 

 

 

 

*When the optional Remote Controller PZ-60DR-E

 

 

 

YELLOW

 

 

 

 

 

 

 

 

 

capacitors per motor

 

 

 

MIN 220VAC 100mA

 

 

 

 

 

 

is used as the M-NET System, connect it to 1

 

 

BY-PASS

GREEN

 

 

 

 

 

 

 

 

as following drawing.

 

 

5VDC

100mA

 

 

 

 

 

 

 

 

2

of TM4 terminal block, and connect M-NET

 

 

 

 

 

 

 

Unchanged a-contact

 

 

 

transmission wire to

A ,

B on TB5 terminal

M

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

block.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(*1)

 

 

 

 

 

NOTE 1.TM1, TM2, TM3, TM4, TB5 shown

 

 

 

 

 

 

 

 

 

TM4

 

 

 

 

C

C

 

 

 

 

 

 

 

 

 

 

Optional Remote controller

 

in dotted lines are field work.

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(PZ-60DR-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Isolator should be provided by the customer.

 

 

 

 

 

 

 

1

 

2nd remote controller

 

 

 

3.Be sure to connect the grounding wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB5 (M-NET)

 

(Max. two remote controllers

 

 

*Attention

 

 

 

 

 

 

 

 

 

 

 

 

installable)

 

 

 

 

 

 

 

 

 

 

 

 

 

M-NET

 

A

B

S

 

 

 

 

 

 

 

 

With this product, the wiring installation method will

 

 

 

 

 

 

Shield Wire

(*1)PZ-41SLB-E and PZ-52SF-E cannot

 

vary according to the design of the system.

 

 

 

 

 

transmission

 

 

 

 

 

 

 

 

cable

 

 

 

 

 

 

be used when using PZ-60DR-E.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Perform electrical installation to meet local electrical regulations.

 

2nd or later main units

 

 

 

 

 

 

 

 

.Always use double insulated PVC cable for the transmission cables.

 

 

 

 

 

 

 

 

 

 

 

.Wiring work must be performed by qualified professionals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.All supply circuits must be disconnected before obtaining access to the terminal devices.

 

 

 

 

 

 

*Specifications may be subject to change without notice.

Definition of Symbols

M1:

Motor for exhaust fan

M2:

Motor for supply fan

C:Capacitor

GM:

Motor for By-pass operation

LS:

Microswitch

TH1:

Thermistor for outside air

TH2:

Thermistor for return air

SW1:

Switch (Main/Sub change)

SW2, 5:

Switch (Function selection)

TM1:

Terminal block (Power supply)

TM2:

Terminal block(External control input)

TM3:

Terminal block (Monitor output)

TM4:

Terminal block

 

(Transmission cable and monitor output)

TB5:

Terminal block (M-NET Transmission cable)

TAB1,TAB2:

Connector (Power supply)

TR1:

Control circuit transformer

TR2,TR3:

By-pass operation transformer

X10,X11,X12: Relay contact

X101,X102,X103: Relay Supply fan speed control X201,X202,X203: Relay Exhaust fan speed control

CN1:

Connector (Transformer primary)

CN2:

Connector (Transformer secondary)

CN5:

Connector (Thermistor)

CN6:

Connector(Microswitch)

CN7:

Connector (Motor for By-pass operation)

CN9:

Connector (Fan motor)

TAB3:

Tab connector (Fan motor)

TAB5:

Tab connector (Fan motor)

CN9:

Connector (Fan motor)

CN10:

Connector (Fan motor)

CN16:

Connector(High/Low/By-pass switch)

CN32:

Connector (Remote control selection)

SA1:

Address setting rotary switch (10 digit)

SA2:

Address setting rotary switch (1 digit)

SYMBOL

: Indicates terminal block.

 

Board insertion connector or fastening

 

connector of control board.

—20—

5.Basic circuit diagram

Circuit board diagram and check points

* Fan drive output voltage: Each 220 to 240 V AC

EA fan drive

 

SA fan drive

(CN9)

 

(CN10)

Extra

 

Extra

High High

Low

High High Low

5 V DC

 

 

(C6)

 

 

LED 1 (Green)

 

 

Normal : unlit

 

 

During

 

 

an error: blinking

 

 

For damper

 

 

motor drive

 

 

(CN7)

 

 

220 to

 

 

240 V AC

 

 

Damper motor

 

 

position detection

 

 

(CN6) *1

 

 

During Lossnay

 

 

ventilation: 12 V DC

 

 

During Bypass

 

 

ventilation: 0 V

 

 

Thermistor

 

 

(RA) (OA)

 

 

(CN5)

 

 

LED 4 (Red)

 

 

Energized: Lit

 

 

Not

 

 

energized: OFF

 

 

LED 2 (Red)

When SW5-6 is OFF

When blinking, an M-

During normal

NET communication

ventilation: 0Ω

error is generated.

During heat exchange

(The number of

ventilation: ∞Ω

blinks indicates the

When SW5-6 is ON

details of the error)

During operation

 

This will be lit

and when the outdoor air

steadily when there

temperature is ≤ -5ºC to

is no (registered)

15ºC: 0Ω

connection to another

While stopped,

M-NET device.

or when the outdoor air

 

temperature is ≥ 15ºC: ∞Ω

 

(TM3 6,7)

 

Common for SA

 

 

 

 

 

 

 

 

 

fan drive

 

 

 

 

 

 

 

 

 

 

(TAB5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transformer

 

 

 

 

 

Common for EA

 

Power supply

 

primary (input)

fan drive

 

220 to 240 V AC

 

(CN1)

(TAB3)

 

(TAB1, TAB2)

 

220 to 240 V AC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

(C5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuse

 

 

 

 

 

 

 

 

 

(5 A/250 V)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15 V DC

 

 

 

 

 

 

 

 

 

 

(C3,C8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12 V DC (C4,C5)

During operation: 0Ω

When stopped: ∞Ω

(TM4 9,10)

Transformer secondary (output) (CN2)

11 to 20 V AC

During an

 

M-NET transmission

error : 0Ω

 

cable (Shielded)

Normal: ∞Ω

 

(TB5 S)

(TM3 7,8)

 

 

 

 

 

For external device connections (TM2)

M-NET transmission cable (PZ-52SF-E, M-NET controller, power supply unit, and City Multi indoor unit)

(TB5 A,B)

Lossnay remote controller (PZ-60DR-E, PZ-41SLB-E) and transmission cable between Lossnay units (TM4 1, 2)

10 to 15V DC

*1: Damper position detection input is only for the LGH-15 to 100 types, and not for the LGH-150 and 200 types.

—21—

6. Fundamentals of operation

● Description of the circuit operation

(1) System Configuration

Lossnay operates through the following system.

 

System

 

 

 

 

 

 

 

 

System Diagram

 

 

 

 

 

 

 

Features

Prepared

Classification

Details

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic

1 Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• One remote controller oper-

Lossnay

 

 

 

 

 

Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ates one Lossnay unit.

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 Remote

 

 

M-NET

Remote

 

 

Transmission cable

 

 

 

controller

 

 

controller

 

 

controller

 

 

 

 

 

(PZ-60DR-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

between the remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller and Lossnay

 

 

 

E, or PZ-

 

 

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41SLB-E)

 

 

 

Remote controller : PZ-60DR-E or PZ-41SLB-E

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Transmission cable terminal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

blocks between Lossnay unit

 

 

 

 

 

M-NET

: M-NET transmission cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

terminal block

 

 

 

 

 

 

 

 

 

 

 

 

R

: Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(PZ-60DR-E or PZ-41SLB-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Two

1 Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Two remote controllers oper-

Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lossnay

 

 

 

 

 

 

 

 

 

remote

unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ate one Lossnay unit. (Last

remote

 

con-

2 Remote

 

 

 

 

 

 

 

 

 

 

M-NET

Remote

 

 

 

 

 

 

 

 

touch priority operation)

controller

 

trollers

controllers

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

(PZ-60DR-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* PZ-60DR-E and PZ-41SLB-E

E or PZ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cannot be used together.

41SLB-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiple

Multiple

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• A maximum of 15 Lossnay

Lossnay

 

 

 

Lossnay

 

 

Lossnay

 

 

 

Lossnay

 

 

units

Lossnay

 

 

 

 

 

 

 

units can be operated by a

remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

system

units

 

M-NET

Remote

 

M-NET

Remote

 

M-NET

Remote

 

single remote controller.

controller

 

 

controller

 

controller

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Group operation)

(PZ-60DR-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• All units will operate in the

E or PZ-

System

 

 

 

 

 

 

 

 

 

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

same mode.

41SLB-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller (PZ-60DR-E,or PZ-41SLB-E)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic

Systems

Level sig-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Lossnay is started/stopped

 

interlock

nal output

 

 

External device

 

 

 

Lossnay

 

by a signal (*1) from an

 

 

 

 

 

 

 

 

 

 

 

ed with

device

 

 

(Other manufacturer’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

external device.

 

 

 

 

 

M-NET

Remote

 

 

 

 

 

 

 

PAC etc.)

 

 

 

 

 

 

 

 

 

 

external

(other

 

 

 

 

 

 

 

 

 

controller

 

• Having a remote control per-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

device

manufac-

 

 

Level (pulse) signal

 

 

 

 

 

 

 

 

 

 

 

 

 

mits last touch priority opera-

 

 

(air con-

turer's

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion with the external device

 

 

dition-

PAC, etc.)

 

 

Output device

 

 

 

 

 

 

 

 

 

 

 

 

 

and the remote controller.

 

ing

or pulse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• A maximum of 15 Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

 

 

units)

signal out-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

units can be operated.

 

 

 

put device

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1: An uncharged a-contact,

 

 

 

(building

 

 

Remote controller (PZ-60DR-E, or PZ-41SLB-E)

12 V DC or 24 V DC level

 

 

 

control

 

 

(Operation without a remote controller is also

signal, or an uncharged a-

 

 

 

system,

 

 

possible.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

contact, 12 V DC or 24 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

etc.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DC pulse signal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mr. Slim

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Lossnay can be

 

 

 

(A-control

 

 

 

Mr. Slim

 

 

 

 

 

 

 

 

Lossnay

 

 

 

started/stopped by an A-con-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or K-con-

 

 

 

indoor unit

 

 

 

 

 

 

 

M-NET

Remote

 

 

 

trol remote controller or a K-

 

 

 

trol

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

control remote controller.

 

 

 

 

 

 

 

 

 

Mr. Slim

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

remote

 

 

 

 

 

 

Mr. Slim-Lossnay

• Lossnay High or Low fan

 

 

 

con-

 

 

 

 

 

 

Lossnay

connection cable

speed can be selected from

 

 

 

 

 

 

 

 

 

interlocked

 

 

 

troller)

 

 

 

 

 

 

(Included parts with

the A-control remote controller.

 

 

 

 

 

 

 

 

signal

 

 

 

 

 

 

Lossnay)

 

 

 

 

 

 

A,K

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Lossnay stand-alone opera-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

tion is permitted from the A-

 

 

 

 

 

 

A-control or K-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control remote controller.

 

 

 

 

 

 

control remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Neither PZ-60DR-E nor PZ-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

41SLB-E can be used.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

— 22—

 

 

 

System

 

System Diagram

 

 

Features

Prepared

Classification

Details

 

 

 

Parts

 

 

 

 

 

 

 

 

Systems Mitsubishi

When using PZ-60DR-E

 

 

• Can be interlocked with a

 

 

interlock

City Multi

City Multi

 

 

Lossnay

 

 

maximum of 16 air condition-

 

 

ed with

air condi-

 

 

 

 

ing units.

 

 

Indoor unit

 

 

Remote

Transmission

 

 

external

tioner

 

 

• Lossnay can be

 

 

 

 

M-NET controller

cable between

 

 

device

(MA

 

 

 

 

the remote

started/stopped, and

 

 

(air con-

remote

MA

 

 

R1

controller and

switched between High and

 

 

dition-

controller

 

 

 

 

Lossnay

Low fan speed by an air con-

 

 

 

 

 

 

 

 

 

 

ing

or ME

M-NET

 

Lossnay remote controller

ditioner remote controller.

 

 

units)

remote

transmission

 

(PZ-60DR-E)

 

 

• Lossnay stand-alone opera-

 

 

 

(Operation without a remote

 

 

 

controller)

cable

 

tion is permitted from an air

 

 

 

 

 

controller is also possible.)

 

 

 

 

When using PZ-52SF-E

 

 

conditioner remote con-

 

 

 

 

 

 

troller.

 

 

 

 

City Multi

 

 

Lossnay

 

 

• Having PZ-60DR-E or PZ-

 

 

 

 

 

 

 

 

 

52SF-E, last touch priority

 

 

 

 

indoorIndoorunit

 

M-NET Remote

 

 

 

 

 

 

 

 

operation is permitted with

 

 

 

 

 

 

controller

 

 

 

 

 

 

MA

 

R2

 

 

the air conditioner remote

 

 

 

 

 

 

 

controller and the Lossnay

 

 

 

 

 

 

 

 

 

 

 

 

M-NET

 

Remote controller for M-NET

remote controller.

 

 

 

 

 

 

 

 

 

 

transmission

 

(PZ-52SF-E)

 

 

*1: PZ-41SLB-E cannot be

 

 

 

 

cable

 

(Operation without a remote

 

 

 

 

 

 

controller is also possible.)

used in this system.

 

 

 

 

Remote controller : Terminal block for trans-

*2: PZ-60DR-E and PZ-52SF-E

 

 

 

 

 

 

mission cable between PZ-

cannot be used together.

 

 

 

 

 

 

60DR-E and Lossnay

 

 

 

 

 

M-NET

: M-NET transmission cable

 

 

 

 

 

 

 

terminal block

 

 

 

 

Control

 

 

R1

: PZ-60DR-E

 

 

 

 

 

 

R2

: PZ-52SF-E

 

 

 

 

Central

Central/in

When using PZ-60DR-E

 

 

• Lossnay batch/independent

• Lossnay

NET

control

depen-

System controller

Power supply unit

 

 

(group) control permitted by

remote

system

dent con-

SC

 

Power supply

 

 

system controller.

controller

M-

for

trol of

 

 

 

Group 1

 

Group 2

• Operation of Lossnay within

(PZ-60DR-

 

Lossnay

multiple

 

 

 

 

 

 

a group is permitted by a

E or PZ-

 

only

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay

Lossnay remote controller.

52SF-E)

 

 

units

(PZ-60DR-E or PZ-52SF-E)

• Centralized

 

 

 

 

 

 

 

 

 

 

 

R1

 

 

 

 

R1

• One group of a maximum of

controllers

 

 

 

Remote controller (PZ-60DR-E)

 

 

16 Lossnay units can be

(G-50A),

 

 

 

Group 3

Group 4

operated.

(PAC-

 

 

 

 

 

 

 

 

 

• Number of Lossnay control

SF44SRA),

 

 

 

Lossnay

Lossnay

Lossnay

 

Lossnay

units

(PAC-

 

 

 

 

 

 

 

 

 

Centralized controller (AG-

YT40ANR

 

 

 

R1

 

 

R1

 

 

150A) : 50 units/50 groups

A), and

 

 

 

When using PZ-52SF-E

 

 

ON/OFF remote controller

(AG-150A)

 

 

 

 

 

(PAC-YT40ANRA) : 50

• Power sup-

 

 

 

M-NET controller

Power supply unit

 

units/16 groups

ply units

 

 

 

SC

 

Power supply

 

Group 2

System remote controller

(PAC-

 

 

 

 

 

 

Group 1

 

(PAC-SF44SRA) : 50

SC50KUA),

 

 

 

 

 

 

 

 

 

units/50 groups

(PAC-

 

 

 

Lossnay

Lossnay

Lossnay

 

Lossnay

 

SF46EPA),

 

 

 

 

 

 

 

 

 

*1: The remote controller (PZ-

and (PAC-

 

 

 

R2

 

 

R2

41SLB-E) cannot be used

SC51KUA)

 

 

 

 

 

 

in this system.

 

 

 

 

Remote controller for M-NET

 

 

 

 

 

 

(PZ-52SF-E)

 

 

 

*2: PZ-60DR-E and PZ-52SF-E

 

 

 

 

Group 3

Group 4

 

 

 

 

cannot be used together.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lossnay

Lossnay

Lossnay

Lossnay

 

 

 

 

 

R2

 

 

R2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* Refer to the technical documentation for details about M-NET system design.

 

 

 

 

 

 

 

— 23—

 

 

● Remote controller list 1 Remote controllers

Rough Classification

Fine Classification

Product

Model

 

 

 

 

For Lossnay independent control

Lossnay remote controller

PZ-60DR-E

 

 

 

 

 

 

 

PZ-41SLB-E

 

 

 

 

For Lossnay M-NET control

Lossnay remote controller

PZ-52SF-E

 

 

 

 

M-NET

MA remote con-

MA remote controller

PAR-20/21MAA

For City Multi air con-

troller

 

 

Wireless remote controller

PAR-FA(FL)31MA

ditioner

 

 

 

 

Compact remote controller

PAC-YT51CRA

 

 

 

 

 

 

 

M-NET remote

ME remote controller

PAR-F27MEA

 

controller

 

 

 

Compact remote controller

PAC-SE51CRA

 

 

 

 

For Mr. Slim

 

A-control remote controller

PAR-21MAA

 

 

 

 

 

 

K-control remote controller

 

 

 

 

 

2 System controller

Classification

Product

Model

 

 

 

System controller

Schedule timer

PAC-YT34STA

 

 

 

 

Group remote controller

PAC-SC30GRA

 

 

 

 

ON/OFF remote controller

PAC-YT40ANRA

 

 

 

 

System remote controller

PAC-SF44SRA

 

 

 

 

Centralized controller

G-50A, AG-150A

 

 

 

(2) Start-up process

When the power is turned on, operation will not be performed for up to 45 seconds to allow Lossnay to perform information settings required for control purposes.

The start-up process can be confirmed by the blinking of LED1 in the Lossnay circuit board (1 second on/1 second off) or the remote controller LED when using the remote controller.

— 24—

(3) Fan control

1Fan speed control for each system

The control indicated below can be performed according to the system that is paired.

●Up to two of the Lossnay remote controllers PZ-60DR-E, PZ-41SLB-E, and PZ-52SF-E can be used in the same group, but they cannot be used together with a different remote controller. When using two remote controllers, be sure to use the same model of remote controller.

Caution ●PZ-41SLB-E cannot be used in M-NET control. When controlling Lossnay in M-NET control, use PZ-60DR-E or PZ-52SF-E.

●When using PZ-60DR-E and mixing the LGH-15 to 100 types together with the LGH-150 and 200 types in a group,set the LGH-15 to 100 types as “Main”.

System Configuration

 

Stand-alone/multi-

 

ple Lossnay and

 

Lossnay remote

 

controller: PZ-

 

60DR-E

 

Stand-alone/multi-

 

ple Lossnay and

 

Lossnay remote

 

controller: PZ-

System

41SLB-E

System interlocked

with Mr. Slim

Basic

 

 

Level signal/pulse

 

signal

 

System interlocked

 

with the output

 

device

 

Stand-alone/multi-

 

ple Lossnay and

 

Lossnay remote

 

controller: PZ-

 

60DR-E

 

Stand-alone/multi-

 

ple Lossnay and

 

Lossnay remote

Control

controller: PZ-

52SF-E

 

 

M-NET

NET-M

Lossnay central

control system

 

 

M-NET

 

System interlocked

 

with City Multi

 

indoor units

 

 

Remote controllers

Fan speed

System controllers

 

Lossnay remote

The remote controller “Fan Speed Adjustment” button permits High

controller

(Extra High)/Low fan speed selection, and the “Extra Low fan

PZ-60DR-E

SPEED” button permits an extra low fan speed selection.

 

(The LGH-150 and 200 types do not provide Extra Low fan speed

 

operation.)

Lossnay remote

The remote controller “Fan Speed Adjustment” button permits High

controller

(Extra High)/Low fan speed selection.

PZ-41SLB-E

(Extra Low fan speed selection is not available from the remote con-

 

troller.)

A-control remote

The A-control remote controller “Ventilation” button permits High

controller

(Extra High)/Low fan speed selection.

K-control remote

(High (Extra High)/Low fan speed selection is not available from the

controller

K-control remote controller.)

(Remote con-

(Extra Low fan speed selection is not available from the A-control

troller connec-

and K-control remote controllers.)

tion prohibited

 

with Lossnay )

 

None

Fixed to High (Extra High) fan speed.

Lossnay remote

The remote controller “Fan Speed Adjustment” button permits High

controller

(Extra High)/Low fan speed selection, and the “Extra Low fan speed”

PZ-60DR-E

button permits an Extra Low fan speed selection.

 

(The LGH-150 and 200 types do not provide Extra Low fan speed

 

operation.)

Lossnay remote

The remote controller “Fan Speed Adjustment button” permits High

controller

(Extra High)/Low fan speed selection.

PZ-52SF-E

(Extra Low fan speed selection is not available from the Lossnay

 

remote controller.)

M-NET controller

The system remote controller, or centralized control remote con-

 

troller “Fan Speed” button or “Ventilation setting” button permits High

 

(Extra High)/Low fan speed selection.

 

(The ON/OFF remote controller and the schedule timer do not permit

 

fan speed selection.)

 

(Extra Low fan speed selection is not available from the system

 

remote controller or the centralized control remote controller.)

ME remote con-

The remote controller “Ventilation” button permits High (Extra

troller

High)/Low fan speed selection.

PAR-F27MEA,

(Extra Low fan speed selection is not available from the ME remote

MA remote concontroller and MA remote controller.)

troller

 

PAR-20/21MAA

 

— 25—

2Fan speed control by function setting

The following fan speed control can be set with PZ-60DR-E or the function selection switch (SW2) on the Lossnay circuit board.

 

 

 

Setting Method

 

 

 

 

 

Function

 

Details

PZ-60DR-E

PZ-60DR-E Not Used

 

(Remote controller

(Function selec-

 

 

 

 

 

 

function selection)

tion switch)

 

 

 

 

 

Extra High

This switches the settable fan speed from the remote controller

Supply fan

 

Air supply SW2-9

/High

and the system controller. Set this when there is a need for

speed setting

: ON

Fan speed

large air volume, or when there is a long duct line.

Extra High

SH: L

Exhaust SW2-10

selection

When set to High fan speed, High/Low fan speed can be set,

High

H: L

: ON

 

and when set to Extra High fan speed, Extra High/Low fan

Exhaust fan

 

 

 

speed can be set.

speed setting

(Refer to page

 

 

 

Extra High

SH: L

38)

 

 

The fan speed display of the remote controller,

 

Display

and the system controller will be the same for

High

H: L

 

 

 

either Extra High or High.

(Refer to page

 

 

 

 

 

 

Multiple

When PZ-60DR-E will not be used in a system of

 

 

41)

 

 

 

multiple Lossnay units, set the function selection

 

 

 

units

 

 

 

 

switches on the Lossnay circuit board for each

 

 

 

 

 

unit.

 

 

 

 

 

 

 

 

Multi venti-

This switches the settable fan speed from the remote controller

Supply fan

 

Air supply SW2-4

lation

and the system controller to a fixed Low fan speed. The sup-

speed setting

: ON

mode

ply/exhaust balance is adjusted to suit the usage environment

Multiple ventila-

Exhaust SW2-5

 

or the place of installation.

tion

: L

: ON

 

 

 

Exhaust fan

 

 

Operation

When both supply and exhaust are set to the multi

(Refer to page

 

ventilation mode, due to operation restrictions PZ-

speed setting

 

 

60DR-E cannot be switched to a setting other

Multiple ventila-

38)

 

 

tion

: L

 

 

 

than Low/Extra Low fan speed. Other remote con-

 

 

 

trollers and system controllers can change the fan

(Refer to page

 

 

 

speed display; however, the fan will remain fixed

 

 

 

41)

 

 

 

 

at Low fan speed.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Multiple

When PZ-60DR-E will not be used in a system of

 

 

 

 

multiple Lossnay units, set the function selection

 

 

 

 

units

 

 

 

 

switches on the Lossnay circuit board for each

 

 

 

 

 

unit.

 

 

 

 

 

 

 

Power

During the first 30 minutes of operation, operation will be at

Power supply/

SW2-3: ON

supply/

High (Extra High) fan speed. This is used when rapid ventila-

exhaust when

 

exhaust

tion is desired at the time of starting operation.

operation starts :

(Refer to page

mode

After 30 minutes have elapsed since starting operation, or

ON

 

38)

(When

when the fan speed set from the remote controller or the sys-

 

 

 

operation

tem controller has been changed to something other than High

(Refer to page

 

starts )

fan speed, power ventilation will be cancelled and the system

41)

 

 

 

will follow the fan speed set by the remote controller or system

 

 

 

 

controller.

 

 

 

 

 

 

 

 

 

 

 

Display

During power ventilation, PZ-60DR-E will display

 

 

 

 

“POWER VENT START”. Other remote controllers

 

 

 

 

 

 

 

 

 

 

and system controllers will display the set fan

 

 

 

 

 

speed, even during power supply exhaust opera-

 

 

 

 

 

tion.

 

 

 

 

 

 

 

 

 

 

Multiple

When PZ-60DR-E will not be used in a system of

 

 

 

 

multiple Lossnay units, set the function selection

 

 

 

 

units

 

 

 

 

switches on the Lossnay circuit board for each

 

 

 

 

 

unit.

 

 

 

 

 

 

 

 

 

— 26—

 

 

Setting Method

 

 

 

 

Function

Details

PZ-60DR-E

PZ-60DR-E Not Used

(Remote controller

(Function selec-

 

 

 

 

function selection)

tion switch)

 

 

 

 

Fan motor

When TM4 9, 0 output settings, and TM3 6, 7 output set-

TM4 9, 0 output setting

delay stop

tings are set to operation monitor with delay function 1 or 2, the

“Operation monitor with delay

(Operation

fan will stop after 3 minutes have elapsed from the OFF opera-

function 1”: SW2-8: ON

monitor

tion when output ON (Closed) is switched to output OFF

TM3 6, 7 output setting

with delay

(Open) by the Lossnay stop instruction.

“Operation monitor with delay

function)

 

function 2”: SW5-6: ON

*Note 1

 

(Refer to page 38)

 

 

* This function cannot be set from

 

 

PZ-60DR-E.

 

 

 

 

 

*Note 1: The fan will continue to operate even after operation is stopped with the remote controller, etc.

3Restrictions when switching fan speed

The following restrictions exist when the fan speed is switched.

When switching between High (Extra High) and Low fan speed, the fan will be stopped for approximately 5 seconds.

When switching between settings other than Extra Low fan speed and Extra Low fan speed, the fan will be

stopped for approximately 10 seconds.

4Air supply fan forced stop

Under the following conditions, Lossnay will force stop of the air supply fan. However, when the following conditions are met while operating at Extra Low fan speed, the air supply fan will stop, and the exhaust fan will operate at Low fan speed.

(When operating at Extra Low fan speed, the air supply fan and the exhaust fan cannot be stopped separately.)

When Mr. Slim is in defrost or stopped due to a fault, in an interlocked system with Mr. Slim that has a duct connection with Lossnay.

(For cold inrush prevention, or falling dust prevention)

When the indoor unit is in defrost, in an interlocked system with a City Multi indoor unit that has a duct connection with Lossnay.

(For cold inrush prevention)

When the outside temperature is -10ºC or lower, the air supply fan is stopped periodically for approximately 10 minutes to 55 minutes.

(To prevent freezing of the Lossnay core)

(4)Ventilation mode control

Lossnay (heat exchange) ventilation or bypass (normal) ventilation is achieved by switching the air duct inside the Lossnay unit with a damper.

1Ventilation mode

There are 3 control modes.

● Lossnay ventilation (heat exchange ventilation) mode: Heat exchange ventilation is performed regularly via

 

the Lossnay core.

● Bypass ventilation (normal ventilation) mode

: Ventilation is performed regularly without going

 

through the Lossnay core.

● Automatic ventilation mode

: A temperature sensor built into the unit provides

 

automatic ventilation to a suitable ventilation mode.

 

In addition, energy saving ventilation is provided by

 

interlocking with a Mr. Slim or City Multi indoor unit.

— 27—

2Damper control for each system

The control indicated below can be performed according to the system that is paired

●Up to two of the Lossnay remote controllers PZ-60DR-E, PZ-41SLB-E, and PZ-52SF-E can be used in the same group, but they cannot be used together with a different remote con-

troller. When using two remote controllers, be sure to use the same model of remote con- Caution troller.

●PZ-41SLB-E cannot be used in M-NET control. When controlling Lossnay in M-NET control, use PZ-60DR-E or PZ-52SF-E.

Basic System

M- NET Control

 

System

Remote controllers

Ventilation mode

 

System controllers

 

 

 

 

Stand-alone/multi-

Lossnay remote controller

The “Function selector” button of the remote controller

 

 

ple Lossnay and

PZ-60DR-E

permits ventilation mode switching for automatic,

 

Lossnay remote

 

Lossnay, and bypass ventilation. Bypass ventilation is

 

controller: PZ-

 

set at the time of night purge operation, and ventilation

 

60DR-E

 

mode switching is not possible.

 

 

 

 

 

Stand-alone/multi-

Lossnay remote controller

The “Function selector” button of the remote controller

 

ple Lossnay and

PZ-41SLB-E

permits ventilation mode switching for automatic,

 

Lossnay remote

 

Lossnay, and bypass ventilation.

 

controller: PZ-

 

 

 

41SLB-E

 

 

 

 

 

 

 

System interlocked

A-control remote controller

Fixed to automatic ventilation.

 

with Mr. Slim

K-control remote controller

 

 

 

(Remote controller connection

 

 

 

prohibited with Lossnay )

 

 

 

 

 

 

Level signal/pulse

None

Fixed to automatic ventilation.

 

signal output

 

 

 

device and external

 

 

 

device only

 

 

 

Stand-alone/multi-

Lossnay remote controller

The “Function selector” button of the remote controller

 

ple Lossnay and

PZ-60DR-E

permits ventilation mode switching for automatic ,

 

Lossnay remote

 

Lossnay, and bypass ventilation. Bypass ventilation is

 

controller: PZ-

 

set at the time of night purge operation, and ventilation

 

60DR-E

 

mode switching is not possible.

 

 

 

 

 

Stand-alone/multi-

Lossnay remote controller

The “Function selector” button of the remote controller

 

ple Lossnay and

PZ-52SF-E

permits ventilation mode switching for automatic ,

 

Lossnay remote

 

Lossnay, and bypass ventilation.

 

controller: PZ-

 

 

 

52SF-E

 

 

 

 

 

 

 

M-NET

M-NET controller

The “Operation mode” button of the system remote con-

 

Lossnay central

 

troller and the centralized controller permits ventilation

 

control system

 

mode switching for automatic , Lossnay, and bypass

 

 

 

ventilation.

 

 

 

(The schedule timer, ON/OFF remote controller, and the

 

 

 

group remote controller do not permit ventilation mode

 

 

 

selection.)

 

 

 

 

 

M-NET

ME remote controller

Fixed to automatic ventilation.

 

System interlocked

PAR-F27MEA,

 

 

with City Multi

MA remote controller

 

 

indoor units

PAR-20/21MAA

 

 

 

 

 

— 28—

3Bypass ventilation prohibited

When the conditions described below are applicable, the ventilation mode will be fixed at Lossnay ventilation. When bypass ventilation has been set from the remote controller or the system controller, damper operation will be set to Lossnay ventilation, even though bypass ventilation is displayed on the ventilation mode display.

When the outdoor temperature is 8ºC or lower. (Product condensation prevention)

When bypass ventilation prohibition has been set under this condition, the prohibition will be cancelled when the outdoor temperature goes from a temperature of less than 10 ºC to one higher than 10ºC.

When there is an outdoor temperature (Outdoor Air) thermistor fault.

When, in the automatic ventilation mode, there is an outdoor temperature (Outdoor Air) or indoor temperature (Return Air) thermistor fault.

When Lossnay is set to the automatic ventilation mode and interlocked with Mr.Slim or City Multi indoor units

set to the fan operation mode.

4Damper operation

The damper provides control with a 30 second period. Accordingly, a delay of 30 seconds maximum may be generated from ventilation mode switching to damper operation.

5Automatic ventilation algorithm temperature map

Ventilation mode switching of Lossnay ventilation/Bypass ventilation in the automatic ventilation mode is in accordance with the following map.

a.Systems interlocked with Mr. Slim and City Multi indoor units

The map will differ depending on the operation mode that has been set with the A-control remote controller or the K-control remote controller for Mr. Slim, or the MA remote controller or the ME remote controller for City Multi indoor units. There will be switching to the ventilation mode in conjunction with the set temperature of the air conditioner remote controller. Note that the “b” map will be followed while Mr. Slim and City Multi indoor units are stopped.

Cooling mode (Winter)

 

40

 

 

 

 

 

 

 

 

 

 

Lossnay

 

 

Undetermined area

 

 

35

Ventilation

 

 

 

 

 

 

ºC

30

Remote controller

 

 

 

 

temperature

 

Set temperature

 

 

 

 

 

25

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

 

Outdoor

 

 

 

 

 

 

 

15

 

 

 

 

 

Ventilation

 

10

Bypass ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Prohibition temperature 8ºC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

Indoor temperature ºC

Heating mode (Summer)

 

40

 

 

 

Undetermined area

 

 

 

Bypass

 

 

 

35

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ºC

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

25

Undetermined area

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bypass

Outdoor

15

 

 

 

 

 

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Lossnay

Set temperature

 

 

4ºC

 

 

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

Indoor temperature ºC

Lossnay ventilation area

Bypass ventilation area

Undetermined area

When operation starts under this condition, Lossnay ventilation will be activated.

When this condition is reached after operation starts, the current ventilation mode is maintained.

— 29—

b.When there is no interlocking with Mr. Slim and City Multi indoor units Pattern 1. Normal ventilation mode

When PZ-60DR-E is used, operation will be at the setting of automatic ventilation adjustment pattern “1” of the remote controller function selection. When PZ-60DR-E is not used, operation will be at the OFF setting of function selection switch (SW2-7) on the Lossnay circuit board.

Outdoor temperature ºC

When an outdoor temperature of 28ºC has not

 

 

When an outdoor temperature of 28ºC has been

 

40

 

been detected within 24 hours

 

 

 

40

 

detected within 24 hours

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

Lossnay

 

 

 

 

 

 

 

35

Lossnay

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

30

 

 

 

Bypass

 

 

 

ºC

30

 

 

 

 

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

 

 

25

 

 

 

 

 

 

 

 

25

Undetermined area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

Outdoor

15

 

 

 

 

 

Bypass

 

 

Bypass ventilation

 

 

 

 

 

Bypass ventilation

 

 

 

Ventilation

 

10

 

Undetermined area

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

Prohibition temperature 8ºC

 

 

 

 

 

5

Prohibition temperature 8ºC

 

 

 

 

 

 

 

 

 

24ºC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24ºC

 

 

 

0

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

5

10

15

20

25

30

35

40

 

0

5

10

15

20

25

30

35

40

 

 

 

Indoor temperature ºC

 

 

 

 

 

 

Indoor temperature ºC

 

 

Lossnay ventilation area

Bypass ventilation area

Undetermined area

When operation starts under this condition, Lossnay ventilation will be activated.

When this condition is reached after operation starts, the current ventilation mode is maintained.

Pattern 2. Outdoor cooling priority mode

When the outdoor temperature is lower than the indoor temperature, this mode actively takes in the outdoor air for cooling.

When PZ-60DR-E is used, operation will be at the setting of automatic ventilation adjustment pattern “2” of the remote controller function selection. When PZ-60DR-E is not used, operation will be at the ON setting of function selection switch (SW2-7) on the Lossnay circuit board.

When an outdoor temperature of 17ºC has not

 

 

 

been detected within 24 hours

 

 

 

40

 

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

Lossnay

 

 

 

 

 

 

35

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ºC

30

 

 

 

 

 

 

 

 

ºC

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

temperature

25

 

 

 

 

 

 

 

Bypass

temperature

25

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

Ventilation

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

 

 

 

 

 

 

 

 

15

Outdoor

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

Undetermined area

10

 

 

 

 

 

 

 

 

 

 

 

5

Bypass ventilation

 

19ºC

 

 

 

5

 

 

Prohibition temperature 8ºC

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

0

 

 

0

5

10

15

20

25

30

35

40

 

Indoor temperature ºC

When an outdoor temperature of 17ºC has been detected within 24 hours

 

Lossnay

 

 

 

 

 

 

 

Ventilation

 

 

 

 

 

 

 

 

Undetermined area

 

 

 

 

 

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

Ventilation

 

 

Bypass ventilation

 

 

 

 

 

 

 

Prohibition temperature 8ºC

19ºC

 

 

 

 

0

5

10

15

20

25

30

35

40

Indoor temperature ºC

Lossnay ventilation area

Bypass ventilation area

Undetermined area

When operation starts under this condition, Lossnay ventilation will be activated.

When this condition is reached after operation starts, the current ventilation mode is maintained.

— 30—