MITSUBISHI MGS SERIES
60Hz/13.8kV
STAND-BY
1060 kW
DIESEL GENERATOR SET
60Hz/1800 rpm/13.8kV
POWER RATING (0.8 P.F.) MODEL CODE
STAND-BY 1060 kW 61S-P623
MGS1000HV with typical options
CONDITIONS & DEFINITIONS
Stand-by: Code: S
Applicable for supplying emergency power at varying load in the event of normal utility power interruption.
Fuel stop power in accordance with ISO15550, IS O3046/1, JISB8002-1, DIN6271 and BS5514.
Conditions:
Engine ratings are based on SAE J1349 standard conditions and also apply at ISO3046/1, DIN6271 & BS5514 standard
conditions.
Fuel rates: based on A STM D975, BS2869 and on fuel oil of 3 5° API (16°C or 60° F) gravity hav ing a LH V of 4 2, 78 0 kJ /kg
(18,390 Btu/lb.) when used at 29°C (85° F) and weighing 838.9 g/liter (7.001 lbs./U.S. gal.).
DIMENSION (Reference Data)
W : Width mm 2020
Total Weight (Dry) kg 12300

MITSUBISHI MGS SERIES
Lubricating oil capacity L 200
Coolant capacity without radiator
Coolant pump external resistance
Cooling fan air flow restriction
Allowable exhaust back pressure
Exhaust flange size (internal diameter)
Brake mean effective pressure
(excluding: intake, exhaust & fan)
Fuel consumption load 100%*
Fuel consumption load 75%*
Combustion air inlet flow rate
Heat rejection to coolant
Heat rejection to exhaust
Heat rejection to atmosphere from engine
Heat rejection to atmosphere from generator
STAND-BY
1060 kW
MGS SERIES DIESEL ENGINE: MITSUBISHI S12H-PTA-S
DIESEL GENERATOR SET
MGS1000HV
V-12, 4 stroke-cycle water-cooled, turbocharged and aftercooled
ENGINE SPECIFICATIONS & TECHNICAL DATA
ENGINE OPERATING DATA
* WITH FAN basis.
Deration for engine
Altitude: 2.5% per 300m (1000ft) above 1,500m
Temperature: 2% per 5℃ (9° F) above 40℃
ENGINE STANDARD EQUIPMENT
Aftercooler
Turbocharger filter
Structure ste el bas e
Crankcase breather
Charging alternator
Lubricating oil cooler
Fuel filters, full flow paper element
Fuel transfer pump, gear driven, plunger type
Electronic type governor
Jacket water heater
Jacket water pump, gear driven
Lubricating oil filter, full flow paper element
Lubricating oil pump, gear driven
Exhaust dry manifold
Radiator, blower fan, fan drive
Manual shutoff
24V DC electric starting motor