Milton CAT D40-6S Spec Sheet

DIESEL GENERATOR SET
FEATURES
Image shown may not reect actual package.
STANDBY 40 ekW 40 kVA
PRIME 36 ekW 36 kVA
60 Hz 1800 rpm 240/120 Volts
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
FUEL/EMISSIONS STRATEGY
• EPA Certied for Stationary Emergency Application (EPA Tier 3 emissions levels)
FULL RANGE OF ATTACHMENTS
• Wide range of bolt-on system expansion
attachments, factory designed and tested
• Flexible packaging options for easy and cost effective installation
SINGLE-SOURCE SUPPLIER
• Fully prototype tested with certied torsional vibration analysis available
WORLDWIDE PRODUCT SUPPORT
• Cat dealers provide extensive post sale support including maintenance and repair agreements
• Cat dealers have over 1,800 dealer branch stores operating in 200 countries
• The Cat S•O•SSM program cost effectively detects
internal engine component condition, even the presence of unwanted uids and combustion by-products
Cat® Model D40-6S, Single Phase
CAT C4.4 DIESEL ENGINE
Reliable, rugged, durable design
• Field-proven in thousands of applications worldwide
• Four-stroke diesel engine combines consistent performance and excellent fuel economy with minimum weight
• Electronic engine control
GENERATOR SET
• Complete system designed and built at ISO 9001 certied facilities
• Factory tested to design specications at full load conditions
CAT EMCP 4 CONTROL PANELS
• Simple user friendly interface and navigation
• Scalable system to meet a wide range ofcustomer needs
• Integrated Control System and Communications Gateway
SEISMIC CERTIFICATION
• Seismic Certication available
• Anchoring details are site specic, and are dependent on many factors such as generator set size, weight, and concrete strength. IBC Certication requires that the anchoring system used is reviewed and approved by a Professional Engineer
• Seismic Certication per Applicable Building codes:
IBC 2000, IBC 2003, IBC 2006, IBC 2009, IBC 2012 CBC 2007, CBC 2010
• Pre-approved by OSHPD and carries an OSP-0321-10 for use in healthcare projects in California
STANDBY 40 ekW 40 kVA PRIME 36 ekW 36 kVA
60 Hz 1800 rpm 240/120 Volts
FACTORY INSTALLED STANDARD & OPTIONAL EQUIPMENT
System Standard Optional
Air Inlet • Dry replaceable paper element type with restriction
indicator
Cooling • Radiator and cooling fan complete with protective guards
• Standard ambient temperatures up to 50°C (122°F)
Exhaust [ ] Industrial
Fuel • Flexible fuel lines to base with NPT connections [ ] Sub-base dual wall UL listed 24 hr fuel tank
Generator • Class H insulation
• Drip proof generator air intake (NEMA 2,IP23)
• Electrical design in accordance with with BS5000 Part 99, EN61000-6, IEC60034-1, NEMA MG-1.33
• IP23 Protection
Power Termination • Circuit breakers, UL/CSA listed, 3 pole (100% rated)
• Power center houses EMCP controller and control terminations (CB)
• Segregated low voltage wiring termination panel
• NEMA 1 steel enclosure, vibration isolated
• Electrical stub-up area directly below circuit breaker
Governor • Adjustable Electronic governor
Control Panels • EMCP 4.2 digital control panel
• Vibration isolated NEMA 1 enclosure with lockable hinged
door
• DC and AC Wiring harnesses
Lube [ ] Lube oil heater
Mounting • Heavy-duty fabricated steel base with lifting points
• Anti-vibration pads to ensure vibration isolation
• Complete OSHA guarding
• Stub-up pipe ready for connection to silencer pipework
Starting/Charging • 12 volt starting motor
• Batteries with rack and cables
General • High gloss polyurethane paint, Caterpillar Yellow except
rails and radiators gloss black
• Anticorrosive paint protection
• All electroplated hardware
[ ] Radiator stone guard [ ] Radiator transition ange
[ ] Residential [ ] Critical mufers [ ] Overhead silencer mounting kit
[ ] Sub-base dual wall UL listed 48 hr fuel tank [ ] Emergency vent 12ft extension [ ] 5 gallon spill containment
[ ] Generator upgrade 1 size [ ] Permanent magnet excitation [ ] Internal excitation [ ] Anti-condensation space heater
[ ] Auxiliary contacts [ ] Shunt trip [ ] Overload shutdown via breaker
[ ] NFPA110 upgrade [ ] Control panel chassis
[ ] IBC Seismic and OSHPD certication per Applicable
Building Codes: IBC2000, IBC20 03, IBC2006, IBC 2009, IBC 2012, CBC 2007, CBC 2010
[ ] Battery charger – UL 10 amp [ ] Battery disconnect switch [ ] Battery removal (does not remove rack and cables) [ ] Coolant Heater
[ ] CSA Certied [ ] Weather protective enclosure Industrial/Critical [ ] Sound attenuated protective enclosure [ ] Caterpillar tool set [ ] Caterpillar White paint
2
Loading...