Milton CAT D175-2 175 User Manual

ANNUNCIATOR
LEHE4753-01
EMCP 3 ANNUNCIATOR
The EMCP 3 Annunciator serves to display generator set system alarm conditions and status indications. The Annunciator has been designed for use on the EMCP 3 J1939 Communication Network and may be used in either local or remote applications, providing customers with enhanced site flexibility.
In local applications, the Annunciator may be mounted on the package generator set with the EMCP 3 Controller to provide a complete package-mounted monitoring solution.
The Annunciator may also be mounted separate from the generator set to provide remote indication of system operating and alarm conditions.
The EMCP 3 Annunciator is configurable to the standards of NFPA 99/110 for emergency standby generator systems.
FEATURES SPECIFICATIONS
The EMCP 3 Annunciator provides sixteen (16) individual points of annunciation, with two (2) LED’s included for each point.
An additional pair of LED’s provides status indication of the J1939 data link connection.
Includes alarm horn with lamp test and alarm acknowledge pushbuttons.
Configurable using standard Caterpillar
®
Service Tool
Configurable to NFPA 99/110 requirements for local and remote annunciation on emergency standby generator systems.
Provides custom label kit including software for customer’s specific alarms and arrangement
Designed and tested to meet stringent impulse shock and operating vibration requirements
Uses high quality shielded twisted-pair cable for robust remote communications
Graphic symbols are provided next to each pair to indicate various alarms and events
The Annunciator can be mounted either locally, on the package generator set, or remotely (up to 800 feet)
Provides superior visibility of the LED’s in direct sunlight
Technical Data
Electrical
Battery Voltage Functional Range: 9 to 32 VDC
Power Consumption
Maximum: 12 watt at 24 VDC Standby: 5 watt at 24 VDC
Control Power: 12-24 VDC Communication: J1939 (Accessory Data Link) Single, 6-pin Connector Alarm
Sound Level 80 db
PHYSICAL
Weight 4 lb or 1.8 kg
ENVIRONMENTAL
Operating Temperature –40° C to 70° C
–40° F to 158° F
Storage Temperature –50° C to 70° C
–58° F to 158° F
Relative Humidity 90%
CERTIFICATIONS
UL Recognized
EMCP 3 ANNUNCIATOR
LED COLOR SCHEME
Each pair of LED’s on the Annunciator consists of two of three colors: green, yellow and red, which allows for custom configuration of status, warning and shutdown conditions. The available colors and combinations are:
STANDARD LED CONFIGURATION
Emergency stop shutdown
Overcrank shutdown
Low coolant temperature warning
High coolant temperature warning/shutdown
Low oil pressure warning/shutdown
Overspeed warning/shutdown
Low coolant level warning/shutdown
Low fuel level warning/shutdown
EPS supplying load status
Control switch not in auto warning
High battery voltage warning/shutdown
Low battery voltage warning/shutdown
BATT charger AC failure warning/shutdown
Low starting air pressure warning/shutdown
Air shutdown damper status
Spare
Row LED 1 LED 2
1 Red Yellow
2 Red Yellow
3 Red Yellow
4 Red Yellow
5 Red Yellow
6 Red Yellow
7 Red Yellow
8 Red Yellow
9 Red Yellow
10 Red Yellow
11 Red Yellow
12 Red Yellow
13 Green Yellow
14 Green Yellow
15 Red Green
16 Red Green
Annunciator Dimensions
A
158 mm 6.22 in
B
139 mm 5.12 in
C
288 mm 11.34 in
Information contained in this publication may be considered confidential. www.cat-ElectricPower.com
Discretion is recommended when distributing.
Materials and specifications are subject to change without notice. © 2005 Caterpillar
LEHE4753-01 (09-05) CAT, CATERPILLAR, their respective logos and “Caterpillar Yellow,” as well as corporate and product All rights reserved.
identity used herein, are trademarks of Caterpillar and may not be used without permission. Printed in U.S.A.