McQuay RAH 407C Installation Manual

0 (0)

Installation and Maintenance Manual

IM 487-5

 

 

Group: Applied Systems

Part Number: IM 487

Date: June 2006

RoofPakApplied Rooftop Systems

Air Handler

RAH 407C - 077C, 12000 to 50000 cfm

RDS 800C - 802C, 4000 to 20000 cfm

US

© 2006 McQuay International

Contents

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Gas Burner Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Hazard Identification Information . . . . . . . . . . . . . . . . . . . . . . . 3 Typical Component Locations . . . . . . . . . . . . . . . . . . . . . . . . . 4 Control Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Controls, Settings, and Functions . . . . . . . . . . . . . . . . . . . . . 12

Mechanical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Ventilation Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Overhead Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 IBC Seismic Compliant Units . . . . . . . . . . . . . . . . . . . . . . . . 20 Roof Curb Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Post and Rail Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Post and Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Rigging and Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Split Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Unit Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Steam Coil Piping (All Units) . . . . . . . . . . . . . . . . . . . . . . . . . 33 Steam Piping Recommendations . . . . . . . . . . . . . . . . . . . . . 33 Steam Trap Recommendations . . . . . . . . . . . . . . . . . . . . . . . 34 Vestibule Assembly Instructions . . . . . . . . . . . . . . . . . . . . . . 38 Damper Assemblies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40 Cabinet Weather Protection . . . . . . . . . . . . . . . . . . . . . . . . . 45 Installing Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45 Installing Duct Static Pressure Sensor Taps . . . . . . . . . . . . . 46 Installing Building Static Pressure Sensor Taps . . . . . . . . . . 47

Electrical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Field Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Field Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Preparing Unit for Operation . . . . . . . . . . . . . . . . . . . . . 52 Spring Isolated Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Relief Damper Tie-Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Adjusting Scroll Dampers . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Adjusting Supply Fan Thrust Restraints . . . . . . . . . . . . . . . . 53 Adjusting Seismic Restraints . . . . . . . . . . . . . . . . . . . . . . . . . 54

Sequences of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Fan Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55 Economizer Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

Unit Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 Enthalpy Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85

External Time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Smoke and Fire Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Smoke Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Freeze Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Entering Fan Temperature Sensor . . . . . . . . . . . . . . . . . . . . 87

Duct High Pressure Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

MicroTech II™ Remote User Interface (UI) . . . . . . . . . . . . . . 87

Variable Frequency Drive Operation . . . . . . . . . . . . . . . . . . . 89

Convenience Receptacle/Section Lights . . . . . . . . . . . . . . . . 89

DesignFlow™ Outdoor Air Damper Option . . . . . . . . . . . . . . 89

Propeller Exhaust Fan Option . . . . . . . . . . . . . . . . . . . . . . . . 92

Exhaust Fan On/Off Control . . . . . . . . . . . . . . . . . . . . . . . . . . 94

Ultraviolet Lights Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95

Ultraviolet Light Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 96

Check, Test, and Start Procedures . . . . . . . . . . . . . . . 97

Servicing Control Panel Components . . . . . . . . . . . . . . . . . . 97

Before Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97

Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Fan Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Economizer Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Heating System Start-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Air Balancing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

Sheave Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Drive Belt Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Mounting and Adjusting Motor Sheaves . . . . . . . . . . . . . . . 101

Final Control Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Servicing Control Panel Components . . . . . . . . . . . . . . . . . 108

Planned Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Unit Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Gas Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Bearing Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109

Setscrews . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

Supply Fan Wheel-to-Funnel Alignment . . . . . . . . . . . . . . . 112

Winterizing Water Coils . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

Control Panel Components . . . . . . . . . . . . . . . . . . . . . . . . . 113

Replacement Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . 117

Service and Warranty Procedure . . . . . . . . . . . . . . . . 119

Limited Product Warranty (North America) . . . . . . 120

Exceptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Sole Remedy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Rooftop Equipment Warranty Regist. Form . . . . . 121

Introduction

Introduction

This manual provides general information about the “C” vintage McQuay RoofPak applied rooftop unit, models RDS and RAH. In addition to an overall description of the unit, it includes mechanical and electrical installation procedures, commissioning procedures, sequence of operation information, and maintenance instructions. For further information on the optional forced draft gas-fired furnace, refer to Bulletin No. IM 684 or IM 685.

The MicroTech II applied rooftop unit controller is available on “C” vintage applied rooftop units. For a detailed description of the MicroTech II components, input/output configurations, field wiring options, requirements, and service procedures, see IM 696-3. For operation and information on using and programming the MicroTech II unit controller, refer to the appropriate operation manual (see Table 1).

For a description of operation and information on using the keypad to view data and set parameters, refer to the appropriate program-specific operation manual (see Table 1).

Table 1: Program specific rooftop unit operation literature

Gas Burner Nameplate

On units that include gas heat, the nameplate is located on the lower right corner of the main control box door. It includes the burner model number, minimum/maximum input, maximum temperature rise, and minimum cfm.

Hazard Identification Information

WARNING

Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.

CAUTION

Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.

Rooftop unit control configuration

Operation manual bulletin

 

number

 

 

 

VFDs

Vendor IM manuals

 

Discharge Air Control (VAV or CAV)

OM 137-2

 

Space Comfort Control

OM 138-2

 

(CAV-Zone temperature control)

 

 

 

Figure 1: Nomenclature

 

 

 

R AH — 047 C S E

RoofPak

Unit Size

RDS 800 = 4000 – 16000 CFM

RDS 802 = 8000 – 20000 CFM

RAH 47 = 12000 – 30000 CFM

RAH 77 = 23000 – 50000 CFM

Heat medium

A = Natural gas

E = Electric

F = Fuel oil

S = Steam

W = Hot water

Y = None

Cooling coil size

S = Standard (low airflow)

L = Large (high airflow)

Y = None or contractor coil

Design vintage

McQuay IM 487-5

3

Introduction

Typical Component Locations

Figure 2 shows a typical blow-through unit with the locations of the major components. Figure 2 shows a typical draw-through unit with the locations of the major components.

These figures are for general information only. See the project’s certified submittals for actual specific dimensions and locations.

Control Locations

All controls are optional. If controls are ordered, Figure 2 shows the locations of the various control components mounted throughout the units. See “Control Panel” on page 5 for the locations of control components mounted in control panels. Additional information is included in Table 2 on page 12 and the wiring diagram legend, which is included in “Wiring Diagrams” on page 58. Figure 2 shows the blow-through heat and the blow-through coil sections.

Figure 2: Control locations

 

 

Supply fan

 

 

 

 

 

discharge

 

 

 

 

 

plenum

 

 

 

 

Heat

section

 

 

 

 

 

 

 

 

 

section

 

 

 

 

DX

 

 

 

 

 

section

 

C9

 

 

 

Filter

 

 

 

 

 

section

 

 

 

 

 

Economizer

 

 

 

 

 

return air

 

 

 

 

 

 

 

 

 

 

SV1, 2

 

 

 

 

DAT

SV5, 6 (optional)

 

 

 

 

 

C19, 20

 

 

 

LT10 (optional)

 

(optional)

 

 

 

S10, REC10 (optional)

 

 

 

 

 

 

 

 

SD1 (optional)

 

 

 

 

 

VM1

 

 

 

 

OAE

(optional)

 

 

 

PC5

OAT

FS1

 

 

 

 

 

(optional)

 

 

 

ACT3

 

 

 

RAT

 

ACT6

 

 

 

LT11 (optional)

 

(optional)

 

 

 

RAE

 

 

 

S11, REC11

 

 

 

(optional)

 

 

 

SD2

 

 

 

 

 

(optional)

 

 

 

 

4

McQuay IM 487-5

Control Panel

The unit control panels and their locations are shown in the following figures. These figures show a typical unit

Figure 3: Control panel locations

Introduction

configuration. Specific unit configurations may differ slightly from these figures depending on the particular unit options.

McQuay IM 487-5

5

Introduction

Figure 4: Typical main control panel, 800C to 802C, 460 volt

 

Remote

 

GCB1

 

 

 

MCB

 

EHB1

VFD remote

 

keypad

ERB1

 

 

 

 

 

 

 

Resistor

 

 

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R24 R25 R28

 

 

 

 

 

 

 

 

R58

 

 

 

 

 

 

SPS1

 

 

 

 

 

R27 R28 R30

R60

 

 

 

 

 

 

R20

R26

 

 

 

 

 

HS1 S1

 

R48

 

R45

R69

 

 

DHL

 

 

 

R46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPS2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMP60

MMP10

MMP20

 

TB1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S4

S7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F3

 

Power

 

 

 

 

 

 

 

 

 

 

 

supply

 

 

Keypad display

Serial conn

 

M60

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

REC1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M10

M20

 

 

 

 

 

 

 

 

 

 

 

 

F1A F1B

F1C

 

 

 

 

See separate

 

 

 

 

 

 

 

 

 

 

 

detail, page 14.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DS1

 

 

 

 

TB3,

 

TB2,

 

 

TB7

GND LUG DS1

SPS1,2 fittings

 

 

 

first seven

remaining

 

 

 

 

 

 

 

 

blocks

blocks

 

 

 

 

for static

 

 

 

 

 

 

 

 

 

 

 

 

pressure tubing

6

 

 

 

 

 

 

 

 

 

 

 

McQuay IM 487-5

McQuay RAH 407C Installation  Manual

Introduction

Figure 5: Typical main control panel, 047C, 460 volt

 

 

VFD remote

 

 

display

 

F1A

GFR1

 

 

 

F1B

 

 

F1C

 

 

14.

 

TB2

 

 

 

 

TB7

SPS1,2

 

 

fittings for

 

 

static pressure

 

 

tubing

 

 

McQuay IM 487-5

 

7

Introduction

Figure 6: Typical main control panel, 077C, 460 volt

 

14.

8

McQuay IM 487-5

Introduction

Figure 7: Typical gas heat panel, 1000 MBH

Figure 9: VFD bypass panel, 40 HP, 460 volt)

 

 

IT

TD10

R22

 

 

 

R20

R23

R21

AS

 

LS2

 

 

LS1

S3

 

 

 

 

 

Figure 10: Electric heat panel, sizes 800, 802C

 

FSG

 

 

 

 

FSG Time

 

 

 

 

 

FB33

FB32

FB31

 

Figure 8: Typical propeller exhaust panel, 3 fans, 460 volt

M33

M32

M31

SR2

 

 

 

 

 

 

 

 

SR3

 

FB43

FB42

FB41

SR1

 

M41

M42

M41

 

 

 

 

 

TB11

 

 

PB3

 

 

McQuay IM 487-5

 

 

 

9

Introduction

 

 

 

 

 

 

Figure 11: Electric heat panel, size 047C

Figure 12: Electric heat panel, size 077C

 

 

 

 

FB33

FB32

FB31

 

FB33

FB32

FB31

M33

M32

M31

 

 

 

 

 

M33

M32

M31

 

 

 

 

 

 

 

 

FB44

FB34

 

FB43

FB42

FB41

H53

 

 

 

 

 

 

 

 

 

 

 

M44

M34

 

M43

M42

M41

TB11

 

 

 

 

 

 

 

 

 

 

FB43

FB42

FB41

H53

 

 

 

M43

M42

M41

 

TB11

GLG3

DS3

GLG3

DS3

10

McQuay IM 487-5

Introduction

Figure 13: Harness plug connector detail

RATS

DATS

OATS

FP1

EPTS

OPEN1

AFD10

AFD20

SV12

SV56

ACT3

OPEN2

OAE

PC5

PC7

HL22

OPEN3

GSHT1

GSHT2

SD1

SD2

DFRH

DFLH

OPEN4

LT10

LT11

LT OP1

LT OP2

McQuay IM 487-5

11

Introduction

Controls, Settings, and Functions

Table 2 below lists all of the unit control devices and associated information.

Table 2: Controls, settings, and functions

Symb

Description

Function

Rese

Location

Setting

Range

Differential

Part no.

ol

t

 

 

 

 

 

 

 

 

Discharge air

Senses discharge air

 

Discharge air

 

 

 

06000470

DAT

temperature

N/A

N/A

 

N/A

temperature

section

 

5

 

sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Duct high limit

Prevents excessive VAV duct

 

Main control

3.5" w.c

0.05–5.0" wc

.05" wc

06549380

DHL

Auto

(12.5–1245.4

(12.5 Pa),

switch

pressures; shuts off fan

panel

(871.8 Pa)

1

 

 

Pa)

fixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering fan air

Senses entering fan air

 

Inlet of supply

 

 

 

06000470

EFT

temperature

N/A

N/A

 

N/A

temperature

fan

 

5

 

sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator frost

Senses low refrigerant

 

Return bends

Opens at

 

 

07250190

 

 

30°F

N/A

N/A

FP1, 2

N/A

of evaporative

protection

temperature

Closes at

1

 

 

 

 

coil

45°F

 

 

 

 

 

 

 

 

 

 

 

 

 

Shuts off fans, opens heating

 

 

38°F (3°C)

 

 

 

 

Freezestat

valve, and closes outdoor

 

Heating

35°F–45°F

12°F (7°C),

06583000

FS1

Auto

or as

damper if low air temperature

section

(2°C–7°C)

fixed

1

 

 

 

required

 

 

at coil is detected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCB

Main control board

Processes input information

N/A

Main control

N/A

N/A

N/A

06000610

box

1

 

 

 

 

 

 

 

 

Enthalpy control

Returns outside air dampers

 

 

 

 

Temperature:

 

 

 

Economizer

“B” or as

 

3.5°F (2°C)

03070670

 

(electro-

to minimum position when

Auto

A–D

 

section

required

Humidity:

2

 

mechanical)

enthalpy is too high

 

 

 

 

 

 

 

5% fixed

 

OAE

 

 

 

 

 

 

 

 

Returns outside air dampers

 

 

Fully CW

 

 

 

 

Enthalpy control

to minimum position when

 

 

 

 

04926220

 

 

Economizer

past “D”

 

 

 

outside air enthalpy is higher

Auto

A–D

N/A

 

(electronic)

section

(when used

1

 

than return air empalthy (use

 

 

 

 

 

 

 

with RAE)

 

 

 

 

 

RAE)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outside air

Senses outside air

 

 

 

 

 

06000470

OAT

temperature

N/A

 

N/A

 

N/A

temperature

 

 

5

 

sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dirty filter switch

Senses filter pressure drop

 

First filter

 

.05-5" wc

.05" wc

06549380

PC5

Auto

As required

(12.5–1245.4

section

(12.5 Pa)

1

 

 

 

 

 

Pa)

 

 

 

 

 

 

 

 

 

Dirty filter switch

Senses filter pressure drop

 

Final filter

 

.05-5" wc

.05" wc

06549380

PC6

Auto

As required

(12.5–1245.4

section

(12.5 Pa)

1

 

 

 

 

 

Pa)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Airflow proving

Senses supply fan pressure

 

Supply fan

.10" wc (25

.03-1.40" wc

.03" wc

06001580

PC7

Auto

(7.5 Pa),

switch

to prove airflow

section

Pa)

(7.5–348 Pa)

1

 

 

fixed

 

 

 

 

 

 

 

 

 

Returnairenthalpy

Used to compare return air

 

Economizer

 

 

 

04926220

RAE

enthalpy to outside air

N/A

N/A

N/A

N/A

 

sensor

enthalpy (used with OAE)

 

section

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Return air

 

 

Return air

 

 

 

06000470

RAT

temperature

Senses return air temperature

N/A

N/A

 

N/A

section

 

5

 

sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

SD1

Smoke detector,

Initiates unit shutdown if

Manu

Discharge air

N/A

N/A

N/A

04925001

supply air

smoke is detected

al

section

 

 

 

 

 

SD2

Smoke detector,

Initiates unit shutdown if

Manu

Return air

N/A

N/A

N/A

04925001

return air

smoke is detected

al

section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Static pressure

Converts static pressure

 

Main control

 

0–5" wc

 

04954500

SPS1

N/A

N/A

(0–1245.4 Pa)

N/A

sensor duct #1

signals to voltage signals

box

7

 

 

 

 

 

 

1–6 V (dc) out

 

 

12

McQuay IM 487-5

Introduction

Table 2: Controls, settings, and functions (continued)

Symb

Description

Function

Rese

Location

Setting

Range

Differential

Part no.

ol

t

 

 

 

 

 

 

 

 

 

Converts static pressure

 

 

 

0–5" wc

 

 

 

Static pressure

signals to voltage signals and

 

Main control

 

 

04954500

 

N/A

N/A

(0–1245.4 Pa)

N/A

 

sensor duct #2

sends them to MicroTech II

box

7

 

 

 

1–6 V (dc) out

 

SPS2

 

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

Static pressure

Converts static pressure

 

Main control

 

-025–0.25" wc

 

04954500

 

sensor: building

N/A

N/A

(-62.3–62.3 Pa)

N/A

 

signals to voltage signals.

box

6

 

(space) pressure

 

 

1–5 V (dc) out

 

 

 

 

 

 

 

 

S1

System switch

Shuts off entire control circuit

N/A

Main control

N/A

N/A

N/A

00135500

(except crankcase heaters)

box

0

 

 

 

 

 

 

S7

ON-OFF-AUTO

Used to manually switch unit

N/A

Main control

N/A

N/A

N/A

 

switch

box

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

McQuay IM 487-5

13

Mechanical Installation

Mechanical Installation

Note – The installation of this equipment shall be in accordance with the regulations of authorities having jurisdiction and all applicable codes. It is the responsibility of the installer to determine and follow the applicable codes.

CAUTION

Sharp edges on sheet metal and fasteners can cause personal injury.

This equipment must be installed, operated, and serviced only by an experienced installation company and fully trained personnel.

Receiving Inspection

When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. If the unit has become dirty during shipment (winter road chemicals are of particular concern), clean it when received.

All units should be inspected carefully for damage when received. Report all shipping damage to the carrier and file a claim. In most cases, equipment ships F.O.B. factory and claims for freight damage should be filed by the consignee.

Before unloading the unit, check the unit nameplate to make sure the voltage complies with the power supply available.

Unit Clearances

Service Clearance

Allow an approximate service clearance as indicated in Figure 14. Also, McQuay recommends providing a roof walkway to the rooftop unit as well as along two sides of the unit that provide access to most controls and serviceable components.

Figure 14: Service clearances, unit with housed DWDI supply fan

72" (1829 mm)

72"

A

B C

(1829 mm)

60" (1524 mm)

Roof

Walkway To Roof Access

Location

Note:

Sections with heating and/or cooling coils or DWDI supply fan must have noted service clearance on the control box side.

D

E

D

C

F

 

 

 

 

24"

 

 

 

 

(635 mm)

 

X

 

 

 

Varies With Unit Arrangement

 

Legend:

 

A = Return Air Section

Refer to Certified Drawing & Note

 

B = Filter Section

 

 

 

 

 

 

 

 

C = Cooling Section

 

Dimension "X"

 

 

D = Cooling/Supply Fan Section

 

RDS 800-802 = 90" (2286mm)

E = Heat Section

 

RAH 47-77 = 96" (2438mm)

F = Discharge Plenum Section

14

McQuay IM 487-5

Mechanical Installation

Figure 15: Service clearances, unit with SWSI plenum supply fan

72" (1829 mm)

72" (1829 mm)

A

B C

D E F

X

 

 

 

 

 

60"

96"

(1524

 

mm)

(2438 mm)

 

 

 

 

 

 

Roof

 

 

To roof

walkway

 

access

 

location

Varies with unit arrangement. Refer to Certified Drawing and note below.

Note:

Sections with heating and/or cooling coils or DWDI supply fan must have noted service clearance on the control box side.

Legend:

A = Return air section

B = Filter section

C = Cooling section

D = Cooling/supply fan section

E = Heat section

F = Discharge plenum section

Dimension "X"

RDS 800–802 = 90" (2286mm)

RAH 47–77 = 96" (2438mm)

Ventilation Clearance

Below are minimum ventilation clearance recommendations. The system designer must consider each application and provide adequate ventilation. If this is not done, the unit will not perform properly.

Unit(s) surrounded by a screen or a fence:

1The bottom of the screen or fence should be at least 1 ft. (305 mm) above the roof surface.

2The distance between the unit and a screen or fence should be as described in Figure 15.

3The distance between any two units within a screen or fence should be at least 120" (3048 mm).

Unit(s) surrounded by solid walls:

1If there are walls on one or two adjacent sides of the unit, the walls may be any height. If there are walls on more than two adjacent sides of the unit, the walls should not be higher than the unit.

2The distance between the unit and the wall should be at least 96" (2438 mm) on all sides of the unit.

3The distance between any two units within the walls should be at least 120" (3048 mm).

Do not locate outside air intakes near exhaust vents or other sources of contaminated air.

If the unit is installed where windy conditions are common, install wind screens around the unit, maintaining the clearances specified (see Figure 16). This is particularly important to prevent blowing snow from entering the outside air intake and to maintain adequate head pressure control when mechanical cooling is required at low outdoor air temperatures.

Overhead Clearance

1Unit(s) surrounded by screens or solid walls must have no overhead obstructions over any part of the unit.

2The following restrictions must be observed for overhead obstructions above the air handler section (see Figure 16):

aThere must be no overhead obstructions above the furnace flue, or within 9" (229 mm) of the flue box.

bOverhead obstructions must be no less than 96" (2438 mm) above the top of the unit.

cThere must be no overhead obstructions in the areas above the outside air and exhaust dampers that are farther than 24" (610 mm) from the side of the unit.

McQuay IM 487-5

15

Mechanical Installation

Figure 16: Overhead clearance

Overhead

Canopy

24" (610 mm) Maximum

2" (51 mm) Minumum Top of Unit to Overhead Obstruction

24" (610 mm) Maximum

9" (229 mm) Minumum to Flue Box Typical All Sides

Flue Box

Figure 17: Side discharge

Notice

On units with side discharge, access to plenum-mounted components becomes difficult once ductwork is installed. Installer must provide access in the ductwork for plenum mounted controls

Side Discharge Opening (Access in Ductwork Must be Removed)

16

McQuay IM 487-5

Roof Curb Assembly and Installation

Locate the roof curb and unit on a portion of the roof that can support the weight of the unit. The unit must be supported to prevent bending or twisting of the machine.

If building construction allows sound and vibration into the occupied space, locate the unit over a non-critical area. It is the responsibility of the system designer to make adequate provisions for noise and vibration in the occupied space.

WARNING

Mold can cause personal injury. Some materials such as gypsum wall board can promote mold growth when damp. Such materials must be protected from moisture that can enter units during maintenance or normal operation.

Install the curb and unit level to allow the condensate drain to flow properly and allow service access doors to open and close without binding.

Integral supply and return air duct flanges are provided with the RAH roof curb, allowing connection of duct work to the curb before the unit is set. The gasketed top surface of the duct flanges seals against the unit when it is set on the curb. These flanges must not support the total weight of the duct work. Assembly of a typical RAH roof curb is shown in Figure 18 on page 18. Parts A through H are common to all units having bottom return openings. Depending on the unit length, Parts L and M may be included with the roof curb kit to create the correct overall curb length.

Mechanical Installation

Assembly instructions

1Set curbing parts A through H per dimensions shown over roof opening or on a level surface (see Figure 18 on

page 18). Note location of return and supply air openings.

2If applicable, set other curbing parts (D, L, M, etc.) in place making sure that the orientation complies with the assembly instructions (see Detail A). Check alignment of all mating bolt holes.

3Bolt curbing parts together using fasteners provided. Tighten all bolts finger tight.

4Square entire curbing assembly and securely tighten all bolts.

5Position curb assembly over roof openings. Curb must be level from side to side and over its length. Check that top surface of the curb is flat with no bowing or sagging.

6Weld curbing in place. Caulk all seams watertight. Remove backing from 0.25" (6 mm) thick × 1.50" (38 mm) wide gasketing and apply to surfaces shown by cross-hatching.

7Flash curbing into roof as shown in Detail B.

8Parts E and F are not required on units with no return shaft within the curb perimeter.

9Parts G and H are not required on units with no supply shaft within the curb perimeter.

10Be sure that electrical connections are coordinated (see Figure 26).

McQuay IM 487-5

17

Mechanical Installation

Figure 18: RAH roof curb assembly instructions

Detail A

Using remaining side supports

in this area, align lengths on

Mopposite sides of assembly and install a cross support

"D" at each side. "Y"

L Inside D

 

 

M

C

Equal Length

 

L

 

Side Supports

 

 

 

 

B

 

 

"X"

 

 

 

Inside

 

 

D

 

 

 

8.75"

E

F

 

 

 

(222mm)

F

 

 

 

Return

 

3.50"

 

 

 

Air

 

(90mm)

A

 

 

87.00"

E

 

 

 

(2210 mm)

 

 

B

Inside

 

 

 

90.00"

 

 

 

(2286 mm)

 

 

94.75"

(2407 mm)

 

3.50"

 

8.75"

(90 mm)

 

(222 mm)

 

 

81.00"

 

 

(2057 mm)

 

G

Inside

 

A

 

 

 

 

H

7.50"

 

Supply

(191 mm)

H

 

Air

2.00"

 

G

D

(51 mm)

 

C

 

 

 

70.75"

 

 

(1797 mm)

See Detail "A"

RAH unit

 

Dimensions

 

X

 

Y

 

in

mm

in

mm

047C

38

965

28

711

077C with flat cooling coil and /or 44"

62

157

38

965

SWSI plenum supply fan

 

5

 

 

077C with staggered or no cooling coil,

62

157

46

1168

and/or 49" SWSI plenum supply fan

 

5

 

 

Figure 19: Roofing detail “B”

Unit base

Curb gasketing

2 × 4 nailer strip

Counterflashing (not furnished)

Flashing (not furnished)

Rigid insulation

Cant strip

Roffing material

(not furnished)

(not furnished)

(not furnished)

Galvanized

 

 

curb

 

 

Main unit

 

 

curb

 

 

18

McQuay IM 487-5

Mechanical Installation

Figure 20: RDS roof curb assembly instructions

 

 

 

6.80"

 

 

 

 

 

(173 mm)

1.50"

 

 

 

20.00"

 

(38 mm)

 

 

 

(508 mm)

 

 

 

 

 

Inside

 

76.00" (1930 mm)

 

 

 

 

G

Inside

 

 

 

C

A

 

 

 

 

 

 

 

 

 

H

7.50"

 

 

 

 

 

 

 

 

H

Supply

(191 mm)

 

 

 

Air

2.00"

 

 

 

 

G

 

 

 

D

(5.1 mm)

 

B

 

 

C

 

 

 

 

 

 

"X"

 

 

 

 

38.80"

Inside

 

 

 

 

 

 

D

 

 

(984 mm)

 

 

 

 

 

 

E

F

 

 

 

"XX"

 

 

 

 

"YY"

F

Return

 

See Detail "A"

 

 

 

Air

 

 

 

A

E

 

 

 

"Y"

 

 

 

 

Inside

 

B

 

 

 

85.00"

 

62.80"

 

 

 

(2159 mm)

 

 

 

 

 

(1594 mm)

 

 

 

 

 

 

 

 

Table 3: RDS roof curb assembly instructions

Unit size

Fan

 

X

 

Y

XX

 

YY

Unit size

Return

 

X

 

Y

XX

 

YY

in

mm

in

mm

in

mm

in

 

mm

fan

in

mm

in

mm

in

mm

in

 

mm

 

None

24.0

610

82.0

2083

6.8

173

1.5

 

38

 

None

24.0

610

82.0

2083

6.8

173

1.5

 

38

800–802C

(2) 15” FC

24.0

610

82.0

2083

6.8

173

1.5

 

38

800–802C

(2) 15" FC

24.0

610

82.0

2083

6.8

173

1.5

 

38

30" AF

30.0

762

76.0

1930

6.8

173

4.5

 

114

30" AF

30.0

762

76.0

1930

6.8

173

4.5

 

114

 

 

 

 

 

40" AF

36.0

914

78.0

1981

14.8

376

3.5

 

89

 

40" AF

36.0

914

78.0

1981

14.8

376

3.5

 

89

McQuay IM 487-5

19

Mechanical Installation

IBC Seismic Compliant Units

It is important to follow these installation instructions for all IBC Seismic compliant McQuay Rooftop units.

IBC Seismic compliant McQuay Rooftop units can be mounted to either a roof curb or a post and rail setup. If using a roof curb, it must be specifically designed for seismic restraint and be IBC seismic compliant (spring isolated or non-isolated type seismic roof curbs are available). Typical construction of a seismic rated roof curb is from structural steel framing and contains seismic hold down brackets for attachment of the rooftop unit (see Figure 21). Post and rail arrangements rated for seismic applications are also available (spring isolated or non-isolated).

IMPORTANT: An acceptable IBC seismic installation provides a direct positive attachment to both the building structure and the roof mounted equipment.

Refer to the roof curb manufacturer’s submittal drawings for actual roof curb assembly, attachment details and rigging instructions for both roof curb and post and rail arrangements.

Figure 21: Typical seismic roof curb (spring isolated)

Roof Curb Arrangement

1Set the rooftop unit on the roof curb (McQuay Rooftop units are designed to overhang from the roof curb).

2Adjust the seismic hold down brackets so they come into contact with the unit base per Figures 22 and 23 on page 21.

aThe seismic hold down brackets should be adjustable and accommodate the overhang of the rooftop unit.

bIf the hold down bracket cannot reach the unit base, use a shim spacer. See Figure 23 on page 21.

3Weld each seismic hold down bracket (and shim spacer, if required) to the unit base as shown in the acceptable weld zone detail in Figure 22 on page 21.

CAUTION

When welding unit to the curb, do not damage wiring (control panel side). Weld ONLY in the specified zone in the acceptable weld zone (see Figure 22 on page 21). Welding must comply with weld fillet size, etc. as indicated in Figure 22 on page 21.

Note – High temperature insulation is installed at the factory to allow for field welding along the lower front edge region of the unit base.

Duct opening

Seismic hold down brackets

Seismic hold down brackets

Structural steel frame

Spring isolator

20

McQuay IM 487-5

Mechanical Installation

Figure 22: Welding of hold down brackets—unit base, cross-sectional view

 

 

Unit power wiring

Unit control wiring

 

 

(by factory)

 

 

(by factory)

 

 

 

 

 

Unit base

 

.25

 

 

 

 

 

Field attachment

 

 

 

weld

 

Weld

.50"

 

 

zone

 

 

 

 

 

 

 

High temp

 

 

 

Insulation

 

 

Acceptable weld zone

Seismic hold down bracket

Roof curb

 

 

 

Figure 23: Shim spacers on hold down brackets

Shim spacer

Unit power wiring

(by factory) Unit control wiring (by factory)

Unit base

It may be necessary for the contractor to field fabricate spacers or new seismic hold-downs for rooftop units having larger overhang dimensions.

Seismic hold

Roof curb

down bracket

McQuay IM 487-5

21

Mechanical Installation

Post and Rail Arrangement

1Set the rooftop unit on the rails. The rails should run lengthwise and support the entire unit base.

2Weld both sides of the unit directly to each rail as shown in Figures 24 and 25 on page 22. The total number of welds required is dependent on the length of the unit.

aMake the fillet welds 2 inches long, spaced 48 inches apart on centers.

bPlace the end welds 6 to 12 inches from the unit edge.

CAUTION

When welding unit to the curb, do not damage wiring (control panel side). Weld ONLY in the specified zone in the acceptable weld zone (see Figure 24 on page 22). Welding must comply with weld fillet size, etc. as indicated in Figure 24 on page 22.

Note – High temperature insulation is installed at the factory to allow for field welding along the lower front edge region of the unit base.

Figure 24: Welding of unit to rail—unit base, cross-sectional view

 

Unit base

Unit power wiring

Unit control wiring

 

(by factory)

 

(by factory)

 

 

 

 

 

Unit base

 

.25

2–48

 

 

Weld

.50"

Field attachment

 

zone

 

 

 

 

 

weld

 

 

 

Rail

 

 

 

Acceptable weld zone

 

 

 

 

Rail

 

 

High temp

 

 

 

insulation

 

Figure 25: Weld locations for rail arrangement

6–12"

 

 

 

 

Rooftop unit

.25

2–48

Weld every 48"

 

Rails

 

 

 

 

6–12"

22

McQuay IM 487-5

Mechanical Installation

Figure 26: Typical power wire entrance, curb view (RDS 800–802 shown; for exact values, refer to submittal)

C

A

20.0

6.8 6.0

RPS only

D

 

 

1.5

 

B

RA

SA

76.0

97.0

OPNG

OPNG

 

 

 

 

 

 

A

B

 

B

 

 

 

 

D

A

See Detail A

7.5

 

2 Typ

 

 

 

6.0

 

 

4 Typ

Unit length minus 6.4

E

8.0

 

 

Detail A

 

12.1

 

 

 

 

 

 

 

0.9 Dia.

5.1

3.0 Dia.

 

 

K.O.

3.4

K.O.

 

4.3

3.1

2.1

2.0

4.6

4.8

9.7

McQuay IM 487-5

23

Mechanical Installation

Post and Rail Mounting

When mounting by post and rail, run the structural support the full length of the unit. Locate the structural member at the base of the unit as shown in Figure 27, assuring the I-beam is well supported by the structural member.

CAUTION

The unit must be level side to side and over the entire length. Equipment damage can result if the unit is not level.

If resilient material is placed between the unit and the rail, insert a heavy steel plate between the unit and the resilient material to distribute the load. Seal cabinet penetrations (electrical, piping, etc.) properly to protect against moisture and weather.

Figure 27: Post and rail mounting

 

99" RAH

 

(2515 mm)

5" *

94" RDS

(2388 mm)

(127mm)

 

Rigging and Handling

Lifting brackets with 2" (51 mm) diameter holes are provided on the sides of the unit.

Use spreader bars, 96" to 100" (2438 to 2540 mm) wide, to prevent damage to the unit cabinet. Avoid twisting or uneven lifting of the unit. The cable length from the bracket to the hook should always be longer than the distance between the outer lifting points.

If the unit is stored at the construction site for an intermediate period, follow these additional precautions:

1Support the unit well along the length of the base rail.

2Level the unit (no twists or uneven ground surface).

3Provide proper drainage around the unit to prevent flooding of the equipment.

4Provide adequate protection from vandalism, mechanical contact, etc.

5Securely close the doors.

6If there are isolation dampers, make sure they are properly installed and fully closed to prevent the entry of animals and debris through the supply and return air openings.

7Cover the supply and return air openings on units without isolation dampers.

Figure 28 shows an example of the rigging instruction label shipped with each unit.

WARNING

Use all lifting points. Improper lifting can cause severe personal injury and property damage.

Figure 28: Rigging and handling instruction label

Unit has either four or six lifting points (four-point shown below).

Rigging cables must be at least as long as distance “A.”

Spreader bars required

A

Caution: Lifting points may not be symmetrical to center of gravity of unit. Balast or unequal

cable lengths may be required.

Lift only as indicated

CAUTION

Lifting points may not be symmetrical to the center of gravity of the unit. Ballast or unequal cable lengths may be required.

24

McQuay IM 487-5

Lifting Points

To determine the required lifting cable lengths and whether four-point or six-point lifting is required, use Tables 4 and 5 and Figure 29.

Referring to Figure 29, note that dimension A is the distance between the outer lifting points. The four outer rigging cables must be equal to or longer than dimension A. Dimension B shows the minimum distance between the outer and the inner lifting points for six-point lifting. Use this to roughly determine the required length of the middle cables for sixpoint lifting. Determine dimension A by subtracting dimensions X and Y from dimension Z (e.g., A = Z – X – Y).

Where:

Z = Total unit length in inches

(refer to certified drawings for this dimension).

X = Outdoor/return air section length (refer to Figure 29 and Table 5 for this dimension).

If A 288" (7315 mm), 4-point lifting is sufficient.

If A > 288" (7315 mm), 6-point lifting is required.

Table 4: RAH X dimension (see Figure 29) Economizer section

Type of economizer

047C

077C

section

 

 

100% OA

0

0

Plenum

48” (1219 mm)

72” (1829 mm)

0–30% OA

48” (1219 mm)

72” (1829 mm)

0–100% economizer

72” (1829 mm)

96” (2438 mm)

0–100% economizer with return fan

72” (1829 mm)

96” (2438 mm)

Table 5: RDS X dimension (see Figure 29) Outdoor/return air section

Outdoor/return air section

800C

802C

100% OA

0

0

Plenum

40” (1016 mm)

52" (1321 mm)

0–30% OA

40” (1016 mm)

52" (1321 mm)

0–100% economizer

40” (1016 mm)

52" (1321 mm)

0–100% economizer with 15" return fan

62" (1575 mm)

0–100% economizer with 30" return fan

52" (1321 mm)

52" (1321 mm)

0–100% economizer with 40" return fan

80" (2032 mm)

Mechanical Installation

Figure 29: Unit type RAH lifting points

4 Lifting Points

 

 

 

 

A

 

Z

 

 

X

 

6 Lifting Points

 

 

 

 

A

 

B

Z

X

 

 

RDS 800: B Min. = 62" (1515 mm)

 

RDS 802: B Min. =

84" (2134 mm)

 

RAH 47: B Min. =

96" (2438 mm)

 

RAH 77: B Min. = 120" (3048 mm)

 

McQuay IM 487-5

25

Mechanical Installation

Split Units

Although units typically ship from the factory as complete units, they can be factory split at the supply fan bulkhead and connected later on the roof. This configuration is ordered if the shipping length or a weight limitation prevents ordering a packaged unit.

A single nameplate is attached to the air handler section and power is supplied to both sections through the optional main control box as in a packaged unit.

RAH Factory Split at Fan

Field reassembly of an RAH unit that shipped split at the fan takes place in three phases: (1) setting the sections,

Figure 30: Set sections

(2) mechanically recoupling the cabinet, and (3) reconnecting power and control wiring.

Phase I. Set sections

1Remove top cap and save for Phase II, Step 1.

2Remove screws on fan panel, leaving retainer clips in place to secure bulkhead. Save screws for Phase II, Step 5.

3Remove plywood and retaining angles from unit and discard.

4Carefully lower both sections of unit (fan end and discharge end) into place, making sure the roof curb engages the recesses in the unit base.

Remove plywood and retaining angles from unit and discard.

Remove top cap and

 

save for reassembly.

Discharge end of unit

 

Fan end of unit

Remove screws on fan panel,

leaving retainer clips in place.

 

 

Save screws for reassembly.

26

McQuay IM 487-5

Mechanical Installation

Phase II. Reassemble cabinet (Figure 31)

1Reinstall top cap removed in Phase I, Step 1.

2Caulk (watertight) ends of splice cap.

3Caulk (watertight) vertical seam.

4Install #10 screws (provided).

5Install screws (.25–20 ×.75) removed in Phase I, Step 2.

6Install splice cover (provided).

Figure 31: Reassemble cabinet

Reinstall top cap saved in step 1

Caulk vertical seam

See detail

Caulk ends of splice cap

Install screws (.25 to 20 × .75) saved from step 1

Splice cover, provided

#10 screws, provided

Nut clip-on, provided

McQuay IM 487-5

27

Mechanical Installation

Phase III. Reconnect power and control wiring

Once the sections are physically reconnected, the ends of the power harness are fed back through the unit base into the junction box, per the unit’s electrical schematics.

CAUTION

Connect the power block correctly and maintain proper phasing. Improper installation can cause severe equipment damage.

1Make electrical connections and reinstall inner raceway cover as shown in Figure 32.

Figure 32: Electrical connections and raceway cover installation

If applicable, install as shown with provided fasteners.

After routing wires,

3.72 ref.

install inner raceway

(94 mm)

cover (see step 6).

 

2When power wire reconnection is complete, reinstall the inner raceway cover in the blank or heat section. Figure 32 shows a typical installation of the raceway cover.

3Run the control harnesses by removing the external raceway covers on either side of the unit split.

4Remove the excess harness length from the external raceway on the downstream side of the split; then route along the raceway, through the bushed hole in the fan section and into the junction box where control wiring terminal blocks are provided for reconnection.

5Make all electrical connections per the unit’s electrical schematics.

6Reinstall the external raceway covers after routing of the control wires is complete.

Field Refrigerant Piping and Charging of DX Coils

Units that ship from the factory with DX coils installed do not include refrigerant piping or refrigerant controls. The coil assembly is ready for field connections at the distributors and at the suction headers. Piping kits that provide the necessary liquid and hot gas piping and control components are available for field installation. Field-installed refrigerant piping may exit the unit cabinet at one of the following locations:

Through the floor of the unit.

Through the discharge and bulkhead of the unit.

Through a cabinet door near the DX coil that is not required for service areas.

CAUTION

For any of the above cabinet penetrations, tightly seal the hole to prevent water or air leakage.

In preparing for field piping, remove the plastic plugs on the distributors and unsweat the copper caps at the suction header connections.

Follow piping design, sizing, and installation information presented in ASHRAE handbooks in the design and installation of interconnecting piping. The DX coil and condensing unit are intended to be set at the same elevation, as close as possible to each other to minimize refrigerant pressure drop. Design piping to prevent liquid refrigerant carryover to the compressor and to provide a continuous return of compressor oil from the system.

CAUTION

The pounds of refrigerant in the system may exceed the capacity of the condenser, depending on the amount of refrigerant in the liquid lines between the DX coil and the condensing unit.

Refer to condenser manufacturer for information about refrigerant capacity. Suitable means of containing the refrigerant is required.

CAUTION

To prevent liquid return and damage to the compressor on systems with optional hot gas bypass, it is important to locate the bypass solenoid valve at the condensing unit and not at the DX coil.

28

McQuay IM 487-5

Piping Recommendations

7Use type K or L clean copper tubing. Thoroughly clean or braze all joints with high temperature solder.Base piping sizes on temperature/pressure limitations as recommended in the following paragraphs. Under no circumstances should pipe size be based strictly upon coil or condensing unit piping connection size.

8Do not exceed suction line piping pressure drop equivalent to 2°F (1°C), 3 psi (20.7 kPa) per 100 feet (30.5 m) of equivalent pipe length. After the suction line size is determined, check the vertical suction risers to verify that oil will be carried up the riser and back to the compressor. Pitch the suction line(s) in the direction of refrigerant flow and make sure they are adequately supported. Lines should be free draining and fully insulated between the evaporator and the compressor. Install a trap on the vertical riser to the compressor.

9To determine the minimum tonnage required to carry oil up suction risers of various sizes, check the vertical suction risers using Table 6. Insulate suction lines inside the unit cabinet to prevent condensation.

Table 6: Minimum tonnage (R-22) to carry oil up suction riser at 40°F saturated suction

Line size O.D.

Minimum tonnage

1 1/8"

1.5

1 3/8"

2.5

1 5/8"

3.8

2 1/8"

7.6

2 5/8"

13.10

3 1/8"

20.4

3 5/8"

29.7

4 1/8"

41.3

10Size the liquid line for a pressure drop not to exceed the pressure equivalent of 2°F (1°C), 6 psi (41.4 kPa) saturated temperature.

Leak Testing

In the case of loss of the nitrogen holding charge, the unit should be checked for leaks prior to charging the complete system. If the full charge was lost, leak testing can be done by charging the refrigerant into the unit to build the pressure to approximately 10 psig and adding sufficient dry nitrogen to

Mechanical Installation

bring the pressure to a maximum of 125 psig. The unit should then be leak tested with halide or electronic leak detector. After making any necessary repair, the system should be evacuated as described in the following paragraphs.

WARNING

Do not use oxygen or air to build up pressure. Explosion hazard can cause severe personal injury or death.

Evacuation

After determining the unit is tight and there are no refrigerant leaks, evacuate the system. Use a vacuum pump with a pumping capacity of approximately 3 cu.ft./min. and the ability to reduce the vacuum in the unit to at least 1 mm (1000 microns).

1Connect a mercury manometer or an electronic or other type of micron gauge to the unit at a point remote from the vacuum pump. For readings below 1 millimeter, use an electronic or other micron gauge.

2Use the triple evacuation method, which is particularly helpful if the vacuum pump is unable to obtain the desired 1 mm of vacuum. The system is first evacuated to approximately 29" (740 mm) of mercury. Then add enough refrigerant vapor to the system to bring the pressure up to 0 pounds (0 microns).

3Evacuate the system again to 29" (740 mm) of vacuum. Repeat his procedure three times. This method is most effective by holding system pressure at 0 pounds

(0 microns) for a minimum of 1 hour between evacuations. The first pulldown removes about 90% of the noncondensables; the second removes about 90% of that remaining from the first pulldown. After the third pulldown, only 1/10 of 1% of noncondensables remains.

Table 7 on page 30 shows the relationship between pressure, microns, atmospheres, and the boiling point of water.

CAUTION

Before replacing refrigerant sensors or protective devices, see “Refrigerant Charge” on page 31 for an important warning to prevent an abrupt loss of the entire charge.

McQuay IM 487-5

29

Mechanical Installation

Table 7: Pressure-vacuum equivalents

Absolute pressure above zero

Vacuum below 1 atmosphere

Approximate fraction

H2O boiling point at each

Microns

PSIA

Mercury (mm)

Mercury (in)

of 1 atmosphere

pressure (oF)

0

0

760.00

29.921

50

0.001

759.95

29,920

1/15,200

–50

100

0.002

759.90

29.920

1/7,600

–40

150

0.003

759.85

29.920

1/5,100

–33

200

0.004

759.80

29.910

1/3,800

–28

300

0.006

759.70

29.910

1/2,500

–21

500

0.009

759.50

29.900

1/1,520

–12

1,000

0.019

759.00

29.880

1/760

1

2000

0.039

758.00

29.840

1/380

15

4,000

0.078

756.00

29.760

1/189

29

6000

0.117

754.00

29.690

1/127

39

8,000

0.156

752.00

29.600

1/95

46

10,000

0.193

750.00

29.530

1/76

52

15,000

0.290

745.00

29.330

1/50

63

20,000

0.387

740.00

29.130

1/38

72

30,000

0.580

730.00

28.740

1/25

84

50,000

0.967

710.00

27.950

1/15

101

100,000

1.930

660.00

25.980

2/15

125

200,000

3.870

560.00

22.050

1/4

152

500,000

9.670

260.00

10.240

2/3

192

760,000

14.697

0

0

1 atmosphere

212

Charging the System

Units are leak tested at the factory and shipped with a nitrogen holding charge. If the holding charge has been lost due to shipping damage, charge the system with enough refrigerant to raise the unit pressure to 30 psig after first repairing the leaks and evacuating the system.

1After all refrigerant piping is complete and the system is evacuated, it can be charged as described in the paragraphs following. Connect the refrigerant drum to the gauge port on the liquid shutoff valve and purge the charging line between the refrigerant cylinder and the valve. Then open the valve to the mid position.

2If the system is under a vacuum, stand the refrigerant drum with the connection up, open the drum, and break the vacuum with refrigerant gas.

3With a system gas pressure higher than the equivalent of a freezing temperature, invert the charging cylinder and elevate the drum above the condenser. With the drum in

this position and the valves open, liquid refrigerant flows into the condenser. Approximately 75% of the total requirement estimated for the unit can be charged in this manner.

4After 75% of the required charge enters the condenser, reconnect the refrigerant drum and charging line to the suction side of the system. Again, purge the connecting line, stand the drum with the connection side up, and place the service valve in the open position.

Important: At this point, interrupt the charging procedure and do prestart checks before attempting to complete the refrigerant charge.

Note – Stamp the total operating charge per circuit on the unit nameplate for future reference.

CAUTION

Adding refrigerant to the suction always risks liquid-related damage to the compressor.

30

McQuay IM 487-5

Loading...
+ 94 hidden pages