McQuay ALP-012D Installation Manual

5 (2)

Installation and Operation Manual

IM 687

 

 

 

Group: Chiller

 

 

 

Part Number: 629950

 

 

 

Date: January 1997

 

 

 

Supersedes: None

 

 

Packaged Air-Cooled Condensing Units

Models ALP-012D - ALP-019D

50 and 60 Hertz

© 1997 McQuay International

Table of Contents

 

INTRODUCTION.............................

3

INSPECTION ...................................

3

INSTALLATION..............................

3

Handling....................................................

3

Location.....................................................

4

Service Access ...........................................

5

Refrigerant Piping ............................

5

General......................................................

5

Refrigerant Piping .....................................

5

Application Considerations ..............

6

Water Piping..............................................

8

Flow Switch.............................................

10

Initial Start-up ................................

11

Holding Charge .......................................

11

Leak Testing ............................................

11

Evacuation...............................................

11

Charging The System...............................

11

Refrigerant Charge ..................................

12

Pre-Startup ..............................................

12

Startup.....................................................

13

Dimensional Data............................

14

Physical Data...................................

16

Electrical Data.................................

17

Field Wiring ....................................

19

Electrical Legend .....................................

21

Normal Sequence Of Operation .....

22

Startup .....................................................

22

Pumpdown ...............................................

22

System Maintenance.......................

23

General ....................................................

23

Fan Motor Bearings .................................

23

Electrical Terminals .................................

23

Condensers ..............................................

23

Refrigerant Sightglass ..............................

23

Service .............................................

24

Thermostat Expansion Valve....................

24

Filter-Driers .............................................

24

Liquid Line Solenoid................................

24

Standard Controls ..........................

25

High Pressure Control ..............................

25

Low Pressure Control...............................

25

Compressor Lockout ................................

25

Compressor Motor Protector ....................

26

Fantrol Head Pressure Control .................

26

Optional Controls ...........................

27

Speedtrol Head Pressure Control ..............

27

Low Ambient Start...................................

27

Hot Gas Bypass ........................................

27

Troubleshooting Chart....................

29

“McQuay” is a registered trademarks of McQuay International. ©1997 McQuay International

“Illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice.”

2

ALP 012D through 019D

IM 687

INTRODUCTION

ALP air-cooled condensing units are designed for outdoor installations and are compatible with either air handling units or chilled water evaporators. Each unit is completely assembled and factory wired before evacuation, charging and testing. Each unit consists of an air-cooled condenser with integral subcooler section, tandem scroll compressors, complete discharge piping and suction and liquid connections for connect to any air or water cooling evaporator.

INSPECTION

When the equipment is received, check all items against the bill of lading and inspect for damage upon arrival. Report all shipping damage to the carrier and file a claim. In most cases, equipment is shipped fob factory and claims for freight damage should be filed by the consignee. Check the unit serial plate before unloading the unit to be sure that it agrees with the power supply available.

INSTALLATION

Note: Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment.

CAUTION

Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Handling

Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything other than the base. Block the pushing vehicle away from the unit to prevent damage to the sheet metal cabinet and end frame See Figure 1.

Figure 1, Suggested pushing arrangement

Blocking required

across full width

Lifting slots are provided in the base of the unit. Arrange spreader bars and cables to prevent damage to the condenser coils or cabinet). See Figure 2.

IM 687

ALP 012D through 019D

3

Figure 2, Suggested lifting arrangement

Spreader bars

recommended

NOTE: Number of fans can vary

(Use Caution)

from this diagram. Lifting method remains the same.

Must use these rigging holes. (Be aware of contol box location.)

Location

Unit Placement

ALP units are for outdoor applications and can be mounted on a roof or ground level. Set units on a solid and level foundation. For roof mounted

applications, install the unit on a steel channel or I- beam frame to support the unit above the roof. For ground level applications, install the unit on a substantial base that will not settle. A one piece concrete slab with footings extended below the frost line is recommended. Be sure the foundation is level (within 1/2” [13 mm] over its length and width). The foundation must support the operating weights listed in the Physical Data tables beginning on

page 16.

On ground level applications protect fins against vandalism using the optional coil guards or by erecting a screen fence. The fence must allow free flow of air to the condenser coil for proper unit operation.

Unit operation is affected by wind. Located the unit so length is parrallel with the prevailing wind. If this is not practical, use wind deflectors.

Clearances

The flow of air to and from the condenser coil must not be limited. Restricting air flow or allowing air recirculation will result in a decrease in unit performance and efficiency. There must be no obstruction above the unit that would deflect discharge air downward where it could be

recirculated back to the inlet of the condenser coil. The condenser fans are propeller type and will not operate with ductwork on the fan outlet.

4

ALP 012D through 019D

IM 687

Install the unit with three feet of side clearance for air entrance to the coil and for servicing. Provide four feet of service access at each end to access the evaporator, compressors, electrical control panel and piping components.

Do not allow debris to accumulate near the unit. Air movement may draw debris into the condenser coil causing air starvation. Give special consideration to low ambient operation where snow can accumulate. Keep condenser coils and fan discharge free of snow or other obstructions to permit adequate airflow.

Service Access

Each end of the unit must be accessible after installation for periodic service. Compressors, filterdriers, and manual liquid line shutoff valves are accessible from the end of the unit. High pressure, low pressure, and motor protector controls are on the compressor. Most operational, safety and starting controls are located in the unit control box.

The condenser fan and motors can be removed from the top of the unit.

Refrigerant Piping

General

Piping design, sizing and installation information presented in ASHRAE Handbooks should, where applicable, be followed in the design and installation of piping. ALP condensing units are adaptable to either chilled water or air handling air conditioning applications. The only restriction on applications is that the evaporator be selected for a system using refrigerant R-22.

Refrigerant Piping

Design and install piping between the condensing unit and the cooling coil to minimize pressure drop, prevent liquid refrigerant carryover to the compressor and to assure a continuous return of compressor oil from the system. Piping sketches and tables are not intended to provide information on all of the possible arrangements.

Piping recommendations include:

1.The use of type K or L clean copper tubing. Thoroughly clean and braze all joints with high temperature solder.

2.Piping sizes should be based on temperature/pressure limitations as recommended in the following paragraphs. Under no circumstances should pipe size be based upon the coil or condensing unit piping connection size.

3.Suction line pressure drop should not exceed the pressure equivalent of 2° (3 psi) per 100 feet of equivalent pipe length. After the suction line size has been determined, the vertical suction risers should be checked to verify that oil will be carried up the riser and back to the compressor. The suction line should be pitched in the direction of refrigerant flow and adequately supported. Lines should be free draining and fully insulated between the evaporator and the compressor. Table 3, shows piping information for units operating at suction temperatures between 40°F and 45°F and a condenser entering air temperature of 95°F. If operating conditions are expected to vary substantially from these operating levels, the pipe sizing should be rechecked.

4.Vertical suction risers should be checked using Table 1 to determine the minimum tonnage required to carry oil up suction risers of various sizes.

5.The liquid line should be sized for a pressure drop not to exceed the pressure equivalent of 2°F (6 psi) saturated temperature.

IM 687

ALP 012D through 019D

5

Table 1. Minimum tonnage to carry oil up suction riser at 40°F saturated suction.

Line Size

1 1/8

1 3/8

1 5/8

2 1/8

2 5/8

3 1/8

3 5/8

4 1/8

Min. Tons

1.50

2.50

3.80

7.60

13.10

20.40

29.70

41.30

NOTE: When compressor minimum tonnage is less than shown in the above table for a given line size, reselection of risers will be required or hot gas bypass at the coil will be required.

Table 2,

Recommended line sizes (Max. equivalent feet of copper tubing*)

 

 

 

 

 

 

 

 

 

 

 

 

SUCTION

 

 

LIQUID

 

MODEL

 

LINE SIZE

 

 

LINE SIZE

 

NUMBER

 

O.D. COPPER

 

 

O.D. COPPER

 

 

 

1 3/8”

1 5/8”

2 1/8”

5/8”

7/8”

1 1/8’

012D

 

70

160

--

35

200

--

015D

 

35

80

300

16

100

365

019D

 

--

50

180

--

60

220

*Equivalent line lengths in the above table are suitable for a unit operating at 40°F sat. suction, 50°F return gas and 95°F ambient.

Table 3. Equivalent feet of straight tubing for copper fittings and valves

FITTING TYPE

5/8”

7/8”

1 1/8”

1 3/8”

1 5/8”

2 1/8”

2 5/8”

3 1/8”

3 5/8”

4 1/8”

ELBOWS

 

 

 

 

 

 

 

 

 

 

90° Standard

1.6

2.0

2.6

3.3

4.0

5.0

6.0

7.5

9.0

10

90° Long Radius

1.0

1.4

1.7

2.3

2.6

3.3

4.1

5.0

5.9

6.7

90° Street

2.5

3.2

4.1

5.6

6.3

8.2

10.

12

15

17

45° Standard

0.8

0.9

1.3

1.7

2.1

2.6

3.2

4.0

4.7

5.2

45° Street

11.3

1.5

2.1

3.0

3.4

4.5

5.2

6.4

7.3

8.5

180° BEND

2.5

3.2

4.1

5.6

6.3

8.2

10

12

15

17

TEES

 

 

 

 

 

 

 

 

 

 

Full Size

1.0

1.4

11.7

2.3

2.6

3.3

4.1

5.0

5.9

6.7

Reducing

1.6

2.0

2.6

3.3

4.0

5.0

6.0

7.5

9.0

10

VALVES

 

 

 

 

 

 

 

 

 

 

Globe Valve, Open

18

22

29

38

43

55

69

84

100

120

Gate Valve, Open

0.7

0.9

1.0

1.5

1.8

2.3

2.8

3.2

4.0

4.5

Angle Valve, Open

7.

9.

12

15

18

24

29

35

41

47

Notes:

1.Liquid and suction lines based on a recommended equivalent pressure drop of 2°F (3 psi for suction line, 6 psi for liquid line) per 100 ft. of equivalent length.

2.When the refrigerant required to charge a system exceeds the pumpdown capacity of the unit plus the capacity of the liquid line (see Table 4), the use of separate refrigerant storage receiver will be required. The pumpdown capacity of each unit is based on the condenser 90% full at 90°F (see physical data).

3.Total equivalent feet for a given piping layout must include the equivalent length of straight pipe for fittings, valves and specialties added to the total run of straight pipe.

4.Piping design, sizing an installation information presented in ASHRAE Handbooks should, where applicable, be followed in the design and installation piping.

5.Units running at 50% load do not require double suction risers.

Application Considerations

Suction Accumulators

Field experience indicates that as the refrigerant charge in a small tonnage system increases, the potential stress level from liquid floodback during system startup and stabilization also increases. Since there is no factory control of condensing unit applications, piping and design, a suction accumulator is recommended. The accumulator’s function is to intercept liquid refrigerant before it reaches the compressor crankcase causing mechanical damage. It should be located in the suction line between the evaporator and compressor, have a refrigerant capacity large enough to hold the maximum amount of refrigerant that could flood through, and must have provisions for a positive return of oil to the crankcase.

VAV Direct Expansion Systems

Variable air volume (VAV) application to direct expansion cooling coil systems is increasingly attractive because of the potential energy savings in fan motor power. Extra care must be exercised in the design of VAV direct expansion systems because of the potential for coil icing, oil trapping, loss of stable expansion valve control, excessive compressor cycling, and nuisance operation of protective controls.

6

ALP 012D through 019D

IM 687

McQuay ALP-012D Installation  Manual

Equipment damage and nuisance tripping can be avoided by proper total system design. Special consideration must be given to reduced load operating conditions as well as peak design, and coil selection, capacity unloading, and system control modified as required to provide a trouble-free system.

Head Pressure Control

Condenser coils on these ALP condensing units are vertical in position and are subject to wind. The standard head pressure control offered controls the operation or speed of condenser fans. This type of control has no effect if condenser coils are subjected to wind.

The design engineer or contractor has the responsibility of locating the equipment or protecting the condenser coil so that prevailing winds have minimum effect on unit performance.

Oil Charge

Excessive piping or refrigerant charge or both may require the addition of some oil to the compressor. If additional oil is required, use Suniso brand for the Copeland compressors. Add only enough oil to maintain an oil level at the indicated point in the compressor sightglass.

Figure 3, Single Circuit Evaporator—Recommended Piping

Figure 4, Recommended Liquid Line Piping

IM 687

ALP 012D through 019D

7

Table 4, Weight of R-22 in copper lines (Pounds Per 100 feet of type L tubing)

LINE SIZE

VOL PER 100

 

WEIGHT OF REFRIGERANT (LBS)

 

O.D.(in.)

FT (CU, FT)

 

 

 

 

 

 

LIQUID @

HOT GAS @

SUCTION GAS

SUCTION GAS

 

 

100°F

120°F

@20°F

@ 40°F

3/8

0.054

3.84

0.202

0.052

0.077

1/2

0.100

7.12

0.374

0.096

0.143

5/8

0.162

11.5

0.605

0.156

0.232

7/8

0.336

24.0

1.26

0.323

0.480

1 1/8

0.573

40.8

2.14

0.550

0.820

1 3/8

0.872

62.1

3.26

0.839

1.25

1 5/8

1.237

88.0

4.62

1.19

1.77

2 1/8

2.147

153.0

8.04

2.06

3.06

2 5/8

3.312

236.0

12.4

3.18

4.72

3 1/8

4.728

336.0

17.7

4.55

6.75

3 5/8

6.398

456.0

24.0

6.15

9.14

4 1/8

8.313

592.0

31.1

8.00

11.19

Liquid Line Components

Liquid line components should include:

1.Filter-drier

2.Refrigerant solenoid valve/115 volt coil

3.Refrigerant sightglass/moisture indicator

4.Expansion valve/R-22

5.Manual shutoff valve

All liquid line components are field supplied and should be selected and installed according to good field piping practices, ASHRAE Guide, and individual component manufacturer recommendations.

Hot Gas Bypass Components

Hot gas bypass kits are available for each ALP unit size. Each kit includes a solenoid valve, a hot gas bypass valve and instruction drawing. See page 8 for hot gas bypass operation.

Table 5, Hot Gas Bypass Kits

ALP UNIT SIZE

KIT NUMBER

LINE SIZE O.D. (IN.)

012D

550443A-03

5/8

015D & 019D

550443A-04

7/8

Refrigerant Piping Connections

Refrigerant piping connections will be made at the compressor end of the unit. Suction and liquid lines should be routed through the compressor enclosure on the side of the unit.

Water Piping

The following section applies to remote mounted DX water chillers.

Local authorities can supply the installer with the proper building and safety codes required for safe and proper installation.

Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the following when installing water piping:

1.Vibration eliminators to reduce vibration and noise transmission to the building.

2.Shutoff valves to isolate the unit from the piping system during unit servicing.

3.Manual or automatic air vent valves at the high points of the system. Install drains at the lowest points in the system.

4.A means of maintaining adequate system water pressure (expansion tank or regulating valve).

8

ALP 012D through 019D

IM 687

5.Temperature and pressure indicators located at the unit to aid in unit servicing.

6.A strainer or other means of removing foreign matter from the water before it enters the pump. Place the strainer far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). The use of a strainer will prolong pump life and keep system performance up.

7.Place a strainer in the water line just before the inlet of the evaporator. This will help prevent foreign material from entering and decreasing the performance of the evaporator.

CAUTION

If separate disconnect is used for the 110V supply to the evaporator heating cable, mark the disconnect clearly to ensure disconnect is not accidentally shut off during cold seasons.

8.The brazed plate evaporator has a thermostat and heating cable to prevent freeze-up down to - 20°F (-29°C). It is suggested that the heating cable be wired to a separate 110V supply circuit. As shipped from the factory, the heating cable is wired to the control circuit. All water piping to the unit must also be protected to prevent freezing.

9.If the unit is used as a replacement chiller on a previously existing piping system, flush the system thoroughly before unit installation. Regular water analysis and chemical water treatment on the evaporator is recommended immediately at equipment start-up.

10.The total water volume in the system should be sufficient to prevent frequent “on-off” cycling. Turnover rate should not be less than 15 minutes for normal variable cooling loads. Turnover rate for process cooling or a constant load,should not be less than 6 minutes.

11.When glycol is added to the water system for freeze protection, the refrigerant suction pressure will be lower, cooling performance less, and water side pressure drop greater. If the percentage of glycol is high, or if propylene is used instead of ethylene glycol, the added pressure drop and loss of performance could be substantial. Reset the freezestat and low leaving water alarm temperatures. The freezestat is factory set to default at 36°F (2.2°C). Reset the freezestat setting to approximately 4 to 5 degress F (2.3 to 2.8 degress C) below the leaving chilled water setpoint temperature. See the section titled “Glycol Solutions” for additional information concerning glycol.

12.Perform a preliminary leak check before insulating the piping and filling the system.

13.Piping insulation should include a vapor barrier to prevent condensation and possible damage to the building structure.

Figure 5, Typical field evaporator water piping

Vent

 

 

 

Outlet

 

 

 

 

Vibration

Flow

Balancing Gate valve

Valved

Eliminator

Switch

valve

 

 

 

pressure

 

 

 

gauge

 

Protect all field piping

 

 

against freezing

 

Vibration

Water

Gate valve

 

Eliminator

 

strainer

 

Drain

 

 

 

 

 

IM 687

ALP 012D through 019D

9

Loading...
+ 21 hidden pages