McQuay ALR C Installation Manual

0 (0)

Installation and Operating Manual

Leaving Water Controller, AS-UNT33n-1

Applied to ALR C/D/E and WHR D/E

IOM UNT33n

Group: Chiller

Date: May 2000

Supersedes: IM 552

© 1996 McQuay International

Table of Contents

 

Introduction........................................................................................

3

Specifications .....................................................................................

4

Installation..........................................................................................

5

Dimensional Data................................................................................

6

Electrical Data.....................................................................................

7

Operation ...........................................................................................

9

Additional Features ............................................................................

11

Settings And Adjustments..................................................................

12

System Checkout and Troubleshooting..............................................

13

Zone Terminal User's Guide..............................................................

16

Zone Terminal Glossary ....................................................................

21

"McQuay" is a registered trademarks of McQuay International ©1996 McQuay International

"Illustrations and information cover McQuay International products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice"

2

IOM UNT33

Introduction

This controller is the standard controller on ALR "C", "D" or “E” vintage and WHR "D" or "E" vintage packaged chillers where control of leaving water temperature is desired. On these units with the controller factory installed, the control is pre-set and calibrated and should not need any adjustment other than the control setpoint.

For further information on the AS-UNT33n-1 Microprocessor based leaving water controller and accessories contact McQuay International for specification sheets for each individual control.

The controller and sensor covered in this Installation and Operating Manual is also available as a substitute replacement for earlier ALR and WHR units.

General Description

The AS-UNT33n-1 Microprocessor-based Leaving Water Control is designed to control multiple capacity steps of cooling from a single sensor.

The AS-UNT33n-1 operation is based on an adjustable Setpoint and Control Band as shown in the OPERATION section of this document. If the leaving chilled water temperature begins to rise to the desired Setpoint plus Control Band/2 (upper limit), Cooling Stage 1 brings on the first stage of cooling. Additional stages of cooling will follow as long as the leaving water temperature remains above the upper limit of the Control Band. As the leaving water temperature begins to drop to Setpoint minus Control Band/2 (lower limit), cooling stages will begin to de-energize.

There will be no energizing or de-energizing of cooling stages as long as the leaving water temperature is between the upper and lower limits of the Control Band.

As a rule, anytime the leaving water temperature is above the upper limit of the Control Band, stages will be energized, and anytime the leaving water temperature falls below the lower limit of the Control Band, stages will be de-energized.

At the initial start of the unit a time delay will occur. There is a 60 second Interstage On Delay between stages. Each stage incorporates minimum on and off timers with a maximum cycle rate of six cycles per hour.

CAUTION-Offering this control device is not intended to imply that rapid cycling of compressors is condoned. If an application produces rapid cycling, the control and/or the application must be reviewed and altered to prevent compressor failure.

Table 1, Standard Control Characteristics

DESCRIPTION

SETTING

AS-UNT-33n-1

 

Setpoint Range

10°F to 60°F (-12°C to

+15°C) Adjustable

 

Control Band Range

0°F to 10°F (0°C to 6°C)

Adjustable

 

Interstage On Delay Between Stages

60 seconds

Minimum Off Time (each stage)

5 minutes

Minimum On Time (each stage)

60 seconds

Soft Start During Start-up

50% command over 5

minutes

 

Table 2, Controller Specific Characteristics

CONTROLLER

NUMBER OF

LEAVING WATER

DESCRIPTION

STAGES

SENSOR

AS-UNT330-1

4 or 6

Honeywell

AS-UNT332-1

8

Honeywell

AS-UNT334-1

4 or 6

Johnson Controls

AS-UNT336-1

8

Johnson Controls

IOM UNT33

3

Specifications

Electrical Ratings:

Input voltage and frequency (terminals

24 VAC–COMMON) 20 to 30 VAC at 50/60 Hz

(50 Hz requires download.)

Power Consumption:

25 VA at 24 VAC and 50/60 Hz

Input Signal:

Honeywell sensor—positive temperature coefficient of 4.8 ohms/Degree F; resistance of 3484 ohms at 77°F.

Johnson Controls sensor—positive temperature coefficient of 3 ohms/Degree F; resistance of 1000 ohms at 70°F.

.

Table 3, Contact Rating

Number of Stages Selection:

Refer to Table 5, Figure 1 for stage selection

Temperature Ranges:

Ambient: -40°F to +150°F.

Humidity Rating:

5 to 90% RH non-condensing.

Leaving Water Sensor:

The Honeywell C7173Al017, Honeywell C7170A1010, or Johnson Controls TE-6300-300 senses Leaving Water Temperature on control terminals AI3 and AI3 COM.

CONTACT

VOLTAGE (V)

INRUSH (VA)

RUNNING (VA)

N.O.

24

240

60

N.C.

24

75

30

N.O.

120/240

750

75

N.C.

120/240

240

40

Table 4, Accessories

Model No.

McQuay

Quantit

Description

Application

Part No.

y

 

 

 

Johnson TE-6313P-1

070312301

1

Outdoor Air Sensor

Used for reset of Leaving Water Setpoint.

Johnson TE-6300-300

070312401

1

Immersion Sensor (30 ft. cord)

Senses Leaving or Return Water Temperature.

Sensor Well

047441506

1

Immersion Well

Used with TE-6300-300.

Johnson TE-6410S-

070312801

depends on

Zone Temperature Sensor

Used for zone temperature reset.

2000

# of zones

 

 

 

Johnson AS-ZTU330-

070312701

1

Zone Terminal

Used for monitoring and local control of

1

designated points.

 

 

 

Honeywell

048442405

1

Immersion Sensor (30 ft. cord)

Sensing of Leaving Water Temperature.

C7173A1017

 

 

 

 

Honeywell

048442402

1

Immersion Sensor (10 ft. cord)

Sensing of Leaving Water Temperature.

C7170A1010

 

 

 

 

Honeywell 121371A

048442403

1

Copper Immersion Well

Used with C7173A1017 or C7170A1010.

Honeywell 121371E

048442404

1

Stainless Steel Immersion Well

Used with C7173A1017 or C7170A1010.

Johnson AS-KIT100-0

 

1

Resistor Test Kit

Used for field diagnostics.

4

IOM UNT33

Installation

STANDARDS COMPLIANCE

The UNT Controller complies with the following standards:

 

* CSA C22.2 No. 205 * UL 916

* IEEE 472

* IEEE 446

* VDE 0871 Class B

 

* IEEE 587 Category A

* IEEE 518

* FCC Part 15, Subpart A, Cl. J

* NEMA ICS 2, Part 2-230

All wiring must comply with local codes and ordinances:

1.Disconnect power before making connections to avoid electrical shock or equipment damage.

2.Check ratings given in the specification and on the product to make sure the controller fits the application.

3.Choose a location for the AS-UNT33n-1 controller that is not exposed to the weather and where controls, connections, and the zone bus phone jack are accessible.

4.Mount the controller with three No. 8 screws through the mounting holes in the base. (See Figure 2.)

5.Install immersion well and sensor bulb in the Leaving Chilled Water piping as instructed by the installation manual for the unit being controlled.

6.Connect 24 VAC to terminals marked 24 VAC and COM. CAUTION: Never spark the 24 V power leads to check for power.

CAUTION: Do not run low-voltage wiring in the same conduit as line-voltage wiring (30 VAC or above) or wiring that switches power to highly inductive loads (such as contactors, coils, motors, or generators).

7.Wire the compressor and capacity controls steps to the individual controller relay terminals as shown in the unit wiring diagram.

8.Adjust SW1 and SW2 on AI2 for the appropriate number of cooling stages. The AS-UNT330-1/AS-UNT334-1 is factory set for 6 stages by Johnson Controls. The AS-UNT332-1/AS-UNT336-1 is factory set for 8 stages.

Table 5, Dipswitch Settings

Dipswitch Settings

 

Factory

Stage

 

Factory Set

 

 

Set

Select

 

 

 

 

 

 

 

 

 

 

AS-UNT33n-1

 

AI 1

AI 2

AI 3

AI 4

AI 5

AI 6

AS-UNT330-1

SW2

 

10 V

 

 

AS-UNT334-1

 

 

2 V

 

 

 

 

4 stage

SW1

 

T

 

 

 

 

 

(set by others)

 

 

V

 

AS-UNT330-1

SW2

 

10 V

 

 

AS-UNT334-1

 

 

2 V

 

 

 

 

6 Stage

SW1

 

T

 

 

 

 

(Factory Set)

 

 

V

 

 

AS-UNT332-1

SW2

 

10 V

 

AS-UNT336-1

 

 

2 V

 

 

 

 

 

8 Stage

SW1

 

T

 

 

 

 

(Factory Set)

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

Figure 1, Analog Input Switches

1

2 3 4

5 6 7 8

O F

 

 

A S- UN T3 3 0 - 1

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A N A LO G I N PU TS

+1

 

 

 

 

 

 

 

 

 

 

 

B NI A RY O U TP U T

 

 

B NI A R Y NI

C O M

 

 

 

 

1

 

2

 

3

 

4

 

5

6

 

 

1

2

3

4

 

 

 

TO

 

 

1

 

2

 

3

 

4

 

5

 

6

7

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PW R

 

ZONE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TATS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A N A L O G I N P U TS

 

B NI A R Y C O M

2 4V

 

 

 

 

2 4V A C TO L O A D S

 

 

C O MM O N

 

 

 

 

 

 

 

A C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

123 456

OF

A NAL O G I N PUTS

B I N ARY I N

B I NA RY O UT PUT S

A N A L O G I N PU TS

Analog Input Switches

IOM UNT33

5

McQuay ALR C Installation  Manual

Dimensional Data

Figure 2, Dimensional Data

 

 

 

 

5.80

 

1.24

 

 

 

These relays are for the

 

 

 

 

 

 

 

7th and 8th stages.

 

 

 

 

 

 

 

 

C

 

 

COOL6

 

 

 

 

COOL 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

McQuay

 

 

C

 

 

 

 

 

RECIP ROCATING

 

 

 

 

 

A

 

 

 

 

 

 

CHILLERCONTROL

 

B

 

 

 

 

 

 

 

 

 

 

C

 

 

 

A

 

 

 

COOL 7

 

SETPOINT

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

 

COOL5

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

COOL4

 

 

 

 

 

 

 

 

 

C

8.95

9.23

8.95

7.78

 

RESET

 

B

 

 

 

 

 

 

 

 

A

 

 

 

COOL3

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

COOL2

 

 

 

 

 

 

CONTROL BAND

 

 

 

 

 

 

 

 

 

 

C

 

 

 

SW2

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

SW1

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

ANALOG INPUTS

BINARY IN

 

 

 

 

 

 

 

 

 

 

 

COOL1

C

 

 

 

 

 

 

 

 

 

 

 

 

 

BINARY OUTPUTS

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

 

0.89

 

14.90

 

 

 

 

 

 

 

 

 

 

 

 

 

= mounting holes

5.16

2.23 0.25

0.74

2.17

2.77

6

IOM UNT33

Electrical Data

Figure 3, Wiring Diagram

Note: See Additional Features on page 11 for explanation.

DEMAND LIMIT*

(1)0-10 VDC

 

25

528

LEAVING

 

26

 

WATER SENSOR

529

SHUTDOWN*

COMP LEAD/LAG*

ICE MODE*

(2)FLOW INTERLOCK

*Indicates

18

optional 512/518 feature. 24VAC

28

519

 

(+)

(-)

2 N 2 N F RE Z OM C 24 + - S U B C A V

AI CM AI1

AI CM

 

AI2

 

ANALOG

 

 

 

 

 

 

 

 

 

 

AI CM

 

AI3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI CM

 

AI4

 

INPUTS

 

 

 

 

 

 

 

 

 

 

 

AI CM

 

AI5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI CM

 

AI6

 

 

 

 

 

 

 

 

 

 

+15VDC +15VDC

 

 

 

 

 

 

 

 

 

 

 

BINARY

 

 

24VAC

 

 

 

 

BI1

 

 

 

 

 

 

 

 

 

 

 

24VAC

 

 

BI2

 

 

 

 

 

 

24VAC

 

BI3

 

IN

 

 

 

 

 

 

 

 

 

 

 

 

24VAC

 

 

BI4

 

 

 

 

 

 

 

P5

 

 

DS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P6

 

 

 

 

 

 

 

 

 

 

P4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1)Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to AI-1 and

(2)Field connections must be made between TB3-18 and BI-4 for unit to operate.

NNotes:

1.Sensor for Outdoor, Return Water, or Zone Temperature Reset options are connected to Al-1 and Al-CM.

2.Field connections must be made between TB3-18 and Bl-4 for unit to operate.

3.If a time clock is desired, it should be installed between 24 VAC and Bl1. The time clock switch should be installed as follows: Open to Run and Close to Stop.

Figure 4, Stage Relay Configuration

 

 

COOL 6

 

COM

McQuay

CHILLERCONT ROL

 

C

C

 

B

 

 

RECIPROCATING

 

 

 

S ET PO I NT

 

A

NC

 

 

 

 

COOL 5

C

 

 

 

B

B

 

 

 

A

 

 

 

COOL 4

 

 

 

 

 

C

NO

RE SET

 

B

 

 

 

A

A

 

 

COOL 3

C

 

 

 

 

 

 

 

 

B

 

 

 

 

A

Stage Relays

 

 

COOL 2

 

 

 

 

 

C ONT ROL BA ND

 

C

 

 

 

 

 

 

 

 

B

 

 

 

 

A

 

 

 

COOL 1

C

 

 

 

 

 

 

 

 

B

 

 

 

 

A

 

Note: Refer to Unit Wiring Diagram for Stage Wiring.

IOM UNT33

7

Table 6, Wiring Location Cross Reference

Lead #

Honeywell (H/W)

Stages

 

Johnson Controls (JCI)

W7100G

 

AS-UNT33n-1

 

 

 

512

TB3-18 to TB3-29

(4,6,8 Stages)

 

Not Needed (See Note 1 and 2)

518

TB3-29 to "TR"

"

 

TB3-18 to 24 VAC

519

"TR"

"

 

Common

522

Ground

"

 

Not Needed

524

"7"

"

 

Not Needed (See Note 3)

525

TB3-23 to TB3-24

"

 

Not Needed

526

"6"

"

 

Not Needed (See Note 3)

527

"P" to "P1"

"

 

Not Needed or Zone Terminal Adjust

528

"T"

"

AI-3

(JCI or H/W Leaving Water Sensor. See

 

appropriate sensor section)

 

 

 

 

529

"T1"

"

AI-CM (JCI or H/W Leaving Water Sensor.

 

See appropriate sensor section)

 

 

 

 

400 OHM Resister

"7" to "8"

4 Stages

 

 

600 OHM Resister

"7" to "8"

6 Stages

 

See Table 5

800 OHM Resister

"7" to "8"

8 Stages

 

 

523

Ground

8 Stages

 

Not Needed

535

"1"

"

 

Not Needed

536

"2"

"

 

Not Needed

537

"3"

"

 

Not Needed

538

"4"

"

 

Not Needed

539

"5"

"

 

Not Needed

Note 1: To install Flow Switch Contacts, connect between TB3-18 and UNT BI-4. Note 2: To install Time Clock Contacts, connect between TB3-18 and UNT BI-1.

Note 3: The options are as follows. (Option A is standard; options B, C, and D require field download. See "Features Requiring Configuration and/or Field Adjustment" section for more information):

A. The standard is Demand Limit Input. 0-10VDC signal is required. Connect leads to AI-1 and AI-CM on the

controller.

B.Johnson Controls Outdoor Air Sensor if Outdoor Air Reset is used.

C.Johnson Controls Zone Temperature Sensor if Zone Temperature Reset is used.

D.Johnson Controls Return Water Sensor if Return Water Reset is used.

8

IOM UNT33

Loading...
+ 16 hidden pages