PUMP RECOMMENDATION FOR
ARMOR 151-200 WATER HEATER
Pump Specifications
Part No. |
Horse Power |
Flanges |
Valute Material |
Flange Material |
Vendor |
Vendor Product Series |
Orientation |
PUM3010 |
1/6 |
1-1/4" |
Bronze |
Bronze |
Armstrong |
E Series |
Vertical |
Installation Specifications
|
Recommended for |
|
Based on |
Pump |
Model Numbers |
Minimum GPM |
Installation Type |
|
Armor Wtr Htr, AW(N,L) 151-200 |
16 GPM (151) & 21 GPM (200) |
Single Water Heater piped to Single Storage Tank |
PUM3010 |
Based on |
Based on |
|
|
Minimum Pipe Diameter |
Connecting piping |
|
|
1-1/4" |
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves |
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.
1
PUMP RECOMMENDATION FOR
ARMOR 286 WATER HEATER
Pump Specifications
Part No. |
Horse Power |
Flanges |
Valute Material |
Flange Material |
Vendor |
Vendor Product Series |
Orientation |
PUM30032 |
2/5 |
1-1/2" |
Bronze |
Bronze |
Armstrong |
E Series |
Vertical |
Installation Specifications
|
Recommended for |
|
Based on |
Pump |
Model Numbers |
Minimum GPM |
Installation Type |
|
Armor Wtr Htr, AW(N,L) 286 |
30 GPM |
Single Water Heater piped to Single Storage Tank |
PUM30032 |
Based on |
Based on |
|
|
Minimum Pipe Diameter |
Connecting piping |
|
|
2" |
Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves |
IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.
2