Lochinvar PUM3010, PUM30032, PUM3012, PUM30003, PUM30004 User Manual

0 (0)
Lochinvar PUM3010, PUM30032, PUM3012, PUM30003, PUM30004 User Manual

PUMP RECOMMENDATION FOR

ARMOR 151-200 WATER HEATER

Pump Specifications

Part No.

Horse Power

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

PUM3010

1/6

1-1/4"

Bronze

Bronze

Armstrong

E Series

Vertical

Installation Specifications

 

Recommended for

 

Based on

Pump

Model Numbers

Minimum GPM

Installation Type

 

Armor Wtr Htr, AW(N,L) 151-200

16 GPM (151) & 21 GPM (200)

Single Water Heater piped to Single Storage Tank

PUM3010

Based on

Based on

 

 

Minimum Pipe Diameter

Connecting piping

 

 

1-1/4"

Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves

IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump Curves-All Pumps” for alternate pumps and pump curves.

1

PUMP RECOMMENDATION FOR

ARMOR 286 WATER HEATER

Pump Specifications

Part No.

Horse Power

Flanges

Valute Material

Flange Material

Vendor

Vendor Product Series

Orientation

PUM30032

2/5

1-1/2"

Bronze

Bronze

Armstrong

E Series

Vertical

Installation Specifications

 

Recommended for

 

Based on

Pump

Model Numbers

Minimum GPM

Installation Type

 

Armor Wtr Htr, AW(N,L) 286

30 GPM

Single Water Heater piped to Single Storage Tank

PUM30032

Based on

Based on

 

 

Minimum Pipe Diameter

Connecting piping

 

 

2"

Maximum 45 feet straight pipe with 4-Elbows, 2-Unions and 2-Ball Valves

IMPORTANT: Read the Armor 151-801 Installation and Operation Manual. If the planned system exceeds the pump capacity in flow and/or head see “Pump-Curves-All Pumps” for alternate pumps and pump curves.