Lochinvar FBN1500 Manual

0 (0)
Lochinvar FBN1500 Manual

CREST

COMMERCIAL BOILER

Submittal Sheet

FBN-Sub-03a

CREST COMMERCIAL CONDENSING BOILER

JOB NAME ______________________________________________________________________

LOCATION ______________________________________________________________________

ARCH./ENGR.____________________________________________________________________

WHOLESALER __________________________________________________________________

MECH. CONTRACTOR ___________________________________________________________

MODEL NO. _____________________________________________________________________

TYPE GAS ______________________________________________________________________

Btu/hr INPUT_____________________________________________________________________

Btu/hr OUTPUT___________________________________________________________________

NOTES

Smart TouchFeatures

>SMART TOUCH™ Touchscreen Operating Control

>Full-Color 8” Touchscreen LCD Display

>Built-in Cascading Sequencer for up to 8 Boilers

>Cascade Multiple Sized Boilers

>Lead/Lag Cascade

>Efficiency Optimized Cascade

>Front-End Loading Capability with CopperFin II and Powerfin Boilers

>Building Management System Integration with 0-10 VDC Input

>Modbus Communications

>Outdoor Reset Control with Outdoor Air Sensor

>Password Security

Domestic Hot Water Prioritization

Low Water Flow Safety Control & Indication Inlet & Outlet Temperature Readout

Freeze Protection Service Reminder Time Clock

>Data Logging

Hours Running, Space Heating Hours Running, Domestic Hot Water Hours Running, Modulation Rate Ignition Attempts

Last 10 Lockouts

>Programmable System Efficiency Optimizers

Night Setback Anti-Cycling

Outdoor Air Reset Curve Ramp Delay

Boost Temperature & Time

>Three Pump Control

System Pump Boiler Pump

Domestic Hot Water Pump

>High-Voltage Terminal Strip

120 VAC / 60 Hertz / 1 Phase Power Supply

(FB1500-3500)

208 VAC / 60 Hertz / 3 Phase Power Supply

(FB4000-5000)

System Pump, Boiler Pump and DHW Pump

Power

>Low-Voltage Terminal Strip

24 VAC Auxiliary Device Relay Auxiliary Proving Switch Contacts Alarm on Any Failure Contacts Runtime Contacts

DHW Thermostat Contacts Unit Enable/Disable Contacts System Sensor Contacts DHW Tank Sensor Contacts Outdoor Air Sensor Contacts Cascade Contacts

0-10 VDC BMS External Control Contact

Standard Features

Up to 93% Thermal Efficiency (AHRI)

Up to 99% Thermal Efficiency in Low Temperature Applications

Modulating Burner with up to 25:1 Turndown Direct-Spark Ignition

Low-NOx Operation

Sealed Combustion

Low Gas Pressure Operation Vertical or Horizontal Venting Category IV Venting up to 100 Feet ASME “H” Stamped Heat Exchanger 316L Stainless Steel Fire Tubes 160 psi Working Pressure

On/Off Switch

Adjustable High Limit with Manual Reset Low Water Cutoff with Manual Reset & Test

High & Low Gas Pressure Switches w/Manual Reset Low Air Pressure Switches

Condensate Trap w/ Blocked Drain Switch Drain Valve

System Sensor Outdoor Air Sensor

Inlet & Outlet Temperature Sensors High Voltage Terminal Strip

Low Voltage Terminal Strip

Downstream Gas Test Cocks

50 psi ASME Relief Valve Temperature & Pressure Gauge

Zero Clearances to Combustible Materials

10-Year Limited Warranty (See Warranty for Details)

1-Year Warranty on Parts (See Warranty for Details)

Optional Equipment

Alarm Bell

BMS Gateway - BACnet or LonWorks

Condensate Neutralization Kit

SMART TOUCH PC Software

Common Vent Kits (Consult Factory on FB4000 and 5000)

*(Available on FB1500-3500 Dual Fuel Gas Train* Coming Soon on FB4000-5000)

Electrical Options (Shipped Loose):

208V/3Ø/60Hz (Models FB1500-3500 only)

480V/3Ø/60Hz

600V/3Ø/60Hz

Codes & Registrations

ANSI Z21.13/CSA Certified

ASME certified, “H” Stamp / National Board California Code Compliant

CSD1 / Factory Mutual / GE Gap Compliant

South Coast Air Quality Management District Qualified

Canadian Registration Number (CRN) AHRI Certified