LG LS-C1260HD, LS-C1120CM, LS-C1420CM, LS-C1420CN, LS-C1260CD Service Manual

...
0 (0)

K

M

Room Air Conditioner

SERVICE MANUAL

MODEL : LS-B0760CM/B0760HM

LS-B0960CM/B0960HM

LS-B0962CM/B0962HM

LS-B0962CD/B0962HD

LS-B0960CD/B0960HD

LS-C1260CM/C1260HM

LS-C1260CD/C1260HD

LS-C1120CM/C1420CM

LS-C1420CN

CAUTION

BEFORE SERVICING THE UNIT,

READ THE "SAFETY PRECAUTIONS" IN THIS MANUAL.

K

M

Contents

Functions...................................................................................................................................... 3 Product Specifications (Cooling Only) ...................................................................................... 5 Product Specifications (Cooling & Heating).............................................................................. 6 Dimensions................................................................................................................................... 7 Maximum Length of Pipe and Freon Extra Charge................................................................... 9 Refrigeration Cycle Diagram..................................................................................................... 10 Wiring Diagram .......................................................................................................................... 11 Operation Details ....................................................................................................................... 13 Display Function ........................................................................................................................ 20 Self-diagnosis Function ............................................................................................................ 20 Installation .................................................................................................................................. 21 Operation .................................................................................................................................... 39 Disassembly of the parts(Indoor Unit) ..................................................................................... 41 2-way, 3-way Valve ..................................................................................................................... 44 Cycle Troubleshooting Guide ................................................................................................... 51 Electronic Parts Troubleshooting Guide.................................................................................. 52 Electronic Control Device ......................................................................................................... 56 Schematic Diagram.................................................................................................................... 59 Exploded View & Replacement Parts List ............................................................................... 61

- 2 -

Functions

Indoor Unit

Operation ON/OFF by Remote controller

Sensing the Room Temperature

• Room temperature sensor(THERMISTOR).

Room temperature control

Maintains the room temperature in accordance with the Setting Temp.

Starting Current Control

Indoor fan is delayed for 5 seconds at the starting.

Time Delay Safety Control

• Restarting is inhibited for approx. 3 minutes.

Indoor Fan Speed Control

• High, Med, Low, Chaos or Auto

Operation indication Lamps (LED)

--- Lights up in Operation

--- Lights up in Sleep Mode

--- Lights up in Timer Mode

--- Lights up in Deice Mode or Hot Start Mode (only Heating Model)

OUT

DOOR --- Lights during in compressor running (for Cooling Model)

Soft Dry Operation Mode

• Intermittent operation of fan at low speed

Sleep Mode Auto Control

The fan is switched to low(Cooling), med(Heating) speed.

The unit will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

Auto Air Control by CHAOS Logic

The fan is switched to intermittent or irregular operation.

The fan speed is automatically switched from high to low speed.

Airflow Direction Control

The louver can be set at the desired position or swing up and down, right and left (not on all models) automatically.

AUTO Wind

• The fan speed is automatically switched from high to low speed.

Deice(defrost) control(Heating)

Both the indoor and outdoor fan stops during deicing.

Hot start after deice ends.

Hot-start Control(Heating)

The indoor fan stops until the evaporator piping temperature will be reached at 28°C.

- 3 -

Remote Controller

Operation ON/OFF

Operation Mode Selection

Cooling Operation Mode (

)

Auto Operation Mode (

)

Soft Dry Operation Mode (

)

Heating Operation Mode (

)

(Cooling model only) (Heatling model only)

 

 

 

Fan Speed Selection

(Low) (Med)

Room, Temperature Display

 

: High: 39°C

 

LOW : 11°C

Temperature Setting

 

 

TEMPERATURE

LOW

HIGH

Cooling

Down to 18°C

 

 

 

 

 

 

Up to 30°C,

 

 

 

 

Setting the Time or timer

Timer Selection

(High)

(AUTO WIND)

 

(CHAOS)

Down to 16°C

Heating

Up to 30°C,

: OFF, ON, OFF ON

Timer Setting

Timer Cancel

: Cancel Sleep Mode, Timer ON or Timer OFF

Sleep Operation

: 1, 2, 3, 4, 5, 6, 7, Off Timer

Airflow Direction Control

Fan Operation Mode

: Fan Operates without cooling or heating.

Reset

- 4 -

Product Specifications (Cooling Only)

 

Model Name

LS-B0760CM

LS-B0960CD LS-B0962CD

LS-C1120CM

LS-C1260CD LS-C1420CM

 

 

 

Item

Unit

 

LS-B0960CM LS-B0962CM

 

LS-C1260CM

LS-C1420CN

 

 

 

 

 

 

Cooling Capacity

BTU/h(kcal/h)

7,300(1,840)

8,700(2,190)

8,700(2,190)

11,000(2,770)

12,000(3,020)

14,000(3,528)

Moisture Removal

ℓ/h

1.0

1.2

1.2

1.2

1.7

1.7

Power Source

 

Ø, V, Hz

1Ø, 220-240V, 50Hz

1Ø, 220V~,60Hz

1Ø, 220-240V,50Hz

1Ø, 220V~,60Hz

Air Circulation

Indoor

m3/min

4.85

5.3

5.3

8.5

10.2

9.5

Outdoor

25

25

25

25

25

25

 

 

Noise Level

Indoor

dB(A)

36±3

39±3

38±3

39±3

41±3

41±3

Outdoor

47±3

49±3

49±3

49±3

50±3

50±3

 

 

Input

 

W

755

920

920

1,050

1,140

1,270

Runnig Current

 

A

3.2

4.0

4.0

4.9

5.0

5.9

E.E.R.

 

BTU/h-W

9.7

9.5

9.5

10.5

10.5

11

Motor Output

Indoor

W

7

10

10

10

15

15

Outdoor

25

25

25

25

25

25

 

 

Dimensions

Indoor

mm

810 x 220.5 x 152

900 x 290 x 183

(W x H x D)

Outdoor

660 x 540 x 260

 

801 x 555 x 262

 

 

Net. Weight

Indoor

kg

6.5

6.5

6.5

10

10

10

Outdoor

27

27

27

33

33

35

 

 

Refrigerant(R-22)

g

540

670

690

1,080

840

980

Airflow Direction Control (Up & Down)

O

O

O

O

O

O

Remocon type

 

 

 

 

L.C.D Wireless

 

 

Service valve

 

Liquid

1/4"(6.35)

 

1/4"(6.35)

 

 

 

 

 

 

 

 

 

 

 

Gas

3 /8"(9.52)

3/8"(9.52)

 

1/2"(12.7)

 

Sleeping Operation

 

O

O

O

O

O

O

Drain Hose

 

 

O

O

O

O

O

Connecting Cable

 

 

 

1.0mm2

 

 

Power Cord

 

 

 

 

1.0mm2

 

 

- 5 -

Product Specifications (Cooling & Heating)

 

Model Name

LS-B0760HM

LS-B0960HD

LS-B0962HD

LS-C1260HD

 

 

 

Item

Unit

LS-B0960HM

LS-B0962HM

LS-C1260HM

 

 

Cooling Capacity

 

BTU/h(kcal/h)

7,000(1,764)

8,500(2,142)

8,500(2,142)

12,000(3,020)

Heating Capacity

 

7,500(1,890)

9,500(2,394)

9,500(2,394)

12,500(3,150)

 

 

Moisture Removal

ℓ/h

1.0

 

1.2

1.2

1.7

Power Source

 

Ø, V, Hz

 

 

1Ø, 220-240V, 50Hz

 

Air Circulation

 

m3/min

Indoor

4.85

5.3

5.6

10.2

 

Outdoor

25

25

25

25

 

 

 

Noise Level

 

dB(A)

Indoor

36±3

39±3

40±1

41±3

 

Outdoor

47±3

49±3

50±1

51±3

 

 

 

Input

Cooling

W

760

 

940

895

1,250

Heating

780

 

1,030

950

1,100

 

 

 

Runnig Current

Cooling

A

3.2

 

4.1

3.8

5.5

Heating

3.3

 

4.4

4.1

4.8

 

 

 

E.E.R.

Cooling

BTU/h·W

9.2

 

9.0

9.5

9.6

C.O.P

Heating

W/W

2.82

 

2.7

2.76

3.3

Motor Output

 

W

Indoor

7

10

10

15

 

Outdoor

25

25

25

25

 

 

 

Dimensions

 

mm

Indoor

 

810 x 220.5 x 152

900 x 290 x 183

(W x H x D)

 

Outdoor

 

660 x 540 x 260

810 x 555 x 262

 

 

 

Net. weight

 

kg

Indoor

6.5

6.5

6.5

10

 

Outdoor

30

30

30

35

 

 

 

Refrigerant(R-22)

 

g

590

 

690

720

810

Airflow Direction Control (Up & Down)

O

 

O

O

O

Remocon Type

 

 

 

 

L.C.D Wireless

 

Service Valve

 

 

Liquid

 

1/4"(6.35)

 

 

 

 

Gas

 

3/8"(9.52)

 

1/2"(12.7)

 

 

 

 

 

Sleeping Operation

 

O

 

O

O

O

Drain Hose

 

 

O

 

O

O

O

Connecting Cable

 

 

 

 

1.0mm2

 

 

Power Cord

 

 

 

 

1.0mm2

 

 

- 6 -

LG LS-C1260HD, LS-C1120CM, LS-C1420CM, LS-C1420CN, LS-C1260CD Service Manual

Dimensions

(1) Indoor Unit

(7K, 9K)

(11K, 12K, 14K)

D

D

H H

Tubing hole cover

Tubing hole cover

Tubing hole cover

50

Tubing hole cover

Hole for piping

Installation plate

2cm

Installation plate

4.5cm

8cm

4cm

Hole for piping

 

MODEL

7K, 9K BTU

11K, 12K, 14K BTU

DIM

 

Series

Series

W

mm

810

900

H

mm

220.5

290

D

mm

152

183

- 7 -

(2) Oudoor Unit (7K, 9K, 11K, 12K, 14K)

W

D

L1

L2

H

L3

L10

 

 

 

 

L9

L4

L6

L5

L7

L8

 

 

 

 

Liquid side 2-way valve

Gas side 3-way valve

 

MODEL

7K, 9K, 11K BTU Series

12K, 14K BTU Series

DIM

 

 

 

 

W

mm

660

801

H

mm

540

555

D

mm

260

262

L1

mm

297

339

L2

mm

18.5

37

L3

mm

523

543.6

L4

mm

17

11.4

L5

mm

447

591

L6

mm

76.5

105

L7

mm

76.5

105

L8

mm

66

72.5

L9

mm

82

86.4

L10

mm

77

77

- 8 -

Maximum Length of Pipe and Freon Extra Charge

Charge amount per 1m

Capacity

STANDARD

 

MAXIMUM LENGTH

Charge amount (g)

 

 

 

 

(Btu/h)

LENGTH(m)

 

 

 

 

per 1m

 

A

 

B

 

 

 

 

 

 

 

 

 

 

 

 

~7000

4

 

7

 

15

20

 

 

 

 

 

 

 

~9000

4

 

7

 

15

20

 

 

 

 

 

 

 

~12000

4

 

7

 

15

20

 

 

 

 

 

 

 

~18000

5

 

15

 

30(25)

40

 

 

 

 

 

 

 

~24000

5

 

15

 

25

40

 

 

 

 

 

 

 

Indoor unit

Oil trap

Outdoor unit

*A, B mean indoor unit higher located than outdoor unit

*Capicity is based on standard length and maximum allowance length is the basis of reliability.

*Oil trap should be installed per 10 meters.

* Numerical value in "( )" is for Rotary Comp. model.

- 9 -

Refrigeration Cycle Diagram

INDOOR UNIT

 

OUTDOOR UNIT

 

LIQUID SIDE

CAPILLARY TUBE

 

 

 

2-WAY VALVE

 

HEAT

 

 

 

HEAT

EXCHANGE

 

 

EXCHANGE

(EVAPORATOR)

 

 

(CONDENSER)

 

 

 

 

 

 

GAS SIDE

 

 

3-WAY VALVE

ACCUMU-

REVERSING

LATOR

VALVE

 

 

COMPRESSOR

COOLING

 

 

HEATING

- 10 -

Wiring Diagram

(1) 7K, 9K, 11K, 12K, 14K BTU Cooling Only

1. Indoor Unit

(7K, 9K, 12K)

(11K, 14K)

POWER

 

 

TRANS

FORCED

 

 

 

OPERATION

 

 

 

 

FORMER

SWITCH

 

 

GN/YL

 

CN-TRANS

 

 

 

 

FAN-CN

 

 

 

1(L) 2(N)

 

 

 

 

 

 

 

 

 

 

N

 

 

 

BL

RY-L

 

 

 

 

 

OR

RY-M

 

 

 

MOTOR

BR

 

 

 

 

 

YL

RY-H

 

CN-TH

 

SH-CAPA 1

 

THERMISTOR

POWER-CN

 

 

BR BL

 

 

 

 

 

 

RD BR

 

 

 

UP/DOWN-CN

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

FUSE T2A

 

STEP

 

 

 

4

3

 

MOTOR

 

 

 

 

 

 

 

 

RY-COMP

 

 

 

 

 

 

 

MAIN PCB

 

 

GN/YN

 

 

 

ASM

 

YL BL

 

 

 

CN-DISP

 

 

 

 

 

 

 

 

 

 

 

 

1(L) 2(N)

PILLAR

 

DISPLAY PCB ASM

 

TERMINAL

 

INDOOR WIRING DIAGRAM

TO OUTDOOR UNIT

TRANS

FORCED

OPERATION

FORMER

SWITCH

THERMISTOR

MAIN PCB

ASM

PILLAR

TERMINAL

DISPLAY PCB ASM

INDOOR WIRING DIAGRAM

2. Outdoor Unit

COMP

FAN

MOTOR

PILLAR

TERMINAL

TO INDOOR UNIT

OUTDOOR WIRING DIAGRAM

- 11 -

(2) 7K, 9K, 12K BTU Cooling & Heating

1. Indoor Unit

POWER

TRANS

FORCED

OPERATION

FORMER

SWITCH

 

CN-TRANS

CN-FAN

CN-TH

THERMISTOR

 

UP/DOWNCN-

STEP

 

MOTOR

RY-COMP

 

 

 

CN-4WAY

 

 

RY-4WAY

MAIN PCB

 

 

ASM

 

RY-FAN

CN-DISP

 

PILLAR TERMINAL

DISPLAY PCB ASM

INDOOR WIRING DIAGRAM

TO OUTDOOR UNIT

2. Outdoor Unit

REVERSING VALVE

FAN MOTOR

PILLAR

TERMINAL

TO INDOOR UNIT

OUTDOOR WIRING DIAGRAM

- 12 -

Operation Details

(1) The function of main control

1. Time Delay Safety Control

3min... The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle. (Protection of compressor)

2sec... The indoor fan is ceased for 2sec. to prevent relay noise.

(Protection of fan relay and micro chip)

• 30sec... The 4-way valve is ceased for 30sec. to prevent the refrigerant-gas abnormal noise when the Heating operation is OFF or switched to the other operation mode.

2. Airflow Direction Control

This function is to swing the louver up and down automatically and to set it at the desired position.

The procedure is as the following.

1st ;Press the ON/OFF Button to operate the product.

2nd ;Press the Airflow Direction Control Button to swing the louver up and down automatically. 3rd ;Repress the Airflow Direction Control Button to set the louver as the desired position.

Operating Mode

Louver Position

 

 

 

Cooling

Start

2

 

 

Auto. Swing

1 4

 

 

 

 

Heating

Start

5

 

 

Auto. Swing

3 6

 

 

 

 

3. Cooling Mode Operation

When selecting the Cooling ( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as following.

 

 

 

Intake Air temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMP. ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SET TEMP.+0.5°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMP. OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SET TEMP.-0.5°C

 

 

 

 

 

 

More than

 

 

 

 

 

More than

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 minutes

 

 

 

 

 

3 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selectig

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selecting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Selectin

INDOOR FAN SPEED

 

 

 

 

 

 

 

 

 

Low

 

 

 

 

 

 

Low

 

 

 

 

 

 

 

fan speed

 

 

 

 

fan speed

 

 

 

 

fan speed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

 

 

ON

 

 

OFF

 

 

 

 

 

 

 

 

ON

ON

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4. Cooling or Heating Mode with Sleep Mode Auto Operation

When selecting the Cooling( ) or the Heating( ) combined with the Sleep Mode Auto Operation( ), the operation diagram is as following.

-13 -

• Cooling Mode with the Sleep Mode

The setting temperature will be raised by 1°C 30minutes later and by 2°C 1 hour later.

The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

 

 

30 minutes

 

 

30 minutes

Intake Air temp.

 

 

 

 

1°C

COMP. ON

 

 

 

1°C

 

 

 

 

 

 

(SET TEMP. +0.5°C

 

 

 

 

 

COMP. OFF

 

 

 

 

 

(SET TEMP. -0.5°C

 

More than

 

More than

 

 

 

3 minutes

 

3 minutes

 

INDOOR FAN SPEED

Low

Low

Low

Low

Low

COMPRESSOR

ON

OFF

ON

OFF

ON

• Heating Mode with the Sleep Mode.

The operation will be stopped after 1, 2, 3, 4, 5, 6, 7 hours.

SETTING TEMP. +3°C

 

 

 

 

 

 

(COMPRESSOR OFF)

 

 

 

 

 

 

SETTING TEMP.

 

 

 

 

 

 

(COMPRESSOR ON)

 

 

 

 

 

 

INDOOR FAN SPEED

Med.

Low or OFF

Med.

Low or OFF

Med.

Low or OFF

COMPRESSOR

ON

OFF

ON

OFF

ON

OFF

- 14 -

5.Auto Operation

The operation procedure is as following.

Press Start/Stop Button

Select Auto Operation Mode

Check the Room temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor fan speed

 

 

 

 

 

 

are automatically decided by Fuzzy rule.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake-air

 

 

 

below 21°C

 

Over

~

 

below

 

 

 

 

Over 24°C

 

 

 

temperature

 

 

 

 

21°C

 

24°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Mode

 

 

 

Heating

 

Soft Dry

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If initial mode is decided, that mode is continued despite of the room temperature changing.

 

 

Auto Operation for Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Condition

 

 

 

 

Intake-air Temperature

Setting Temperature

 

Fan Speed

Air DirectionControl

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over 26°C

 

25°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over 24°C~below 26°C

 

Intake air -1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When Auto Operation

 

 

 

Over 22°C~below 24°C

Intake air -0.5°C

 

 

 

 

 

 

 

 

 

 

initial start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over 20°C~below 22°C

Intake air temperature

 

Controlled by

 

 

 

1/f rhythm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fuzzy logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below 20°C

 

20°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Over 20°C~below 30°C

 

Fuzzy control

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When Switch to Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

below 20°C

 

20°C

 

 

 

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

over 30°C

 

30°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Intake-Air temp.

 

 

 

 

Setting Temp. +0.5°C

 

 

 

 

(Compressor OFF)

 

 

 

 

Setting Temp. -0.5°C

 

 

 

 

(Compressor ON)

 

 

 

 

INDOOR FAN SPEED

 

Fuzzy Speed

 

 

COMPRESSOR

ON

OFF

ON

OFF

 

 

- 15 -

 

 

Auto Operation for Soft Dry

The Setting temperature will be same that of the current intake-air temperature.

-Compressor ON temperature; Setting temperature +1°C

-Compressor OFF temperature; Setting temperature -0.5°C

Auto Operation for Heating

Intake Air temp.

below 20°C

Over 20°C~below 21°C

 

 

 

Setting temp.

20°C

Intake air temperature +0.5°C

 

 

 

- 16 -

6.Heating Mode Operation

The unit will operate according to the setting by the remote controller and the operation diagram is shown as following.

For 9K, 12K Models

Intake Air temp.

 

 

 

 

 

 

 

 

Setting temp. +3°C

 

 

 

 

 

 

 

 

(Compressor OFF)

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

A

 

 

 

 

 

 

 

Setting temp.

 

 

 

 

 

 

 

 

(Compressor ON)

 

 

minimum

 

minimum

 

minimum

 

 

 

 

 

 

 

 

 

 

10sec.

 

10sec.

 

10sec.

 

 

Hot

 

 

 

 

 

 

 

 

Start

 

 

 

 

 

 

 

INDOOR FAN SPEED

OFF

Selecting

LOW

OFF

LOW

Selecting

LOW

OFF

fan speed

fan speed

 

 

 

 

 

 

 

COMPRESSOR

 

ON

 

OFF

 

ON

 

OFF

• A point; The indoor pipe temperature to be 35°C.

The indoor fan operates minimum 10sec. even if falls lower than 35°C.

• B point; The indoor pipe temperature to be 35°C.

The indoor fan operates minimum 10sec. even if falls lower than 35°C.

7. Hot-Start Control

The indoor fan stops until the evaporator piping temperature will be reached at 28°C. (BY TEMPERATURE)

The operation diagram is as following.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PIPE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEMP 28°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60 sec.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR

 

 

 

 

 

 

 

 

SELECTING

 

 

 

 

 

 

 

OFF

 

 

LOW

 

 

 

FAN SPEED

 

 

 

 

 

 

FAN SPEED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPRESSOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT-START BY TEMPERATURE

- 17 -

8. Deice Control

Deicing operation is controlled by timer and sensing the indoor pipe temperature.

Deicing operation checks the indoor pipe temperature and Intake-air temperature at 25 minutes and 60 minutes on starting of heating operation, and discriminates by temperature difference.

When the heating operation passed 25 minutes, the temperature ( T1=TE1–TR1) is checked and memorized with checking the indoor pipe temperture (TE1) and the indoor Intake-air temperature (TR1).

When the heating operation passed 60 minutes, deicing operation checks the indoor pipe temperature (TE2) and the indoor Intake-air temperature (TR2), and checks indoor pipe temperature(TE2), the temperature difference ( T2=TE2–TR2) and the temperature difference Td(= T1– T2) of T1, T2.

If temperature of indoor pipe is below 32°C Deicing function operates at the priority I condition. If temperature of indoor pipe is over 32°C Deicing function operates at the priority II condition.

If the temperature difference ( Td) become more than the option temperature, deicing operation starts.

At that time, deicing operation time is decided.

The deicing operation time starts after deicing operation started.

If deicing operation start, above heating operation time is reset, so if deicing operation is finished, the heating operation time is recounted.

The deicinig time and the operation diagram are as following.

TEMP °C

60 minutes

 

 

 

 

 

 

 

 

 

 

 

 

25 mins

 

 

 

 

25 mins

 

TE1

 

 

 

 

 

 

 

 

 

TE2

 

 

 

T1

T2

T2

 

 

T1

Pipe Temp.

 

 

 

 

 

 

Intake Air

 

 

 

 

Hot

 

Temp.

 

 

 

 

 

Heating

 

 

Deicing

Start

Heating

 

 

 

COMPRESSOR

ON

 

 

ON

ON

ON

4-WAY VALVE

ON(Heating Operation)

 

OFF

ON

ON

OUTDOOR FAN

ON

 

 

OFF

ON

ON

INDOOR FAN

ON

 

 

OFF

 

ON

DEICE LED

OFF

 

 

ON

 

OFF

(DEICING DIAGRAM)

Priority I

TE2

below 30°C

 

30~31°C

 

 

31~32°C

 

 

Over 32°C

 

 

 

 

 

 

 

 

 

Deicing Time

12mins

 

11mins

 

 

10mins

 

Heating Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

Priority II

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1T2=Td

Over 3.5°C

 

3.0 3.5°C

 

2.5 3.0°C

 

2.0 2.5°C

 

below 2.0°C

 

 

 

 

 

 

 

 

 

 

 

 

 

Deicing Time

12mins

 

11mins

 

10mins

 

9mins

 

Heating Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

- 18 -

9. Soft Dry Operation.

During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, the compressor OFF temperature is the setting temperature minus 0.5°C.

When the room temperature rises over the compressor ON temperature, the operation mode is switched to the cooling mode.

When the room temperature falls between the compressor ON temperature and OFF temperature, the operation mode is switched to the Soft Dry Operation.

In this temperature range, 10min. Dry operation, 5.5min operation OFF, 1.5min. only fan operation repeat. During 10min Dry operation, even if the room temperature falls below compressor OFF temperature, 10min(MAX) Compressor ON from starting of Dry operation which includes 4 min. Compressor ON operation below the compressor OFF temperature.

In micom dehumidify mode, control of fan speed is as following.

 

 

 

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROOM TEMP.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dry operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING TEMP.+1°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(COMP. ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING TEMP.-0.5°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(COMP. OFF)

 

 

 

 

 

1 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

2 minutes

 

 

 

 

 

 

 

 

5.5 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 minutes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR FAN SPEED

Selecting

OFF

LOW

LOW

OFF

LOW

LOW

fan speed

COMPRESSOR

ON

OFF

 

ON

OFF

 

ON

10. Forced operation

If you lose wireless remote controller, you can operate the unit with forced operation switch.

The standard conditions are as following.

 

Cooling Model

 

Heat pump Model

 

 

 

 

 

 

Room Temp ≥ 24°C

21°C ≤Room Temp 24°C

Room Temp 21°C

 

 

 

 

 

 

 

Operation Mode

Cooling

Cooling

Soft Dry

Heating

 

 

 

 

 

Indoor Fan Speed

High

High

Low

High

 

 

 

 

 

Setting Temp.

22°C

22°C

Room Temp.

24°C

 

 

 

 

 

- 19 -

Display Function

1. Heating Model

2.Cooling Model

 

 

Operation Indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation Indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Cooling, Soft Dry, Fan, Heating

 

 

 

 

 

 

 

 

 

• Cooling, Soft Dry, Fan, Heating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer Indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Timer Indicator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Timer Mode

• Timer Mode

 

Sleep Timer Indicator

Sleep Timer Indicator

 

• Sleep Mode

• Sleep Mode

 

Deicer Indicator

Outdoor unit operation

OUT

 

 

DOOR

• Hot-start, Deice

• Outdoor Unit Operating or not

 

Self-diagnosis Function

1. Protection of the eveporator pipe from frosting

If the temperature of the indoor pipe is below 0°C after 7 mins from starting the compressor, the compressor and the outdoor fan is stopped, and then after 3 mins delay of the compressor and the temperature of the indoor pipe is over 7°C, the compressor and the outdoor fan is reoperated.

2. Thermistor Cut Off of Short

Cut Off/Short : Blinks on and off the operation mode LED. (0.5 sec ON/3 sec OFF)

- 20 -

Installation

1. Installation of Indoor, Outdoor unit

1) Selection of the best location

1. Indoor unit.

There should not be any heat source or steam near the unit.

There should not be any obstacles to prevent the air circulation.

A place where air circulation in the room will be good.

A place where drainage can be easily obtained.

A place where noise prevention is taken into consideration.

Do not install the unit near the door way.

Ensure the spaces indicated by arrows from the wall, ceiling, fence, or other obstacles.

More than

More than 5 cm

5 cm

 

More than eye-level

More than

5 cm

2. Outdoor unit.

If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radia-

tion from the condenser is not restricted.

More than 10 cm

More than 10 cm

 

• There should not be any animals or plants which

 

 

could be affected by hot air discharged.

 

 

• Ensure the spaces indicated by arrows from the wall,

 

 

ceiling, fence, or other obstacles.

 

 

 

More than 70 cm

 

- 21 -

2) Indoor Unit Installation

The mounting wall should be strong and solid enough to prevent it from the vibration.

1.Mount the installation plate on the wall with four Type "A" screws.

Always mount the Installation plate horizontally by aligning the marking-off line with using the thread and a level.

2.Drill the piping hole with 70mm dia. holecore drill.

Drill the piping hole at either the right or the left and the hole should be slightly slant to the outdoor side.

Installation Plate

Type "A" screw

marking-off line

Thread

Weight

The lower left and right side of Installation Plate

<7K, 9K BTU>

Left rear piping

Right rear piping

80mm

 

20mm

20mm

 

50mm

ø 70mm

ø 70mm

<11K, 12K, 14K BTU>

Left rear piping

Right rear piping

A

A

Center

Center

A

A

ø 70mm

ø 70mm

WALL

Indoor

Outdoor

 

5~7mm

- 22 -