This documentation exclusively describes the communication module E94AYCPM (PROFIBUS).
Note!
This documentation supplements the Mounting Instructions supplied with the
communication module and the "Servo Drives 9400" Hardware Manual.
The Mounting Instructions contain safety instructions which must be observed!
The features and functions of the communication module are described in detail.
Typical applications are explained with the help of examples.
The theoretical connections are only explained in so far as they are necessary for comprehending
the function of the communication module.
This documentation does not describe the software of other manufacturers. No responsibility is
taken for corresponding information given in this documentation. Information on how to use the
software can be obtained from the documents of the host system (master).
All brand names used in this documentation are trademarks of their respective owners.
Tip!
Detailed information about PROFIBUS can be found on the website of the PROFIBUS &
PROFINET user organisation:
www.profibus.com
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD175
This documentation is intended for all persons who plan, install, commission and maintain the
networking and remote servicing of a machine.
Tip!
Current documentation and software updates with regard to Lenze products can be found
in the download area at:
www.Lenze.com
Validity information
The information given in this documentation is valid for the following devices:
Extension moduleType designationFrom hardware
version
PROFIBUS communication moduleE94AYCPM1A01.11
Screenshots/application examples
All screenshots in this documentation are application examples. Depending on the firmware
version of the communication module and the software version of the Engineering tools installed
(»Engineer«, »STEP7«), the screenshots in this documentation my differ from the actual screen
display.
From software
version
6Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
This manual uses the following conventions to distinguish between different types of information:
Type of informationWritingExamples/notes
Numbers
Decimal separatorPointThe decimal point is always used.
Example: 1234.56
Hexadecimal0x[0 ... 9, A ... F]Example: 0x60F4
Binary
• Nibble
Text
Version informationText colour blueAll pieces of information that only apply to or from a specific
Program name» «The Lenze PC software »Engineer«...
WindowitalicsThe message window... / The Options dialog box ...
Variable nameSetting bEnable to TRUE...
Control elementBoldThe OK button ... / The Copy command ... / The Properties tab
Sequence of menu
commands
HyperlinkUnderlined
Symbols
Page reference ( 8)Optically highlighted reference to another page. Can be
Step-by-step instructions
In inverted commas
Point
Example: ’100’
Example: ’0110.0100’
software version of the controller are highlighted
accordingly in this documentation.
Example: This function extension is available from software
version V3.0!
... / The Name input field ...
If several successive commands are required for executing a
function, the individual commands are separated from each
other by an arrow: Select the command File
Optically highlighted reference to another topic. Can be
activated with a mouse-click in this online documentation.
activated with a mouse-click in this online documentation.
Step-by-step instructions are indicated by a pictograph.
Open to...
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD177
Always observe the specified safety measures to avoid severe injury to persons and
damage to property!
Always keep this documentation to hand in the vicinity of the product during operation.
2.1General safety and application instructions
Danger!
If you disregard the following basic safety measures, this can cause severe injury to
persons and damage to material assets.
Lenze drive and automation components ...
• must only be used as directed.
Application as directed
• must never be commissioned in the event of visible damage.
• must never be technically modified.
• must never be commissioned before they have been completely mounted.
• must never be operated without the covers required.
• can - depending on their degree of protection - have live, moving or rotating parts during and
after operation. Surfaces can be hot.
For Lenze drive components ...
• use only the accessories approved.
• use only original spare parts from the manufacturer.
Observe all specifications given in the attached and associated documentation.
• This is the precondition for safe and trouble-free operation and for obtaining the product
features specified.
Features
• The procedural notes and circuit details described in this document are only proposals. It is up
to the user to check whether they can be adapted to the particular applications. Lenze does not
take any responsibility for the suitability of the procedures and circuit proposals described.
( 13)
( 12)
10
Only qualified personnel may work with and on Lenze drive and automation components.
According to IEC 60364 and CENELEC HD 384, these are persons ...
• who are familiar with the installation, assembly, commissioning and operation of the product.
• who have the corresponding qualifications for their work.
• who know all regulations for the prevention of accidents, directives and laws applicable on site
and are able to apply them.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
2Safety instructions
2.2Device- and application-specific safety instructions
2.2Device- and application-specific safety instructions
• During operation, the communication module must be firmly connected to the standard device.
• With external voltage supply, always use a separate power supply unit, safely separated to EN
61800-5-1 in every control cabinet (SELV / PELV).
• Only use cables corresponding to the given specifications.
Bus cable specification
( 26)
Documentation for the standard device, control system, plant/machine
All other measures prescribed in this documentation must also be implemented.
Observe the safety instructions and application notes specified in the documentation.
2.3Residual hazards
Protection of persons
If the Servo Drives 9400 are operated on a phase earthed mains with a rated mains voltage ≥ 400 V,
external measures need to be implemented in order to ensure protection against accidental
contact.
Protective insulation
Device protection
The communication module contains electronic components which may be damaged or destroyed
by electrostatic discharge.
Installation
( 21)
( 16)
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1711
If the Servo Drives 9400 are operated on a phase earthed mains with a rated mains
voltage ≥ 400 V, external measures need to be implemented in order to ensure
protection against accidental contact.
Possible consequences:
Death or severe injury
Protective measures:
If protection against accidental contact is required for the control terminals of the
controller and the terminals of the plugged-in device modules, ...
• a double isolating distance must be provided.
• the components to be connected must be provided with a second isolating distance.
Note!
The existing protective insulation in the Servo Drives 9400 is implemented according to
EN 61800-5-1.
16
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
Documentation for the standard device, control system, plant/machine
Observe the notes and wiring instructions given in the documentation.
5.2.1Network topology
The following examples show two simple RS485 networks.
Every segment of the network must be terminated at both ends. The bus terminators of the
PROFIBUS are marked with a "Z" in the below examples.
In the case of an RS485 network of only one segment, the PROFIBUS master (M) with the integrated
bus terminator starts the segment while the bus terminating resistor in the connector of the last
PROFIBUS station (S) must be activated.
M
Z
Z
SSS
1
[5-3]RS485 network with one segment
An RS485 network consisting of several segments contains repeaters (R) for connecting the
segments. The repeaters are provided with integrated bus terminating resistors.
M
Z
Z
Z
SSS
Z
R
SS
Z
R
Z
123
[5-4]RS485 network with a repeater
E94YCPM012a
E94YCPM012b
If no repeater is to be used at the end of the segment, the bus terminating resistor must be activated
in the connector of the last device. The bus termination is supplied by the station itself.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1723
If the communication module is supplied externally, the bus terminator can be supplied
independently of the standard device supply.
External voltage supply
( 28)
Note!
The bus terminator must always be supplied. Otherwise, the bus can get unstable.
Activating the bus terminating resistor
Number of stations
( 25)
M
RR
SSSS S
123
2133PFB004
[5-5]Number of stations
SegmentMaster (M)Slave (S)Repeater (R)
1131-
230-
2-301
3-301
24
Tip!
Repeaters do not have a station address. When calculating the maximum number of
stations, they reduce the number of stations by 1 on each side of the segment.
Repeaters can be used to build up line and tree topologies. The maximum total bus system
expansion depends on ...
• the baud rate used;
• the number of repeaters used.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
The length of the bus cable depends on the baud rate and cable type used. The data in the following
table applies to PROFIBUS cables of "FC-Standard Cable" cable type .
Baud rateLength
9.6 ... 93.75 kbps1200 m
187.5 kbps1000 m
500 kbps400 m
1500 kbps200 m
3000 ... 12000 kbps100 m
Note!
The baud rate depending of the data volume, cycle time and number of stations should
only be selected as high as required for the application.
Tip!
We recommend taking the use of optical fibres into consideration for high baud rates.
Advantages of optical fibres:
• External electromagnetic interferences have no effect on the transmission path.
• Bus lengths of several kilometres are also possible with higher baud rates.
• The bus length is ...
• independent of the baud rate;
• dependent on the optical fibre used.
26
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
During commissioning, plant-specific data such as motor parameters, operating parameters,
responses, and parameters for fieldbus communication are defined for the controller. Lenze devices
use codes for this purpose.
The codes of the controller and for communication are saved to the memory module in a nonvolatile data set.
In addition, there are codes for diagnosing and monitoring the stations.
Note!
When parameterising the communication module, please observe that the code number
depends on the slot of the Servo Drive 9400 in which the communication module has
been inserted.
The first two digits of the code number indicate the slot:
•C13nnn for slot MXI1
Parameters of the communication module for slot MXI1
•C14nnn for slot MXI2
Parameters of the communication module for slot MXI2
You also have to set the Communication-relevant parameters of the standard device
( 91)
.
( 93)
( 102)
6.1Before initial switch-on
Stop!
Before switching on the controller for the first time, check ...
• the entire wiring for completeness, short circuit and earth fault:
• whether the bus system is terminated through a bus terminating resistor at the first
and last physical bus station.
Activating the bus terminating resistor
( 25)
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1729
The host (master) must be configured before communication with the communication module is
possible.
Configuration for the host system (master) and the DP-V0 parameter data channel
For configuring the PROFIBUS you must read the device description file of the communication
module into the master.
The device description file for the E94AYCPM communication module (PROFIBUS) can be found in
the download area at:
www.Lenze.com
The following language variants of the device description file can be used:
• LENZ07A8.GSD (source file, English)
• LENZ07A8.GSG (German)
• LENZ07A8.GSE (English)
Defining the user data length
The user data length is defined during the initialisation phase of the master.
The Servo Drives 9400 support the configuration of a maximum of 32 process data words (max.
64 bytes). The optional activation of the cyclic parameter data channel additionally occupies
4 process data words (8 bytes). The transfer of PROFIsafe messages, too, occupies 4 additional
process data words.
The user data lengths for process input data and process output data are the same.
Description of the device data base file
Selection textParameter data
DRIVECOM-PAR
(cons) + PCD (nW
cons)
PCD (nW cons)-n words-n words
PCD (nW)--4 words4 words
Safety (4W)-4 words-4 words
n = 1 ... 32 process data words
with consistency
Process dataAssigned
with consistencywithout consistency
Yesn words-4 + n words
IO memory
30
Example of selecting the device data base file
DRIVECOM-PAR (cons) + PCD (8W cons)
• "Drivecom-PAR (cons)" = DP-V0 parameter data channel (4 words)
• "PCD (8W cons)" = 8 process data words
Tip!
A detailed description of consistency is given in the chapter "Consistent parameter data
( 76).
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
Via Tool Calling Interfaces (TCI) you can connect to a TCI-capable integrated development
environment and parameterise and diagnose your field devices without having to exit the
integrated development environment.
You cannot set the TCI communication path directly in the »Engineer«. The selection is carried out
by the »STEP7« Siemens software.
The TCI function requires a PN/DP-CPU. Information on the Siemens PLC types that are equipped
with the TCI function is provided via the Siemens Support at:
http://support.automation.siemens.com
How to configure TCI communication:
1. Alllocate names for the individual axes in the »Engineer« project.
In our case, "9400" was allocated for 9400 HighLine, and "8400" for 8400 StateLine:
34
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
• create the Lenze PROFIBUS stations with the corresponding station addresses and
•create a PROFIBUS network.
Here a Servo Drive 9400 (address 3) and an Inverter Drive 8400 (address 4) are operated on
the PROFIBUS.
• The names of the PROFIBUS slaves in the »HW Config« must be identical to those of the
corresponding Lenze axes in the »Engineer« (here "9400" and "8400").
• The selection of the process data configuration has no impact on TCI communication.
3. Establish an Ethernet connection to the PROFIBUS CPU.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1735
14. Start the transfer of the TCI communication parameters in the »HW Config« using the right
mouse button and the menu command Start device tool L-force Engineer.
15. If the »Engineer« has already been started with the applicable project, the following
message will appear:
• The message says that the »Engineer« project is not set to a TCI communication path and
provides information on whether this action is to be executed now.
• If you confirm the message with Yes, the applicable TCI communication parameter
settings of the »STEP7« project are transferred to the »Engineer«.
40
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
If the »Engineer« has not already been started, it is started automatically now and you have
to open the applicable project.
If the project selected has not been set to a TCI communication path yet, this can now be
executed with Yes:
16. The transfer of the TCI communication parameters is documented in the »Engineer«
message window.
Here the communication settings have been carried out successfully. The individual
PROFIBUS addresses in the respective codes have been adapted to the »STEP7« project.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1741
The PROFIBUS master and controller communicate through the exchange of data telegrams via
PROFIBUS. The user data area of the data telegram contains parameter data or process data. In the
controller, different communication channels are assigned to the parameter data and process data.
Communication channels
The process data channel serves to transfer process data.
• The process data serve to control the drive controller.
• The host (master) can directly access the process data. In the PLC, for instance, the data are
directly saved to the I/O area.
• Process data are not saved in the controller.
• Process data are transferred cyclically between the host system and the controllers (permanent
exchange of current input / output data).
• Process data are, for instance, setpoints, actual values, control words and status words.
• The Servo Drives 9400 can exchange a maximum of 32 process data words (16 bits/word) per
direction.
Note!
Observe the direction of the information flow!
Process input data (Rx data):
• Process data from the controller (slave) to the master
Process output data (Tx data):
• Process data from the master to the controller (slave)
The parameter data channel serves to transfer parameter data.
• The parameter data channel provides access to all Lenze codes.
• In general, the parameter data transfer is not time-critical.
• Parameter data are, for instance, operating parameters, diagnostic information, and motor
data.
• Parameter data changes must be saved via code C00002 of the Servo Drives 9400.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1743
The Servo Drives 9400 HighLine enable the individual mapping of process data. For this purpose, the
»Engineer« is provided with a port configurator.
Below you can find a description of the steps required to implement a process data communication
with a higher-level control, in which a control word/status word and a 32-bit setpoint/actual value
are exchanged.
Note!
The »Engineer« screenshots shown on the following pages are only examples for the
setting sequence and the resulting screens.
PDO mapping with the »Engineer«
1. You can carry out the mapping of the process data in the »Engineer« on the Process data
objects tab of the respective fieldbus communication module:
2. Select the receive object PDO_RX0:
44Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
3. Click the Edit PDO button. The Process data object structure:PDO_RX0 selection window
opens:
Here you can map the individual ports from the Port selection list into the receive PDO
"PDO_RX0" by clicking the >> button. With the Up and Down buttons, you can change the
order of the ports within the PDO.
Note
The port mapping is not a configuration, which can be carried out online for the Servo
Drive 9400 HighLine. For this purpose, the »Engineer« project must be updated and then
the application must be downloaded.
In the following example, the ports "LPortControl1" and "Lport32In1" have been mapped
into the receive PDO "PDO_RX0" and the ports "LPortStatus1" and "LPort32Out1" have been
mapped into the transmit PDO "PDO_TX0":
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1745
4. Now link the mapped ports to the application signals in the selected technology
application.
• If the »FB Editor« is not activated, you can use the multiplexer codes (from code C03000
onwards) for this purpose.
• If the »FB Editor« is activated, the multiplexer codes are no longer available. In this case,
you have to do the linking directly in the »FB Editor«.
46Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
The E94AYCPM communication module supports the cyclic and acyclic transmission of parameter
data:
• Cyclic DP-V0 parameter data are based on the DRIVECOM profile.
If the parameter data channel is active according to DP-V0, it is assigned an additional 4 words
of input / output data.
• Acyclic DP-V1 parameter data are based on the PROFIdrive profile.
9.1Addressing of the parameter data
The parameter data are addressed via codes which can be found in this documentation and in the
corresponding documentation of your controller.
Parameter reference
Addressing of Lenze parameters
In the case of the DP-V0 parameter data channel, the parameters of a device are not addressed
directly via Lenze code numbers, but via indices (bytes 3 + 4) and subindices (byte 2).
The conversion is made via an offset (24575 / 0x5FFF):
•PROFIBUS-DP index
•PROFIBUS-DP index
Example of C00105 (quick stop deceleration time):
•PROFIBUS-DP index
•PROFIBUS-DP index
The parameter values are entered into the user data (bytes 5 to 8) of the telegram.
( 91)
= 24575 - Lenze code number
dec
= 0x5FFF - Lenze code number
hex
= 24575 - 105 = 24470
dec
= 0x5FFF - 0x69 = 0x5F96
hex
hex
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1747
Request and response control for the parameter data channel
[9-1]Method of reading for bits 0 ... 7
Bit 0 ... 2: Request
Read/write request from the master to the controller
000 No request
001 Read request
Reading parameter data from the controller
010 Write request (write data to the controller)
Writing parameter data to the controller
100 Data transfer abort by the master
Data transfer abort by the master
Index
Low byte
76543210
( 51)
Data 4 /
Error 4
( 50)
( 50)
Data 3 /
Error 3
Data 2 /
Error 2
Data 1 /
Error 1
Bit 3
Reserved
Bit 4/5: Data length
Data length ≤ 4 bytes in the telegram bytes 5 ... 8 (data 1 ... 4 / error 1 ... 4)
00 1 byte
01 2 bytes
10 3 bytes
11 4 bytes
Bit 6: Handshake
Indicates a new request.
• The state of this (toggle) bit is changed by the master for every new request.
• The controller copies the bit into its response telegram.
Bit 7: Status
Status information from the controller to the master when sending the request confirmation.
This status bit informs the master whether the request has been carried out without errors.
0 Request completed without errors.
Bytes 5 ... 8 contain a parameter value (Data 1 ... 4 ).
1 Request not completed because of an error.
• The set status bit indicates that the telegram is an "error telegram".
Data communication with PROFIBUS-DP-V0 is characterised by cyclic diagnostics and cyclic process
data and parameter data transfer.
An optional service expansion is the acyclic parameter data transfer of PROFIBUS-DP-V1. This
service does not impair the functionality of the standard services under PROFIBUS-DP-V0.
PROFIBUS-DP-V0 and PROFIBUS-DP-V1 can be operated simultaneously in the same network. This
enables the step-by-step expansion or retrofitting of a system.
The services of PROFIBUS-DP-V1 can be used by the class 1 master (PLC) and the class 2 master
(diagnostics master, etc.).
The integration of the acyclic service into the fixed bus cycle depends on the corresponding
configuration of the class 1 master:
• With configuration, a time slot is reserved.
• Without configuration the acyclic service is appended when a class 2 master acyclically accesses
a DP-V1 slave.
Features
• Parameter number and subindex addresses with a width of 16 bits each.
• Several parameter requests can be combined to one request (multi-parameter request).
• There is always only one parameter request in process (no pipelining).
• A parameter request/response must fit into a data block (max. 240 bytes). Requests/responses
cannot be split into several data blocks.
• No spontaneous messages are transferred.
• There are only acyclic parameter requests.
• Profile-specific parameters can be read independently of the slave state.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1757
• When a read request is processed, no parameter value is written to the slave.
• In the case of a multi-parameter read request, the parameter attribute, index, and
subindex are repeated with the number "n" of the requested parameters.
• A read request must not exceed the maximum data length of 240 bytes.
Request header
Byte 1Byte 2Byte 3Byte 4
Request referenceRequest identificationAxisNumber of indices
FieldData typeValues
Request referenceU8This value is specified by the master
Request identificationU80x01: Request parameters for reading
AxisU80x00 or 0x01
Number of indicesU80x"n" (n = number of parameters requested)
Parameter attribute
Byte 5Byte 6
AttributeNumber of subindices
FieldData typeValues
AttributeU80x10: Value
Number of subindicesU80x00
(For array elements: Enter the number of array elements
required.)
Index and subindex
Byte 7Byte 8Byte 9Byte 10
IndexSubindex
High byteLow byteHigh byteLow byte
FieldData typeValues
IndexU160x0001 ... 0xFFFF (1 ... 65535)
SubindexU160x0001 ... 0xFFFF (1 ... 65535)
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1761
In the PROFIBUS communication system, data are permanently exchanged between the host (CPU +
PROFIBUS master) and the standard device via the plugged-on communication module. Both the
PROFIBUS master and the CPU (central processing unit) of the host access a joint memory: the dual
port memory (DPM).
The DPM permits a data exchange in both directions (write/read):
Central processing unit
(CPU)
It could happen that a slower PROFIBUS master writing would be overtaken by a faster CPU reading
within a cycle time without any further data organisation.
In order to avoid such an impermissible state, the parameter data to be transmitted must be marked
as "consistent".
Data communication with consistent data
With consistency, either "reading" or "writing" is possible when the master and the CPU
simultaneously access the memory:
• The PROFIBUS master transfers data only as a complete data set.
• The CPU can only access completely updated data sets.
• The PROFIBUS master cannot read or write data as long as the CPU accesses consistent data.
The result becomes clear from the example below:
CPU wants to read!Master wants to write simultaneously!
Central processing unit
(CPU)
Dual port memory
(DPM)
Dual port memory
(DPM)
PROFIBUS master
PROFIBUS master
1. As the master can only write if the CPU does not read, the master waits until the data are read
completely by the CPU.
2. The master only writes a complete data set into DPM.
Configuring consistent data
Note!
Consistency is achieved by an appropriate PROFIBUS master configuration.
For this purpose, refer to the documentation for your configuring software.
76
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
PROFIBUS enables the transfer of safe information via the PROFIsafe protocol in accordance with
the "PROFIsafe - Profile for Safety Technology" specification, version 2.0.
Note!
A safety bus system (PROFIsafe) can only be operated via the upper module slot MXI1 of
the Servo Drive 9400.
• The PROFIsafe data are sent in the first slot of a PROFIBUS data telegram.
• One bit of the PROFIsafe data is always used to control specific safety functions.
• The structure of the PROFIsafe data is described in the PROFIsafe profile.
• The length of the PROFIsafe data (also called PROFIsafe message) always is 8 bytes.
Documentation for the safety module SM301 (E94AYAE)
Here you can find detailed information on the PROFIsafe connection.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1777
11Monitoring
11.1Permanent interruption of PROFIBUS communication
11.1Permanent interruption of PROFIBUS communication
If PROFIBUS communication is interrupted permanently, e.g. by cable breakage or failure of the
PROFIBUS master, no process data are transmitted to the slave being in the "Data Exchange" state.
After the watchdog monitoring time determined by the PROFIBUS master has expired, the response
parameterised under C13880/1
The process data handling depends on the setting in C13885
master can either be used or set to zero.)
Preconditions for a controller (slave) response
/ C14880/1 is executed in the controller (slave).
/ C14885. (The last data sent by the
• A monitoring time of 1 ... 65534 ms is set for the "Data_Exchange" state (C13881
A value of "65535 ms" (Lenze setting) deactivates the monitoring.
• A response is set for the slave in C13880/1
• The slave is in the "Data_Exchange" state.
• The watchdog monitoring time is configured correctly in the master.
If one of these preconditions is not met, the response to the absence of cyclic process data telegrams
from the master is not executed.
Settings and displays in the »Engineer«
/ C14880/1 (Lenze setting: "No response").
( 80)
/ C14881).
78
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
11Monitoring
11.2Short-time interruption of PROFIBUS communication
11.2Short-time interruption of PROFIBUS communication
From software version 01.21, the current DP states are displayed in C13868 / C14868.
POWER ON
Set_Slave_Add
Slave_Diag
Chk_Cfg, not o.k.
Set_Prm, not o.k.
[11-1] DP states (Decentralized Peripherals) for short-time interruption of communication
The master detects the communication fault and transfers the slave to the "WAIT_PRM" state of the
DP state machine after only a few microseconds (see Fig. [11-1]
Only after the state chain of the DP state machine ending in the "Data_Exchange" state
(DATA_EXCH) has been passed through, the watchdog monitoring time calculated for the slave (in
milliseconds) continues to run.
WAIT_PRM
WAIT_CFG
Chk_Cfg, o.k.
DATA_EXCH
Slave_Diag
Get_Cfg
Slave_Diag
Set_Prm
Get_Cfg
).
Note!
The watchdog monitoring time does not continue to run when the slave does not reach
the "Data_Exchange" state due to repeated communication errors (e.g. caused by loose
contact).
2133PFB006
Additional monitoring for the data exchange
An additional monitoring function for data exchange is available under C13881
monitoring function already becomes active when the "Data_Exchange" state is exited and the
parameterised time (0 ... 65535 ms) has expired. The active monitoring function triggers the
response parameterised under C13880/1
/ C14880/1.
/ C14881. This
Note!
Observe the following condition for the time setting:
Monitoring time for data exchange (C13881
PROFIBUS (C13882/1
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1779
The response to a communication error between the communication module and the standard
device can be set via the standard device codes C01501
in slot MXI2)
( 92).
(module in slot MXI1) and C01502 (module
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1781
For diagnosing faults of the PROFIBUS module, the LEDs on the front panel are available.
Furthermore, you can query the current bus status via codes C13861
12.1LED status displays
/ C14861.
Note!
During normal operation, the LED BS blinks and the LED MS is permanently lit.
LED status displayPos.ColourStateDescription
MSGreenOnThe communication module is supplied with voltage
BlinkingThe communication module is supplied with voltage,
MERedOnAn error concerning the communication module has
BSGreenBlinkingThe communication module is in the DATA_EXCH
OffThe communication module is not active on the
BERedOnBus error/fault is active (e.g. bus cable unplugged).
DERedOnThe communication module is not accepted by the
and has established a connection to the standard
device.
but has not yet established a connection to the
standard device. (Standard device is switched off,
initialising or not present.)
occurred.
state ("Data_Exchange"). Data are exchanged via the
PROFIBUS.
fieldbus or is being initialised.
standard device or the standard device is not active.
(See notes in the documentation for the standard
device.)
82
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
Errors in the standard device and its plugged-in modules are transmitted to the PROFIBUS master in
the form of advanced diagnostic messages.
Structure of the diagnostic message
ByteDescription
1 Bit 0: Station does not exist (set by the master).
Bit 1: Slave is not ready for data exchange.
Bit 2: Configuration data do not correspond.
Bit 3: Slave has extended diagnostic data.
Bit 4: Requested function is not supported by the slave.
Bit 5: Slave response is invalid (set by the master)
Bit 6: Incorrect parameter setting
Bit 7: Slave has been parameterised by another master (set by the master).
2 Bit 0: Slave must be parameterised again.
Bit 1: Static diagnostics
Bit 2: Permanently set to "1".
Bit 3: Watchdog active
Bit 4: Freeze command received.
Bit 5: Sync command received.
Bit 6: Reserved
Bit 7: Slave is deactivated (set by the master).
3 Bit 7: Diagnostics overflow - amount of diagnostic information present in the slave is too large to fit
into one telegram.
4 Bits 0 ... 7: Master address after parameter setting ("0xFF" without parameterisation)
5 Bits 0 ... 7: ID number (high byte)
6 Bits 0 ... 7: ID number (low byte)
7Header
• The header contains the block length of the advanced diagnostics including the header byte.
• In this case, the value of the entry is "0x0A" (bytes 7 ... 16 = 10 bytes).
8 Status_Type
The value of this entry is fixed. For the following bit assignment it is "0x81":
• Bit 7 = 1: "status"
• Bit 0 = 1: "status message"
• Value of all other bits = 0
9Slot_Number
The value of the slot number is "0x00".
10 Specifier
• A detected error is entered in the specifier with the identification "0x0" (status coming).
• An eliminated error is entered in the specifier with the identification "0x02" (status going).
• If no errors are indicated, the entry in the specifier has the value "0x00" (no further
differentiation).
11 PROFIsafe, error number of the safety module SM301 (E94AYAE)
• If an error occurs in the safety module, byte 11 (low byte) and byte 12 (high byte) contain the
12
corresponding error number.
• See also documentation for the safety module.
13 ... 16 Error code of the Servo Drive 9400
•Code C00168 can be used to read out the contents of the fault memory.
• Detailed information on the error codes of the Servo Drive 9400 can be found in the
documentation of the controller.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1785
12.3.1Example 1: Error in parameter data "Incorrect PROFIsafe target address"
This error was caused while communication of the PROFIBUS master was established because the
PROFIsafe target address configured in the PROFIBUS master does not correspond to the set address
anymore.
ByteValue
[hex]
1x Standard data (PRM_Fault)
...
6
70A Block length of the advanced diagnostics = 10 bytes
881 Status message
900Slot 0
1001 Status coming
1140 PROFIsafe error "0x0040" (64)
1200
1300 No other error message
......
1600
Description
GSG: "F address differ to F_Dest_Add"
12.3.2Example 2: Error "Undervoltage in the DC bus" in the Servo Drive 9400
ByteValue
[hex]
1x Standard data (PRM_Fault)
...
6
70A Block length of the advanced diagnostics = 10 bytes
881 Status message
900Slot 0
1001 Status coming
1100 No PROFIsafe/safety error
1200
130F Error message 0x447B000F "Undervoltage in DC bus"
1400
157B
1644
Description
• Response: "Fault"
• Instance ID: 1
• Module ID: 0x7B
• Error ID: 0x0F
86
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
This chapter supplements the error list for the Servo Drive 9400 contained in the software manual
and in the »Engineer« online help with the error messages of the communication module.
Software manual/online help for Servo Drive 9400
Here you can find general information on diagnostics & fault analysis and on error
messages.
13.1Short overview of the PROFIBUS error messages
The following table lists all PROFIBUS error messages in numerical order of the error number.
Furthermore the preset error response and – if available – the parameters for setting the error
response are specified.
Tip!
When you click the cross-reference in the first column, you will see a detailed description
(causes and remedies) of this error message.
Error numberDesignationResponse (Lenze setting)Adjustable in
hexdec
0x00c83100
0x00c85531
0x00c85532
0x00c85533
0x00c86010
0x00c86011
0x00c86100
0x00c86101
0x00c86110
0x00c8641f
0x00c86420
0x00c88130
0x00c88131 13140273Profibus: Data_Exchange state exited0: No responseC13880/1
0x00c88132 13140274Profibus watchdog: DP-V1 MSAC2 elapsed0: No responseC13880/2
13119744Profibus: Lost connection to 9400 base device0: No response-
This chapter lists all PROFIBUS error messages in the numerical order of the error numbers. Possible
causes and remedies as well as responses to the error messages are described in detail.
Profibus: Lost connection to 9400 standard device [0x00c83100]
Response (Lenze setting printed in bold)Setting: not possible
: None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
• Network cable (plug) is defective.
• Network cable is not connected to the PROFIBUS
terminal X201.
• Voltage supply is interrupted.
Profibus: No memory access [0x00c85531]
Check cables and terminals.
Connect network cable to the PROFIBUS terminal X201.
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
CauseRemedy
Access to memory was not possible.Repeat the download of the application
Profibus: Read memory error [0x00c85532]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
CauseRemedy
Parameter could not be read.Repeat the download of the application
Profibus: Write memory error [0x00c85533]
Response (Lenze setting printed in bold)Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning : Information
CauseRemedy
Parameter could not be written.Repeat the download of the application
(including module)
(including module)
(including module)
Profibus: Restart after watchdog reset [0x00c86010]
Response (Lenze setting printed in bold)Setting: not possible
None System fault : Fault Trouble Quick stop by trouble Warning locked Warning Information
CauseRemedy
Module defective.If this occurs repeatedly, contact the Lenze service.
88
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
This chapter supplements the parameter list and the table of attributes contained in the software
manual and in the »Engineer« online help for the Servo Drive 9400 with the parameters of the
E94AYCPM (PROFIBUS) communication module.
Software manual/»Engineer« online help for Servo Drive 9400
Here you can find general information on parameters.
14.1Communication-relevant parameters of the standard device
This chapter lists the communication-relevant parameters of the Servo Drive 9400 in numerically
ascending order.
C00615
C00636
Parameter | Name:
C00615 | Resp. to imp. device conf.
Response to incorrect device configuration
Selection list
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
0 No response
SubcodesLenze settingInfo
C00615/10: No responseReserved
C00615/21: FaultResp. to imp. module in MXI1
C00615/31: FaultResp. to imp. module in MXI2
C00615/40: No responseReserved
C00615/50: No responseReserved
; Read access ; Write access CINH PLC-STOP No transfer
Parameter | Name:
C00636 | Resp. to new module in MXI1
Response when a new module has been inserted in module slot 1 of the standard device.
Selection list (Lenze setting printed in bold)
1 Error
6 Information
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
; Read access ; Write access CINH PLC-STOP No transfer
Data type: UNSIGNED_32
Index: 23960
Data type: UNSIGNED_32
Index: 23939
= 5D98
d
= 5D83
d
h
h
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1791
14Parameter reference
14.1Communication-relevant parameters of the standard device
14.2Parameters of the communication module for slot MXI1
This chapter lists the parameters of the E94AYCPM communication module (PROFIBUS) for slot
MXI2 of the Servo Drive 9400 in numerically ascending order.
C13231
C13489
C13531
C13789
C13850
Parameter | Name:
C13231 | Service code
This code is for device-internal use only and must not be overwritten by the user!
Parameter | Name:
C13489 | Service code
This code is for device-internal use only and must not be overwritten by the user!
Parameter | Name:
C13531 | Service code
This code is for device-internal use only and must not be overwritten by the user!
Parameter | Name:
C13789 | Service code
This code is for device-internal use only and must not be overwritten by the user!
Data type: UNSIGNED_64
Index: 11344
Data type: UNSIGNED_8
Index: 11086
Data type: UNSIGNED_64
Index: 11044
Data type: UNSIGNED_8
Index: 10786
= 2C50
d
= 2B4E
d
= 2B24
d
= 2A22
d
h
h
h
h
Parameter | Name:
C13850 | All words to master
Data type: UNSIGNED_16
Index: 10725
= 29E5
d
Display of the process data words transferred from the communication module to the PROFIBUS master.
In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data words
are valid.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13850/1
...
C13850/32
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
h
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1793
14Parameter reference
14.2Parameters of the communication module for slot MXI1
Display of the process data words transferred from the PROFIBUS master to the communication module.
In the subcodes 1 ... 32, all process data words to the master are displayed. Only the configured process data words
are valid.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13851/1
...
C13851/32
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13852 | All words to standard device
Data type: UNSIGNED_16
Index: 10723
= 29E3
d
Display of the process data words 1 ... 32 transferred from the communication module to the standard device.
In the subcodes 1 ... 32, all process data words from the communication module are displayed.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13852/1
...
C13852/32
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
h
h
C13853
C13854
Parameter | Name:
C13853 | All words from standard device
Data type: UNSIGNED_16
Index: 10722
d
Display of the process data words 1 ... 32 transferred from the standard device to the communication module.
In the subcodes 1 ... 32, all process data words from the standard device are displayed.
Display area (min. value | unit | max. value)
065535
SubcodesInfo
C13853/1
...
C13853/32
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13854 | COM word to standard device
Data type: BITFIELD_32
Index: 10721
d
Available from software version 01.21!
This code is for device-internal use only and must not be overwritten by the user!
= 29E2
= 29E1
h
h
94
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
14Parameter reference
14.2Parameters of the communication module for slot MXI1
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
Data type: UNSIGNED_8
C13864 | Active station address
Display of the active station address
If all DIP switches 1 ... 64 are in the "OFF" position (Lenze setting), the station address set in C13899
and is displayed here after switching on.
Setting the station address
( 31)
Display area (min. value | unit | max. value)
0255
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Index: 10712
Index: 10711
= 29D8
d
= 29D7
d
becomes active
h
h
C13865
C13866
Parameter | Name:
C13865 | Display: Most recent PRM data
Data type: OCTET_STRING
Index: 10710
= 29D6
d
Display of the last parameter data sent by the PROFIBUS master with the "Set-Prm" telegram (ASCII string with 24
characters)
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13866 | Display: Most recent CFG data
Data type: OCTET_STRING
Index: 10709
= 29D5
d
Display of the last configuration data sent by the PROFIBUS master with the "Chk-Cfg" telegram (ASCII string with
22 characters)
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
h
h
96
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
14Parameter reference
14.2Parameters of the communication module for slot MXI1
Display of the last diagnostic data sent to the PROFIBUS master (ASCII string with 16 characters)
Advanced diagnostic message
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13868 | Display: DP state
( 85)
Data type: UNSIGNED_8
Index: 10707
= 29D3
d
Available from software version 01.21!
Display of the DP states (Decentralized Peripherals)
Short-time interruption of PROFIBUS communication
( 79), see fig. [11-1]
Selection list (read only)
0 Waiting for parameterisation
1 Waiting for configuration
2 Data exchange
3 n/a
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13880 | Reaction on communication fault
Data type: UNSIGNED_8
Index: 10695
= 29C7
d
Monitoring response to a communication fault on the PROFIBUS
A change in the monitoring response is effective immediately.
Permanent interruption of PROFIBUS communication
( 78)
Selection list
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
6 Information
SubcodesLenze settingInfo
C13880/10: No responseThe response set here for the "Watchdog/Data
Exchange" monitoring function is executed if the bus
station ...
• does not receive a message from the master within
the watchdog monitoring time (displayed in C13882/
1) if there is an active connection.
• detects that it is no longer in the "Data_Exchange"
status. Please see also the notes given under C13881
C13880/20: No responseThe response set here for the "DPV1 MSAC2" monitoring
is executed if the bus station does not receive a "DPV1
MSAC2" message from the master within the monitoring
time (displayed in C13882/2
) if there is an active
connection) and the MSAC2 connection is stopped by the
slave.
Note: We recommend only setting "information" as
response so that no drive-relevant response is executed.
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
h
.
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1797
14Parameter reference
14.2Parameters of the communication module for slot MXI1
If the "Data Exchange" state is exited, the response parameterised under C13880/1 is carried out when the
monitoring time for data exchange set here has expired.
• A value of "65535" in this code deactivates the monitoring function.
• A change in monitoring is effective immediately.
• The value set here for the monitoring time must be smaller than the watchdog monitoring time ( C13882/1
Permanent interruption of PROFIBUS communication
( 78)
Setting range (min. value | unit | max. value)Lenze setting
0ms65535 65535 ms
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13882 | Monitoring time: Watchdog
Data type: UNSIGNED_32
Index: 10693
Display of the watchdog monitoring time determined by the PROFIBUS master
• A change in the watchdog monitoring time is immediately effective.
• Monitoring starts with the receipt of the first telegram.
• When a value of "0" is displayed, the monitoring function is deactivated.
Permanent interruption of PROFIBUS communication
( 78)
Display area (min. value | unit | max. value)
0ms4294967295
SubcodesInfo
C13882/1Watchdog monitoring time
C13882/2DP-V1 MSC2
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
= 29C6
d
= 29C5
d
h
).
h
C13885
Parameter | Name:
C13885 | Clear process data
Data type: UNSIGNED_8
Index: 10690
= 29C2
d
Selection of the process data which the controller will process in the event of a PROFIBUS failure in order to maintain
internal communication.
Selection list (Lenze setting printed in bold)
0 Use of most recent master PDOs
1 PDOs are set to the value '0'
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
98
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
14Parameter reference
14.2Parameters of the communication module for slot MXI1
Bit-coded selection of the error responses in the standard device causing the external diagnostic bit ("diag bit") to
be set (see PROFIBUS specification; bit 3 of byte 1 of the DP diagnostic messages).
• The diagnostic bit is sent to the PROFIBUS master where it is evaluated separately.
• The diagnostic bit is always set when a system error occurs.
• The Lenze setting "0" means that the diagnostic bit is not set for the following error responses.
• An advanced diagnostic message is always sent.
Value is bit-coded:
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
C13887 | Suppress signalling diag. mess. upon
Data type: BITFIELD_8
Index: 10688
= 29C0
d
Available from software version 01.20!
Selection of the error responses not causing a diagnostic request to the PROFIBUS master.
A diagnostic request is always signalled if a system error or an error message from the SM301 (E94AYAE) safety
module occurs.
The Lenze setting "0" means that for each of the following error responses a diagnostic request is signalled.
Value is bit-coded:Info
Bit 0 Error
Bit 1 Trouble
Bit 2 Quick stop by trouble
Bit 3 Warning locked
Bit 4 Warning
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Error message 0x00c88130
Available from software version 01.21!
Selective suppression of the error message "Available
connection to 9400 standard device lost"
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX COM MOT
h
h
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD1799
14Parameter reference
14.2Parameters of the communication module for slot MXI1
• Only required if the SM301 (E94AYAE) safety module is used.
• A unique PROFIsafe target address must be assigned to each controller.
Setting range (min. value | unit | max. value)Lenze setting
165534 1
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX ; COM MOT
Parameter | Name:
C13899 | Station address
Data type: UNSIGNED_8
Index: 10676
= 29B4
d
Optional setting of the station address (instead of setting via DIP switches 1 ... 64)
• The station address set here only becomes effective if the DIP switches 1 ... 64 have been set to OFF prior to mains
switching.
• The active station address is displayed under C13864
.
Note: A change of the station address will not be effective until the " Save parameter set" device command has been
executed and another mains switching for the communication module/controller has been performed.
Setting the station address
( 31)
Setting range (min. value | unit | max. value)Lenze setting
3126 3
; Read access ; Write access CINH PLC-STOP No transfer PDO_MAP_RX PDO_MAP_TX ; COM MOT
Parameter | Name:
C13900 | Firmware product type
Data type: VISIBLE_STRING
Index: 10675
= 29B3
d
Display of the product type (string with a length of 8 bytes)
The following identification code is displayed: "E94AFCPM".
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
h
h
h
C13901
C13902
Parameter | Name:
Data type: VISIBLE_STRING
C13901 | Firmware compilation date
Display of the compilation date of the firmware (string with a length of 20 bytes)
The date ("MMM DD YYYY") and time ("hh:mm:ss") are displayed, e.g. "Mar 21 2005 12:31:21".
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Parameter | Name:
Data type: VISIBLE_STRING
C13902 | Firmware version
Display of the firmware version (string with a length of 5 bytes)
Example: "01.21"
; Read access Write access CINH PLC-STOP No transfer PDO _MAP_RX PDO_MAP_TX COM MOT
Index: 10674
Index: 10673
= 29B2
d
= 29B1
d
h
h
100
Lenze · E94AYCPM communication module (PROFIBUS®) · Communication Manual · DMS 12.0 EN · 11/2012 · TD17
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.