information on specific
contents at the beginning and to the index at the end of the
Operating Instructions.
topics,
simply refer to the table of
These Operating Instructions use a series of different
provide quick reference and to highlight
This
Symbol
refers to items of information intended to facilitate
Operation.
Notes
which should be observed to avoid possible darnage to or
destruction
Notes
operating personnel.
of equipment.
which should be observed to avoid health risks to the
important
items.
Symbols
to
lenze
1
General safety and Operating Instructions for drive converters
in conformity with the Low-Voltage Directive 79/23/EEC
-
1. General
In operation, drive converters, depending on their
degree of protection, may have live, uninsulated, and
possibly also moving or rotating parts, as well as hot
surfaces.
In case of inadmissible removal of the required covers,
or improper use, wrong installation or maloperation,
there is the danger of serious personal injury and
damage to property. For further information, see
documentation.
All operations serving transport, installation and
commissioning as well as maintenance are to be carried
out by skilled technical personnel. (Observe IEC 364 or
CELEC HD 384 or DIN VDE 0100 and IEC 664 or
DINNDE 0110 and national accident prevention rules!)
For the purposes of these basic safety instructions,
“skilled technical personnel” means persons who are
familiar with the installation, mounting, commissioning
and operation of the product and have the qualifications
needed for the performance of their functions.
2. Intended use
Drlve converters are components designed for inclusion
in electrical installations or machinery.
In case of installation in machinery, commissioning of
the drive converter (i.e. the starting of normal operation)
is prohibited until the machinery has been proved to
conform to the provisions of the Directive 89/392/EEC
(Machinery Safety Directive - MSD). Account is to be
taken of EN 60204.
Commissioning (i.e. the starting of normal operation) is
admissible only where conformity with the EMC
Directive (89/336/EEC) has been established.The drive
converters meet the requirements of the Low-Voltage
Directive 73/23/EEC. They are subject to the
harmonized standards of the series prEN 50178/DIN
VDE 0160 in conjunction with EN 50439-1NDE 0660,
part 500, and EN 60146lVDE 0558.
The technical data as well as information concerning the
supply conditions shall be taken from the rating plate
and from the documentation and shall be strictly
observed.
3. Transport, storage
The instructions for transport, storage and proper use
shall be complied with.
The climatic conditions shall be in conformity with prEN
50178.
4. lnstallatlon
The installation and cooling of the appliances shall be in
accordance with the specifications in the pertinent
documentation.
The drive converters shall be protected against
excessive strains. In particular, no components must be
bent or isolating distances altered in the course of
transportation or handling. No cantact shall be made
with electronic components and contacts. Drive
converters contain electrostatic sensitive components
which are liable to damage through improper use.
Electric components must not be mechanically damaged
or destroyed (potential health risks).
5. Electrlcal connectlon
When working on live drlve converters, the applicable
national accident prevention rules (e.g. VB 4) must be
complied with.
The electrical installation shall be carried out in
accordance with the relevant requirements (e.g. cross
sectlonal areas of conductors, fusing, PE connection).
For further information, see documentation.
Instructions for the installation in accordance with the
EMC requirements, like screening, earthing, location of
filters and wiring, are contained in the drive converter
documentation. They must always be complied with,
also for drive converters bearing a CE marking.
Observance of the limit values required by EMC law is
the responsibility of the manufacturer of the installation
or machine.
6. Operation
Installations, which include drive converters shall be
equipped with additional control and protective devices
in accordance with the relevant applicable safety
requirements, e.g. Act respecting technical equipment,
accident prevention rules, etc. Changes to the drive
converters by means of the operating software are
admissible.
After disconnection of the drive converter from the
voltage supply, live applicance parts and power
terminals must not be touched immediately because of
possibly energized capacitors. In this respect, the
corresponding signs and markings on the drive
converter must be respected.
During operation, all covers and doors shall be kept
closed.
7. Maintenance and servicing
The manufacturer’s documentation shall be followed.
KEEP SAFETY INSTRUCTIONS IN A SAFE PLACE!
Please observe the product-specific safety and Operating Instructions stated in these Operating
Instructions.
Table
Planning
of contents
l Feiatures
2 Technical data
2.1 General data
2.2 Dimensions
2.3
2.4
Application
2.5 CE conformity
2.51 EC Low-Voltage
2.5.2
3 Application-specific
3.1 Applications with extreme overload, peak torque up to
230% of the rated motor torque
3.2 Applications with high overload, peak torque up to 170 % of
the rated motor torque
3.3 Applications with medium overload, peak torque up to
135 % of the rated motor torque
4 Handling
4.1 Mechanical installation
4.2 Electrical installation
4.2.1
4.22
4.2.:3
4.2.4 Switching on the motor side
of the 8600 series variant dancer-Position control
Scope
of delivery
as directed
Directive (73/23/EEC)
Electromagnetit
Motor
Installation in compliance with EMC
CE-typical drive
protection
Compatibility
controller selection19
System
(89/336/EEC)
9
11
11
12
12
13
14
15
16
19
20
21
22
22
23
24
24
25
27
5 Wiring
5.1 Power connections
5.1 .l Tightening torques of the power terminals
5.2 Control connections
52.1 Analog inputs and
52.2
Further
5.2.3 Description of the analog inputs and Outputs
5.2.4 Description of
5.2.5 Digital inputs and Outputs
5.2.6 Description of the digital iunputs and Outputs
5.2.7 Frequency output 6, fd
5.3 Operation with DC-bus supply
5.3.1 Connection of several drives
5.3.2 DC-voltage supply
5.4 Screenings
5.5 Grounding of control electronics
inputs and
Outputs
Outputs
further
inputs and Outputs
28
28
29
29
30
30
31
31
32
34
35
36
36
36
37
37
lenze
3
6 Accessories
6.1
Brake
resistors
6.1 .l Selection of the brake resistor
6.1.2 Technical data of brake resistors
6.2 Mains
6.2.1 Selection of the mains
6.2.2 Technical data of mains
6.3 Motorfilter
6.3.1 Technical data of motor filters
6.4 Sine filter
6.4.1 Technical data of sine filters
6.5
6.6
6.6.1 Ratings of
6.6.2 Technical data of
6.7 Accessories for digital frequency networking
7 Accessories for networking
7.1 Connecting module 211 OIB-
7.2 Connecting module
7.3 Connecting
7.4 Level
7.5 Adapter
8 Initial switch-on
Chokes
Gable protection
RFI
filters
RFI
elements
converter
FIS485
Choke
Chokes
filters
RFI
filters
InterBus-S
2130lB-
for
2101 IP- LECOM-NB
(LECOM
PROFIBUS
Optical
fibre cables-LECOM-LI53
interface
X6)
38
38
39
41
42
43
44
45
46
47
48
49
50
50
51
51
52
52
52
53
53
54
-
-
Parameter setting
1 Keypad
1.1 Key
1.2 Plain text display
2 Basic Parameter setting
2.1 Changing Parameters
2.1 .l
2.2 Save Parameters
2.3 Load Parameters
3 Basic settings
3.1
3.1 .I Controller enable
3.1.2
3.2 Configuration
3.2.1 Example of how to select a
3.3 Signal-flow
3.4 Features of
3.4.1
3.4.2 Digital frequency input
3.5 Features of
3.6 Offset and
3.7 Control mode
3.7.1 V/f-characteristic control
3.7.2 Io control
3.8 Minimum field frequency fdmin
3.9 Maximum field frequency fdmax
3.10
functions
Parameter setting by two
Operating mode
Quick stop / Select
Chart
for
Speed-controlled
(CO05
= -o- to
Setpoint
Acceleration and deceleration times Tir, Tif
-15)
setpoint
input with
setpoint
gain
adjustment
1
2
Codes
direction
master current
of rotation
configuration
Operation
55
55
55
56
56
58
58
58
59
59
60
60
62
63
64
66
66
69
68
68
69
70
72
73
73
74
-
4
lenze
4 Closed-loop speed control
4.1 Analog act. value
4.2 Digital act. value
4.3 Frequency
4.4 Adjustment of the act. value gain
4.4.1 Automatic adjustment
4.4.2 Manual adjustment
4.5 Setting of the controller Parameters79
4.6 Additional functions
5 Programming of the freely assignable inputs and
5.1 Freely assignable digital inputs
5.2 Functions of the freely assignable digital inputs
5.2.1 Set TRIP
52.2 Reset TRIP
5.2.3 DC-injection brake
5.2.4 JOG frequencies
5.2.5 Additional acceleration and deceleration times
4.3 Checking the voltage supply on the control board 8602MP
indication
Stage
Stage
Index
7
lenze
Planning
1
Features of the 8600 series
variant dancer-Position control
In addition to numerous
various functions
which
used for winding applications.
Another possibility is to activate a torque control.
For more detailed information
chapters
9 and
10.
Power Stage
lWide mains voltage range: 3 x 330 to 528V AC or
470 to 740V DC
lControllers with
.
4kHz
chopper
lOutput frequency up to
V/f-rated frequency up to 960Hz
lOverload
lOverload monitoring
.
Integrated brake transistor, external brake resistors in
capacity
enclosure as
lConnections for DC bus supply
Standard
functions, this variant offers
are required for a dancer-Position control
about
the
special
functions see
IGBTs,
protected against short circuits
frequency, adjustable up to
16kHz
480Hz,
up to 200% rated
tan
be set
current
for a short time
Option
IP20
Control Stage
.
Digital control unit with
lSimple Parameter setting and diagnosis using keypad and
line display in German, English, and
.
Parameter setting
l
Vif-characteristic
lHigh breakaway torque by magnetizing-current control
lConstant
lSpeed control using DC
lCurrent limitation with
lMotor overload monitoring via PTC input
lSerial
interface (RS232C/RS485)
Speed
control with linear or
due to
16-bit
during
Operation
Slip compensation
tacho
V/f
lowering for stall-protected Operation
microprocessor
French
language
Square
characteristic
or incremental
encoder
for external Parameter setting
and Operation
.
Field bus connecting
modules
as
Option tan
be integrated
two-
SpeciaI functions
lDancer-Position controller with speed and
diameter
evaluation
l
Diameter
lSoft insertion of the dancer-Position controller via ramp
generator or
lSensor compensator for fault and
lTorque control with
detection
multiplication
via analog input
with the main
Speed limitation
diameter
setpoint
corrections
function
Approvals
+
VDE 0160, VDE reg.-no. 86694
lUL 508, file no. 132659
(types
8602 to 8611)
-
-
2
Technical data
2.1
Mains voltage:
Output voltage:
Output frequency:
Chopper frequency:
Threshold of the integrated brake
chopper
Enclosure:
Ambient temperature:
Noise
Permissible
permissible
Influence of installation altitude on1000 m: 100% rated
the rated
General data
immun@
pollution
current:
3 x
46OV
Permissible voltage range:
(as alternative:
3 X 0
(V -
When using a mains
reduced to approx. 96% of the mains voltage.
The 8200 series consists of electrical devices which are designed
for application in industrial power installations.
The controllers are directed
-
as components for the control of variable
AC motors
-
for the installation into control cabinets or control boxes
-
as controllers for the installation of drive
The controllers comply with the
EC Low-Voltage Directive.
Drive Systems with 8600 controllers which are assembled
according to the requirements for CE-typical drive
chapter
The CE-typical drive
intended
-
-
The CE-typical drive Systems are not suited for the connection
to IT mains (mains without earth-potential reference)
the earth-potential reference of the RFI filter.
The controllers are not appliances but directed as components
to be assembled into drive Systems for industrial use.
The controllers themselves do not form machines for the
purpose of the EC Machinery Directive.
4.2.2) comply with the EC EMC Directive.
Systems
for the Operation at public and non-public mains
for the application in industrial, commercial and residential
areas
protection
with the 8600 controllers are
Speed
drives with
Systems
requirements of the
Systems
(see
because
of
lenze
13
2.5CE conformity
What is the purpose of EC directives?
EC directives are issued by the
for the determination of common technical requirements
(harmonization) and cet-tification procedures within the
Community. At the moment, there are 21 EC directives of product
ranges.
the member states. A certification issued by one member state is
valid automatically without any
states.
The texts of the directives are restricted to the essential
requirements. Technical details are or will be determined by
European
What does the CE mark imply?
After a verification, the conformity to the EC directives is
affixing a CE mark. Within the EC there are no commercial barriers
for a product with the CE mark. The enclosure of a conformity
cet-tification is not necessary according to most directives.
Therefore, the customer is not able to appreciate
EC directives applies to a product and
are considered in the conformity verification.
A drive
the Low-Voltage
Directive
The CE conformity of the installed
responsibility of the
Systems
conformity to the EMC
The directives are or will be
harmonized Standards.
controller
only general recommendations have been issued so far.
(see page
with the CE mark itself corresponds exclusively to
Directive.
User.
26ff),
Lenze has already proved the CE
Directive.
European
fut-ther
For the compliance with the EMC
For the
installation
Council and are intended
European
conver-ted
approval in all other member
which
machine
to national laws of
certified
which
of the 21
harmonized Standards
remains the
of CE-typical drive
by
What is the aim of the EMC
The EC
effective
disturbances or be affected by such disturbances.
The aim is the limitation of the generation of
disturbances so that the Operation of radio and telecommunication
Systems
immunity of the equipment against
ensured so that the Operation
What is the
The Low-Voltage
for use with a rated voltage between 50V and 1 OOOV AC and
between 75 and 1500V DC and
The use of e.g. electrical equipment in explosive atmospheres and
electrical
The
which
also be designed to
Directive
for “equipment”
and other equipment is possible and that a suitable
objective
does not endanger the safety of man or
relating to
objective
Parts
in passenger and goods lifts are excepted.
of the Low-Voltage
of the Low-Voltage
Directive
conserve
Directive?
Electromagnetit
which
may either
tan
be achieved.
is
effective
under
Directive
material
Compatibility is
Cause electromagnetic
electromagnetic
electromagnetic
for all electrical equipment
normal ambient conditions.
is to ensure that
assets.
disturbances is
Directive?
animals
is
placed
only
that electrical equipment
on the market. lt should
14
lenze
2.5.1
EC
Declaration
-
for the purpose of the
of
Conformity ‘95
EC Low-Voltage
amended by:
The
controllers
of the 8600 series were developed, designed, and
Directive (73/23/EEC)
CE mark directive
(93/68/EEC)
manufactured in compliance with the above-mentioned EC directive
under
the sole responsibility of
Lenze GmbH & Co KG, Postfach 101352, D-31763 Hameln
The compliance with the protective requirements of the above
mentioned EC directive was confirmed by the award of the
EMC
label
of the accredited test laboratory VDE Prüf- und
Zertifizierungsinstitut, Offenbach.
Standards and regulations considered:
DIN VDE 0160
5.88
+ Al
14.69
+ A2.110.66
prDIN
EN 50176
Classification
VDE0160/11.94
DIN VDE 0100
EN 60529
IEC 249 / 1 1 OB6
IEC 249 / 2-15 /
IEC 326 / 1
EN 60097 / 9.93
DIN VDE 0110
/l-2 /1/89 1201 EU90
12/89
IO/90
Electronie
Standards for the
Degrees of
Base
Printed circuits, printed boards
Creepage distances and clearances
equipment for use in electrical power
erection
of power installations
protection
material for printed circuits
VDE-
installation
Hameln,
lsnze
27/11/1995
15
2.5.2 EC
for the purpose of the EC
Declaration
of Conformity ‘95
Directive
relating to
Electromagnetit
amended by:First amended directive
The controllers of the 8600 series
Operation for the purpose of the regulation
compatibility (EMVG of
directive - of
integrating the
The controllers are directed to be installed in a machine or to be
assembled together with other components to form a machine or a
System. The controllers on their own are not machinery for the
purpose of the EC directive relating to machinery.
Until
the conformity of the machinery where the controllers are to
be installed with the regulations of the EC directive relating to
machinery is proved, commissioning of the controllers is prohibited.
Hameln,
27/11 0995
18
3
-
3.1
Application-specific controller selection
Applications with extreme overload,
peak torque up to 230% of the rated motor torque
--
For applications where a very extreme
overload torque are necessary (e.g. presses,
machines).
-
The controller provides 200% of the rated torque for
a maximum of 30s.
With cyclic overload, the ratio between overload to
cycle time must not exceed 0.2.
-
For these applications, the monitoring of the output
current
is set to
using the
(factory setting)
-
Please note that a maximum ambient temperature of
50°C is permissible.
Codes
Operation with rated power
Cl 19 and Cl20 (see page 82)
starting
and
drilling
r
8Eil5
-
hue
EVF8611-E-V009
EVF8614-E-V009
EVF13615-E-V00955.0110.0220.076.291.496.01270
19
3.2
Applications with high overload,
peak torque up to 170 % of the rated motor torque
-
For applications
overload behaviour of a controller (e.g. general
mechanical engineering, hoists, travelling drives,
calenders).
-
The controller provides 150% of the rated torque for
a maximum of 30s.
For cyclic overload, the ratio overload to cycle time
must not exceed 0.1.
-
For this
current
using the
-
Please note that a maximum ambient temperature
of 45°C is permissible.
TYQe
application,
is set to Operation with
Order no.
which
require a Standard
the monitoring of the output
increased power
Codes
Cl 19 and Cl20 (see page 82)
Rated
motor
power
kW
M,
Mt
~~
lncontrol
8606EVF8606-E-V009
6607EVF8607-EA'009
8608
EVF86IWE4'009
8609EVF8609-E-V009
8610EVF8610-E-V00922.0
8611EVF8611-E-V00930.0
8612EVF6612-E-V00937.0
7.5
11.0
15.0
18.5
-
-
20
3.3
Applications with medium overload,
peak torque up to 135 % of the rated motor torque
-
For applications where only a
overload torque are necessary (e.g. Ventilators,
w-w+
-
The
controller
provides 110% of the rated torque for
a maximum of 30s.
For cyclic overload, the ratio overload to cycle time
must not exceed 0.1.
-
For this
current
using the
-
Please note that a maximum ambient temperature
application,
the monitoring of the output
is set to Operation with
Codes Cl
19 and Cl20 (see page 82 )
of 40°C is permissible.
small
starting and
maximum power
M
MN
10control
EVF8606-E-V009
-
EVF8614-E-V009
l These data are valid for a maximum ambient temperature of
30°C.
x
Lenze
21
4
Handling
4.1
Mechanical installation
These frequency controllers must only be used as built-in
units.
Install
the controller
bottom.
Allow
a free space of
controllers 8612 . . . 8615 this free space must also be allowed
at both sides. Ensure unimpeded Ventilation of cooling air.
If the cooling air contains pollutants (dust,
grease,aggressive
functions,
separate air
If the controller is permanently subjected to Vibration or
to assembly and Service operations in the area of the
controller connections, the
installation
Personne1
must be free
of
electrostatic Charge.
These persons
fixing screw or another grounded metal
tan discharge
themselves by
part
touching
the PE
in the control
cabinet.
lAll control inputs and Outputs of the controller are mains-
isolated. The mains isolation has a
inputs and Outputs must be integrated into another
protection
against
direct
contact.
basic
insulation. The control
level
of
Use insulated operating elements, connect the mechanical
screw
fastener
of the
setpoint
potentiomenter (accessory kit)
with PE.
lUnused control inputs and Outputs must be protected with plugs
or the
covers
included in the delivery.
lWhen using current-operated protective equitpment:
-
The
-
controllers
As result, a DC-fault
are internally equipped with a mains rectifier.
current
may prevent the tripping of the
current-operated protective equipment after a short-circuit to
frame.
Therefore, we recommend additional measures such as
protective multiple
current-operated
-
When dimensioning the tripping
e.1.c.b.
please observe, that the capacitive leakage currents
between
cable screens
earthing
e.1.c.b.
and RFI
or universal-current sensitive
current
of current-operated
filters
may result in false
tripping.
lThe regulations
conductors must be observed. The
conductor must be at least as large as the
cable
connection.
lIn the
case
about
of
condensation,
the
minimum Cross section
Cross-section
Cross section
only connect the Controller vwhen
of PE
of the PE
of the
visible moisture has evaporated.
lBefore first switching-on of the controller check whether there is
an
earth
fault at the output side, if so, remove it.
which
occur
during
Operation will be detected, the controller will
be switched off and indicate the fault message
lThe internal
current
limitation
tan
be overloaded when
Earth
“OCl”.
faults
connecting or disconnecting the controller very often. With cyclic
mains connection, the Controller
tan
be switched on every 3
minutes.
lReplace
defective
fuses only with the specified type and when
no voltage is applied.
The controller remains live for up to 3 minutes after mains
disconnection.
hze
23
4.2.1 Motor protection
The units do not have a
For monitoring the motor temperature
tan
be used.
The connection possibilities are shown on page 28.
When using group drives, a motor protection relay is required for
each
motor.
When using motors which do not have a suitable insulation for
controller Operation:
-
Connect motor filters for protection (see page 45).
Please contact your motor manufacturer.
Please note:
These frequency controllers generate an output frequency of up to
480 Hz when set correspondingly. The connection of a motor which
is not suitable for this frequency may result in a hazardous
overspeed.
full
motor protection.
PTCs
orthermal contacts
4.2.2 Installation in compliance with EMC
-
lLenze has built up typical drives with these controllers and has
verified the conformity. In the following this
System
is called
“CE-typical drive system”.
If
you observe the
CE-typical drive
Problems
and you
pat-tially
System,
tan
easy measures for the
the controller will not
be sure to comply with the EMC
installation
Cause
of
any EMC
Directive.
lThe following configurations
-
The user himself
tan
their integration into the drive
tan
now be selected by the
determine the
System
System
components and
and is then held
User:
responsible for the conformity of the drive.
-
The user
tan
select the CE-typical drive
System
for which
the manufacturer has already proved the conformity.
For deviating installations, e.g.
-
use of unscreened cables,
-
use of group filters instead of the assigned RFI filters,
-
without mains
Choke
the conformity to the CE-EMC Directives requires a check of the
machine
or
System
regarding the EMC limit values.
The user of the machine is responsible for the compliance
with the EMC
Directive.
_-
24
4.2.3 CE-typical drive
-
Components of the CE-typical drive
System
sytem
-
Controller,
assembly board.
The
chapter
RFI
System
filter and mains
components are
Choke
are mounted on one
functionally
wired according to the
5, section: Planning of the Operating Instructions.
Installation of CE-typical drive Systems
The
electromagnetic
method and accuracy of the
compatibility of a
installation. Special care
machine
depends on the
must be
taken of:
l filters,
l
screens
l grounding.
and
Filters
Only use suitable mains filters and mains Chokes.
Mains filters reduce impermissible high-frequency disturbances to a
perrnissible value.
Mains
caused
Motor cables
Chokes
reduce low-frequency disturbances, especially those
by long motor cables.
which
are longer than 50 m must be protected
additionally (motor filter or sine filter).
Screens
All cables from and to
Lenze
System
cables meet these requirements.
Ensure that the motor
(Signal
cables and mains cables). Mains input and motor output
must not be connected to one terminal
Lay cables as
close
t3e controller
cable
is laid separately from the other cables
must be screened.
Strip.
as possible to the reference potential. Dangling
cables are like antennas.
Grounding
Ground
all metall-conductive components
mains Chokes) using suitable cables from a
Maintain the min.
regulations. For EMC, the
the
Cross
section.
Cross sections
surface
prescribed in the safety
of the contact is important, not
lmue
(controllers,
central Point
mains filters,
(PE bar).
25
Installation
lConnect the Controller, mains fitter, and mains
Choke
to the
grounded mounting plate. Zinc-coated mounting plates
permanent contact. If the mounting plates are painted, the paint
must be removed in
9
When using several mounting plates they
with as large surface as possible
lConnect the
Screen
every case.
must
(e-g.
using
of the motor cable to the
be connected
topper
bands).
Screen
connection
of the Controller and to the mounting plate of a surface as large
as possible. We recommend to use ground
metal mounting
surfaces
to connect the
clamps
Screen
to the mounting
on bare
plate with as large surface as possible,
allow
a
-
screened cable
If contactors, motor
protection
switches or terminals are located
urface
in the motor cable, the screens of the connected cables must
also be connected to the mounting plate with as
[arge
surface
as possible.
PE and the
box.
Metal
connection of the
Screen
should be connected in the motorterminal
cable glands at the motor
Screen
and the motor housing with as large a
terminaJ
box ensure a
surface as possible.
If
the mains cable between mains filter and Controller is longer
than 0.3 m, the cable must be screened. Connect the
the mains cable directly to the Controller
moduie
Screen
and to the
of
mains filter and connect it to the mounting plate with as large as
possible surface.
When using a brake resistor, the
cable
must
be directly connected to the
Screen
of the brake resistor
controller
and the brake
resistor and it must be connected to the mounting platte with a
surface
The control cables must be screened. Digital
as large as possible.
contra1
cables
must be screened at both ends. Connect the screens of the
contra! cables to the
leaving as
little
Screen
connections of the Controllers
unscreened cable as possible.
When using the Controllers in residential areas an additional
screening with a damping of Z 10 dß is required to
limit
the
noise emission. This is usually achieved by installation into
enclosed, grounded conrol cabinets or boxes made of metal.
26
Please note:
lIf units,
which
do not comply with the noise immunity EN
2 required by the CE, are operated next to the Controllers, an
electromagnetic
interference of these units is possible.
50082.
lenze
Part of the CE-typical drive
System
on mounting plate
-
LlLZ
L3 Connection mains fuse
Ll LZ
L3 Connection mains fuse
Paint-free bare metalPaint-free bare metal
^^^A^_, -...a----
, contact surfaces
Ill
I
-.
Conductive
connection between
mounting plate and
Cables between mains filterCables between mains filter
and controller longer than 0.3 m
PE connection
-
and controller longer than 0.3 m
must be screened
n.mmn,TA
Screened
control cables
/’ c’
I /’
6.’
,,
4.2.4 Switching on the motor side
Switching on the motor side is permissible for an emergency stop
as
weil
as
during
normal Operation.
Please note that when switched with the controller enabled, this
may
Cause
the fault message
long motor cables, the fault
capacitances
of the
device
tan become
is triggered. In these
to reduce the fault currents
OCl (shott circuitiearth
current
on the interfering cable
fault). For
so large that the short circuit monitoring
cases,
(See
a motor filter is
page 45).
necessary
Screened motor cable,
connect
Screen
also at the motor side,
large
cross-section
contact to the motor
housing required
to PE
kue
27
5
Wiring
5.1
Power connections
28
@
Gable
(3 M
(3>
Mains
@
Mains
All power terminals remain live up to 3 minutes after mains
disconnection!
protection
ains contactor
choke
filter
@ Brake
@
(3
[XI
resistor
Motor
Terminal
Screen connections at the
filterEine
cabinet
controller
filter
Strip
in the control
Loading...
+ 128 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.