LAARS Mighty Therm VW Installation Manual

Installation and Operation Instructions Document 2052D
Installation and Operation Instructions for
Mighty Therm
Model VW Sizes 2000-5000 Volume Water Heaters
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician, qualified in hot water heater installation and maintenance. Improper installation and/or operation could create carbon monoxide gas in flue gases which could cause serious injury, property damage, or death. Improper installation and/or operation will void the warranty.
WARNING
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency, or gas supplier.
H0147700D
Page 2
LAARS Heating Systems
TABLE OF CONTENTS
SECTION 1. General Information
1.1 Introduction...................................................3
1.2 Flow Requirements.......................................3
1.3 Water Chemistry...........................................4
SECTION 2. Installation
2.1 Heater Placement.........................................4
2.2 Indoor Installation .........................................4
2.2.1 Combustion Air Supply .................................4
2.2.2 Venting ......................................................... 5
2.3 Installation of Outdoor Heater ....................... 6
2.4 Gas Supply and Piping ................................. 6
2.5 Electrical Wiring............................................8
2.6 Water Piping of System ................................ 8
2.7 Water Expansion ..........................................8
2.8 Pump Installation ..........................................9
2.9 Tank Installation ........................................... 9
2.10 Water Pressure .......................................... 10
SECTION 3. Operation
3.1 Initial Start Up .............................................12
3.2 To Start Up System .................................... 12
3.3 To Turn Off Heater ..................................... 13
3.4 To Shut Down System ................................ 13
SECTION 4. Maintenance
................................................................... 13
SECTION 5. Troubleshooting and Analysis of Service Problems
................................................................... 14
SECTION 6. Conversion of VW from Indoor to Outdoor Models
6.1 Conversion Procedure ................................ 16
6.1.1 Section I...................................................... 16
6.1.2 Section II..................................................... 16
SECTION 7. Parts Description and Order Numbers
7.1 General Information.................................... 19
7.2 Parts List .................................................... 19
Mighty Therm Volume Water Heaters
Page 3
SECTION 1. General Information
WARNING
The Model VW Volume Water Heater must be installed in accordance with the procedures outlined in this manual. Warranty does not apply to heaters not installed or operated in accordance with these procedures. Consult local building and safety codes before proceeding with work. The installation must conform to the requirements of the authority having jurisdiction or, in the absence of such requirements, to the latest edition of the National Fuel Gas Code, ANSI Z223.1, and/or in Canada, CANI B-149 requirement.
When required by the authority having jurisdiction, the installation must conform to American Society of Mechanical Engineers safety code for controls and safety devices for automatically fired heaters No. CSD-1, and in Canada CGA 3.3. Any modification to the water heater, its gas controls, gas orifices, wiring or draft diverter may void the Laars warranty. If field conditions require such modifications, consult factory.
1.1 Introduction
This manual provides information for the installation and operation of Laars Volume Water
Heaters. It is strongly recommended that all application and installation procedures be reviewed completely before proceeding with the installation. Consult the factory, or local factory representative, with any problems or questions regarding this equipment. Experience has shown that most operating problems are caused by improper installation.
Model VW heaters are available from the factory in two configurations: An indoor version and an outdoor version. In addition, the heaters are field convertible. See Section 6 of this manual.
Some accessory items are shipped in separate packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage immediately upon delivery, and advise the carrier of any shortages or damage. Any such claims should be filed with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment whether visible or concealed.
1.2 Flow Requirements
All low volume hot water heaters must have continuous flow through the heat exchanger when firing for proper operation. The system pump must be capable of developing sufficient pressure to overcome the resistance of the heater plus the entire circulating system at the designed flow rate.
Figure 1 – Heater Configuration - Model VW.
OutdoorIndoor
Page 4
LAARS Heating Systems
1.3 Water Chemistry
Laars equipment is designed for use in a wide variety of water conditions. The water velocity maintained in the heat exchanger tubes is kept high enough to prevent scaling from hard water, and at the same time, low enough to avoid corrosion from soft water. Most of the urban areas in the country have water that is compatible with this equipment. In some areas a water supply will contain a heavy quantity of scaling chemicals, or the water may be extremely soft and corrosive. In rare situations, the water will contain both scaling chemicals and corrosive chemicals such as calcium, or sodium chloride. These conditions may be the result of a nearby well or pumping station, and the particular condition may not be characteristic of the entire city water system.
If an installer observes damage from these conditions to any water handling equipment in the area, a factory representative should be contacted immediately for assistance in minimizing maintenance costs. If erosion is present, the pump impeller can be replaced to reduce water velocity. If scaling conditions are bad, tube cleaning maintenance schedules can be established to prevent tube burn-out and cracking. Neglecting the problem could mean serious damage to the heater and water system.
Scaling can be recognized as a layer deposited on the inner walls of the tubes which reduces the inner diameter of the tube. Scale can be any color or texture; smooth or rough, granular or amorphous. Erosion is generally evidenced by pitting, cavitation, ridges and “islands” on the inner walls of the tubes. Where this condition results from extremely soft water sources, or as a result of a water softening program, the internal copper surfaces will be extremely shiny. Other chemicals, such as chlorine or chlorides in the water, will result in dark surfaces of erosion.
In areas where the water supply is extremely corrosive, it is advisable to order the heater with cupronickel tubes in the exchanger.
Damage from scaling, corrosion, or erosion is not covered by the warranty.
SECTION 2. Installation
2.1 Heater Placement
The heater must be placed to provide clearances on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces.
All heaters must be installed on a non­combustible flooring. Under no circumstances can heaters be installed on carpeting.
The National Fuel Code allows a heater to be placed on other than a non-combustible surface when such an installation complies with the local codes. This code specifies the surface under the heater be protected with hollow masonry no less than 4" thick, covered with sheet metal at least 20 gauge in thickness. Such masonry must be laid with ends unsealed, and joints matched in such a way as to provide a free circulation of air from side to side through the masonry (see Figure 2).
Base Must Extend Out Min. 12" On All Sides Of Heater Frame
Concrete Blocks Or Tile Min. 7" High With 3" Min. Air Openings
Blocks must provide solid base and be braced so they cannot slip out of place. Air openings in blocks must be arranged to provide unobstructed opening through entire width or length of base.
Figure 2. Non-Combustible Base.
Clearance Indoor Outdoor From (Inches) (Inches)
Top 24 — Water Conn. Side 24 24 Opposite Side 24 24 Front 48 48 Rear 24 24 Vent 6
Table 1 – Minimum Heater Clearances From
Combustible Surfaces.
Metal Plate 20 Ga. Min. Under Entire Heater
2.2 Indoor Installation
2.2.1 Combustion Air Supply
1. The heater location must provide sufficient air
supply for proper combustion, and ventilation of
the surrounding area as outlined in the latest
edition of ANSI standard Z223.1 and in Canada,
CAN1-B149 requirement, and any local codes
that may be applicable. Inadequate combustion
air supply may result in incomplete combustion
and consequent sooting of the heat exchanger
and unsafe operation of the heater.
Mighty Therm Volume Water Heaters
Page 5
2. In the United States, the most common requirements specify that the space shall communicate with the outdoors in accordance with method 1 or 2, which follow. Where ducts are used, they shall be of the same cross­sectional area as the free area of the openings to which they connect.
Method 1:
Two permanent openings, one commencing within 12" (30 cm) of the top and one commencing within 12" (30 cm) of the bottom of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors. When directly communicating with the outdoors directly, or through vertical ducts, each opening shall have a minimum free area of 1 square inch per 4000 Btu/hr (550 square mm/kW) of total input rating of all equipment in the enclosure. When communicating to the outdoors through horizontal ducts, each opening shall have a minimum free area of not less than 1 square inch per 2000 Btu/hr (1100 square mm/kW) of total input rating of all equipment in the enclosure.
Method 2:
One permanent opening, commencing within 12" (30 cm) of the top of the enclosure shall be permitted. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that directly communicate with the outdoors, and shall have a minimum free area of 1 square inch per 3000 Btu/hr (734 square mm/kW) of the total input rating of all equipment located in the enclosure. This opening must not be less than the sum of the areas of all vent connectors in the confined space.
Other methods of introducing combustion and ventilation air are acceptable, providing they conform to the requirements in the applicable codes listed above.
In Canada, Table 2 does not apply. Consult local building and safety codes or, in absence of such requirements, follow CAN/CGA B149.
3. Exhaust Fans or Vents: Any equipment which exhausts air from the heater room can deplete the combustion air supply or reverse the natural draft action of the venting system. This could cause flue products to accumulate in the heater room. Additional air must be supplied to compensate for such exhaust. The information in Table 2 is not applicable in installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualified engineers.
Indoor Each Opening* Size (Square Inches)
2000.......................................................... 500
2450.......................................................... 613
3050.......................................................... 763
3500.......................................................... 875
4050......................................................... 1013
4500......................................................... 1125
5000......................................................... 1250
Net Free Area in Square Inches*
*Area indicated is for one of two openings; one at floor level and one at the ceiling, so the total net free area would be double the figures indicated. For all other conditions, refer to latest edition of ANSI Bulletin Z223.1.
Note: Check with louver manufacturers for Net Free Area of louvers. Correct for screen resistance to the Net Free Area if a screen is installed. Check all local codes applicable to combustion air.
Table 2– Minimum Recommended Air Supply
To Heater Room.
4. If a blower or fan is used to supply air to the heater room, the installer should make sure it does not create drafts which could cause nuisance shutdowns of the pilot. If a blower is necessary to provide adequate combustion air to the heater, a suitable switch or equivalent must be wired into the heater control circuit to prevent the heater from firing unless the blower is operating.
5. The heater must be completely isolated and protected from any source of corrosive chemical fumes such as emitted by trichlorethylene, perchlorethylene, chlorine, etc.
2.2.2 Venting
1. Laars heaters have built-in draft diverters for natural draft operation and must not be connected into any portion of a mechanical draft system under positive pressure. The flue outlet must be connected to a clear, unobstructed vent of adequate capacity terminating above the highest point of the building with an approved vent cap. The venting system should be installed according to the latest edition of ANSI Z223.1 and any local codes having jurisdiction, and/or in Canada follow CAN1-B149 standard.
Important Note: Do not use sheet metal screws
at the snap lock joints of Type B gas vents.
2. Do not weld or fasten the vent pipe to the heater draft hood. The weight of the stack must not rest on the heater. The draft hood and heater top must be easily removable for normal heater service and inspection.
Page 6
LAARS Heating Systems
Control Wiring for Draft Fan
Figure 3. Draft Inducer/Power Venter.
3. Avoid long horizontal runs of the vent pipe, and too many 90° elbows, reductions and restrictions. Horizontal runs should have at least a 1/4" rise per foot in the direction of flow. A vent connector shall be supported for the design and weight of the material employed to maintain clearances and prevent physical damage and separation of joints.
4. Avoid terminating heater vents near air conditioning or air supply fans. The fans can pick up exhaust flue products from the heater and return them inside the building, creating a possible health hazard. A minimum of 4 feet horizontal distance must be maintained from electric meters, gas meters, and relief equipment.
5. Always use double-wall or insulated vent pipe (Type B or equivalent). In cold weather, uninsulated outside vents can chill the rising flue products, blocking the natural draft action of the venting system. This can create a health hazard by spilling flue products into the heater room.
6. Avoid oversize vent piping or extremely long runs of the pipe which may cause excessive cooling and condensation. Rule of Thumb: The total length of the vent, including the connector and any offset, should not exceed 15 feet for every inch of vent diameter. Longer total lengths shown in venting tables are based on maximum capacity, not condensation factors.
7. When the installation of a draft fan is necessary in the venting system to which a Laars heater is to be connected, the installation should be engineered by competent personnel following good engineering practices. The draft fan supplier should be consulted for correct size. The installation should be in accordance with the latest edition of ANSI Z223.1 and any local codes having jurisdiction. In Canada follow CAN1-B149 standard. When a draft fan is installed, a suitable draft switch must be used
and wired into the heater control circuit at terminal designated “Field Interlock,” to prevent firing of the heater unless a positive draft has been established (see Figure 3).
2.3 Installation of Outdoor Heater
Caution
Outdoor installations are not recommended in areas where the danger of snow blockage exists.
1. Standard outdoor units are shipped with two vent stacks and vent caps that must be installed on the vent outlets.
2. Locate the heater to provide the minimum clearances as listed in Section 2A, “Placement of Heater.”
3. Do not locate the heater in an enclosure or wall recess. Avoid location where wind deflection off structures might cause down draft. When such wind conditions are possible, locate the heater at least three (3) feet from the structures.
4. Never install the heater under any kind of roof overhang. Do not locate the heater below or adjacent to any doors, windows, louvers, grills, etc. which communicate in any way with an inhabited area of a building. Even though such communication might be through another structure such as a garage or utility room (see Figure 4).
Figure 4. Incorrect Outdoor Installation.
2.4 Gas Supply and Piping
Review the following instructions before
proceeding with the installation.
1. Verify that the heater is fitted for the proper type of gas by checking the rating plate. Laars heaters are normally equipped to operate below a 2000 foot altitude. Heaters equipped to operate at higher altitudes have appropriate stickers or tags attached.
Mighty Therm Volume Water Heaters
Page 7
2. Use the figures in Table 3 to provide adequate gas piping (check local code for BTU capacity required). See Table 4.
3. A trap (drip leg) must be provided ahead of the gas controls (see Figure 5). Where required by code, provide a second manual gas shutoff valve. Do not remove manual valve furnished with the heater.
4. The heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig. The heater must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig.
Distance from Gas Meter or Last Stage Regulator
Indoor
Outdoor
Size
Size
2000 –– 2-1/2 2 3 2-1/2 3 3 2450 2200 3 2-1/2 3 2-1/2 3-1/2 3 3050 2800 3 2-1/2 3-1/2 3 3-1/2 3 3500 3200 3 2-1/2 3-1/2 3 4 3-1/2 4050 3600 3-1/2 3 4 3-1/2 4 3-1/2 4500 4000 3-1/2 3 4 3-1/2 5 4 5000 4500 4 3-1/2 4 3-1/2 5 4
NOTES:
These figures are based on 1/2" water column pressure drop.
Check supply pressure and local code requirements before proceeding with work.
Pipe fittings must be considered when determining gas pipe sizing.
0-100' 100-200' 200-300'
Nat. L P Nat. L P Nat. LP
5. Provide gas supply pressure to the heater as follows:
Natural Gas LPG
Min. (inches water column) 7 11 Max. (inches water column) 9 14
Note: The heater and all other gas appliances
sharing the heater gas supply line must be firing at maximum capacity to properly measure the inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.
6. The correct burner manifold gas pressure is stamped on the rating plate. The regulator is pre­set at the factory, and normally requires no further adjustment.
7. The gas manifold and control assembly was tested and conform to the safe lighting and other performance criteria specified in the latest editions of ANSI Z21.13 and CGA 3.3 Low Pressure Heater Standard.
8. Before operating the heater, the complete gas supply system and all connections must be tested for leaks using a soap solution. Do not use raw flame.
Caution
Since some leak test solutions, including soap and water, may cause corrosion or stress cracking, the piping must be rinsed with water after testing, unless it has been determined that the leak test solution is noncorrosive.
Arrangement of gas train components for on-off,
2-stage and 4-stage firing are shown schematically in the Gas Piping Diagram (see Figure 6).
Table 3. Gas Line Selection Chart For
Natural and Propane Gas.
Figure 5. T-Fitting Sediment Trap Installation.
* Standard on sizes 3050-5000 ** Sizes 2000 & 2450 use one pilot gas valve
Figure 6. Typical Gas Piping Diagram.
Page 8
r
LAARS Heating Systems
2.5 Electrical Wiring
Electrical diagrams are included with the packet
provided with each unit.
WARNING
The heater must be electrically grounded in accordance with the most recent edition of the National Electrical Code and ANSI/NFPA 70 , and in Canada, follow Canadian Electrical Code CSA C22.1. Do not rely on the gas or water piping to ground the metal parts of the heater. Many times, plastic pipe or dielectric unions isolate the heater electrically. Service and maintenance personnel who work on or around the heater may be standing on wet floors and could be electrocuted by a poorly grounded heater.
1. Check heater wiring and pump for correct voltage, frequency and phase. If the pump circuit is other than 115V, check to see that the heater is provided with an appropriate transformer.
2. Wire the heater and pump exactly as shown in the wiring diagram supplied with the heater.
3. The pump and heater must be electrically interlocked so the heater cannot come on unless the pump is running.
4. All field installed electrical safety devices and all field installed devices (draft switches, relays, timers, outdoor temperature reset devices, etc.) can be connected to the heater wiring at points shown in the wiring diagram designated “Field Interlock.”
2.6 Water Piping of System
1. Be sure to provide valves at the inlet and outlet to the heater so it can be readily isolated for service.
A butterfly or similar type of valve is recommended.
2. The pressure relief valve must be installed in the tapped opening provided in the heater header, or on the "T" connection on the heater outlet side, with its outlet piped but not fastened to a drain
or floor sink. Special attention must be given to relief valve settings in installations where the heater is located on the ground floor of a tall building. In both instances, the static pressure of the system is elevated, and could cause the relief valve to leak. Where no special setting of the relief valve is ordered, the factory will furnish a 125 psi setting. Never reduce the relief valve opening. If necessary, install the relief valve in a Tee immediately past the heater outlet.
3. The weight of all water and gas piping should be supported by suitable hangers or floor stands.
4. Check piping diagrams with local applicable plumbing, heating and building safety codes.
5. All two-temperature systems using temperature valves must have forced recirculation in the low temperature building loop.
6. A check valve installed at the hot water inlet to the tempering valve will prevent cold water from being drawn in reverse through the tempering valve into the hot water.
7. When installing a tempering valve, locate it at the bottom of the antithermosyphon loop at least 24" high to prevent excessive hot water from entering the mixed water supply (see Figure 7). Bring the cold water supply up from the floor to the valve.
8. Keep thermometer bulbs in moving water. Use of a bushing will cause temperature readings to be off 10° or more (see Figure 8).
9. Insulate all pipes containing hot water, especially in unheated areas. Sizing charts assume this condition exists. Excessive heat loss of exposed piping adds to gas consumption and could result in insufficient hot water during peak demand periods. If pipes are uninsulated, a larger heater must be used.
2.7 Water Expansion
When cold water is heated, it expands. If no
water is being used during the heat-up period, the expanded water will normally back up into the city mains.
Hot Water
Hot Water Storage Tank
Figure 7. Tempering Valve Installation. Figure 8. Thermometer Bulb.
Floor
Tempered Water
24"
Automatic Tempering Valve
Right Wrong
Cold Wate
Loading...
+ 16 hidden pages