KROHNE IFC-210E User Manual

Condensed Instructions
IFC 210 E IFC 210 E-EEx
Signal converters for electromagnetic flowmeters
©
KROHNE 05/2002 7.10006.11.00
Operating and check elements
No. 3.18393.01
Amplifier (ADC)
No. 3.17116.01
Outputs/inputs (I/O)
No. 3.19005.01
Contents
1 Electrical connection: Power Pages 2-11 2 Electrical connection: Outputs Pages 12-18 3 Start-up Pages 19 4 Operator control of signal converter Pages 20-27
PLEASE NOTE
These concise instructions do not include the following: device description, technical data, standards, approvals, etc., nor conditions pertaining to product liability and warranty.
The operator is, however, obligated to take note of these sections in the detailed Installation and Operating Instructions.
References to chapters
All references to chapters in these Condensed Instructions refer to those of the detailed “Installation and Operating Instructions”. It is important that the detailed Instructions be referred to for all chapters omitted from these Condensed Instructions. This particularly concerns installation and operation in hazardous areas!
Sect. 1.1 Part A System installation and start-up
1 (OHFWULFDOFRQQHFWLRQSRZHUVXSSO\
1.1 Location and important installation notes
Electrical connection in accordance with VDE 0100
installations with line voltages up to 1000 V” or
Do not cross or loop
separate cable
Use outputs and inputs.
Protect flowmeters or switchgear cabinets with built-in devices from direct sunshade if necessary.
installed in switchgear cabinets
When use fans or heat exchangers. (dust-free air and no aggressive gases)
Do not expose signal converters to intense
distance between primary head and signal converter
Keep Sect. 1.3.4 for maximum permissible length of signal and field current cables.
Use the supplied KROHNE optional
Always ensure head. If the GK is not identical, set the signal converter to the GK of the primary head. Refer also to Section 4.
Dimensions of signal converter,
signal cable B
calibrate
primary constant GK is identical
IMPORTANT!
For EEx versions, also pay regard to all special directions included in Sect. 6.1 and 13.
Only the EEx primary head may be installed in the hazardous area. The signal converter must be installed outside the hazardous area!
cables
.
entries (see below) for power supply, field current cables, signal lines,
signal cable A
(Type BTS).
primary head and signal converter
refer to Section 10.4.
equivalent others national regulations
, signal converters must be adequately cooled, e.g.
vibration
(Type DS), standard length 10 m (33 ft), or
; refer to instrument nameplate for the primary
”Regulations governing heavy-current
.
together
sunlight
as short as possible. Refer to
. Therefore, when installing,
. Fit a
.
2 IFC 210 E
05/2002
Part A System installation and start-up Sect. 1.2
1.2 Power supply - Electrical connection
PLEASE NOTE !
Rated values: The flowmeter housings meets the requirements of IP 20 in conformity with EN 60529. No protection against water and moisture. If necessary, take appropriate protective measures. The selected creepage distances and clearances have been dimensioned in conformity with VDE 0110 and IEC 664 for contamination category 2. Supply circuits and output circuits are designed to meet the standards of overvoltage class II.
Fuse protection, disconnecting device: fuse protection for the feeding power circuit, and also a disconnecting device (switch, circuit breaker) for isolating the signal converters must be provided (see also Sect. 1.3.5).
Power supply 100-230 V AC (Tolerance zone: 85-255 V AC)
Note information on instrument nameplate: supply voltage and frequency
Connection diagrams for electrical connection between primary head and signal converter: refer to Section 1.3.5.
Power supply 24 Volt AC / DC (Tolerance zone: AC 20.4 - 26.4 V / DC 18 - 31.2 V)
Note information on instrument nameplate: supply voltage and frequency
For measurement reasons, connect an FE functional ground conductor.
If connected to a functional extra-low voltage source (24 V AC / DC, 48 V AC), provide for protective separation (PELV) in conformity with e.g. VDE 0100 / VDE 0106 or IEC 364 / IEC 536, or equivalent national regulations.
Connection diagrams for power supply and electrical connection between primary head and signal converter: refer to Section 1.3.5.
IMPORTANT!
For EEx versions, also pay regard to all special directions included in Sect. 6.1 and 13.
Only the EEx primary head may be installed in the hazardous area. The signal converter must be installed outside the hazardous area!
IFC 210 E 3
05/2002
Sect. 1.3.1 Part A System installation and start-up
1.3 Electrical connection of separate primary heads
1.3.1 General remarks on signal lines A and B and field current line C
Proper operation of the equipment is ensured when KROHNE signal lines A and B are used with foil screen and magnetic shield.
Signal lines must be firmly installed.
Shields are connected via stranded drain wires.
Underwater or underground routing is possible.
Insulating material flame-retardant to IEC 332.1 / VDE 0742.
Low-halogen, unplasticized signal lines which remain flexible at low temperatures.
Signal line A (type DS) with double shielding
1 Stranded drain wire, 1st shield, 1.5 mm 2 Insulation
3 Stranded wire 0.5 mm2 (3.1 red/3.2 white) 4 Special foil, 1st shield 5 Insulation 6 Mu-metal foil, 2nd shield 7 Stranded drain wire, 2nd shield, 0.5 mm2 8 Outer sheath
Signal line B (type BTS) with triple shielding (bootstrap line)
1 Dummy glider wire 2 Insulation (2.1 red/2.2 white) 3 Special foil, 1st shield (3.1/3.2) 4 Insulation (4.1/4.2) 5 Stranded wire 0.5 mm 6 Stranded drain wire, 1st shield, 0.5 mm2 (6.1 / 6.2) 7 Special foil, 2nd shield 8 Stranded drain wire, 2nd shield, 1,5 mm2 9 Insulation 10 Mu-metal foil, 3rd shield 11 Stranded drain wire, 3rd shield,, 0,5 mm2 12 Outer sheath
Field current line C
Line 2 × 0,75 mm2, 2 × 1,5 mm2 or 4 × 1,5 mm2Cu, single shielding (Cu = copper cross section) The cross section depends on the required cable length, see table in Section 1.3.4.
IMPORTANT!
For EEx versions, also pay regard to all special directions included in Sect. 6.1 and 13.
Only the EEx primary head may be installed in the hazardous area. The signal converter must be installed outside the hazardous area!
2
2
(5.1 red/5.2 white)
4 IFC 210 E
05/2002
Part A System installation and start-up Sect. 1.3.2
1.3.2 Stripping (preparation) of signal cables
Please note: The numbers in the drawings designate the stranded drain wires of signalling cables
A and B, see sectional drawings in Sect. 1.3.1.
primary head Converter
Length primary head Length Converter
mm inch mm inch a 90 3.60 a 40 2.80 b 8 0.30 b 10 0.30 c 25 1.00 d 8 0.30 d 5 0.30 e 70 2.80 e 20 2.00
Signal cable A (type DS),
double shielding
for primary head
Signal cable A (type DS),
double shielding
for IFC 210 E Converter
Signal cable A
bending radius
bending radius
50 mm (≥ 2”)
50 mm ( 2”)
Signal line B (type BTS),
with triple shielding (bootstrap)
for primary head
Signal cable B
bending radius
bending radius
50 mm (≥ 2”)
50 mm ( 2”)
Customer-supplied materials V Tin-coat all stranded drain wire ends! W Insulation tubing (PVC), Ø 2.0-2.5 mm (Ø 1”) X Heat-shrinkable tubing or cable sleeve Y Wire end sleeve to DIN 41 228: E 1.5-8 Z Wire end sleeve to DIN 41 228: E 0.5-8
Signal line B (type BTS),
with triple shielding (bootstrap)
for IFC 210 E Converter
IFC 210 E 5
05/2002
Sect. 1.3.3 Part A System installation and start-up
1.3.3 Grounding of primary head
All flowmeters must be grounded.
The grounding conductor should not transmit any interference voltages.
Do not ground any other electrical device together with this conductor.
The primary head is connected to ground by means of an FE functional ground conductor.
Special information on grounding various primary heads is contained in the separate installation instructions for primary heads.
These instructions also contain detailed descriptions on how to use grounding rings and how to install primary heads in metal or plastic pipes or internally coated pipelines.
IMPORTANT!
For EEx versions, also pay regard to all special directions included in Sect. 6.1 and 13.
Only the EEx primary head may be installed in the hazardous area. The signal converter must be installed outside the hazardous area!
1.3.4 Cable lengths (max. distance between signal converter and primary head) Abbreviations and explanatory notes
used in the following tables, diagrams and connection diagrams A Signal cable A (type DS), with double shielding, see diagram A for max. length B Signal line B (type BTS) with triple shielding, max. length see diagram B C Field current cable min. cross-section (AF) and max. length, see Table D High-temperature silicone cable, 3 × 1.5 mm
2
(14 AWG) Cu, (with single shielding,
max. length 5 m (16 ft)
E High-temperature silicone cable, 2 × 1.5 mm
2
(14 AWG) Cu, max. length 5 m (16 ft)
Cross section of field current line C in Cu, see table
A
F
L Cable length
Electrical conductivity of the process liquid
κ
ZD Intermediate connection box required in connection with cables D and E for primary heads
ALTOFLUX IFS 4000 F, PROFIFLUX IFS 5000 F and VARIFLUX IFS 6000 F in cases where process temperatures exceed 150 °C (302 °F)
6 IFC 210 E
05/2002
Part A System installation and start-up Sect. 1.3.4
Recommended length of signal cable A (Type DS) and B (Type BTS)
Primary head Meter size Signal cable
DN mm inch A B AQUAFLUX F 10 - 1600 ECOFLUX IFS 1000 F 10
- - 15
25 ALTOFLUX IFS 2000 F 150 - 250 6 - 10 A1 B1 ALTOFLUX IFS 4000 F 10
200 - ­PROFIFLUX IFS 5000 F 2.5
- - 15
25 VARIFLUX IFS 6000 F 2.5 - 15
25 - 80 1 - 3 A2 B2
ALTOFLUX M 900 10 - 300
150
150
1600
100
3
/8 - 64 A1 B1
3
/
- - ½
8
1
3
/
8
8
1
/
10
1
1
/10 - ½ A4 B3
3
/8 - 12 A1 B1
6
- - 6 64
- - ½
4
A4 A3
A2 A1
A4 A2
B3 B2
B2 B1
B3 B2
Diagram A Diagram B
Field current cable C
Length L Cross section AF (Cu), minimum
0 – 150 m 5 – 500 ft 2 x 0.75 mm2 / 2 × 18 AWG 150 – 300 m 500 – 1000 ft 2 x 1.50 mm2 / 2 × 14 AWG 300 – 600 m 1000 – 1900 ft 4 x 1.50 mm2 / 2 × 12 AWG
IFC 210 E 7
05/2002
Sect. 1.3.5 Part A System installation and start-up
1.3.5 Connection diagrams for power supply and primary head PLEASE NOTE: Undocumented contacts/terminals to remain unwired.
The figures in brackets indicate the stranded drain wires for the shields (see cross-sectional drawing of signal cable in Section 1.3.1).
Electrical connection to VDE 0100 "Regulations governing heavy-current installations with line voltages up to 1000 V" or equivalent national regulations.
24 V AC / DC power supply:
Functional extra-low voltage with protective separation in conformity with VDE 0100, Part 410 or equivalent national regulations (IFC 020 E: 24 V DC in preparation).
Fuse protection of the feed line circuit with I
≤ 16 A is required. Also, a disconnecting
RAT
device (switch/circuit breaker) must be provided in the vicinity of the solidly connected signal converters or device groups, refer to EN 61 010. This disconnecting device must be easy to reach and also identifiable as such.
Contacts 2d, 2z, 4d, 4z of
*
XA must be electrically
connected.
Connection to 8d and/or
**
8z of XA.
Contacts d2 to d32 of XB
***
are of leading type, for connection of PE (safety conductor) or FE (functional ground). At least 4 contacts with adequate cross-section to be electrically connected.
Important:
Electrical connection of EEx primary heads and EEx signal converters To be carried out as described in Sect. 1.3.6.
8 IFC 210 E
05/2002
Part A System installation and start-up Sect. 1.3.5
I Signal cable A (type DS) II Signal cable B (type BTS)
IFC 210 E IFC 210 E
Process temperature < 150°C (302°F)
Primary head Primary head
III Signal cable A (type DS) IV Signal cable B (type BTS)
IFC 210 E IFC 210 E
Process temperature > 150°C (302°F)
Primary head Primary head
IFC 210 E 9
05/2002
Loading...
+ 18 hidden pages