4.9 Proportional Integral Derivative Block (PID) ................................................................. 68
5 Notes82
2
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
1.1 Scope of the document
These instructions are supplementary to the standard product documentation of the signal
converter. The details depicted therein, in particular the safety information are valid and should
be adhered to. The present supplementary instructions provide additional information for the
devices when being operated and connected to a Foundation Fieldbus.
INFORMATION!
The present supplementary instruction for the signal converter with Foundation Fieldbus
interface, plus the software with the DD and CCF files are included in our scope of supply, in
addition to those items delivered for the standard device.
1.2 Device description
The ultrasonic flowmeters are designed exclusively for the continuous measurement of actual
volume flow, mass flow, molar mass, flow speed, velocity of sound, gain, SNR and diagnosis
value.
Your measuring device is supplied ready for operation. The factory settings for the operating
data have been made in accordance with your order specifications.
SAFETY INSTRUCTIONS 1
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
3
2 TECHNICAL DATA
2.1 Foundation Fieldbus data
Description
TypeUltrasonic flowmeter
Physical layerFoundation Fieldbus protocol that agrees with IEC 61158-2 and FISCO model;
galvanically isolated
Communication standardH1
ITK version5.2
Data blocks
Function blocks1 x Enhanced Resource Block (RB)
1 x Customer Transducer Block Main (TB)
1 x Customer Transducer Block Auxiliary (TB)
1 x Customer Transducer Block Special (TB)
6 x Analog Input Block (AI)
2 x Integrator Block (IT)
1 x Proportional Integral Derivate Block (PID)
1x Arithmetic Block (AR)
Execution timeAnalog Input Block: 10 ms
Integrator Block: 15 ms
Proportional Integral Derivate Block: 25 ms
Arithmetic Block: 20 ms
GFC 300
Electrical connections
Device power supplyNot intrinsically safe: 9...32 VDC
Intrinsically safe: 9...24 VDC
Basic current10.5 mA
Maximum error current16.5 mA (= basic current + error current = 10.5 mA + 6 mA)
Start current after 10 ms14 mA
Polarity sensitivityNo
Minimum cycle time250 ms
4
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
3.1 Cable types
The cable types are specified according to IEC 61158-2. Shielded cables offer the advantage of
malfunction-free operation with adequate protection against electromagnetic influences, and
make it possible to employ the full performance of the Foundation Fieldbus system.
ELECTRICAL CONNECTIONS 3
Core cross-section
Cable typeAAAABBBBCCCCDDDD
Max. length
incl. branch line
0.8 mm2 or
AWG 18
twisted pair,
individually
shielded
1900 m / 6200 ft1200 m / 3900 ft400 m / 1300 ft200 m / 650 ft
0.32 mm2 or
AWG 22
individual or
multiple twisted
pairs with overall
shield
0.13 mm2 or
AWG 26
multiple twisted
pairs, without
shielding
1.25 mm2 or
AWG 16
multiple nontwisted cables,
without shielding
In non-hazardous areas the maximum number of field devices is limited to 32. For detailed
information refer to the following table.
In non-hazardous areas the ignition protection class of the devices and the limited electric power
available limit the number of field devices to 4.
Number of devicesCable lengths for number of devices per branch line
1 device2 devices3 devices4 devices
25...321m/ 3.3ft1m/ 3.3ft1m/ 3.3ft1m/ 3.3ft
19...2430 m / 100 ft1m/ 3.3ft1m/ 3.3ft1m/ 3.3ft
15...1860 m / 200 ft30 m / 100 ft1m/ 3.3ft1m/ 3.3ft
13...1490 m / 300 ft60 m / 200 ft30 m / 100 ft1m/ 3.3ft
1..12120 m / 400 ft90 m / 300 ft60 m / 200 ft30 m / 100 ft
All bus segments must be fitted with a terminator at both ends.
3.2 Shielding and grounding
• For optimum electromagnetic compatibility of systems it is extremely important that the
system components, and particularly the bus cables connecting the components, are
shielded and that such shields - if possible - form an unbroken cover.
• Hence, it follows that, for use in non-hazardous duty systems, the cable shield should be
grounded as often as possible.
• In Ex systems an adequate equipotential bonding in the hazardous and non-hazardous
location along the entire Fieldbus installation is strongly recommended. Multiple grounding
of the shield is of advantage.
INFORMATION!
The use of twisted and shielded cables is strongly recommended, otherwise EMC protection of
the signal converter cannot be assured.
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
5
3 ELECTRICAL CONNECTIONS
3.3 Electrical connection of FOUNDATION Fieldbus
INFORMATION!
The wiring between the device and the FOUNDATION Fieldbus cable is independant of polarity.
The signal converter FOUNDATION Fieldbus interface will operate only if the additional power
supply for the device is connected/available.
For a detailed description of the electrical connections please refer to the standard signal
converter handbook.
Connection to a spur
or
GFC 300
Connection to a trunk
1 e.g. incoming data lines
2 e.g. outgoing data lines
or
6
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
3.4 Topology of FF networks
An example of mixed topology of FF networks is shown in the following example.
Connection is best made via short branch cables and T connectors. This connection type makes it
possible to connect and disconnect the devices without interrupting the bus or the
communication.
ELECTRICAL CONNECTIONS 3
1HSE network
2H1 bus
3Intrisically safe, explosive area
B1+B2Bridge = coupling element for H1 bus
and HSE network
D1-D3Device = field devices, own power
supply, for non potentially explosive
areas
D4-D6Intrinsically safe devices, external
power supply, for potentially explosive
areas
I.S.Intrinsically safe barrier
JBJunction box for field devices
PSPower supply
Switch = connection of multiple HSE
sub networks
TTerminator
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
7
4 OPERATION
GFC 300
4.1 Settable functions
• For Foundation Fieldbus the totalizers of the signal converter are not available!
• The following tables describe only the menus, functions and parameters that are different
between the standard signal converter and the Foundation Fieldbus signal converter.
• For the electrical connections of the outputs, inputs and all settings of functions that are not
listed in the following tables refer to the standard product documentation.
No.Displayed textDescription and settings
A quick setup
A2TagIdentifier for the measurement in a plant, appears in the display header
B test
B3.5Foundation fieldbusDisplay information about Foundation fieldbus interface.
(maximum 8 digits).
Note: Only read, not changeable!
C setup
C5.1.1TagIdentifier for the measurement in a plant, appears in the display header
C3TotalizerNot available for Foundation Fieldbus devices!
C4I/O HARTNot available for Foundation Fieldbus devices!
C5.42. meas. pageIn case of Foundation Fieldbus device, the second measurement page is
C5.4.1measurement 1.lineSelect: AI1...6 analog inp. / PID / INT1..2 integrator / AR
C5.4.2format 1.lineFixed number of digits after the decimal point or automatic, where the
C5.4.3measurement 2.lineSelect: AI1...6 analog inp. / PID / INT1..2 integrator / AR
C5.4.4format 2.lineFixed number of digits after the decimal point or automatic, where the
C5.4.5measurement 3.lineSelect: AI1...6 analog inp. / PID / INT1..2 integrator / AR
C5.4.6format 3.lineFixed number of digits after the decimal point or automatic, where the
C5.8Foundation Field-
C5.8.1SimulateSelect: disabled / enabled
C5.8.2InformationDisplay information about hardware and software versions, the calibration
(maximum 8 digits).
Note: Only read, not changeable!
meant to check the output values of the different function blocks. Only
Foundation Fieldbus values can be selected here. The analogue inputs are
shown with exactly the value, seen on the bus system.
number of digits is automatically adjusted to the available space.
number of digits is automatically adjusted to the available space.
number of digits is automatically adjusted to the available space.
and test date of this interface.
8
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
4.2 Description of the FF block system
The Foundation Fieldbus is a Local Area Network (LAN) for connecting field devices like sensors
and actuators. One of the main benefits of Foundation Fieldbus is line saving in comparison to
the traditional 4...20 mA technology.
The different device functions are implemented in a block-based scheme within a user
application. In this block scheme, a distinction is made between the Resource Block, Transducer
Block and Function Block.
OPERATION 4
1 Resource Block (RB)
2 Transducer Block (TB)
3 Function Block (FB)
4 Device FF communication
5 Foundation Fieldbus
4.3 Used abbreviations
AIAnalogue Input BlockBLKBlock mode
ARArithmetic BlockMAN Manual mode
ITIntegrator BlockMixMix mode (R, W and R/W)
PIDProportional Integral Derivate BlockAuto Automatic mode
RBResource BlockOOSOut Of Service mode
TBTransducer BlockODObject Directory
RReadSPSet Point
WWriteIVInitial Value
R/WRead and WritePVProcess Value (factory settings)
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
9
4 OPERATION
4.4 Resource Block (RB)
The following tables list the Resource Block parameters in alphabetical order.
It describes characteristics of the Fieldbus device (e.g. device name, serial number, etc.) and is
not included in the functional tasks of the signal converter for FF.
The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.
4.4.1 Foundation Fieldbus parameters for Resource Block
Parameter
Parameter
ParameterParameter
DD name
ALERT_KEY
ALERT_KEY
ALERT_KEYALERT_KEY
Alert Key
Alert Key
Alert KeyAlert Key
BLOCK_ERR
BLOCK_ERR
BLOCK_ERRBLOCK_ERR
Block Error
Block Error
Block ErrorBlock Error
MODE_BLK
MODE_BLK
MODE_BLKMODE_BLK
Block Mode
Block Mode
Block ModeBlock Mode
TARGET
Target
ACTUAL
Actual
PERMITTED
Permitted
AccessDescription and settingsInitial Value
R/WThe identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
Setting:
1...255
RThis parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
Setting:
• Other: Non-specific error active
• Block Configuration: Error detected in block configuration
• Link Configuration: Error detected in link configuration
• Simulation Active: Simulation enabled in this block
• Local Override: Output tracking of faultstate active
The block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the "Active" status in the "Status"
attribute. As soon as the "Unreported" status is cleared by the
alert reporting task, another block alert may be reported
without clearing the "Active" status, if the subcode has
changed.
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
11
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
GFC 300
AccessDescription and settingsInitial Value
Alarm StateRA discrete enumeration which gives an indication of whether
Time StampRThe time when evaluation of the block was started and a
SubcodeRAn enumeration specifying the cause of the alert to be
ValueRThe value of the associated parameter at the time the alert
CLR_FSTATE
CLR_FSTATE
CLR_FSTATECLR_FSTATE
Clear Fault State
Clear Fault State
Clear Fault StateClear Fault State
CONFIRM_TIME
CONFIRM_TIME
CONFIRM_TIMECONFIRM_TIME
Confirm Time
Confirm Time
Confirm TimeConfirm Time
CYCLE_SEL
CYCLE_SEL
CYCLE_SELCYCLE_SEL
Cycle Selection
Cycle Selection
Cycle SelectionCycle Selection
CYCLE_TYPE
CYCLE_TYPE
CYCLE_TYPECYCLE_TYPE
Cycle Type
Cycle Type
Cycle TypeCycle Type
DD_RESOURCE
DD_RESOURCE
DD_RESOURCEDD_RESOURCE
DD Resource
DD Resource
DD ResourceDD Resource
DD_REV
DD_REV
DD_REVDD_REV
DD Revision
DD Revision
DD RevisionDD Revision
DEV_REV
DEV_REV
DEV_REVDEV_REV
Device Revision
Device Revision
Device RevisionDevice Revision
R/WWriting a "Clear" to this parameter will clear the device fault
R/WThe minimum time between retries of alert reports.640000
R/WUsed to select the block execution method for this resource.Uninitialized
RIdentifies the block execution methods available for this
RString identifying the tag of the resource which contains the
RRevision of the DD associated with the resource - used by an
RManufacturer revision number associated with the resource -
the alert is active and whether it has been reported.
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active reported / Active - not reported
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
reported.
Setting:
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
was detected.
Setting:
0...255
state if the field condition, if any, has cleared.
Setting:
Uninitialized / Off / Clear
Setting:
0...4294967295 in [1/32 ms]
Setting:
Scheduled / Block execution
resource.
Setting:
Scheduled / Block execution
Device Description for this resource.
Setting:
≤ 32 digits
interface device to locate the DD file for the resource.
Setting:
Dependent on device version.
used by an interface device to locate the DD file for the
resource.
Setting:
Dependent on device version.
Uninitialized
Uninitialized
Other
0
Off
Scheduled
Block execution
blanks
Dependent on
device version.
Dependent on
device version.
12
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
DEV_TYPE
DEV_TYPE
DEV_TYPEDEV_TYPE
Device Type
Device Type
Device TypeDevice Type
FAULT_STATE
FAULT_STATE
FAULT_STATEFAULT_STATE
Fault State
Fault State
Fault StateFault State
FEATURES
FEATURES
FEATURESFEATURES
Features
Features
FeaturesFeatures
FEATURES_SEL
FEATURES_SEL
FEATURES_SELFEATURES_SEL
Features Selection
Features Selection
Features SelectionFeatures Selection
FREE_SPACE
FREE_SPACE
FREE_SPACEFREE_SPACE
Free Space
Free Space
Free SpaceFree Space
FREE_TIME
FREE_TIME
FREE_TIMEFREE_TIME
Free Time
Free Time
Free TimeFree Time
GRANT_DENY
GRANT_DENY
GRANT_DENYGRANT_DENY
Grant Deny
Grant Deny
Grant DenyGrant Deny
GRANT
Grant
DENY
Deny
HARD_TYPES
HARD_TYPES
HARD_TYPESHARD_TYPES
Hardware Types
Hardware Types
Hardware TypesHardware Types
ITK_VER
ITK_VER
ITK_VERITK_VER
ITK Version
ITK Version
ITK VersionITK Version
(Interoperatibility Test
Kit)
OPERATION 4
AccessDescription and settingsInitial Value
RManufacturer's model number associated with the resource -
used by interface devices to locate the DD file for the
resource.
Setting:
GFC300
RCondition set by loss of communication to an output block,
failure promoted to an output block or a physical contact.
When fault state condition is set, then output function blocks
will perform their "FSTATE" actions.
Setting:
Uninitialized / Off / Clear
RUsed to shows supported resource block options.Reports
Setting:
Reports / Soft W Lock / MVC Report Distribution supported /
MVC Publishing/Subcribing supported / Multi-bit Alarm (BitAlarm) Support
R/WUsed to select resource block options.Reports
Setting:
Reports / Soft W Lock / MVC Report Distribution supported /
MVC Publishing/Subscribing supported / Multi-bit Alarm (BitAlarm) Support
RPercent of the memory available for further configuration.
Zero in a preconfigured resource.
Setting:
0.0…100.0
RPercent of the block processing time that is free to process
additional blocks.
Setting:
0.0…100.0
R/WOptions for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
R/WDepending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - "Program, Tune, Alarm or Local".
Setting:
Program / Tune / Alarm / Local / Operate
R/WThe Denied attribute is limited for use by a monitoring
application in an interface device and may not be changed by
an operator.
Setting:
Program denied / Tune denied / Alarm denied / Local denied /
Operate denied
RThe types of hardware available as channel numbers.Scalar input
RMajor revision number of the interoperability test case used to
register this device.
GFC300
Clear
Soft W Lock
MVC Report
Distribution
supported
MVC
Publishing/Subcrib
ing supported
Multi-bit Alarm
(Bit-Alarm)
Support
Soft W Lock
0.0
0.0
-
Uninitialized
Uninitialized
5
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
13
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
LIM_NOTIFY
LIM_NOTIFY
LIM_NOTIFYLIM_NOTIFY
Limit Notify
Limit Notify
Limit NotifyLimit Notify
MANUFAC_ID
MANUFAC_ID
MANUFAC_IDMANUFAC_ID
Manufacturer ID
Manufacturer ID
Manufacturer IDManufacturer ID
MAX_NOTIFY
MAX_NOTIFY
MAX_NOTIFYMAX_NOTIFY
Maximum Notify
Maximum Notify
Maximum NotifyMaximum Notify
MEMORY_SIZE
MEMORY_SIZE
MEMORY_SIZEMEMORY_SIZE
Memory Size
Memory Size
Memory SizeMemory Size
MIN_CYCLE_T
MIN_CYCLE_T
MIN_CYCLE_TMIN_CYCLE_T
Minimium Cycle Time
Minimium Cycle Time
Minimium Cycle TimeMinimium Cycle Time
NV_CYCLE_T
NV_CYCLE_T
NV_CYCLE_TNV_CYCLE_T
Nonvolatile Cycle
Nonvolatile Cycle
Nonvolatile Cycle Nonvolatile Cycle
Time
Time
TimeTime
RESTART
RESTART
RESTARTRESTART
Restart
Restart
RestartRestart
RS_STATE
RS_STATE
RS_STATERS_STATE
Resource State
Resource State
Resource StateResource State
SET_FSTATE
SET_FSTATE
SET_FSTATESET_FSTATE
Set Fault State
Set Fault State
Set Fault StateSet Fault State
SHED_RCAS
SHED_RCAS
SHED_RCASSHED_RCAS
Shed Remote Cascade
Shed Remote Cascade
Shed Remote CascadeShed Remote Cascade
SHED_ROUT
SHED_ROUT
SHED_ROUTSHED_ROUT
Shed Remote Out
Shed Remote Out
Shed Remote OutShed Remote Out
TEST_RW
TEST_RW
TEST_RWTEST_RW
Test R Write
Test R Write
Test R WriteTest R Write
UPDATE_EVT
UPDATE_EVT
UPDATE_EVTUPDATE_EVT
Update Event
Update Event
Update EventUpdate Event
UnacknowledgedR/WA discrete enumeration which is set to "Unacknowledged"
AccessDescription and settingsInitial Value
R/WMaximum number of unconfirmed alert notify messages
allowed.
Setting:
0...255
RManufacturer identification number - used by an interface
device to locate the DD file for the resource.
Setting:
KROHNE
RMaximum number of unconfirmed alert notify messages
possible.
Setting:
0...255
RAvailable configuration memory in the empty resource. To be
checked before attempting a download.
RTime duration of the shortest cycle interval of which the
resource is capable (in [1/32 ms]).
RInterval between writing copies of NV parameters to non-
volatile memory. Zero means never (in [1/32 ms]).
R/WAllows a manual restart to be initiated. Several degrees of
restart are possible. They are 1: Run, 2: Restart resource, 3:
Restart with defaults and 4: Restart processor.
Setting:
Uninitialized / Run / Resource / Defaults / Processor
RState of the function block application state machine.Standby
R/WAllows the fault state condition to be manually initiated by
selecting "Set".
Setting:
Off
R/WTime duration at which to give up on computer writes to
function block RCAS locations.
Setting:
0...4294967295 in [1/32 ms]
R/WTime duration at which to give up on computer writes to
function block ROUT locations.
Setting:
0...4294967295 in [1/32 ms]
Read/write test parameter - used only for conformance
testing.
Note: Subelements "1..15" have no function!
This alert is generated by any change to the static data.-
when an update occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
OPERATION 4
AccessDescription and settingsInitial Value
Update StateRA discrete enumeration which gives an indication of whether
Time StampRThe time when evaluation of the block was started and a
Static RevisionRThe static revision of the block whose static parameter was
Relative IndexRThe OD index of the static parameter whose change caused
WRITE_ALM
WRITE_ALM
WRITE_ALMWRITE_ALM
Write Alarm
Write Alarm
Write AlarmWrite Alarm
UnacknowledgedR/WA discrete enumeration which is set to "Unacknowledged"
Alarm StateRA discrete enumeration which gives an indication of whether
Time StampRThe time when evaluation of the block was started and a
SubcodeRAn enumeration specifying the cause of the alert to be
Discrete ValueRThe value of the associated parameter at the time the alert
MixThis alert is generated if the write lock parameter is cleared.-
the alert has been reported.
Setting:
Uninitialized / Reported / Not reported
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
changed and is being reported. It is possible for the present
value of static revision to be greater than this because static
can be changed at any time.
Setting:
0…65535
this alert, minus the FB starting index. If the update event was
caused by a write to multiple parameters at the same time,
then this attribute will be zero.
Setting:
0…65535
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
the alert is active and whether it has been reported.
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active reported / Active - not reported
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
reported.
Setting:
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
was detected.
Setting:
Discrete State 0...16
Uninitialized
Uninitialized
0
0
Uninitialized
Uninitialized
Uninitialized
Other
State 0
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
15
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
WRITE_LOCK
WRITE_LOCK
WRITE_LOCKWRITE_LOCK
Write Lock
Write Lock
Write LockWrite Lock
WRITE_PRI
WRITE_PRI
WRITE_PRIWRITE_PRI
Write Priority
Write Priority
Write PriorityWrite Priority
4.4.2 Manufacturer specific parameters of the signal converter for Resource Block
Parameter
Parameter
ParameterParameter
DD name
DEV_DESCRIPTION
DEV_DESCRIPTION
DEV_DESCRIPTIONDEV_DESCRIPTION
Device Description
Device Description
Device DescriptionDevice Description
DB_DEVICE
Data Base GDC
C_NUMBER_DEVICE
C-Number Device
C_NUMBER_
PRODUCT
C-Number Production
CONVERTER_MODEL
Converter Model
LOGICAL_PLACE
Logical Place
SUPPLY_OPTION
Supply Option
DISPLAY_OPTION
Display Option
IO_SELECTION
IO1 Modular IO
IO_MODULE_A
IO2 Module Term. A
IO_MODULE_B
IO Module Term. B
DIAGNOSIS
DIAGNOSIS
DIAGNOSISDIAGNOSIS
Diagnosis
Diagnosis
DiagnosisDiagnosis
MEMORY_SUMMARY
Memory Summary
AccessDescription and settingsInitial Value
R/WIf set, no writes from anywhere are allowed, except to clear
WRITE_LOCK. Block inputs will continue to be updated.
Setting:
Uninitialized / Not locked / Locked
RPriority of the alarm generated by clearing the write lock.0
Setting:
0...15
Not locked
AccessDescription and settingsInitial Value
RDescribes some characteristics of the device.-
RData base version of the GDC device.Current data base
RCurrent C-Number of this device.Current C-Number
RC-Number of production; this number identifies the type of
electronics, can be found on the signal converter assembly
sticker as well.
RThe model of signal converter.GFC300
RSetting:
Error / Standard / Extended standard / Special
RSupply of sensor and electronics option.As ordered
Configuration error or missing / Standard / Eastern Europe /
Northern Europe / Southern Europe / Far East / Japanese /
Chinese / Russian
RSetting:
Configuration error or missing / Foundation Fieldbus
RSetting:
Configuration error or missing / Without carrier / Exi
Opt.:Current Out act + PO/CI pas / Exi Opt. : CurrOut pas +
PO/CI pas / Exi Opt.2 : CurrIn act + PO/CI pas / Exi Opt.2 :
CurrIn pas + PO/CI pas / Exi Opt.3 : 2x CurrIn act
RNot used.-
RDetailed diagnosis of the device.-
RSummary of self diagnosis.ok
Setting:
ok / bit 8…15 not used / EEPROM / FRAM / FLASH / ROM
application / ROM boot area / RAM ext / RAM int / Task Control
version
of device
Current C-Number
of production
Standard
As ordered
Foundation
Fieldbus
-
GFC 300
16
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
OPERATION 4
AccessDescription and settingsInitial Value
FRAM_DIAG
FRAM Diagnosis
workLOADRWork load of the processor.Current work load
DIAGNOSIS_BLK
DIAGNOSIS_BLK
DIAGNOSIS_BLKDIAGNOSIS_BLK
Diagnosis Block
Diagnosis Block
Diagnosis BlockDiagnosis Block
RB_DIAG
RB Diagnosis
TB1_DIAG
TB1 Diagnosis
TB2_DIAG
TB 2
RResult of FRAM self diagnosis.ok
Setting:
ok / not supported action / unknown / busy / wait / first init /
changed / bit09 / parameter error/ page error/ chip error/
write error / warning: inconsistent / warning: uncertain /
warning: write cycles / warning: one header / ok, page high
RDetailed diagnosis of the blocks.-
RReason for bits set at BLK_ERR and other diagnosis.Current diagnosis
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / Operating System / new: ID, DEV_TYPE, SNR / no GDC
Communication / Startup GDC, data invalid / Startup Sensor,
data valid / C-Number doesn't match to FF Software /
Hardware changed, C raw != C detected / Data Base doesn't
match to FF Software / MODE_BLK.PERMITTED doesn't
include Auto / MODE_BLK.TARGET is set OOS / GDC bold F
message / GDC F message / write from GDC to RB/TB doesn't
work / GDC Mfr unknown / GDC serial number / Boardinfo
incomplete or corrupt / action: write from GDC to RB/TB /
GDC W: no, M: no / GDC W: no, M: some /
GDC W: some, M: no / GDC W: no, M: all /
GDC W: all, M: no / GDC W: some, M: some /
GDC W: some, M: all / GDC W: all, M: some /
GDC Communication few loss / RS_STATE is not On-Line /
simulation active / unknown reason / Ok
RReason for bits set at BLK_ERR and other diagnosis.Current diagnosis
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC, data invalid /
Startup Sensor, data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action: write from GDC to RB/TB / GDC Communication few
loss / no unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / unknown reason / Ok
RReason for bits set at BLK_ERR and other diagnosis.Current diagnosis
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC, data invalid /
Startup Sensor, data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action: write from GDC to RB/TB / GDC Communication few
loss / no unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / temperatur input / pressure input / p & T input /
unknown reason / Ok
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
17
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
GFC 300
AccessDescription and settingsInitial Value
TB3_DIAG
TB 3
AI1/2/3/4/5/6_DIAG
AI1/2/3/4/5/6
Diagnosis
PID_DIAG
PID Diagnosis
IT1/2_DIAG
IT1/2 Diagnosis
RReason for bits set at BLK_ERR and other diagnosis.Current diagnosis
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no GDC Communication / Startup GDC, data invalid /
Startup Sensor, data valid / Data Base doesn't match to FF
Software / MODE_BLK.PERMITTED doesn't include Auto /
MODE_BLK.TARGET is set OOS / GDC bold F message / GDC F
message / write from GDC to RB/TB doesn't work / Sensor
serial number / Sensor calibration date / GDC unit not
convertible to TB.prim_val / prim_val is outside range /
action: write from GDC to RB/TB / GDC Communication few
loss / no unit of GDC / GDC unit can't be converted to
TB.prim_range / a GDC value was not received / a GDC short
status is fatal or warn2 / PRIMARY_VALUE_1.status is
Uncertain / unknown reason / Ok
RReason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Setting:
Startup Device / RB : MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN , Startup to Auto /
CHANNEL is uninitialized / UNIT of CHANNEL selected
TB.prim_val not convertible to XD UNIT / XD_SCALE :
difference between EU_100 and EU_0 is to less / OUT_SCALE :
difference between EU_100 and EU_0 is to less / L_TYPE is
uninitialized / L_TYPE is direct , XD_SCALE is not equal
OUT_SCALE / IO_OPTS no unit conversion , XD UNIT doesn’t
match to UNIT of TB.prim_val / SIMULATE_STATUS is not
Good , Simulation is active / SIMULATE_STATUS limitted ,
STATUS_OPTS is set , Simulation active / Simulation is active /
Transducer Block MODE_BLK.ACTUAL is OOS / CHANNEL
selected TB.prim_val.status is Bad / TB.prim_val.status is
limitted , STATUS_OPTS is set / CHANNEL selected
TB.prim_val.status is Uncertain / OUT.value exceeds
OUT_SCALE / unknown reason / Ok
RReason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
BYPASS is uninitialized / SHED_OPT is uninitialized /
PV_SCALE : EU_100 <= EU_0 / OUT_SCALE: EU_100 <= EU_0 /
TRK_SCALE: EU_100 <= EU_0 / FF_SCALE: EU_100 <= EU_0 /
unknown reason / Ok
RReason for OUT.status not Good, bits at BLK_ERR and other
diagnosis.
Setting:
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
INTEG_TYPE is uninitialized / IN_1 and IN_2 are not
connected / TIME_UNIT1 and TIME_UNIT2 are uninitialized /
CLOCK_PER <= period of execution / TIME_UNIT and
TIME_UNIT2 is uninitialized / IN_1.status is Bad / IN_2.status
is Bad / IN_1.value is NaN or INF / IN_2.value is NaN or INF /
PCT_INCL < UNCERT_LIM / PCT_INCL < GOOD_LIM /
PULSE_VAL1 and PULSE_VAL2 are 0 / TOTAL_SP is 0: cyclic
reset / unknown reason / Ok
Current diagnosis
Current diagnosis
Current diagnosis
18
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
OPERATION 4
AccessDescription and settingsInitial Value
AR_DIAG
AR Diagnosis
DIAGNOSIS_DEV
DIAGNOSIS_DEV
DIAGNOSIS_DEVDIAGNOSIS_DEV
Diagnosis Device
Diagnosis Device
Diagnosis DeviceDiagnosis Device
RReason for OUT.status not Good, bits at BLK_ERR and other
RDisplay of maximum 8 (error) messages.Current diagnosis
diagnosis.
Startup Device / RB: MODE_BLK.ACTUAL is OOS / Memory
failure / no schedule / period of execution / period of
execution to large / MODE_BLK.PERMITTED doesn't include
Auto / MODE_BLK.TARGET is set OOS / MODE_BLK.TARGET is
set MAN / MODE_BLK.ACTUAL is MAN, Startup to Auto /
ARITH_TYPE is uninitialized / RANGE_HI < RANGE_LO /
COMP_LIM_HI < COMP_LIM_LO / OUT_LIM_HI < OUT_LIM_LO
/ IN_x.status is Bad / unknown reason / Ok
F: F:
display / current in-/output A / current in-/output B / current
in-/output C / software user interface / hardware settings /
hardware detection / RAM/ROM error IO1 / RAM/ROM error
IO2 / Fieldbus / communication dsp-up / sensor driver /
uProc. / dsp / parameter frontend / application error / open
circuit A / open circuit B / open circuit C / over range A
(current) / over range B (current) / over range C (current) /
over range A (pulse) / over range B (pulse) / over range D
(pulse) / active settings / factory settings / backup 1 settings /
backup 2 settings / wiring A (output) / wiring B (output) /
wiring A (input) / wiring B (input) / flow exceeding limit / signal
lost path 1 / signal lost path 2 / signal lost path 3 / transducer
delay / temperature input / pressure input / p & T input / VoS
monitor
S:
S: out of specification / overflow counter 1 (C) / overflow
S: S:
counter 1 (B) / overflow counter 2 / overflow counter 3 /
backplane invalid / error current A / error current B /
unreliable 1 / unreliable 2 / unreliable 3 / front end calibration
/ dsp timing error
Current diagnosis
Current diagnosis
DISPLAY_CNFG
DISPLAY_CNFG
DISPLAY_CNFGDISPLAY_CNFG
Display Configuration
Display Configuration
Display ConfigurationDisplay Configuration
DISP_LINE1
Display Line 1
DISP_LINE2
Display Line 2
DISP_LINE3
Display Line 3
ELECTRONIC_INFO
ELECTRONIC_INFO
ELECTRONIC_INFOELECTRONIC_INFO
Electronic Information
Electronic Information
Electronic InformationElectronic Information
IDENT_NUMBER
Ident Number
ELECTRONIC_REV
Electronic Revision
PRODUCTION_DATE
Production Date
C:
C:checks in progress / simulation flow / simulation VoS /
I: I:
stopped / counter 3 stopped / power fail / control input A
active / control input B active / over range display 1 / over
range display 2 / backplane sensor / backplane settings /
backplane difference / optical interface / write cycles overfl. /
baudrate search / no data exchange / start up
R/WSelect the function block output value to display at which line.
RInformation about ident number, electronic revision and
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
19
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
FF_BOARD_INFO
FF_BOARD_INFO
FF_BOARD_INFOFF_BOARD_INFO
FF Circuit
FF Circuit
FF CircuitFF Circuit
Board Information
Board Information
Board InformationBoard Information
IDENT_NUMBER
Ident Number
HARDWARE_ID
Hardware Ident
Number
SOFTWARE_VER
FF Software Version
PRODUCTION_DATE
Production Date
CALIBRATION_DATE
Calibration Date
FF_SERIAL_NO
FF Board
Serial Number
OPERATION_HOUR
OPERATION_HOUR
OPERATION_HOUROPERATION_HOUR
Operation Hours
Operation Hours
Operation HoursOperation Hours
PASSWRD
PASSWRD
PASSWRDPASSWRD
Password
Password
PasswordPassword
PROTECT_INFO
PROTECT_INFO
PROTECT_INFOPROTECT_INFO
Protection Information
Protection Information
Protection InformationProtection Information
SERIAL_NO
SERIAL_NO
SERIAL_NOSERIAL_NO
Serial Number
Serial Number
Serial NumberSerial Number
SW_SIMULATE
SW_SIMULATE
SW_SIMULATESW_SIMULATE
Software Simulate
Software Simulate
Software SimulateSoftware Simulate
GFC 300
AccessDescription and settingsInitial Value
RFor details see subelements."Actual values"
RActual ident number
Actual hardware number
Actual software version
Date of production
Date of calibration
Actual serial number
ROperation hours since first power-up.Curent operation
hours
R/WPassword to activate access rights to restricted parameters.0
RCurrent protection level to restricted parameters.Production
Setting:
Concentration / bit 5…7 (not used) / User / User / Service
Level / Production / Custody Transfer / Write Lock
RDevice serial number and serial number of the system.Current serial
number
R/WEnable/disable simulation like simulate "Hardware jumper".Disable
Setting:
Disable / Active
20
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
4.5 Analog Input Block (AI 1...6)
The following tables list the Analog Input Block parameters in alphabetical order.
It describes characteristics of the measurement values obtained from the Transducer Block in a
user defined way and to deliver it to the control system. There are also some parameters in the
Analog Input Block, that can be configured to get a measurement value quality as desired by the
user.
The following tables contain short parameter description, factory settings (Initial Value (IV)) and
possible settings.
Parameter
Parameter
ParameterParameter
DD name
Alert Key
Alert KeyR/WThe identification number of the plant unit. This information
Alert KeyAlert Key
BLOCK_ERR
BLOCK_ERR
BLOCK_ERRBLOCK_ERR
Block Error
Block Error
Block ErrorBlock Error
MODE_BLK
MODE_BLK
MODE_BLKMODE_BLK
Block Mode
Block Mode
Block ModeBlock Mode
TARGET
Target
ACTUAL
Actual
PERMITTED
Permitted
AccessDescription and settingsInitial Value
may be used in the host for sorting alarms, etc.
Setting:
1...255
RThis parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
Setting:
• Other: Non-specific error active
• Block Configuration: Error detected in block configuration
• Link Configuration: Error detected in link configuration
• Simulation Active: Simulation enabled in this block
• Local Override: Output tracking of faultstate active
• Output Failure: Failure detected in output hardware
• Memory Failure: Memory error detected
• Lost Static Data: Static parameters cannot be recovered
• Lost NV Data: Non-volatile parameters cannot be recovered
• Readback Check: Failure detected in READBACK
• Maintenance Needed: Device NEEDS maintenance NOW
• Power Up: Recovery from power failure
• Out Of Service: Block actual mode is out of service
MixThe actual, target, permitted and normal modes of the block.-
R/WBy setting this parameter to an allowed value (one of the value
from permitted modes) user can change the block execution
mode. Changing of modes is required to change the access
permissions available to various parameters.
Setting:
Auto / OOS
RThis is the current mode of the block, which may differ from
the target based on operating conditions. Its value is
calculated as part of block execution.
Setting:
Auto / OOS
R/WDefines the modes which are allowed for an instance in the
block. The permitted mode is configured based on application
requirements.
Setting:
Auto / OOS
OPERATION 4
0
Other
OOS
OOS
Auto
OOS
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
21
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
AccessDescription and settingsInitial Value
GFC 300
NORMAL
Normal
ST_REV
ST_REV
ST_REVST_REV
Static Revision
Static Revision
Static RevisionStatic Revision
STRATEGY
STRATEGY
STRATEGYSTRATEGY
Strategy
Strategy
StrategyStrategy
TAG_DESC
TAG_DESC
TAG_DESCTAG_DESC
Tag Description
Tag Description
Tag DescriptionTag Description
ACK_OPTION
ACK_OPTION
ACK_OPTIONACK_OPTION
Acknowledge
Acknowledge
Acknowledge Acknowledge
Option
Option
OptionOption
ALARM_HYS
ALARM_HYS
ALARM_HYSALARM_HYS
Alarm Hysteresis
Alarm Hysteresis
Alarm HysteresisAlarm Hysteresis
ALARM_SUM
ALARM_SUM
ALARM_SUMALARM_SUM
Alarm Summary
Alarm Summary
Alarm SummaryAlarm Summary
CurrentRThe active status of each alarm.Uninitialized
UnacknowledgedRThe unacknowledged state of each alarm.Uninitialized
UnreportedRThe unreported states of each alarm.Uninitialized
DisabledRThe disabled state of each alarmUninitialized
BLOCK_ALM
BLOCK_ALM
BLOCK_ALMBLOCK_ALM
Block Alarm
Block Alarm
Block AlarmBlock Alarm
R/WThis is the mode which the block should be set to during
normal operating conditions.
Setting:
Auto / OOS
RThe revision level of the static data associated with the
function block. The revision value will be incremented each
time a static parameter value in the block is changed.
Setting:
0...65535
R/WThe strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
Setting:
0...65535
R/WThis is the user description of the intended application of the
block.
Setting:
≤32 digits
R/WSelection of whether alarms associated with the function
block will be automatically acknowledged.
Setting:
HiHi Alm Auto Ack / Hi Alm Auto Ack / LoLo Alm Auto Ack / Lo
Alm Auto Ack / Blk Alm Auto Ack / Fail Alm Auto Ack / Off
Spec Alm Auto Ack / Maint Alm Auto Ack / Check Alm Auto
Ack
R/WAmount the PV must return within the alarm limits before the
alarm condition clears. Alarm hysteresis is expressed as a
percent of the PV span.
Setting:
0...50%
MixThe current alert status, unacknowledged states, unreported
states and disabled states of the alarms associated with the
function block.
Setting:
HiHi Alarm / Hi Alarm / LoLo Alarm / Lo Alarm / Block Alarm
Setting:
HiHi Alarm Unack / Hi Alarm Unack / LoLo Alarm Unack / Lo
Alarm Unack / Block Alarm Unack
Setting:
HiHi Alarm Unrep / Hi Alarm Unrep / LoLo Alarm Unrep / Lo
Alarm Unrep / Block Alarm Unrep
Setting:
HiHi Alarm Disabled / Hi Alarm Disabled / LoLo Alarm
Disabled / Lo Alarm Disabled / Block Alarm Disabled
MixThe block alarm is used for all configuration, hardware,
connection failure or system problems in the block. The cause
of the alert is entered in the subcode field. The first alert to
become active will set the "Active" status in the "Status"
attribute. As soon as the "Unreported" status is cleared by the
alert reporting task, another block alert may be reported
without clearing the "Active" status, if the subcode has
changed.
Auto
0
0
blanks
Uninitialized
0.5
-
-
22
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
OPERATION 4
AccessDescription and settingsInitial Value
UnacknowledgedR/WA discrete enumeration which is set to "Unacknowledged"
Alarm StateRA discrete enumeration which gives an indication of whether
Time StampRThe time when evaluation of the block was started and a
SubcodeRAn enumeration specifying the cause of the alert to be
ValueRThe value of the associated parameter at the time the alert
CHANNEL
CHANNEL
CHANNELCHANNEL
Channel
Channel
ChannelChannel
R/WThe number of the logical hardware channel that is connected
when an alarm occurs, and set to "Acknowledged" by a write
from a human interface device or other entity which can
acknowledge that the alarm/event has been noticed.
the alert is active and whether it has been reported.
Setting:
Uninitialized / Clear - reported / Clear - not reported / Active reported / Active - not reported
change in alarm/event state was detected that is unreported.
The time stamp value will be maintained constant until alert
confirmation has been received - even if another change of
state occurs.
Setting:
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
reported.
Setting:
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
was detected.
Setting:
0...255
to this I/O block. This information defines the transducer to be
used going to or from the physical world.
Note:
Note:
Note:Note:
W = Writeable only by setting "OOS" in MODE_BLK
Setting:
0 Uninitialized
1 volume flow
2 corr. volume flow
3 mass flow
4 molar mass
5 enthalpy flow
6 spec. enthalpy
7 density
8 flow speed
9 process temperature
10 process pressure
11 electronic temperature
12 velocity of sound
13 gain
14 SNR
15 velocity of sound 1
16 gain 1
17 SNR 1
18 velocity of sound 2
19 gain 2
20 SNR 2
21 velocity of sound 3
22 gain 3
23 SNR 3
Uninitialized
Uninitialized
Uninitialized
Other
0
Uninitialized
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
23
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
FIELD_VAL
FIELD_VAL
FIELD_VALFIELD_VAL
Field Value
Field Value
Field ValueField Value
StatusRDigital transducers, unlike their analogue versions, can detect
ValueRA numerical quantity entered by a user or calculated by the
GRANT_DENY
GRANT_DENY
GRANT_DENYGRANT_DENY
Grant Deny
Grant Deny
Grant DenyGrant Deny
GRANT
Grant
DENY
Deny
HI_ALM
HI_ALM
HI_ALMHI_ALM
High Alarm
High Alarm
High AlarmHigh Alarm
HI_HI_ALM
HI_HI_ALM
HI_HI_ALMHI_HI_ALM
High High Alarm
High High Alarm
High High AlarmHigh High Alarm
Settings of 5 subelements for previous 2 parameters High Alarm and High High Alarm:
UnacknowledgedR/WSetting:
Alarm StateRSetting:
Time StampRSetting:
SubcodeRSetting:
ValueRA numerical quantity entered by a user or calculated by the
HI_HI_LIM
HI_HI_LIM
HI_HI_LIMHI_HI_LIM
High High Limit
High High Limit
High High LimitHigh High Limit
HI_HI_PRI
HI_HI_PRI
HI_HI_PRIHI_HI_PRI
High High Priority
High High Priority
High High PriorityHigh High Priority
HI_LIM
HI_LIM
HI_LIMHI_LIM
High Limit
High Limit
High LimitHigh Limit
HI_PRI
HI_PRI
HI_PRIHI_PRI
High Priority
High Priority
High PriorityHigh Priority
AccessDescription and settingsInitial Value
RRaw value of the field device in percent of the PV range, with a
status reflecting the transducer condition, before signal
characterization (L_TYPE) or filtering (PV_FTIME).
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
algorithm.
Options for controlling access of host computers and local
control panels to operating, tuning and alarm parameters of
the block.
R/WDepending on the philosophy of the plant, the operator or a
higher level device (HLD) or a local operator's panel (LOP) in
the case of "Local", may turn on an item of the "Grant"
attribute - "Program, Tune, Alarm or Local".
Setting:
Program / Tune / Alarm / Local / Operate
R/WThe deny attribute is provided for use by a monitoring
application in an interface device and may not be changed by
an operator.
Setting:
Program denied / Tune denied / Alarm denied / Local denied /
Operate denied
The status for High Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
MixThe status for High High Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
Uninitialized / Acknowledged / Unacknowledged
Uninitialized / Clear - reported / Clear - not reported / Active reported / Active - not reported
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
algorithm.
R/WThe setting for High High Alarm in engineering units.
Setting range see in the following part.
R/WPriority of the High High Alarm.
Setting see in the following part.
R/WThe setting for High Alarm in engineering units.
Setting range see in the following part.
R/WPriority of the High Alarm.
Setting see in the following part.
GFC 300
-
Bad
Non Specific
Not Limited
0.0
-
Uninitialized
Uninitialized
-
-
Uninitialized
Uninitialized
Uninitialized
Other
0.0
NaN
0
NaN
0
24
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
GFC 300
Parameter
Parameter
ParameterParameter
DD name
OPERATION 4
AccessDescription and settingsInitial Value
Setting range for previous 2
parameters:
x_y_LIM
x_y_Limit
Setting for previous 2
parameters:
x_y_PRI
x_y_Priority
IO_OPTS
IO_OPTS
IO_OPTSIO_OPTS
IO Options
IO Options
IO OptionsIO Options
(IO = Input/Output)
(IO = Input/Output)
(IO = Input/Output)(IO = Input/Output)
L_TYPE
L_TYPE
L_TYPEL_TYPE
Linearization Type
Linearization Type
Linearization TypeLinearization Type
LO_ALM
LO_ALM
LO_ALMLO_ALM
Low Alarm
Low Alarm
Low AlarmLow Alarm
LO_LO_ALM
LO_LO_ALM
LO_LO_ALMLO_LO_ALM
Low Low Alarm
Low Low Alarm
Low Low AlarmLow Low Alarm
Settings of 5 subelements for previous 2 parameters Low Alarm and Low Low Alarm:
UnacknowledgedR/WSetting:
Alarm StateRSetting:
Time StampRSetting:
SubcodeRAn enumeration specifying the cause of the alert to be
ValueRA numerical quantity entered by a user or calculated by the
LO_LIM
LO_LIM
LO_LIMLO_LIM
Low Limit
Low Limit
Low LimitLow Limit
LO_LO_LIM
LO_LO_LIM
LO_LO_LIMLO_LO_LIM
Low Low Limit
Low Low Limit
Low Low LimitLow Low Limit
LO_PRI
LO_PRI
LO_PRILO_PRI
Low Priority
Low Priority
Low PriorityLow Priority
LO_LO_PRI
LO_LO_PRI
LO_LO_PRILO_LO_PRI
Low Low Priority
Low Low Priority
Low Low PriorityLow Low Priority
R/WOptions which the user may select to alter input and output
R/WDetermines if the values passed by the TB to the AI block may
R/WThe setting for Low Alarm in engineering units.
R/WThe setting for Low Low Alarm in engineering units.
0: The associated alert may clear when the priority is changed
to 0, but it will never occur.
1: The associated alert is not send as a notification. If the
priority is above 1, then the alert must be reported.
2: Reserved for alerts that do not require the attention of a
plant operator, e.g. diagnostic and system alerts. Block alarm,
error alarm and update event have a fixed priority of 2.
be used directly (Direct) or if the value is in different units and
must be converted linearly (Indirect) or with square root (Ind
Sqr Root), using the input range defined by the transducer and
the associated output range.
W = Writeable only by setting "OOS" in MODE_BLK
Setting:
Uninitialized / Direct / Indirect / Ind Sqr Root
The status for Low Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
The status for Low Low Alarm and its associated time stamp.
Settings of 5 subelements see in the following part.
Uninitialized / Acknowledged / Unacknowledged
Uninitialized / Clear - reported / Clear - not reported / Active reported / Active - not reported
MM / DD / YY (Month / Day / Year)
HH:MM:SS (Hour:Minute:Second)
reported.
Setting:
Other / Block Configuration / Link Configuration / Simulation
Active / Local Override / Device Fault State / Device
Maintenance / Input Failure / Output Failure / Memory
Failure / Lost Static Data / Lost NV Data / Readback Check /
Maintenance Needed / Power Up / Out Of Service
algorithm.
Setting range see in the following part.
Setting range see in the following part.
Setting see in the following part.
Setting see in the following part.
0
Uninitialized
Uninitialized
-
-
Uninitialized
Uninitialized
Uninitialized
Other
0.0
(-NaN)
(-NaN)
0
0
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
25
4 OPERATION
Parameter
Parameter
ParameterParameter
DD name
AccessDescription and settingsInitial Value
GFC 300
Setting range for previous 2
parameters:
x_y_LIM
x_y_Limit
Setting for previous 2
parameters:
x_y_PRI
x_y_Priority
LOW_CUT
LOW_CUT
LOW_CUTLOW_CUT
Low Cutoff
Low Cutoff
Low CutoffLow Cutoff
OUT
OUT
OUTOUT
Output
Output
OutputOutput
StatusRDigital transducers, unlike their analogue versions, can detect
ValueR/WA numerical quantity entered by a user or calculated by the
OUT_SCALE
OUT_SCALE
OUT_SCALEOUT_SCALE
Output Scale
Output Scale
Output ScaleOutput Scale
EU_100
EU at 100%
EU_0
EU at 0%
Units IndexR/WDevice Description units code index for the engineering unit
Decimal PointR/WThe number of digits to the right of the decimal point which
PV
PV
PVPV
Process Value
Process Value
Process ValueProcess Value
StatusRDigital transducers, unlike their analogue versions, can detect
ValueRA numerical quantity entered by a user or calculated by the
PV_FTIME
PV_FTIME
PV_FTIMEPV_FTIME
PV F Time
PV F Time
PV F TimePV F Time
(Process Value
(Process Value
(Process Value (Process Value
Filter Time
Filter Time
Filter Time Filter Time
Constant)
Constant)
Constant)Constant)
R/WLimit used in square root processing. A value of zero percent
R/WThe primary analogue discrete value calculated as a result of
R/WThe high and low scale values, engineering units code and
R/WThe engineering unit value which represents the upper end of
R/WThe engineering unit value which represents the lower end of
R/WTime constant of a single exponential filter for the PV, in
0: The associated alert may clear when the priority is changed
to 0, but it will never occur.
1: The associated alert is not send as a notification. If the
priority is above 1, then the alert must be reported.
2: Reserved for alerts that do not require the attention of a
plant operator, e.g. diagnostic and system alerts. Block alarm,
error alarm and update event have a fixed priority of 2.
of scale is used in block processing if the transducer value
falls below this limit, in %of scale. This feature may be used to
eliminate noise near zero for a flow sensor.
Setting:
≥0.0
executing the function.
Note:
Note:
Note:Note:
W = Writeable only by setting "OOS" in MODE_BLK
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
algorithm.
number of digits to the right of the decimal point to be used in
displaying the OUT parameter and parameters which have the
same scaling as OUT.
range of the associated block parameter.
range of the associated block parameter.
descriptor for the associated block value.
Setting:
All units are possible.
should be used by an interface device in displaying the
specified parameter.
Either the primary analogue value for use in executing the
function or a process value associated with it.
faults that make the measurement bad or prevent the
actuator from responding. This additional, valuable
information will be passed along with each transmission of a
data value in the form of a status attribute.
algorithm.
seconds.
Setting:
0.0…60.0
0
0
-
-
-
-
100.0
0.0
Uninitialized
0
-
0
0.0
0
26
www.krohne.com07/2012 - 4001866001 - AD GFC 300 FF R01 en
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.