www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
Page 3
ESK
GENERAL SAFETY INFORMATION 1
This supplementary “Ex” instruction applies to explosion protected versions of the
electronic signal outputs ESKII, ESK2A and ESK3-PA. It supplements the installation and
operating instructions issued for the non-hazardous-duty versions.
These instructions only contain data relevant to explosion protection. The technical
specifications of the installation and operating instructions for the non-hazardous-duty
version remain valid unless explicitly excluded or replaced by these Instructions.
Electronic signal outputs of the ESKII, ESK2A and ESK3-PA series have been certified in
accordance with European Directive 94/9 EG (ATEX 100a) to European standards EN 60079- X for
use in potentially explosive areas as stated in
by the Physikalisch-Technische Bundesanstalt (PTB).
This certification and its boundary conditions must be observed.
Installation, startup and maintenance may be carried out only by personnel trained in explosion
Installation, startup and maintenance may be carried out only by personnel trained in explosion
Installation, startup and maintenance may be carried out only by personnel trained in explosion Installation, startup and maintenance may be carried out only by personnel trained in explosion
protection !
protection !
protection !protection !
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
3
Page 4
2 DEVICE VERSIONS AND MARKING
2.1 Description
ESK II and the update version ESK2A are a 4...20mA loop transmitter in 2-wire technology, used
as a signal output. The linear analog signal output represents the volume or massflow of a VAmeter or the level of a levelmeter.
ESK3-PA provides additional information for connecting and operating a PROFIBUS-PA field bus.
The details in these instructions, especially the safety instructions, have not been modified by
this supplement, and must continue to be observed.
The signal converter ESK3-PA is designed in the context of the modular concept. Installation and
attachment are identical to the signal converter ESKII and ESK2A.
2.2 Safety description code
ESK
The safety description code consists of the following elements:
1 EEEElectronic SSSSignal output KKKKrohne
2 Designs of the signal output :
II
II - Analog signal output 4-20mA with HART signal
IIII
2A
2A - Analog signal output 4-20mA with HART signal
2A2A
3-PA
3-PA - Digital signal output for Profibus-PA in conformity with FISCO model
3-PA3-PA
1
positions not needed can be omitted from the description code.
1
4
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
Page 5
ESK
2.3 Marking
Marked housing
The housing is marked with the type designation of the electronic signal outputs ESK .... as
shown below
ESKII / ESK2A
DEVICE VERSIONS AND MARKING 2
1 Manufacturer
2 European Conformity
3 Certification details
4 Type according to description code
5 Serial number
6 Year of manufacture
ESK3-PA
1 Manufacturer
2 European Conformity
3 Certification details
4 Type according to description code
5 Serial number
6 Year of manufacture
The description code is described in the section before. The aboriginal marking of all types
according to EN50014 is registered to EEx ia IIC.
2.4 Category / Zone
The electronic signal outputs ESK .... are designed in category 2 for use in zone 1.
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
5
Page 6
2 DEVICE VERSIONS AND MARKING
2.5 Ignition protected types
The power circuits of the electronic signal outputs ESK .... are designed to conform with the
intrinsically safe type classified in level of protection “ia”. Operation with intrinsically safe
circuits in level of protection "ib" is also allowed.
2.6 Temperature classes
Depending on temperature class and ambient temperature, the electronic signal outputs
ESK .... are approved for the process temperatures contained in the following table.
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
Page 7
ESK
3.1 Installation
Installation to be carried out by qualified persons in conformity with installation standards
for potentially explosive areas (e.g. EN 60079-14 / VDE 0165).
The information given in the installation and operating instructions as well as in the
supplementary instructions (Ex) and the EU certificate must be observed.
The suitability of the electronic signal output for the intended use should be checked by
referring to the nameplate.
Special attention must be given to the following points.
INSTALLATION AND OPERATION 3
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
7
Page 8
4 SAFETY FEATURES
4.1 Electrical connection
The electronic signal outputs must be connected to intrinsically safe circuits. The maximum
safety-related values are listed below.
ESKII / ESK2A
Connection by way of a certified intrinsically safe isolation amplifier with the following
maximum values:
• Ui =30 V
• Ii =100 mA
• Pi =1,0 W
For the interconnection to intrinsically safe circuits note the following values:
• Ci = 20 nF
• Li ≈ 0 µH
ESK
ESK3-PA
Connection by way of a certified segment coupler with the following maximum values:
• Pi =5,32W
• Ui =24 V
• Ii =380mA
For the interconnection, the permissible limit values for the Profibus-PA in conformity with
the FISCO model must be observed.
Pinning
The electronic signal outputs are electrically connected at the terminals. The table shows
the polarity at the terminals
TerminalPolarity of terminals for electronic signal output
NumberESKIIESK2A / ESK3-PA
11+Not polarity sensitive
12-
Terminal polarity of ESK ....
Connection lines
The connection lines for the intrinsically safe circuits must be selected in keeping with the
applicable installation standard (e.g. EN 60079-14 / VDE 0165).
8
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
Page 9
ESK
Repairs relevant to safety in relation to explosion protection may only be carried out by the
manufacturer, his authorized agent, or under the supervision of qualified experts.
5.1 Maintenance
The electronic signal outputs are maintenance-free under normal operating conditions and
when used as intended.
Within the scope of checks required to be carried out in hazardous areas to maintain systems in
proper working order, the following visual inspections should be carried out at regular intervals:
• Inspect the housing, the terminals and the incoming lines for signs of corrosion and
damage.
SERVICE 5
5.2 Dismantling
Due to the intrinsically safe supply of the electronic signal output ESK ..., replacement
during operation is possible, but should preferably be carried out in off-load condition.
If this is not possible, the boundary conditions for intrinsic safety (e.g. no grounding or
interconnection of different intrinsically safe circuits) must be observed during dismantling.
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
9
Page 10
5 SERVICE
.
ESK
10
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
Page 11
ESK
SERVICE 5
.
www.krohne.com09/2008 • 4000333901 MA ESK-Ex- II2G-AD-R01 en
SingaporeSingapore
Tokyo Keiso - KROHNE (Singapore)
Pte. Ltd.
14, International Bus iness Park,
Jurong East
Chiyoda Building, #01-01/02
Singapore 609922
Phone: (65) 6567 4548
Fax : (65) 6567 9874
tks@tokyokeiso-krohne.com.sg
Republic of South Africa
Republic of South Africa
Republic of South AfricaRepublic of South Africa
KROHNE Pty. Ltd.
Bushbock Close
Corporate Park South
Midrand, Gauteng
P.O. Box 2069
Midrand, 1685
Tel.: +27 (0)11 314 1391
Fax: +27 (0)11 314 1681
midrand@krohne.co.za
Spain
Spain
SpainSpain
I.I. KROHNE IBERIA, S.r.l.
Poligono Indust rial Nilo
Calle Brasil, nº. 5
28806 Alcalá de Henares Madrid
Phone: +34 (0)91 883 2152
Fax: +34 (0)91 883 4854
krohne@krohne.es
USA
USA
USAUSA
KROHNE, Inc.
7 Dearborn Road
Peabody, MA 01960
Phone: +1 (800) FLOWING
Phone: +1 (978) 535 6060 (in MA)
info@krohne.com
Representatives
Algeria
Argentina
Cameroon
Canada
Chile
Columbia
Croatia
Denmark
Ecuador
Egypt
Finland
Gabon
Ghana
Greece
Hong Kong
Hungary
Indonesia
Iran
Ireland
Israel
Ivory Coast
Japan
Jordan
Kuwait
Libya
Lithuania
Malaysia
Mauritius
Mexico
Morocco
New Zealand
Peru
Portugal
Romania
Saudi Arabia
Senegal
Slovakia
Slovenia
Sweden
Taiwan
Thailand
Tunisia
Turkey
Venezuela
Yugoslavia