Keyence FS-N10 Series Instruction Manual

Page 1
1
Digital Fiber Sensor
FS-N10 Series
Instruction Manual
Read this manual before using the product in order to achieve maximum performance. Keep this manual in a safe place after reading it so that it can be used at any time.
Hints on Correct Use
malfunction or be damaged due to no ise.
When using a commercially available switching regulator, ground the frame ground terminal
and ground terminal.
Do not use the FS Series outdoors, or in a place where extraneous light can enter the light-
receiving element directly.
Due to individual dispersio n characteristics and the dif ference in fiber unit models, the maxi-
mum sensing distance or displayed value may not be the same on all units.
If the sensor is used for a long time with the APC function enabled and the LED is imposed
with a heavy load, the current consumption of the sen sor for light emission will become con­stant and 'END APC' will be displayed. The sensor can still be used in this case. However, replace the sensor if even small changes in received light intensity should be detected for precise detection.
Precautions on Regulations and Standards
UL Certificate
This product is an UL/C-UL Listed pr oduct.
UL File No. E301717
Category NRKH,NRKH7
Enclosure Type 1 (Based on UL50)
Be sure to consider the following specifications when using this product as an UL/C-UL Listed Product.
Use the power supply with Class 2 output defined in NFPA70 (NEC: National Electrical Code).
Power supply/ Control input/ Control output shall be connected to a single Class 2 source only.
Use with the over current protection device which is rated 30V or more and not more than 1A.
Included accessories
Instruction Manual 1pc.
FS-N10 Series Quick Start
Quick Start
*1 This is a channel switch on 2-output types. This is not equipped with the 0-line type. *2 Press and hold the [MODE] button to make advanced setting changes.
Names of Each Part of the Main Unit and Expansion Unit
*1 Setting to "M" locks the power mode to MEGA mode. The switch is a channe l switch for the
two output type. This is not equipped with the 0-line type.
*2 On the FS-N1C, this is an M8 connector rather than a cable. On the FS-N1EN, this is
an e-CON connector.
Mounting Unit
Mounting on a DIN Rail
1 Align the claw at the bottom of the main body with
the DIN rail, as shown in figure1. While pushing the main body in the direction of the arrow 1, push down in the direction of arrow 2.
2 To dismount the sensor, raise the main body in
the direction of the arrow 3 while pushing the main body in the direction of arrow 1.
Installation on a Wall (Main Unit Only)
1 Attach the unit to the optional mounting bracket (OP-
73880), and secure with two M3 screws as shown in figure2.
Connecting Fiber Unit
1 Open the dust cover in the direction shown by
arrow 1.
2 Move the fiber lock lever in the direction shown
by arrow 2.
3 Insert a fiber unit into the amplifier as indicated
by arrow 3 (approximately 14 mm).
4 Move the fiber lock lever in the direction shown
by arrow 4 to secure the fiber.
Failure to follow these instructions may lead to death or seri­ous injury.
Failure to follow these instructions may lead to injury.
Failure to follow these instructions may lead to product dam­age (product malfunction, etc.)
Provides additional information on pr oper operation.
This provides useful tips for the feature being descr ibed.
See "FS-N10 Series User's Manual" for details on the features of the FS-N10 Series and detailed instructions for configuration.
This product is just intended to detect the object(s). Do not
use this product for the purpose to protect a human body or a part of human body.
This product is not intended for use as explosion-proof
product. Do not use this product in a hazardous location and/or potentially explosive atmosphere.
This product uses DC power. Do not apply AC power. The
product may explode or burn if an AC voltage is applied.
Danger
Warning
Caution
Note
Tip
Warning
Fine sensitivity adjustment
Mode/Output *2
Press the [MODE] button once, then
to select L-on or D-onuse
Preset function
Configure easily with a single press when receiving light
DownUp
Power select switch *
1
Standard ⇔MEGA (fixed)
Setting value
Light intensity
Sensitivity setting
Press once each for workpiece/no workpiece
Sub screen (Displayed in green)
Main screen (Displayed in red)
Dust cover
Fiber lock lever
Manual button
( )
MODE button (MODE)
Power select switch*
1
Cable*
2
Expansion protective cover
Expansion connector
Preset button (PRESET)
SET button (SET)
Operation status indicators
Digital display
PST indicator
DTM indicator
3
2
figure1
1
OP-73880
figure2
Fiber insertion sign
1
3
2
4
96M11513
Page 2
2
.
Connecting Multiple Amplifiers
Up to 16 expansion units can be connected to one main un it. However, two output types will be treated as two main units.
1 Remove the protection covers from the main unit
and expansion unit(s).
2 Install the amplifiers on the DIN rail one at a time.
3 Slide the main unit and expansion unit(s) together.
Engage the two claws of the expansion unit with the recesses on the main unit side until you hear/ feel a click.
4 Attach the end units (opt ion: OP-26751) to the DIN
rail in the same way as step (2).
5 Secure the amplifiers between the end units.
Tighten the screws at the top (two screws x two units) with a Phillips screwdriver to fix the end units.
Calibration Method
Detecting Even Small Differences
z
Two-point Calibration
Two-point calibration is the basic method of calibration. Press the [SET] button onc e without the workpiece, and then press it once agai n with the workpiece.
1 Press the [SET] button with no workpiece.
[SET] will be displayed on the sub-menu (green display).
2 Press the [SET] button with workpiece.
The values will be set and the submenu (green display) will flash. The values will be set to the mid-point between the light intensity when there is no workpiece, and the light intensity when there is a workpiece.
If "----" flashes for two seconds on the main screen, the light intensity is too small between conditions when the workpiece is absent and when it is present. These values will be set, but there is the possibility that det ection may become unstable.
Other Calibration Methods
Increased Resistance to Dust and Dirt
z
Maximum Sensitivity Calibration
In the state shown below, press and hold the [SET] button for three seconds or more. Stop pushing when "5'6" flashes. The sensitivity is set slightly higher than the received light intensity.
Calibrate with a Moving Workpiece
z
Fully Automatic Calibration
Press and hold the [SET] button with no workpiece in place. While “5'6” is flashing, pass a workpiece through. (Continue pressing the [SET] button while the workpiece passes through.)
Position Workpiece
z
Positioning Calibration
Press the [SET] button with no workpiece. Place the workpiece in the location you wish to position it. Press and hold the [SET] button for at least 3 seconds. Release the button when "5'6" flashes.
Simple, User Friendly Functions
Setting the Current Value to 100.0
With the FS-N10 Series, you can set the current value to 100.0 using simple operations. Standardizing the current value makes it possible for the sensor amplifiers t o instantly differ­entiate reductions in light intensity and is useful in predicting the need for maintenance.
If a thin fiber unit is used, an adapter provided with the thin fiber unit will be required. Unless the correct adapter is connected, the thin fiber unit will be loose and not detect targets correctly (the adapter is supplied with the fiber unit).
To connect the coaxial reflective type fiber unit to the amplifier, connect the
single-core fiber to the transmitter side, and connect the multiple-core fiber to the receiver side.
Mount on DIN rail and install on metal surface when connecting to multiple amplifiers or mounting main units together.
When connecting with units other than N-bus (a general term for the KEY­ENCE wire-saving connection system) compatible sensor amplifiers, including the FS-N10 Series, and the network unit NU Series, consult your nearest KEYENCE dealer.
Turn the power off before connecting multiple expansion units.
D o not touch the expansion connector with your bare hands.
Note
φ1.3
φ1.0
Adapter A
(OP-26500)
Adapter B
(OP-26501)
Cable outer dia Adapter Appearance
Receiver
Transmitter
Single-core fiber
Multi-core fiber
Warning
Note
OP-26751 (a set of two)
Workpiece
Workpiece
The various Preset functions listed below cannot be used when the Zero­Shift function is enabled. Disable the Zero-Shift function before executing the following functions.
The Preset functions are not suited for transparent workpieces and other cases of detection with low light intensity differences.
You can disable various Preset functions by pressing and holding the [PRESET] button.
Workpiece
Thrubeam model
: with
workpiece
: without
workpiece
Reflective model
Press and hold for 3 seconds or more
Press and hold for 3 seconds or more
Workpiece
Common to
Thrubeam
and
Models
Reflective
While pressing the [SET] button
pass through a workpiece
Settings complete
Press and hold until "
UGV
" flashes
Common to
Thrubeam
and
Models
Reflective
Workpiece
Press [SET] button once with no workpiece
Press and hold [SET] button with
workpiece
Settings complete
Press and hold until "
UGV
" flashes
Note
Tip
Page 3
3
z
Preset Function
This function adjusts the current value to "". With light received, press the [PRESET] button. The current value is set to "".
Pressing the [PRESET] button changes the setting and current value as shown below.
• Presetting with preset disabled:
The setting is changed to "". The setting can be changed via the normal calibration method.
• Presetting with preset enabled:
Only the current value is changed to "", and the setting is not changed.
.
z
Work-Preset Function
This function adjusts the current value to "". After executing the Preset function in a condition in which you would like "" to be dis­played, executing this function in a condition in which you would like "" to be displayed, will adjust any two points to "" and "".
Pressing the [PRESET] button and the button at the same time will set the current value at that time to "". Values that have been set to "" with the Preset function cannot be changed.
z
Maximum Sensitivity Preset Function
This function sets conditions that will serve as reference, to "" and adjusts conditions with slightly high light intensity as "". This is useful when you would like to perform detection using the background as a reference with reflect ive models. In the following conditions, press and hold the [PRESET] button for 3 seconds or more then release your finger when "#WVQ" is flashed.
The maximum value for the light intensity while the [PRESET] button is being pressed is
set to ", and light-intensity that is slightly higher than the maximum value at that time will be adjusted to "".
The setting value is ""
The green [PST] indicator will light up.
z
Full Auto Preset Function
This function automatically differentiates between two conditions (presence/absence of workpiece) and adjusts the current values to "" and "". This is effective for cases when the workpiece is moving at high-speed. Press and hold the [PRESET] button with no workpiece in place. While "#WVQ" is flashing, pass a workpiece through. (Continu e pressing the [PRESET] button while the work piece passes through.)
Near-maximum values while the [PRESET] button is being pr essed and held are
adjusted to "" and near-minimum values are adjusted to "" .
The setting value is changed to ""
The green [PST] indicator will light up.
Set Current Value to "0"
z
The Zero Shift Function
This function is primarily used with reflective models. Press the [PRESET] button and button at the same time.
The current value is set to "".
Green "PST" light s up
z
Disable the Zero Shift Function
Press and hold the [PRESET] button to disable the zero shift function.
Adjusting the current intensity value when it is too large (when saturated).
z
Use the Saturation Recovery Function
Press the [SET] button while pressing the [MODE] button.
After adjusting the light transmission level and light intensity sensitivity, the current values will be adjusted to within the ranges listed in the table that follows.
*HIGH SPEED
z
Disable Saturation Recovery
When the saturation recovery function is enabled, press th e [SET] button while pressing the [MODE] button to cancel it.
Handy Uses for the Preset Function
This function is most useful when performing simple detection using a thru­beam model fiber unit (e.g. completely blocked detectio n, such as when all light axes of the fiber unit are interrupted by opaque workpieces).
The Work-Preset function can be used while the Preset function is in use (when Preset is enabled).
When using this function with reflective models, "" will be displayed when there is a workpiece, and "" will be displayed when there is no workpiece, making it easy to know when t he workpiece is present or absent. Additionally, even when with a reflective model, the background h as higher light intensity than the workpiece, if you set a condition with low light intensity to "" using the Preset function and then using the Work-Preset function, register a condi­tion with high light intensity as "", the background will display as "" and when the workpiece is present, it will be displayed as "".
Cannot be executed when the Preset function is already being used (when the [PST] indicator is flashing). Press and hold the [PRESET] button to dis­able the Preset function be fore executing this function.
Green "PST" lights up
Press [PRESET] button once
with no
workpiece
Setting is "

"
Current value is "

"
Tip
Important
Green "PST" lights up
Current value is ""
100.0
[
PRESET] +
3.0
.0
Workpiece
Tip
Workpiece
Thrubeam model : with workpiece
: without workpiece
Press and hold for 3 seconds or more
Press and hold for 3 seconds or more
Reflective model
Note
Cannot be executed when the Preset function is already being used (when the [PST] indicator is flashing). Press and hold the [PRESET] button to dis­able the Preset function before executing this function.
The zero shift and preset function cannot be used together. To use the preset function, you must first disable the zero shift function.
Handy Uses for the Zero Shift Function
This function is primarily used to set the current value to "0" on a reflective model fiber unit.
When a reflective model is first installed, the light intensity is sometimes not set to "0". If this happens, using the zero shift function to set the value to "0" when there is no workpiece allows for easier understanding of the difference in light intensity.
Power mode Light intensity setting range
HSP*, FINE, TURBO 2047 ± 350
SUPER 4095 ± 500
ULTRA, MEGA 5000 ± 600
Handy Uses for the Saturation Recovery Function
This function is useful when the intensity value is saturated after installation. This function corrects the saturatio n via a simple operation, by automatically calibrating the light transmission level and light intensity gain.
Workpiece
Press and hold until "#WVQ" flashes
While pressing the [PRESET] button pass through a workpiece
Settings complete
Common to Thrubeam and Reflective Models
Note
Note
Tip
Press the [SET] button while pressing the [MODE] button.
Tip
Page 4
4
Output Switch
Either light-ON (L-on) mode or dar k-ON (D-on) mode can be selected.
1 While the current value is displayed, press the [MODE] button once.
2 Use to switch the output (.QP/&QP), then press the [MODE] button again.
The output change completes, and the display returns to the current value.
Connecting to External Devices
Cable Types
M8/e-CON Connector Types
M8 connector Cable (Sold Separately)
For FS-N11CN/N11CP/N12CN/N12CP/N13CP/N14CP
Error Displays and Corrective Actions
Consult your nearest KEYENCE office regarding error displays other than the ones listed above.
Initializing the Settings
Initialization Method
1 Press and hold the [SET] and [PRESET] buttons simultaneously for three seconds.
2 Use the to select "456", then press the [MODE] button. 3 Use the to select "K0K6", then press the [MODE] button.
After initialization is complete, the display returns to the current value.
z
Initial Settings
Using a Fiber Cutter and Cautions for Use
Using a Fiber Cutter
1 Insert the fiber into the cutter hole. 2 Bring down the blade in a single,
swift motion to cut the fiber.
Cautions for Using a Fiber Cutter
The fiber cutter comes with the fiber unit.
When cutting a fiber unit to be attached to the FS-N10 Series, be sure to use a gray fiber cut-
ter (OP-87098)
Stopping the blade midway could cause a bad cut plane, reducing the detection range.
Do not use the same hole twice.
Function Configuration
Basic Setting
*1 You can press the button to set between the range of 2 to 2.
FS-N11N/N12N/N13N/N14N FS-N11P/N12P/N13P/N14P
*1 FS- N11N/N13N only *2 FS- N13N/N14N only
*1 FS-N11P/N13P only *2 FS-N13P/N14P only
FS-N11MN
FS-N11CN/N12CN/N11EN/N12EN FS-N11CP/N12CP/N13CP/N14CP
*1 FS- N11CN/N11EN only *1 FS-N11CP/N13CP only
*2 FS-N13CP/N14CP only *3 FS-N11CP/N12CP only
Error display Cause Solution
ErC Overcurrent in the control output.
Check the load and return the current within the rated value.
ErE Failed to write/load the internal data. Perform initialization (p.4).
End APC Large load on the light sour ce.
Replace the sensor if highly precise detection is required.
Loc The keylock function is ON.
For disabling (setting) method, see "FS-N10 Series User's Manual".
12 to 24 VDC
DC3.3V
Black (Control output 1)
(Control output 2)
PLC, etc.
White
Pink
*2
*2
Brown
*1
0V
Load
Load
Blue
*1
Sensor main circuit
Overcurrent
protection circuit
(Short-circuit current 1 mA or less)
12 to 24 VDC
Black (Control output 1)
(Control output 2)
*2
PLC, etc.
White
Pink
*2
Brown
*1
0V
Load
Load
Blue
*1
Sensor main circuit
Overcurrent
protection circuit
(Short-circuit current 2 mA or less)
0 V
Brown
Black
Monitor output (1 to 5V)
Orange
Load
Blue
(Control output)
12 to 24 VDC
Device with input impedance 10 kΩ or more
Protection
circuit
Sensor main circuit
Overcurrent
protection circuit
*1
*1
DC3.3V
Sensor main circuit
Overcurrent
protection circuit
12 to 24 VDC
PLC, etc.
0V
(Short-circuit current 1 mA or less)
PLC, etc.
0V
(Short-circuit current 1 mA or less)
(Control output)
Load
*3
*1
*1
Sensor main circuit
Overcurrent
protection circuit
12 to 24 VDC
PLC, etc.
0V
(Short-circuit current 2 mA or less)
(Control output 1)
(Control output 2)
*2
Load
Load
123
4
M8 connector Pin layout
FS-N11CN/N12CN
e-CON connector Pin layout
FS-N11EN/N12EN
123
4
M8 connector Pin layout
OP-73864 (Cable length: 2 m)
OP-73865 (Cable length: 10 m)
1
2
3
4
Connected pin No.
Pin - Pin and wire color table
1 Brown 2 3 4
White Blue Black
Wire color
Setting Initial Value
Power mode FINE
Detection mode Std (Normal)
Setting value 50
Output switch L-on
Failure to follow the cautions below could reduce the detection range.
Press and hold for 3 seconds or more
Fiber
Always insert fiber from the side with writing
Fiber cutter (OP-87098)
2
1
MODE
Press and hold for 3 seconds or more
HIGH SPEED mode
FINE mode
TURBO mode
SUPER mode
ULTRA mode
MEGA mode
Normal sensitivity setting method
Percentage Calibration*
1
Zero-shift calibration
Settings complete
Go to detection setup mode
Go to display setup mode
Go to system setup mode
MODE
MODE
MODE
MODE
J52
(KPG 6WT$ 5W24
7.64 /')#
5V) 5V) 5V)
5'6

    
5VF
5'V2 15'V
'0&
(W0E &K52
5;5
5'6 5'6
Return to normal display
MODE
Page 5
5
Detection Settings
*1 Press the button to set between the range of and (ms).
*2 Press the button to set the retouch sensitivity to a range of between .'W and .'W
and set the warning output level to a range of between 12 and 2.
*3 Press the button to toggle between Q((/Q0/-''2. *4 Can be set between the range of and . *5 Can be set between the range of  and . *6 Can be used only for the types with the external input.
Note that these functions can be used via communication when connecting with the network unit NU Series.
*7 Only monitor output types (FS-N11MN).
Display Settings
*1 Press the button to toggle between 5VF/2`2A/D`DA/2AD`/2`DA
*2 Press the button to set between the range of 2 and 2.
System Settings
*1 Main unit only.
Two Ou tpu t
*2
*1 Press the button to set between the range of and (ms).
*2 Only 2 output types (FS-N13N/N13P/N14N/N14P/N13CP/N14CP).
Normal (light intensity) detection mode
DATUM1 mode *
2
Timer OFF
Off-delay timer *
1
On-delay timer *
1
One-shot timer *
1
DATUM2 mode *
2
Area detection mode
Rising Edge Detection Mode
Falling Edge Detection Mode
Settings complete
Go to display setup mode
Go to system setup mode
Return to original detection setup mode
External input off
External calibration input
Preset input
Zero shift input
Reset input
Light transmission OFF input
Pause mode transition input *
3
Sleep mode transition input
Light emission power selection *
4
Analog scaling *
5
Return to normal display
*6
*7
MODE
MODE
MODE
Normal display method
Reverse display
Settings complete
Go to system setup mode
Go to detection setup mode
Return to original display setup mode
Sub-display off
Extended display
Bar display
Excess gain display
Light intensity hold display *
1
Excess gain hold display *
1
L-on / D-on display
Disable the saturation of the Preset function
Enable the saturation of the Preset function *
2
Return to normal display
MODE
MODE
Disable APC
Enable APC
Settings complete
Go to detection setup mode
Go to original display setup mode
Return to system setup mode
Normal operation
Twice the number of interference-prevention units as
56&
(response time 2 times slower)
Eco feature off
Enable eco feature
Reduce power consumption (response time 4 times slower)
Disable common key operations
Enable common key operations
Standard current value display
Maximum current value display (4 times hysteresis)
Return to normal display
*1
Light intensity detection mode
Limit setting output mode
Auto reset
User reset
Warning output mode
Timer OFF
Off-delay timer *
1
On-delay timer *
1
One-shot timer *
1
Settings complete
Return to normal display
MODE
Page 6
Specifications
*1 Use a cable length of 30 m or less for M8 connector and e-CON connector types. *2 Counted as 1 output when connecting with the network unit NU Series. *3 FS-N11MN only *4 SUPER : 1.2 ms, ULTRA : 1.8ms, MEGA : 4.2 ms *5 Input time is 25 ms (ON)/25 ms (OFF) only when external calibration input is selected. *6 In creases 100 mW (4.0 mA) for High Speed mode *7 One or two more units connected: -20 to +55°C; 3 to 10 more units connected: -20 to +50°C; 11 to 16 more units connected: -20 to +45°C. When using 2-outputs, one unit is counted as two units.
All temperature regulations are for when the unit is mounted on a DIN rail and installed on metal sheeting.
Type Standard 1 output High functionality 2 output
Monitor output
0-line
Cable/M8 connector
Cable
M8 connector
*1
e-CON connector
*1
Cable
M8 connector
*1
Cable -
Main unit/expansion unit
Main unit
Expansion unit
(with output cable)
Main unit
Expansion unit
(with output cable)
Main unit
Expansion unit
(with output cable)
Main unit
Expansion unit
(with output cable)
Main unit
Expansion unit
(with output cable)
Main unit
Expansion unit
(without output cable)
Model NPN FS-N11N FS-N 12N FS-N11CN FS-N12CN FS-N11EN FS-N12EN FS-N13N FS-N14N - - FS-N11MN
FS-N10
PNP FS- N11P FS-N12P FS-N11CP FS-N1 2CP - - FS-N13P FS-N14P FS-N13CP FS-N14CP -
Control output
1 output 1 output 1 output 1 output 1 output 1 output 2 output 2 output 2 output 2 output 1 output
N/A
*2
Monitor output (1 to 5 V)----------1 output­External input - - 1 input 1 input 1 input 1 input 1 input 1 input - - - ­Light source LED Red 4-element LED (wavelength 630 nm) Response time
50 μs (HIGH SPEED)/250 μs (FINE)/500 μs (TURBO)/1 ms (SUPER)/4 ms (ULTRA)/16 ms (MEGA)
Output toggle Light-ON/dark-ON toggle Timer function Timer OFF, OFF delay, ON delay, One-shot Control output
NPN output NPN open collector 24 V; 1 output max: 100 mA or less; 2 output total:
100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less
PNP output PNP open collector 24 V; 1 output max: 100 mA or less; 2 output total:
100 mA or less (used stand-alone)/20 mA or less (multiple connections); residual voltage 1 V or less
Monitor output
*3
1 to 5 V voltage output; load resistance 10 kΩ or more; repeat precision ± 0.5% of F.S.; 1 ms response time (HIGH SPEED, FINE, TURBO)
*4
External input
input time 2 ms (ON)/20 ms (OFF) or more
*5
Expansion Units Up to 16 units can be connected (total of 17 units including the main unit). Note that the two-output type is counted as two units. Protection circuit Protection against reverse power connection, output overcurrent, and output surge Number of interference
prevention units
0 for HIGH SPEED; 4 for FINE; 8 for TURBO/SUPER/ULTRA/MEGA (When set to double, the number of interference-prevention units will be doubled.)
Rating
Powe r vo ltage
12 to 24 V DC ± 10% ripple (P-P) 10% or less
NPN
Normal:900 mW or less (36 mA max. at 24 V, 48 mA max. at 12 V)
*6
Eco on mode:800 mW or less (32 mA max. at 24 V, 39 mA max. at 12 V)
*6
Eco Full mode:470 mW or less (19 mA max. at 24 V, 23 mA max. at 12 V)
PNP
Normal : 950 mW or less (39 mA max. at 24 V, 52 mA max. at 12 V)
*6
Eco on mode : 850 mW or less (35 mA max. at 24 V, 44 mA max. at 12 V)
*6
Eco Full mode : 520 mW or less (21 mA max. at 24 V, 26 mA max. at 12 V)
Normal : 1050 mW or less (42 mA max. at 24 V,
56 mA max. at 12 V)
*6
Eco on mode : 950 mW or less (38 mA max. at 24 V,
47 mA max. at 12 V)
*6
Eco Full mode : 600 mW or less (24 mA max. at 24 V,
29 mA max. at 12 V)
-
Environme ntal resistance
Operating ambient luminance
Incandescent lamp: 20,000 lx or less; Sunlight: 30,000 lx or less
Operating ambient temperature
-20 to +55 °C (no freezing)
*7
Operating ambient humidity
35 to 85% RH (no condensation)
Vibration resistance
10 to 55 Hz Compound amplitude 1.5 mm, 2 hours for each of X,Y,Z axis
Shock resistance
500 m/s2 3 times for each of X,Y,Z axis Case material Both main unit and expansion unit housing material: Polycarbonate Case dimensions H30.3mm x W9.8mm x L71.8mm Weight Approx 75g Approx 45g Approx 22g Approx 22g Approx 22g Approx 22g Approx 80g Approx 70g Approx 22g Approx 22g Approx 75g Approx 20g
IIIInnnn
str
stru
stru
stru
ument
menta
menta
menta
ation for Science
tion for Science a
tion for Science a
tion for Science aannnndddd I I IInnnndddduuuussss
try
try
try
try