See Figure 3 for the Drive Layout. See Table 4, on page 17, for description of the Keypad,
4-Digit Display, LEDs, and Potentiometer.
The drive contains 8 LEDs to provide indication of the drive’s status and operating mode (REM,
LCL, FWD, REV, STOP, OL, PGM, Hz). The Keypad is used for Local Operation of the drive.
For Remote Operation see Function Group 2, on page 57. To operate the drive using the
Potentiometer, set Function 2.00 to "0001".
WARNING! Do not depend on the LEDs or the 4-Digit Display to no longer be
illuminated as a guaranteed power off condition. Be sure that the main power switch or
circuit breaker is in the "OFF" position before servicing the drive.
FIGURE 3
DRIVE LAYOUT
(SHOWN WITH FRONT COVER REMOVED)
(SEE DESCRIPTIONS, ON PAGE 17)
16
RUN
STOP
FWD
REV
MEMORY
MODULE
DESCRIPTIONS OF 4-DIGIT DISPLAY, LEDs, KEYS, AND POTENTIOMETER
TABLE 4
No. Feature Description
1
2
4-Digit Display: Provides readout of drive status, operating parameters,
and faults.
REM LED: Indicates that the drive is set for Remote Operation.
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RUN
STOP
FWD
REV
LCL LED: Indicates that the drive is set for Local (Keypad) Operation.
FWD LED: Indicates that the drive is set for Forward Direction.
REV LED: Indicates that the drive is set for Reverse Direction.
STOP LED: Indicates that the drive is in Stop Mode.
OL LED: Indicates that the drive is in Overload.
PGM LED: Indicates that the drive is in Program Mode.
Hz LED: Indicates that the display is set to show Drive Output Frequency
(in Hz).
RUN / STOP Key: Starts and Stops the drive.
FWD/REV Key: Changes motor direction.
Up Key: Increases Output Frequency, Set Frequency, Function Number
Value, and Code setting.
Down Key: Decreases Output Frequency, Set Frequency, Function
Number Value, and Code setting.
Left Shift / Reset Key: Moves the changeable digit or Resets the drive
after a fault has cleared.
LOCAL / REMOTE Key: Used to toggle between Local (Keypad)
Operation or Remote Operation. When in Local (Keypad) Operation, the
LCL LED will remain illuminated. When in Remote Signal Operation, the
REM LED will flash 1 second on and 1 second off.
PROGRAM / DISPLAY Key: Puts the drive into Program Mode or Display
Mode. If pressed while Set Frequency is displayed, the previously entered
Function Number will be shown. If pressed while Function Number is
displayed, the Set Frequency will be shown. When more than one display
function is enabled, the key is used to toggle between displays.
17
18
READ / ENTER Key: Reads or Enters a Function Value or Code Setting.
Potentiometer: Sets the Drive Output Frequency in lieu of the Keypad. To
change the Keypad for Potentiometer Operation, set Function 2.00 to
code "0001".
17
7 MOUNTING INSTRUCTIONS
It is recommended that the drive be mounted vertically on a flat surface with adequate
ventilation. Leave enough room above and below the drive to allow for AC Line, motor
connections, and any other connections that are required. Care should be taken to avoid
extreme hazardous locations where physical damage can occur. When mounting the drive in an
enclosure, the enclosure should be large enough to allow proper heat dissipation so that the
ambient temperature does not exceed 40 °C (104 °F) at full rating. See Figure 4, below, and
Figure 5, on page 19.
WARNING! DO NOT USE THIS DRIVE IN AN EXPLOSIVE ENVIRONMENT. AN
EXPLOSION CAN CAUSE SERIOUS OR FATAL INJURY. THIS DRIVE IS NOT EXPLOSION
PROOF.
FIGURE 4
CASE "A" DRIVES MECHANICAL SPECIFICATIONS (INCHES / mm)
0.225
4X Ø
5.72
RUN
STOP
FWD
REV
18
KBDF SERIES
2.80
71.1
3.40
86.4
6.785
172
7.25
184
5.10
130
CASE "B" DRIVES MECHANICAL SPECIFICATIONS (INCHES / mm)
FIGURE 5
0.225
4X Ø
5.72
RUN
STOP
FWD
REV
7.357 7.825
187
199
KBDF SERIES
3.80
96.5
4.40
112
6.25
159
19
8 ELECTRICAL CONNECTIONS
The drive is designed with contactor-type feed-throughs to facilitate wring of the AC Line input,
Motor, and Ground connections, as shown in Figures 7 – 13, on pages 22 – 24. See Table 5, on
page 22.
The removable cover allows access to the terminal blocks and jumpers for wiring and setting up
the drive for Remote Operation in lieu of the Keypad (Local Operation).
Note: Wire the control in accordance with the National Electrical Code requirements and other
local codes that may apply to the application.
WARNING! HIGH VOLTAGE! Read Safety Warnings, on page 9, before using the
drive. Disconnect the main power before making connections to the drive. To avoid
electric shock, be sure to properly ground the drive.
Application Notes:
1. To avoid erratic operation, do not bundle AC Line input and motor wires with each other. Also,
do not bundle motor wires from multiple drives in the same conduit. Use shielded cables on all
signal wiring over 12" (30 cm). The shield should be earth grounded on the drive side only.
2. Be sure to properly fuse each AC Line conductor that is not at ground potential. Do not fuse
neutral or grounded conductors. A separate AC Line switch or contactor must be used as a
disconnect so that each ungrounded conductor is opened. For fuse or circuit breaker selection,
see Table 3, on page 15. Also see Section 8.2, on page 24.
3. If operation with a Ground-Fault Circuit-Interrupter (GFCI) is required, see Function 0.04, on
page 55.
20
GENERAL CONNECTION DIAGRAM
FIGURE 6
2
2
1
3
Notes: 1. Multi-Function Input Terminals (MFIT 1 – 5 on TB1 of the drive) are factory set for
N.O. Contacts or NPN Transistors (J1 set to the "N.O. / NPN" position), which use the internal
power supply. For NPN Transistors, which use an external power supply (5 – 24 Volts DC), set
Jumper J1 to the "EXT" position. For PNP Transistor circuits, which use the internal power
supply or an external power supply (5 – 24 Volts DC), set Jumper J1 to the "PNP" position.
2. Multi-Function Output Relay Contact Ratings: 1 Amp at 30 Volts DC, 0.5 Amp at 125 Volts
AC, and 0.25 Amp at 250 Volts AC. 3. Multi-Function Input Terminals (MFIT 6 – 7 on TB1 of the
IODF) only accept N.O. Contacts or NPN Transistors (which use the internal power supply).
21
DRIVE TERMINAL BLOCK WIRE AND TIGHTENING TORQUE SPECIFICATIONS
TABLE 5
Maximum
Wire Size
(Cu)
Description Location Model
Multi-Function Input
Terminals and Signals In/Out
TB1 on Drive and IODF
(Under Cover)
(2)
(1)
AWG mm2Lbs-in kg-cm
All 16 1.312.7 3.1
Recommended
Tightening
Torque
Multi-Function
Output Relay
AC Line Input and Ground Top of Drive
AC Line Input and Ground Top of Drive
Motor and Ground Bottom of Drive
Motor, Ground, and Dynamic
Brake Module
(3)
TB2 on Drive
and TB3 on IODF
(Under Cover)
Bottom of Drive
(2)
Case
Case
Case
Case
16 1.312.6 2.9
All
14 2.087 8.1
"A"
12 3.3112 14
"B"
14 2.087 8.1
"A"
12 3.3112 14
"B"
Notes: 1. Case "A" Drives: Models KBDF-13, 23, 23F, 23D, 23P, 14, 24, 24F, 24D, 24P, 16, 27,
27F, 27D, 27P. Case "B" Drives: Models KBDF-29, 42, 43, 45, 48. 2. The IODF is an optional
accessory for all models. 3. The Dynamic Brake Module is an externally mounted optional
accessory for Case "B" drives only.
8.1 AC LINE INPUT AND GROUND
Connect the AC Line input and ground (earth) to the drive as shown in Figures 7 – 13, on pages
22 – 24. Connect the Ground (earth) to the drive chassis Terminal "GND".
Note: The rated AC Line voltage of the drive must match the actual AC Line input voltage. See
Electrical Ratings, Table 3, on page 15.
Models KBDF-13, 14, 16:
Designed for 115 Volt
1-phase AC Line input. Connect the AC Line input
hot lead to Terminal "L1" and the neutral lead to
MODELS KBDF-13, 14, 16
FIGURE 7
AC LINE AND GROUND CONNECTIONS
Terminal "N". See Figure 7.
Note: 230 Volts AC will be applied to the motor
with 115 Volt AC Line input.
22
Models KBDF-23D, 24D, 27D: Designed for 115 and 208/230 Volt 1-phase AC Line input. For
115 Volt Line input, connect the AC Line input hot lead to Terminal "L1" and the neutral lead to
Terminal "N". For 208/230 Volt AC Line input, connect to Terminals "L1" and "L2". See Figure 8.
Note: 230 Volts AC will be applied to the motor with 115 Volt AC Line input.
MODELS KBDF-23D, 24D, 27D
AC LINE AND GROUND CONNECTIONS
Models KBDF-23, 23F, 24, 24F, 27, 27F:
Designed for 208/230 Volt 1-phase AC Line input.
Connect the AC Line input to Terminals "L1" and
"L2". See Figure 9.
Models KBDF-23P, 24P:
Volt 3-phase AC Line input. Connect the AC Line
input to Terminals "L1", "L2", and "L3". See Figure
10.
Models KBDF-27P, 29:
Connect the 1-Phase AC Line Input to Terminals "L1" and "L2". Connect the 3-Phase AC Line
input to Terminals "L1", "L2", and "L3". See Figure 11.
Designed for 208/230
Designed for 208/230 Volt 1-Phase and 3-Phase AC Line Input.
AC LINE AND GROUND CONNECTIONS
FIGURE 8
FIGURE 11
MODELS KBDF-27P, 29
MODELS KBDF-23, 23F, 24, 24F, 27, 27F
AC LINE AND GROUND CONNECTIONS
AC LINE AND GROUND CONNECTIONS
FIGURE 9
FIGURE 10
MODELS KBDF-23P, 24P
23
Models KBDF-42, 43, 45, 48: Designed for
400/460 Volt 3-Phase AC Line Input. Connect
the AC Line Input to Terminals "L1", "L2", and
"L3". See Figure 12.
8.2 AC LINE INPUT FUSING
The drive does not contain AC Line fuses. For the recommended fuse or circuit breaker rating,
see Table 3, on page 15. Do not fuse motor leads.
Most electrical codes require that each ungrounded conductor contain circuit protection. Do not
fuse neutral or ground connections.
It is recommended to install a fuse (Littelfuse 326, Buss ABC, or equivalent) or a circuit breaker
(Square D QOU or equivalent) in series with each ungrounded conductor.
8.3 MOTOR AND GROUND
Connect the Motor to Terminals "U", "V", and "W". Connect the Ground (earth) to Terminal
"GND". See Figure 13.
Motor cable length should not exceed 100 feet (30 m) – special reactors may be required –
consult our Sales Department.
Be sure that the Motor Current (Function 0.01) is programmed to the actual motor nameplate
current rating. Do not exceed the drive's maximum current rating.
Note: If the motor does not rotate in the desired direction, either: 1. Reverse any two motor
leads (with the AC Line disconnected and the motor stopped). 2. Use the FWD/REV Key. 3. Use
Function 1.02 to reprogram forward and reverse direction.
FIGURE 13
MOTOR AND GROUND CONNECTIONS
All Case "A" Drives All Case "B" Drives
MODELS KBDF-42, 43, 45, 48
AC LINE AND GROUND CONNECTIONS
FIGURE 12
24
8.4 REMOTE OPERATION
The Drive is designed with a removable cover to access the Multi-Function Inputs and Outputs
and jumpers to set up the drive for remote operation. It also allows access to install the optional
accessories. See Table 6. Also see Table 7, on page 26.
To remove the cover, press on the finger grips on both side corners of the cover until the
retaining clips disengage from the base and lift it up.
After mounting the drive, setting the jumpers, and all connections are complete, replace the
cover by inserting the tab into the slot on the drive and gently pressing down on the cover until it
snaps into place.
IMPORTANT: For remote operation of the drive, both a Start Command and a Frequency
Command must be given.
Application Notes:
1. For additional programmable Multi-Function Inputs and Output install the Optional IODF
Input/Output Multi-Function Expansion Module (Part No. 9646). The IODF mounts onto the drive
under the front cover. See Appendix A, on page 64.
2. DIDF For direct communication between the drive and Modbus RTU protocol, install the
optimal DIDF RS-232 and RS-485 Modbus RTU Communication Module (Part No. 9647). See
Appendix B, on page 67.
TABLE 6
DRIVE MULTI-FUNCTION INPUT TERMINAL, FUNCTION,
AND FACTORY CODE ASSIGNMENT
Location Drive IODF
Multi-Function
Input Terminal*
Number On
Terminal Block
Function
Factory Code
Setting
Code
Description
1 2 3 4 5 6 7
5 6 7 8 9 14 15
7.00 7.01 7.02 7.03 7.04 7.05 7.06
0000 0001 0002 0009 0010 0003 0004
Preset
Frequency
Operation
Preset
Frequency
Operation
Preset
Frequency
Operation
Reset N.O. Start
Up
Frequency
Command
Down
Frequency
Command
*Each Multi-Function Input Terminal is controlled by a specific Function. Although factory set to
a specific code, they can also be reprogrammed to any code "0000" – "0012" listed in Table 7,
on page 26. Also see Function Group 7, on page 60.
25
DRIVE INPUT AND OUTPUT CONNECTIONS
TABLE 7
1
Terminal Blocks No. Description Specifications
1 Power Supply –5 Volts DC at 1 mA Max.
2 Power Supply +5 Volts DC at 1 mA Max.
3 Analog Signal Input
0 – ±5 / ±10 Volts DC,
0 – 20 / 4 – 20 mA DC
4 Common2 ──
TB1
on Drive
312 456 8791110 12
TB1
on IODF
5 MFIT 1
6 MFIT 2
N.O. Contacts or NPN / PNP Transistors
7 Preset Frequencies,
Up Frequency Command,
Down Frequency Command,
Accel/Decel #2,
7 MFIT 3
8 MFIT 4
9 MFIT 5
10
External
Power Supply Input
Forward/Stop Command,
Reverse/Stop Command,
External Fault (N.O. Contact), Reset, N.O.
Start (2-Wire or 3-Wire Start/Stop), N.C.
Stop (3-Wire Start/Stop),
External Fault (N.C. Contact)
5 – 24 Volts DC Input
11 Common2 ──
12 Analog Output 0 – 5 Volts DC
Open Collector
13
Output
14 MFIT 6
15 MFIT 7
MFIT 1 – MFIT 5 Above
NPN
Same As
16 Common2 ──
17 Power Supply +5 Volts DC at 1 mA Max.
18 Analog Input #2 0 – 2.5 thru 0 – 25 Volts DC
2
──
Run, Fault,
Target Frequency (5.03 ± 5.04),
Frequency Threshold Level (> 5.03 –5.04),
Frequency Threshold Level (< 5.03 +5.04),
2
t or I•t Fault, Load Loss (See 5.05),
I
External Fault
TB2
on Drive
on IODF
TB3
19 Common
N.O. Normally Open
COM Relay Common3
N.C. Normally Closed
Notes: 1. For additional inputs and outputs, install the optional IODF Input/output Multi-Function
Expansion Module (Part No. 9646). See Appendix A, on page 64. 2. Common Terminals "4",
"11", "16", and "19" are internally wired together. 3. Relay Commons are not internally wired to
Common Terminals "4", "11", "16", and "19".
26
8.4.1 START/STOP AND FORWARD/REVERSE
The drive can be started and stopped using 2-Wire or 3-Wire Start/Stop Contacts connected to
the Multi-Function Input Terminals. Also, some applications may require a jumper, which will
provide automatic starting of the drive when either a forward or reverse contact is closed. See
Figure 14, below, for the connections and drive programming.
Application Note: A frequency command must also be given for the drive to run.
WARNING! STOP is not to be used as an Emergency Stop or safety disconnect
since it is not fail-safe. Use only the AC line for this purpose.
APPLICATION NOTES FOR AUTO/MANUAL START MODE (FUNCTION 1.05)
1. If the drive is set for Manual Start Mode ("0000" (factory setting)), Manual Start with Ride-
Through ("0001"), or Auto Start After Undervoltage Fault Clears ("0002"), it will have to be
manually restarted after the external fault has been cleared. Use the Reset Key on the Keypad
or the external Reset Contact to restart the drive.
2. If the drive is set for Auto Start All Faults (Except Short circuit Fault) ("0003"), it will
automatically restart after the external fault has been cleared, for the number of restart attempts
set in Function 1.07 (factory set to 3). After which, the drive will have to be restarted using the
Reset Key on the Keypad or the external Reset Contact.
3. If the drive is set for Auto Start All Faults (Except I
2
t, I•t, and Short Circuit Faults) ("0003"), it
will automatically restart after the external fault has been cleared.
8.4.1.1 AUTOMATIC START
Some applications will require that the drive automatically start when the AC Line is applied. See
Figure 14, for connections and drive programming.
WARNING! Using a jumper to automatically start or restart the drive will cause the
motor to run at the Set Frequency of the drive when the AC Line is applied.
FIGURE 14
AUTOMATIC START
CONNECTIONS AND DRIVE PROGRAMMING
Program Function Setting
1.00: Run/Stop-Forward/Reverse Control 0001: External Contacts*
0002: Auto Start After Undervoltage Fault Clears
1.05: Auto/Manual Start Mode
(Choose a code (0002, 0003, or 0004) as required by
the application.)
7.15: Increment of Up/Down Frequency (Hz) 0.01 – 30.00 Hz (1.00 Hz*)
0000: Free Running*
0001: Incremental Change
*Factory setting.
**Use with Function 7.14 code "0001" only.
36
8.4.2.4 PRESET FREQUENCY CONTROL
The drive is factory programmed for 7 Preset Frequencies, which can be selected using remote
contacts connected to Multi-Function Input Terminals "1", "2", and "3" (TB1 Terminals "5", "6",
and "7"). See Table 8, for the terminals to select for the preset frequencies.
The 7 Preset Frequencies are obtained using a combination of Multi-Function Input Terminals 1,
2, 1+2, 3, 1+3, 2+3, 1+2+3. The Preset Frequencies can be changed from their factory settings
by reprogramming Function 7.07 – 7.13.
8th Preset Frequency: If none of the Multi-Function Input Terminals are activated, the drive will
operate at the Stored Set Frequency (Function No. 3.00) of 5.00 Hz. If the 8th Preset Frequency
is not required, set Function No. 3.00 to 00.00 Hz.
Note: For Preset Frequency Operation, the drive does not have to be reprogrammed for
Other Programmable Functions of the Multi-Function Output Relay (Function 5.00)
Description
Code
0000: Run
0001: Fault
0002: Target Frequency (Function 5.03 ± Function 5.04)
0003: Frequency Threshold Level (>Function 5.03 – Function 5.04)
0004: Frequency Threshold Level (<Function 5.03 + Function 5.04)
0005: I
2
t or I•t Fault
0006: Load Loss (See Function 5.05)
0007: External Fault
41
8.4.5 ANALOG OUTPUT
An Analog Output is provided, which puts out a 0 – 5 Volt DC signal and will linearly follow the
parameter programmed in Analog Output 1 Mode (Function 5.14). It can be used to monitor
Output Frequency, Set Frequency, Motor Voltage, Bus Voltage, and Motor Current. See Figure
34, for connections and drive programming. See Figure 35, for Analog Output 1 Gain settings
(factory set to 100%).
FIGURE 34
ANALOG OUTPUT
CONNECTIONS AND DRIVE PROGRAMMING
Program Function Setting
0000: Output Frequency*
0001: Set Frequency
5.14: Analog Output 1 Mode
5.15: Analog Output 1 Gain (%) 0 – 200% (100%*)
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
*Factory setting.
FIGURE 35
ANALOG OUTPUT GAIN
42
9 HIGH VOLTAGE DIELECTRIC WITHSTAND TESTING (HI-POT TEST)
Testing agencies such as UL, CSA, etc., usually require that equipment undergo a hi-pot test. In
order to prevent catastrophic damage to the drive, which has been installed in the equipment,
the following procedure is recommended. A typical hi-pot test setup is shown in Figure 36.
All drives have been factory hi-pot tested in accordance with UL requirements.
CAUTION! This is an AC Hi-Pot Test for all models except models with built-in RFI (EMI)
filters. On Models KBDF-23F, 24F, 27F only perform a DC Hi-Pot Test.
WARNING! All equipment AC Line inputs must be disconnected from the AC
power.
Connect all equipment AC power input lines together and connect them to the H.V. lead of the
Hi-Pot Tester.
Connect the RETURN of the Hi-Pot Tester to the frame on which the drive and other auxiliary
equipment are mounted.
The Hi-Pot Tester must have an automatic ramp-up to the test voltage and an automatic ramp-
down to zero voltage.
Note: If the Hi-Pot Tester does not have automatic ramping, then the hi-pot output must be
manually increased to the test voltage and then manually reduced to zero. This procedure must
be followed for each machine being tested. A suggested Hi-Pot Tester is Slaughter Model 2550.
CAUTION! Instantly applying the hi-pot voltage will cause irreversible damage to the drive,
which will void the warranty.
FIGURE 36
TYPICAL HI-POT TEST SETUP
IMPORTANT!
CAUTION!
RUN
STOP
FWD
REV
KBDF SERIES
43
10 DRIVE OPERATION
Before operating the drive, read Section 10.3, below, for instructions on the Keypad Operation.
See Figure 3, on page 16, for the keypad layout. The 4-digit display can indicate various
functions of the drive: Set Frequency, Motor RPM, Output Current and Voltage, Custom Units,
Function Numbers, Function Codes or Values, and Fault Codes. See Section 11, on page 52.
See Section 12, on page 54, for information on programming the drive. If an error message
appears while programming the drive, see Section 11, on page 52.
10.1 START-UP PROCEDURE
After the drive has been properly setup and all connections completed, the start-up procedure
can begin. If the AC power has been properly brought to the drive, the LEDs will indicate the
drive's status, as described in Table 4, on page 17. See Section 11, on page 52, for the Digital
Readout Codes.
To start the drive, press the RUN Key. The motor will begin to accelerate to the Set Frequency.
The factory set frequency is 05.00 Hz.
10.2 LOCAL/REMOTE OPERATION
The drive can be used for Local (Keypad) or Remote Operation. In this mode, the drive
frequency setting can be toggled between the Keypad and a process signal using the
LOCAL/REMOTE Key.
To disable the Local/Remote toggling feature, see Function 2.03, on page 57.
Note: The drive will power up in the mode it was set in before it was powered off. If the drive
was in Local (Keypad) Operation (factory setting), it will power up in Local (Keypad) Operation. If
the drive was set for Remote Operation, it will power op in Remote Operation.
Application Note: The STOP Key will always stop the drive whether it is in Local (Keypad)
operation or Remote Operation.
WARNING! The STOP Key is never to be used as safety disconnect since it is
not fail-safe. Use only the AC Line for this purpose.
10.3 KEYPAD DESCRIPTION
The Keypad has eight (8) keys, which are used to program drive functions. The eight (8) LEDs
provide indication of the drive’s operational status. A Main Speed Potentiometer is also provided
to set the Drive Frequency (Function 2.00 set to "0001"). See Table 4, on page 17.
Note: To avoid damage, never operate the keypad with a screwdriver or other sharp-ended tool.
44
10.4 FLOW CHARTS FOR IMPORTANT PROGRAMMING FUNCTIONS
See Figures 37 – 44, on pages 45 – 51, for the flow charts to program important functions. The
flow charts also serve as a guide to understand the programming procedure.
Note: See Table 10, on pages 52 and 53, for a description of the Digital Readout codes.
FIGURE 37
FLOW CHART TO PROGRAM MOTOR CURRENT FROM 6.7 AMPS TO 5.5 AMPS
*Rating shown is for Models KBDF-27, KBDF-27F, KBDF-27D (2 HP, (1.5 kW)), and KBDF-29
(1-Phase). See Table 3, on page 15, for the factory setting of Function 0.01 for all other models.
45
FLOW CHART TO CHANGE SET FREQUENCY FROM 5.00 Hz TO 43.21 Hz*
FIGURE 38
(DRIVE IN STOP MODE)
RUN
STOP
*If Function 2.02 is set to "0000", frequency change requires pressing the ENTER Key.
Throughout this sequence, you must proceed to the next step within 20 seconds, before the
"Press Enter Key" step, or the display will revert back to "0500". The new value will be stored in
Function 3.00.
46
FLOW CHART TO PROGRAM ACCEL TIME FROM 1.5 SECONDS TO 120 SECONDS
FIGURE 39
*The factory setting of Accel Time (Function 3.03) is "1.5" seconds. Therefore, the left digits
must be changed first since an Accel setting of "000.0" is not allowed.
47
FLOW CHART TO PROGRAM THE DRIVE TO DISPLAY MOTOR RPM
FIGURE 40
*The factory setting of display Mode (Function 4.00) is Frequency ("0000").
48
FLOW CHART TO PROGRAM THE DRIVE TO DISPLAY CUSTOM UNITS "012.0"
FIGURE 41
Notes: 1. The factory setting of Display Mode (Function 4.00) is Frequency ("0000"). 2. The
factory setting of Custom Units Significant Digits (Function 4.01) is "0100". 3. The factory setting
of Custom Units Display (Function 4.02) is Whole Numbers ("0000"). 4. The Custom Unit setting
"012.0" will be displayed at full speed.
49
FLOW CHART SHOWING MOTOR CURRENT, MOTOR VOLTAGE, AND BUS VOLTAGE
FIGURE 42
ADDED TO THE BASIC DISPLAY*
RUN
STOP
*Functions 4.04, 4.05, and 4.06 set to "0001".
FIGURE 43
FLOW CHART TO PROGRAM THE DRIVE FOR REMOTE OPERATION ONLY*
*Disables Local (Keypad) Operation.
50
FLOW CHART TO PROGRAM THE DRIVE FOR 50 Hz MOTORS
FIGURE 44
51
11 4-DIGIT DISPLAY READOUT CODES
The 4-digit display provides readout of drive status, operating parameters, and faults. See Table
10, below and on page 54, for the Digital Readout Codes displayed and their descriptions.
WARNING! Do not depend on the LEDs or the 4-Digit Display to no longer be
illuminated as a guaranteed power off condition. Be sure that the main power switch or
circuit breaker is in the "OFF" position before servicing the drive.
TABLE 10
DIGITAL READOUT CODES
Display Description
Drive Stopped: Indicates that the drive is in the Stop Mode. Function 4.03 set to
"0001".
Parameter Changed: Momentarily flashes. Indicates that a parameter has been
successfully changed.
Function No.: Consists of a Group No. (digits on the left side of the decimal point)
and a Group Code No. (digits on right side of decimal point).
Motor Current Display: When the display is set to show Motor Current, the format
will be "XX.XA". Function 4.04 set to "0001".
Motor Voltage Display: When the display is set to show Motor Voltage, the format
will be "XXXu". Function 4.05 set to "0001".
52
Bus Voltage Display: When the display is set to show Bus Voltage, the format will
be "XXXU". Function 4.06 set to "0001".
Low Voltage Trip: Indicates that the AC line input voltage is below the Undervoltage
Trip Point specified in Table 3, on page 15.
Low Voltage Recovery: Indicates that a Low Voltage Trip occurred and the AC line
input voltage has returned to within the operating range specified in Table 3, on page
15.
Overvoltage Trip: Indicates that the AC line input voltage is above the Overvoltage
Trip Point specified in Table 3, on page 15.
Overvoltage Recovery: Indicates that an Overvoltage Trip occurred and the AC line
input voltage has returned to within the operating range specified in Table 3, on page
15.
Overload Trip (I2t Timeout): Indicates that the motor has been overloaded for an
extended period of time.
External Fault Trip: Indicates that an external fault has occurred at one of the
MFITs. Functions 7.00 – 7.06 set to "0008" or "0012".
Display Description
Short Circuit Fault: Indicates that the drive detected a short circuit at the motor
(phase-to-phase).
AC Line Phase Loss Detection: Indicates that the drive has detected a loss of one
of the phases in the 3-phase AC line input applied to Models KBDF-23P, 24P, 27P,
29, 42, 43, 45, 48.
Data Enter Error: Indicates that the drive is in the Program Mode and a non-valid
parameter change has been attempted.
Communication Watchdog Trip: A valid communication message was not received
within the time specified in Function 10.05.
IODF Error: Indicates that the drive has lost communication with the IODF.
Key Error: The UP and Down Keys are disabled for editing the frequency or the
FWD/REV Key is disabled for changing direction.
On-Board Memory Error: The On-Board Memory on the Drive is not detected.
DIGITAL READOUT CODES (CONTINUED)
TABLE 10
Memory Module Error: The Memory Module is not detected.
Horsepower Code Error: The program selected is not compatible with the Drive.
Program Revision Error: The program selected is not compatible with the Drive.
Checksum Error: The program selected is corrupt.
Program Location Blank Error: The program location selected does not contain
any data.
Fault Recovery: The drive monitors many faults. See Function 1.05, on page 56, for restarting
the drive after a fault has been cleared. See Table 4, on page 17, for descriptions of the
Diagnostic LEDs. See Appendix A, on page 64, for IODF faults.
Drive Faults: Undervoltage ("–LU–"), Overvoltage ("–OU–"), Short Circuit at the motor (phase-
to-phase) ("–SC–"), I
2
t or I•t Fault ("OL–t"), and Phase Loss Protection (Models KBDF-23P, 24P,
27P, 29, 42, 43, 45, 48) ("–PL–").
53
12 PROGRAMMABLE FUNCTION LIST (Rev. A)
All functions have been factory set, as shown in the tables on pages 55 – 63. The Detailed
Programmable Function List is available – contact our Sales Department.
Programming Mode: When the drive is put into the Programming Mode (see Figure 45) a
Function No. will be displayed. A Function No. consists of a Group No. (digits on the left side of
the decimal point) and a Group No. Code (digits on the right side of the decimal point). The
digits can be changed using the Up and Down Keys. The Left Shift Key is used to move the
changeable digit.
When the READ Key is pressed, either a Code or Value will be displayed. Codes have specific
descriptions. Values have numeric ranges.
Application Note: The programming of the drive can be performed without a motor connected.
On drives with 3-phase AC line input requirements, the programming can be performed with
single-phase AC line input. The drive's Phase Loss Detection will not trip the drive without the
motor connected.
To program multiple drives, the optional Programming Kit (Part No. XXXX) can be used to
upload the drive program and facilitate downloading it to multiple drives. The optional Memory
Module (Part No. 9634) can be used to program the drive and/or for cloning multiple drives.
FIGURE 45
FUNCTION NO. DESCRIPTION
Function No. which Contains A Code
Function Group No. Description
0 Motor and Drive Parameters
1 Run/Stop Mode
2 Frequency Control
3 Drive Operating Parameters
4 Digital Display Modes
5 Multi-Function Output Relay and Output Signal Operation
6 Drive Status and Reset
7 Multi-Function Input Terminals
8 PID
9 Analog Input Signal Operation
10 Communication Mode (DIDF Option Board Required)
11 Advanced Vector Control (Encoder and DIDF Option Board Required)
12 Reserved Functions (OEM Only)
54
Function No. which Contains A Value
Programmable Function Groups
Function Group 0: Motor and Drive Parameters
Function
No. Description Range/Code
0.00 * Rated Motor Frequency (Hz)
0.01 * Motor Nameplate Current (Amps) —
0.02 * Reserved — — —
0.03 * Torque Mode
0.04 * GFCI Operation
0.05 * Motor Nameplate Frequency (Hz)
0.06 *
Motor Nameplate Voltage
(% Drive Output)
(2)
(5)
0000: 60 Hz
0001: 50 Hz
0002: Special (Set by 0.05)
0000: Constant Torque (Machinery)
0001: Variable Torque (HVAC)
0000: GFCI Operation Disabled
0001: Operation with Standard GFCI
0002: Operation with Sensitive GFCI
(3, 4)
30 – 240 60, 50
0 – 100 100
Notes: (1) Factory Setting is the drive rated output current. This function is used to enter the
Motor Nameplate Rated Current, which allows proper operation of the I
Factory
Setting
2
t Motor Overload
User
Setting
0000
(1)
0000
0000
(6)
Protection. (2) GFCI operation overrides the Switching Frequency set by Function 3.15.
(3) When the drive is set for 50 Hz motors (Function 0.00 set to code "0001"), the Motor
Frequency factory setting will automatically reset to 50 Hz. (4) The Motor Frequency for
standard 50 Hz or 60 Hz motors is set by Function 0.00. For custom motors (e.g., 100 Hz) set
Function 0.00 to code "0002" and Function 0.05 to the Motor Nameplate Rated Frequency.
(5) This function is used for motors with non-standard nameplate rated voltage (e.g., 80 Volts
AC). (6) The factory set output of the drive is 100% of the AC Line input voltage. In 60 Hz Mode
(Function 0.00 set to code "0000") the drive output will be 230 Volts, maximum, for 230 Volt
motors. In 50 Hz Mode (Function 0.00 set to code "0001") the drive output will be 220 Volts,
maximum, for 220 Volt motors.
*Functions which can only be changed while the drive is in the Stop Mode.
55
Function Group 1: Run/Stop Mode
Function
No. Description Range/Code
1.00 * Run/Stop-Forward/Reverse Control
(1)
0001: External Contacts
0002: Communication
(2)
0000: Keypad
0000: Instant Reverse
0001: Stop Command Must be Given
0005: I
0006: Load Loss (See 5.05)
0007: External Fault
(3)
(4)
(5)
5.03 Frequency Reached (Hz) 0.00 – 240.0 0.00
5.04 Frequency Bandwidth (± Hz) 0.00 – 30.00 1.00
Load Loss Threshold
5.05
(% Motor Current, Set by Function
(5)
25 – 90 60
0.01)
5.06–5.13 Reserved — — —
0000: Output Frequency
Analog Output 1 Mode
5.14
(Terminals 11, 12) (0 – 5 Volts DC)
0001: Set Frequency
0002: Motor Voltage
0003: Bus Voltage
0004: Motor Current
5.15 Analog Output 1 Gain (%) 0 – 200 100
Factory
Setting
User
Setting
0000
0001
0005
0000
Note: (1) IODF Option Board required. (2) The Multi-Function Output Relay contacts and Open
Collector Outputs will change state due to all Faults and Recovered Faults. (3) The Multi-
Function Output Relay contacts and Open Collector Outputs will activate above the setting in
Function 5.03 and deactivate below the setting in Function 5.03 minus the setting in Function
5.04. (4) The Multi-Function Output Relay contacts and Open Collector Outputs will activate
below the setting in Function 5.03 and deactivate above the setting in Function 5.03 plus the
setting in Function 5.04. (5) The Load Loss Threshold function is not functional during
acceleration/deceleration or Stop Mode.
58
Function Group 6: Drive Status and Reset
Function
No. Description Code
6.00 * Drive ID — —
6.01 * Software Version — —
6.02 * Drive Horsepower — —
6.03 * Fault Log 1
6.04 * Fault Log 2
— —
— —
6.05 * Fault Log 3 — —
6.06–6.09 Reserved — — —
1110: 50 Hz Operation
6.10 ** Reset Drive to Factory Setting
1111: 60 Hz Operation
1010: Default Program
(See 6.11 and 6.12)
6.11 ** Program Location
6.12 ** Program Number
0000: On-Board Memory
0001: Memory Module (Removable)
0001: Program 1 0003: Program 3
0002: Program 2 0004: Program 4
0001: Copy from Memory Module to On-board Memory
0002: Copy from On-board Memory to
6.13 ** Memory Copy Operation
Memory Module
0003: Copy Active Program to
On-Board Memory
0004: Copy Active Program to
Memory Module
6.14 ** On-board Memory Program Number
6.15 ** Memory Module Program Number
6.16 ** Memory Module Operation
0001: Program 1 0003: Program 3
0002: Program 2 0004: Program 4
0001: Program 1 0003: Program 3
0002: Program 2 0004: Program 4
0000: Manual Read/Write Operation
0001: Automatic Read on Power up
Factory
Setting
User
Setting
0000
0000
0001
0000
0001
0001
0000
*Read only.
**Functions which can only be changed while the drive is in the Stop Mode.
59
Function Group 7: Multi-Function Input Terminals
Function
No. Description Range/Code
(1)
7.00 * Multi-Function Input 1 (Terminal 5)
7.01 * Multi-Function Input 2 (Terminal 6)
7.02 * Multi-Function Input 3 (Terminal 7)
7.03 * Multi-Function Input 4 (Terminal 8)
7.04 * Multi-Function Input 5 (Terminal 9)
7.05 *
7.06 *
Multi-Function Input 6 (Terminal 14)
(1, 4)
Multi-Function Input 7 (Terminal 15)
(1, 4)
0000: Preset Frequency Operation
0000
0001: Preset Frequency Operation
0002: Preset Frequency Operation