Application Note |
A350P |
Issue Date |
December 31, 2004 |
APPLICATION NOTE
A350P Proportional Temperature Control
of Johnson Controls® VA-7152 and VA-8052 Valve Actuators
IMPORTANT: Use the A350P temperature control only as an operating control. Where failure or malfunction of the A350P control could lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into the control system. Incorporate and maintain other devices such as supervisory or alarm systems or safety or limit controls intended to warn of, or protect against, failure or malfunction of the A350P temperature control.
Application
The A350P proportional temperature control can control VA-7152 and VA-8052 series valve actuators. Applications can use a common 24 VAC power supply (Figure 1 and Figure 2) or a Y350 power module and a separate power supply transformer for the actuator (Figure 3 and Figure 4).
A350P
L1
L2
Class 2
A350P
<![if ! IE]><![endif]>24V
<![if ! IE]><![endif]>C
<![if ! IE]><![endif]>VDC
<![if ! IE]><![endif]>SN
<![if ! IE]><![endif]>I
<![if ! IE]><![endif]>V
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Sensor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
<![if ! IE]> <![endif]>VA-8052 COM TRANS |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
VAAC-8052COM |
|
<![if ! IE]> <![endif]>IN |
<![endif]>V I SN VDC C 24V
|
|
|
|
Sensor |
|
L2 |
|
|
|
<![if ! IE]> <![endif]>_COMTRANS |
|
L1 |
|
|
|
|
|
1 |
2 |
3 |
4 |
<![if ! IE]> <![endif]>_ |
|
<![if ! IE]> <![endif]>7152-VA |
|||||
VA-7152 |
|
|
|||
Class 2 |
|
|
|
|
Note: Terminals 2 and 3 are connected internally as common on VA-7152 series actuators.
Figure 1: Wiring an A350P Controller to a VA-7152 Valve Actuator Using a Common Transformer to Power the Application
©2004 Johnson Controls, Inc. Code No. LIT-9305008
Figure 2: Wiring an A350P Controller to a VA-8052 Valve Actuator Using a Common Transformer to Power the Application
Table 1: Johnson Controls Actuator Terminals Wired to a Common Power Supply
A350P Control |
VA-7152 |
VA-8052 |
Terminal |
Terminal |
Terminal |
|
|
|
C |
2, 3 |
COM |
24V |
1 |
AC |
V |
4 |
IN |
Note: Terminals 2 and 3 are connected internally as common on VA-7152 series actuators.
IMPORTANT: Always maintain polarity when wiring A350P controls to VA-7152 and VA-8052 actuators. Failure to maintain polarity can result in damage to the A350P control and the actuators.
1
www.johnsoncontrols.com