Johnson Controls CBL-22/3-FC-PLN Data Sheet

4 (3)
Johnson Controls CBL-22/3-FC-PLN Data Sheet

FIELD CONTROLLER (FC) BUS CABLE 22-3C SHIELDED PLENUM

PART NO.

CBL-22/3-FC-PLN

 

 

 

 

Description

22/3 stranded shielded plenum FC Bus communication cable

 

 

 

 

Construction

This cable consists of a) three bare copper-insulated conductors with an overall shield

 

and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket

 

removal.

Approvals

UL Standard 444, NEC Article 800 – CMP, CE, RoHS

 

 

 

 

CONSTRUCTION PARAMETERS

 

 

 

 

 

 

 

Conductor and Stranding

22 AWG bare copper 7x30

 

 

 

 

Insulation Material and Thickness

Low smoke PVC, 0.009"

Number of Conductors

3

 

 

 

 

 

 

Shield

Alum/poly, 100% coverage

 

 

 

 

Drain

24 AWG 7x32 tinned copper

 

Jacket Material and Thickness

Low smoke PVC, 0.015"

 

 

 

Overall Cable Diameter

0.131" nominal

 

 

Approximate Cable Weight

13.3 lbs/1,000 ft

Flame Rating

UL: UL910/NFPA262

 

C(UL): FT6

 

 

 

 

ELECTRICAL AND ENVIRONMENTAL PROPERTIES

 

 

 

 

 

Temperature Rating

0˚C to +75˚C

Operating Voltage

300 V rms (maximum)

 

 

Capacitance Between Conductors @ 1 kHz

25 pF/ft

 

 

Nominal Conductor DC Resistance @ 20˚C

16.1 ohms/1,000 ft

Maximum Recommended Current

2.8 amps per conductor @ 25˚C

 

 

 

 

APPEARANCE AND PACKAGING

 

 

 

 

 

Insulation Colors

Black, blue, white

Jacket Color

Blue

 

 

Legend (Surface Ink Print)

JCI FC Bus Cable 22AWG (UL) Type CMP

 

C(UL) Type CMP FT6 Northflex ROHS

Packaging

Available in 1,000-foot reels and pull-out boxes.

 

 

 

The jacket is sequentially footmarked.