FIELD CONTROLLER (FC) BUS CABLE 22-3C SHIELDED PLENUM
PART NO. |
CBL-22/3-FC-PLN |
||
|
|
|
|
Description |
22/3 stranded shielded plenum FC Bus communication cable |
||
|
|
|
|
Construction |
This cable consists of a) three bare copper-insulated conductors with an overall shield |
||
|
and drain wire and b) an overall jacket. The cable has a rip cord for easy jacket |
||
|
removal. |
||
Approvals |
UL Standard 444, NEC Article 800 – CMP, CE, RoHS |
||
|
|
|
|
CONSTRUCTION PARAMETERS |
|
|
|
|
|
|
|
Conductor and Stranding |
22 AWG bare copper 7x30 |
||
|
|
|
|
Insulation Material and Thickness |
Low smoke PVC, 0.009" |
||
Number of Conductors |
3 |
|
|
|
|
|
|
Shield |
Alum/poly, 100% coverage |
||
|
|
|
|
Drain |
24 AWG 7x32 tinned copper |
|
|
Jacket Material and Thickness |
Low smoke PVC, 0.015" |
||
|
|
|
|
Overall Cable Diameter |
0.131" nominal |
||
|
|
||
Approximate Cable Weight |
13.3 lbs/1,000 ft |
||
Flame Rating |
UL: UL910/NFPA262 |
||
|
C(UL): FT6 |
||
|
|
|
|
ELECTRICAL AND ENVIRONMENTAL PROPERTIES |
|
|
|
|
|
||
Temperature Rating |
0˚C to +75˚C |
||
Operating Voltage |
300 V rms (maximum) |
||
|
|
||
Capacitance Between Conductors @ 1 kHz |
25 pF/ft |
||
|
|
||
Nominal Conductor DC Resistance @ 20˚C |
16.1 ohms/1,000 ft |
||
Maximum Recommended Current |
2.8 amps per conductor @ 25˚C |
||
|
|
|
|
APPEARANCE AND PACKAGING |
|
|
|
|
|
||
Insulation Colors |
Black, blue, white |
||
Jacket Color |
Blue |
||
|
|
||
Legend (Surface Ink Print) |
JCI FC Bus Cable 22AWG (UL) Type CMP |
||
|
C(UL) Type CMP FT6 Northflex ROHS |
||
Packaging |
Available in 1,000-foot reels and pull-out boxes. |
||
|
|
||
|
The jacket is sequentially footmarked. |