Johnson Controls J15 User Manual

0 (0)

349687-JTG-A-1007

TECHNICAL GUIDE

SERIES 20

SINGLE PACKAGE GAS/ELECTRIC UNITS

AND SINGLE PACKAGE AIR

CONDITIONERS

J15, 18, 20 & 25 DJ

15 & 25 NOMINAL TONS

12.00 EER (15 TONS), 11.70 EER (17.5 TONS),

11.3 EER (20 TONS), 10.5 EER (25 TONS)

DESCRIPTION

Johnson Controls Series 20 J**DJ units are convertible single package high efficiency rooftops. All models have independent dual refrigerant circuits for efficient part load operation. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof.

All units include:

Powder Paint finish that meets ASTM-B-117 750 hour salt spray standards

Two-stage cooling provided by dual independent refrigeration circuits with expansion valves, filter-driers, high and low pressure/loss of charge switches and freezestats

Scroll compressors

Two-stage heating provided by dual independent heat exchangers with aluminized steel tubes, redundant gas valves, spark ignition with induced draft logic

Permanently lubricated motors

Bottom or side air discharge configuration capability (field convertible)

Belt Drive Blower Motor with high static drive option

Constant supply air volume (CV) with optional variable air volume (VAV)

Manufactured under the quality standards of ISO9001

Zero-25% fixed air damper with hood

Copper tube/aluminum fin coils

Hinged filter access and tool free latched doors

Hinged tool free blower, blower motor, filters and electrical panel access

Rigging holes in base rails for lifting

Single point power connection

Complete factory package - tested, charged and wired

CSA agency approvals on all units

WARRANTY

One-year parts warranty

A Five-year parts warranty on the compressors and electric heat elements

Ten-year parts warranty on the gas-fired heat exchangers

FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE

349687-JTG-A-1007

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 5 FIELD-INSTALLED ACCESSORIES. . . . . . . . . . . . . 7 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . 37

 

LIST OF FIGURES

 

Fig. #

Pg. #

1

UNIT CUTAWAY. . . . . . . . . . . . . . . . . . . . . . . . . . .

. . . 5

2

ALTITUDE/TEMPERATURE CONVERSION

 

 

FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 15

3

TYPICAL J**DJ FIELD WIRING DIAGRAM . . . . . .

. . 29

4

FRONT VIEW DIMENSIONS . . . . . . . . . . . . . . . . .

. . 30

5

REAR VIEW DIMENSIONS . . . . . . . . . . . . . . . . . .

. . 31

6

UNIT DIMENSIONS J15, 18, 20 & 25 DJ

 

 

(RAINHOOD). . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

. . 32

7

UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . .

. . 33

8

TYPICAL UNIT APPLICATIONS . . . . . . . . . . . . . .

. . 33

9

FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . .

. . 34

10

UNIT ROOF CURB DIMENSIONS . . . . . . . . . . . . .

. . 35

11

ROOF CURB DUCT OPENINGS DIMENSION . . .

. . 35

12

CUT AWAY OF ROOF CURB . . . . . . . . . . . . . . . .

. . 35

13

TYPICAL UNIT WIRING DIAGRAM . . . . . . . . . . . .

. . 36

 

LIST OF TABLES

 

Tbl. #

Pg. #

1

SOUND POWER RATING. . . . . . . . . . . . . . . . . . . .

. . . 9

2

CAPACITY RATINGS - (ARI 360) . . . . . . . . . . . . . .

. . . 9

3

GAS HEAT RATIINGS. . . . . . . . . . . . . . . . . . . . . . .

. . . 9

4

COOLING CAPACITIES FOR J15DJ . . . . . . . . . . .

. . 10

5

COOLING CAPACITIES FOR J18DJ . . . . . . . . . . .

. . 11

6

COOLING CAPACITIES FOR J20DJ . . . . . . . . . . .

. . 12

7

COOLING CAPACITIES FOR J25DJ . . . . . . . . . . .

. . 13

Tbl. #

Pg. #

8 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 14

9SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY 180 MBH - BOTTOM DUCT

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

10SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY 210 MBH - BOTTOM DUCT

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

11 SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY 240 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

12 SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT 180 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

13SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT 210 MBH - BOTTOM DUCT

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

14SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT 240 MBH - BOTTOM DUCT

CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

15 SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

16 BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . 23 17 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . . 23 18 POWER EXHAUST PERFORMANCE . . . . . . . . . . . . 23

19 J**DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET. . . . . . . . . . . . . . . . . . . . . . 24

20 J**DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET. . . . . . . . . . . . . . . . . . . . . . 26

21 J**DJ VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . 28 22 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 23 SUPPLY FAN VFD WEIGHTS, IN LBS. . . . . . . . . . . . 29 24 ELECTRIC HEAT CORRECTION FACTORS. . . . . . . 29 25 UTILITIES ENTRY DATA . . . . . . . . . . . . . . . . . . . . . . 30 26 MINIMUM CLEARANCES. . . . . . . . . . . . . . . . . . . . . . 32 27 FOUR AND SIX POINT LOADS . . . . . . . . . . . . . . . . . 34

2

Johnson Controls Unitary Products

349687-JTG-A-1007

PRODUCT NOMENCLATURE

15-25 Ton Series 20 Model Number Nomenclature

J15 D J N24 A 2 A AA 1 0 1 2 4 A

Nominal Cooling Capacity

J15 = 15 Ton

J18 = 17.5 Ton

J20 = 20 Ton

J25 = 25 Ton

Product Category

D = A/C, Single Pkg., R-22

Product Identifier

J = 11.0+ EER A/C

Heat Type and Nominal Heat Capacity

C00 = Cooling Only. No field installed electric heat

Gas Heat Options

N24 = 240 MBH Output Aluminized Steel

N32 = 320 MBH Output Aluminized Steel

S24 = 240 MBH Output Stainless Steel

S32 = 320 MBH Output Stainless Steel

Electric Heat Options

E18 = 18 KW

E36 = 36 KW

E54 = 54 KW

E72 = 72 KW

Airflow

A = Std. Drive

B = Std. Drive/Single Input Econo.

C = Std. Drive/Single Input Econo./Power Exhaust (Downflow Only)

D = Std. Drive/Motorized Damper

E = Std. Drive/Motorized Damper/Barometric Relief J = Std. Drive/Single Input Econo./Barometric Relief N = Hi Static Drive

P = Hi Static Drive/Single Input Econo.

Q = Hi Static Drive/Single Input Econo./Power Exhaust (Downflow Only)

R = Hi Static Drive/Motorized Damper

K = Hi Static Drive/Motorized Damper/Barometric Relief S = Hi Static Drive/Single Input Econo./Barometric Relief

Voltage

2 = 208/230-3-60

4 = 460-3-60

5 = 575-3-60

Product Style

A = Style A

Configuration Options (not required for all units)

These four digits will not be assigned until a quote is requested, or an order placed.

SS Drain Pan

Johnson UNT 1126 Controller (N2 protocol), DFS, APS

Johnson Light Commercial Controls System (LCCS) Rtu Controller

Hot Gas Bypass (Standard on VAV, Optional on CV)

Variable Air Volume, VFD

Variable Air Volume, VFD and Manual Bypass

Variable Air Volume, VFD (BAS ready - for customer provided VFD controller)

Variable Air Volume, VFD and Manual Bypass (BAS ready)

Variable Air Volume, VFD Ready (for customer provided, field installed drive)

 

 

 

2" Pleated filters

 

 

 

 

4" Pleated filters

 

 

 

 

BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)

 

 

 

Double Wall Construction

 

 

 

 

 

 

For valid combinations of the above; see the equipment price pages or

 

 

 

 

 

the Unitary Sales Tool program; all combinations are not available

 

 

 

 

 

 

 

 

 

 

Product Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

1 = First Generation

 

 

 

 

 

2 = Second Generation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Additional Options

 

 

 

 

 

 

 

 

 

 

Standard Cabinet

Hinged Filter Door & Tool Free Access Cabinet

 

 

 

 

 

 

 

 

 

AA = None

 

 

 

BA = Hinged Filter Door & Tool Free Access Panels

 

AB = Phase Monitor

 

 

 

BB = Phase Monitor, Hinged Filter Door & Tool Free

 

AC = Coil Guard

 

 

 

Access Panels

 

AD = Dirty Filter Switch

 

 

 

BC = Coil Guard, Hinged Filter Door & Tool Free

 

AE = Phase Monitor & Coil Guard

Access Panels

 

AF = Phase Monitor & Dirty Filter Switch

BD = Dirty Filter Switch, Hinged Filter Door &

 

AG = Coil Guard & Dirty Filter Switch

Tool Free Access Panels

 

AH = Phase Monitor, Coil Guard & Dirty Filter Switch

BE = Phase Monitor & Coil Guard, Hinged Filter

 

RC = Coil Guard & American Flag

Door & Tool Free Access Panels

 

TA = Technicoat Condenser Coil

BF = Phase Monitor & Dirty Filter Switch, Hinged

 

TJ = Technicoat Evaporator Coil

Filter Door & Tool Free Access Panels

 

TS = Technicoat Evaporator & Condenser Coils

BG = Coil Guard & Dirty Filter Switch, Hinged Filter

 

 

 

 

 

 

 

 

Door & Tool Free Access Panels

 

 

 

 

 

 

 

 

BH = Phase Monitor, Coil Guard & Dirty Filter Switch,

 

 

 

 

 

 

 

 

Hinged Filter Door & Tool Free Access Panels

 

 

 

 

 

 

 

ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be

 

 

located in digits 15-18.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installation Options

 

 

 

 

 

 

 

 

A = No Options Installed

 

N = Options 2 & 3

 

 

B = Option 1

 

P = Options 2 & 4

 

 

C = Option 2

 

Q = Options 2, 3, & 4

 

 

D = Options 1 & 2

 

R = Options 3 & 4

 

 

E = Option 3

 

S = Option 5

 

 

F = Option 4

 

T = Options 1 & 5

 

 

G = Options 1 & 3

 

U = Options 1, 3, & 5

 

 

H = Options 1 & 4

 

V = Options 1, 4, & 5

 

 

J = Options 1, 2 & 3

 

W = Options 1, 3, 4, & 5

 

 

K = Options 1, 2, & 4

 

X = Options 3 & 5

 

 

L = Options 1,3 & 4

 

Y = Options 4 & 5

 

 

M = Options 1, 2, 3, & 4

 

Z = Options 3, 4 & 5

 

 

 

 

 

 

 

 

 

 

 

 

Options

 

 

 

 

 

 

 

 

1 = Disconnect

 

4 = Smoke Detector R.A.

 

 

2 = Non-Pwr'd Conv. Outlet

 

5 = Pwr'd Conv. Outlet

 

 

3 = Smoke Detector S.A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Johnson Controls Unitary Products

3

FEATURES

All Series 20 J**DJ models are available with a wide variety of factory-mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switch, and coil guard to make them suitable for almost every application.

All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation.

All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with factory installed power exhaust are suitable for bottom duct connections only. For bottom duct, you remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, you replace the supply and return air panels on the rear of the unit with a side duct flange accessory.

All models are available with these “factory mounted” outdoor air damper options:

Single enthalpy economizer with or without power exhaust

BAS-ready economizer with or without power exhaust

Motorized outdoor air damper

Barometric Relief Damper

A fixed outdoor air intake assembly will be shipped in the return air compartment of all units ordered without an economizer or motorized outdoor air damper option. The assembly includes a rain hood with a damper that can be set for 10, 15 or 25% outdoor air. With bottom duct connections, the intake damper assembly should be mounted over the opening in the return air panel. With horizontal ductwork, it should be mounted on the return air duct.

All supply air blowers are equipped with a belt drive that can be adjusted to meet the exact requirements of the job. A high static drive option is available for applications with a higher CFM and/or static pressure requirement. A variable air volume (VAV) option using a variable frequency drive is available for applications requiring a constant supply duct pressure. A differential pressure transducer is used to monitor supply duct static pressure and return a speed reference signal to the VFD to control the output of the indoor blower motor.

All compressors include scroll compressors and internal pressure relief. Every refrigerant circuit includes an expansion valve, a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/ loss of charge switch to protect all system components. A hot gas bypass option, consisting of an adjustable compressor discharge bypass valve, is available for low cooling load applications.

Advanced Controls - Unit control boards have standardized a number of features previously available only as options or by utilizing additional controls.

349687-JTG-A-1007

Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.

Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button.

Lead-Lag - An integrated Lead-Lag option allows equal run time hours on all compressors, thereby extending the life of all compressors. This option is selectable on the unit control board.

Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.

Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.

Nuisance Trip Protection and Strikes - To prevent nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the associated compressor.

On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.

All units have long lasting powder paint cabinets with 750 hour salt spray test approval under ASTM-B117 procedures.

All models are CSA approved.

Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty.

Gas Heat Operation - All gas heat units are built with two heating sections for two equal stages of capacity control. Each section includes a durable heat exchanger

4

Johnson Controls Unitary Products

Johnson Controls J15 User Manual

349687-JTG-A-1007

UNIT

FIGURE 1 - UNIT CUTAWAY

with aluminized steel or optional stainless steel tubes, a

ble of introducing up to 100% outdoor air with nominal

redundant gas valve, spark ignition, power venting, an

1% leakage type dampers.

ignition module for 100% shut-off and all of the safety

The enthalpy system contains one sensor that monitors

controls required to meet the latest ANSI standards.

the outdoor air and determines when the air is cool

The gas supply piping can be routed into the heating

enough and dry enough to provide free cooling.

compartment through a hole in the base pan of the unit

The rainhood is painted to match the basic unit and must

or through a knockout in the piping panel on the front of

be field-assembled before installing.

the unit.

 

Electric Heat Operation - All electric heat models (fac-

BAS-READY ECONOMIZER - Includes a slide-in / plug-

in damper assembly with fully modulating spring-return

tory installed only) are wired for a single power source

motor actuator with zero to 95-degree rotation capable of

and include a bank of nickel chromium elements

introducing up to 100% outdoor air with nominal 1% leak-

mounted at the discharge of the supply air blower to pro-

age type dampers.

vide a high velocity and uniform distribution of air across

 

the heating elements. Every element is fully protected

Actuator requires 2-10 VDC input from an external

against excessive current and temperature by fuses and

source, such as a field-installed or factory-installed BAS

two thermal limit switches.

controller. BAS-ready actuators have an adjustable auxil-

The power supply wiring can be routed into the control

iary end-switch for optional power exhaust control.

 

box through a threaded pipe connection in the base pan

For units with optional VAV control, a factory-installed,

of the unit or through a knockout in the wiring panel on

dry bulb sensor determines if outdoor air temperature is

the front of the unit.

low enough to provide free-cooling operation. (Field-

FACTORY-INSTALLED OPTIONS

installed humidity sensors for either outdoor air or out-

door & return air streams are available for single

SINGLE INPUT ELECTRONIC ENTHALPY ECONO-

enthalpy and differential enthalpy configurations, respec-

tively).

MIZERS - Includes a slide-in / plug-in damper assembly

 

with fully modulating spring-return motor actuator capa-

The rainhood is painted to match the basic unit and must

 

be field-assembled before installing.

Johnson Controls Unitary Products

5

POWER EXHAUST - Our economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. BAS-ready economizer actuators have an adjustable auxiliary end-switch to provide a range of damper positions available to energize power exhaust.

The exhaust fan, motor and controls are installed and wired at the factory. The rain hood must be assembled and installed in the field.

The power exhaust option can only be used on bottom duct configurations.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

BAROMETRIC RELIEF DAMPER - This damper option can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1" processes. Coating is applied by total immersion of the complete coil for maximum protection.

ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures.

VARIABLE AIR VOLUME (VAV) - A factory-installed variable frequency drive (VFD), mounted in the Blower Access compartment, is used to control the speed of the indoor blower motor in order to maintain a constant static pressure in the supply duct. A pressure transducer and VAV control board are mounted inside the control box. The drive comes completely wired and pre-programmed from the factory.

An optional, factory-installed manual bypass switch available with factory-installed VFD can be found in the Blower Motor Access compartment. The switch can be used to either route power to the VFD for modulating control of the blower motor, to bypass the drive and operate the motor at full speed, or to power the drive (and not the motor) for diagnostic purposes.

349687-JTG-A-1007

Due to space limitations, VAV is not available with any of the factory-installed BAS options described below, but is available with ‘BAS-ready’ models. Terminal blocks are provided in the control box for field wiring of the cus- tomer-installed BAS.

A ‘VFD-ready’ option provides the provisions for a cus- tomer-installed drive. The unit comes with a mounting bracket installed in the Blower Access compartment which may accommodate other vendor’s drives depending on their size. In order to utilize the unit’s mounting bracket, the maximum recommended drive dimensions are as follows:

For 5-hp motor applications ........................

13” H x 6” W x 7” D

For 7.5 thru 15-hp motor applications .........

13” H x 8” W x 8” D

If the drive will not fit in the allotted space, then it will have to be mounted elsewhere; either within the building on a perpendicular wall which is not subjected to excessive temperature, vibration, humidity, dust, corrosive gas, explosive gas, etc., or within an appropriate enclosure rated for outside installation to safeguard against moisture, dust and excessive heat.

A terminal block located in the control box is provided for field connection of the VFD controls.

HOT GAS BYPASS - To allow for low cooling load operation, a direct-acting pressure-modulating bypass control valve installed on the system #1 discharge line is used to divert high temperature, high pressure refrigerant around the TXV in order to maintain a desired minimum evaporator pressure. HGBP is standard on all units with VAV and optional with CV units.

FILTER OPTIONS - Standard units are shipped with 2” throw-away filters installed. 2” pleated and 4” pleated filters are offered as a factory installed option.

CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or you may order the unit with a “non-powered” convenience outlet that can be wired in the field.

DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.

DOUBLE WALL CONSTRUCTION - Optional double wall construction is available to provide smooth inner surfaces for easy and effective cleaning to reduce risk of dirt and bacterial accumulation. Fiberglass insulation is sandwiched between heavy gauge steel sheets to form a durable, rigid casing to withstand higher working pressures and impact forces. The heavy-duty construction provides excellent acoustic and thermal insulation and eliminates erosion of insulation material and contamination of the air stream.

6

Johnson Controls Unitary Products

349687-JTG-A-1007

 

SMOKE DETECTORS - (supply air & return air) The

Johnson UNT 1126 Rooftop Controller - N2 protocol

smoke detectors stop operation of the unit by interrupting

with air proving and dirty filter sensors. Hardware con-

power to the control board if smoke is detected within the

tains generic application logic; field engineering and/or

air compartment.

modification may be required.

Factory installed smoke detectors in the return air may be subjected to freezing temperatures during “off” times due to outside air infiltration. These smoke detectors have an operation limit of 32°F to 131°F. Smoke detectors installed in areas that could be outside those limitations will have to be moved to prevent having false alarms.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.

STAINLESS STEEL DRAIN PAN - An optional rust-proof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

HIGH STATIC DRIVE - Includes a belt and blower pulley upgrade to enhance blower performance.

DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

HINGED FILTER DOOR/”TOOL FREE” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance.

NOTE:Knobs are shipped separately within the unit to prevent shipping damage. These must be field installed for tool free operation.

HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR, FILTER AND ELECTRIC ACCESS PANELS - This option allows for complete hinged and tool free access to the unit's blower, blower motor, filters and electrical panel sections.

CONTROL OPTIONS

Johnson Light Commercial System (LCCS) - Provides rooftop system integration for LCCS single zone, change-over bypass and VAV systems.

FIELD-INSTALLED ACCESSORIES

SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers.

The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling.

The rainhood is painted to match the basic unit and must be field-assembled before installing.

MOTORIZED OUTDOOR AIR INTAKE DAMPER - Includes a slide-in / plug-in damper assembly with a 2- position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down.

The rain hood is painted to match the basic unit and must be field assembled before installing.

ROOF CURBS - Fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly.

They're designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports.

HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet.

PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane.

HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit.

SIDE DUCT FLANGES - One-inch flanges replace the supply and return air panels on the rear of the unit to accommodate horizontal duct connections. These flanges can also be used individually for bottom supply/ horizontal return or horizontal supply/bottom return. They cannot be used on units with power exhaust.

BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This

Johnson Controls Unitary Products

7

accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct.

HIGH STATIC DRIVE - A smaller blower pulley and a shorter belt increase the speed of the supply air blower for applications with a higher CFM and/or static pressure requirements.

ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

349687-JTG-A-1007

FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

WOOD SKID - Allows unit to be handled with 90” forks.

CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of- phase condition.

8

Johnson Controls Unitary Products

349687-JTG-A-1007

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

RPM

BHP

63

125

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

10Ft.2

 

 

 

 

J15DJ

6,000

1.00

1,080

4.60

99

99

89

82

84

77

 

72

67

89

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J18, 20 DJ

8,000

1.00

1,120

6.65

102

102

92

85

87

80

 

75

70

92

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J25DJ

10,000

1.30

1160

12.5

108

108

98

91

93

86

 

81

76

98

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1

MODEL

MBH

EER2

IPLV3

COOLING ONLY

 

 

 

J15DJC/E00

178

12.0

12.5

J18DJC/E00

208

11.7

12.7

J20DJC/E00

230

11.3

12.0

J25DJC/E00

292

10.5

11.2

COOLING WITH GAS HEAT

 

 

 

J15DJN/S

178

12.0

12.5

J18DJN/S

208

11.7

12.7

J20DJN/S

230

11.3

12.0

J25DJN/S

292

10.5

11.2

COOLING WITH ELECTRIC HEAT

 

 

J15DJE18

178

12.0

12.5

J15DJE36

178

12.0

12.5

J15DJE54

176

11.8

12.2

J15DJE72

176

11.8

12.2

J18DJE18

208

11.7

12.7

J18DJE36

208

11.7

12.7

J18DJE54

206

11.5

12.4

J18DJE72

206

11.5

12.4

J20DJE18

230

11.3

12.0

J20DJE36

230

11.3

12.0

J20DJE54

228

11.1

11.7

J20DJE72

228

11.1

11.7

J25DJE18

292

10.5

11.2

J25DJE36

292

10.5

11.2

J25DJE54

290

10.3

11.0

J25DJE72

290

10.3

11.0

1.Certified in accordance with the Unitary Large Equipment certification program which is based on ARI Standard 340/360.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.IPLV = Integrated Part Load Value.

TABLE 3: GAS HEAT RATIINGS

MODEL

MBH INPUT

MBH OUTPUT

J15DJN/S24

300

240

 

 

 

J15DJN/S32

400

320

J18DJN/S24

300

240

 

 

 

J18DJN/S32

400

320

J20DJN/S24

300

240

 

 

 

J20DJN/S32

400

320

J25DJN/S24

300

240

 

 

 

J25DJN/S32

400

320

NOTE: All gas units are two-stage heating. First stage is 50% of total.

S.S.E. = Steady State Efficiency (80%) - output divided by input.

For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct system, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across electric heating elements or gas heat exchanger tubes.

Johnson Controls Unitary Products

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

349687-JTG-A-1007

TABLE 4: COOLING CAPACITIES FOR J15DJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on Evaporator Coil

 

 

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

Total2

 

 

95°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

 

Total2

 

Sensible Capacity (MBH)*

 

Total

 

 

Sensible Capacity (MBH)*

 

 

 

 

 

 

 

 

CFM

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

 

(°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

 

 

 

 

 

 

 

72

206.8

 

11.94

119.7

106.8

 

94.0

81.2

68.3

-

-

196.1

 

12.98

115.7

102.9

 

90.1

77.3

64.4

-

-

4500

67

187.4

 

11.64

148.6

135.7

 

122.9

110.1

97.2

84.4

71.6

178.1

 

12.70

144.6

131.8

 

119.0

106.1

93.3

80.5

67.6

62

169.3

 

11.37

169.3

162.1

 

149.3

136.5

123.6

110.8

98.0

161.7

 

12.49

161.7

157.0

 

144.2

131.4

118.5

105.7

92.9

 

 

 

 

 

 

57

166.8

 

11.36

166.8

164.1

 

151.3

138.5

125.6

112.8

100.0

163.4

 

12.53

163.4

160.3

 

147.5

134.7

121.8

109.0

96.2

 

72

212.8

 

12.00

132.2

117.0

 

101.8

86.7

71.5

-

-

201.2

 

13.06

127.9

112.7

 

97.6

82.4

67.2

-

-

5250

67

192.8

 

11.70

163.5

148.3

 

133.2

118.0

102.8

87.7

72.5

182.8

 

12.78

159.2

144.0

 

128.8

113.7

98.5

83.3

68.2

62

174.2

 

11.43

174.2

170.7

 

161.7

146.6

131.4

116.3

101.1

166.0

 

12.57

166.0

163.6

 

156.2

141.0

125.9

110.7

95.5

 

 

 

 

 

 

57

171.6

 

11.42

171.6

170.3

 

163.9

148.8

133.6

118.4

103.3

167.7

 

12.61

167.7

166.2

 

159.8

144.6

129.4

114.3

99.1

 

72

218.9

 

12.06

144.7

127.2

 

109.7

92.2

74.7

-

-

206.4

 

13.14

140.0

122.5

 

105.1

87.6

70.1

-

-

6000

67

198.3

 

11.76

178.4

160.9

 

143.4

125.9

108.4

90.9

73.4

187.5

 

12.86

173.7

156.2

 

138.7

121.2

103.7

86.2

68.7

62

179.2

 

11.49

179.2

179.2

 

174.2

156.7

139.2

121.7

104.2

170.2

 

12.65

170.2

170.2

 

168.2

150.7

133.2

115.7

98.2

 

 

 

 

 

 

57

176.5

 

11.48

176.5

176.5

 

176.5

159.0

141.5

124.0

106.6

172.0

 

12.69

172.0

172.0

 

172.0

154.5

137.0

119.5

102.0

 

72

224.3

 

12.14

156.2

136.7

 

117.2

97.8

78.3

-

-

211.4

 

13.22

150.4

131.0

 

111.5

92.0

72.5

-

-

6600

67

203.2

 

11.83

192.2

172.8

 

153.3

133.8

114.3

94.9

75.4

192.0

 

12.93

185.1

166.7

 

147.2

127.7

108.2

88.8

69.3

62

183.6

 

11.57

183.6

183.6

 

181.1

161.7

142.2

122.7

103.2

174.3

 

12.72

174.3

174.3

 

173.3

153.8

134.4

114.9

95.4

 

 

 

 

 

 

57

180.9

 

11.56

180.9

180.9

 

180.9

161.4

141.9

122.5

103.0

176.2

 

12.76

176.2

176.2

 

176.2

156.7

137.2

117.7

98.3

 

72

229.7

 

12.22

167.7

146.3

 

124.8

103.3

81.9

-

-

216.4

 

13.30

160.8

139.4

 

117.9

96.4

75.0

-

-

7200

67

208.1

 

11.91

206.1

184.6

 

163.2

141.7

120.3

98.8

77.3

196.6

 

13.01

196.6

177.1

 

155.7

134.2

112.8

91.3

69.8

62

188.1

 

11.64

188.1

188.1

 

188.1

166.6

145.1

123.7

102.2

178.5

 

12.80

178.5

178.5

 

178.5

157.0

135.6

114.1

92.6

 

 

 

 

 

 

57

185.3

 

11.63

185.3

185.3

 

185.3

163.8

142.3

120.9

99.4

180.4

 

12.84

180.4

180.4

 

180.4

158.9

137.4

116.0

94.5

 

 

 

 

 

 

 

105°F

 

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

72

184.9

 

14.46

111.3

98.5

 

85.6

72.8

60.0

-

-

173.7

 

15.93

106.8

94.0

 

81.2

68.3

55.5

-

-

4500

67

167.9

 

14.19

140.0

127.2

 

114.3

101.5

88.7

75.9

63.0

157.7

 

15.68

135.4

122.6

 

109.7

96.9

84.1

71.2

58.4

62

152.9

 

14.00

152.9

149.0

 

136.2

123.4

110.5

97.7

84.9

144.1

 

15.50

144.1

141.0

 

128.2

115.4

102.5

89.7

76.9

 

 

 

 

 

 

57

155.3

 

14.03

155.3

152.1

 

139.3

126.5

113.6

100.8

88.0

147.3

 

15.53

147.3

143.9

 

131.1

118.3

105.4

92.6

79.8

 

72

189.7

 

14.51

123.4

108.2

 

93.1

77.9

62.7

-

-

178.3

 

15.95

118.9

103.7

 

88.6

73.4

58.2

-

-

5250

67

172.3

 

14.24

154.6

139.5

 

124.3

109.1

94.0

78.8

63.6

161.8

 

15.70

150.1

134.9

 

119.8

104.6

89.4

74.3

59.1

62

156.9

 

14.05

156.9

155.0

 

148.1

132.9

117.7

102.6

87.4

147.8

 

15.52

147.8

146.3

 

139.9

124.8

109.6

94.4

79.3

 

 

 

 

 

 

57

159.4

 

14.08

159.4

157.8

 

151.4

136.2

121.1

105.9

90.8

151.2

 

15.55

151.2

149.5

 

143.1

127.9

112.7

97.6

82.4

 

72

194.6

 

14.56

135.5

118.0

 

100.5

83.0

65.5

-

-

182.8

 

15.97

131.0

113.5

 

96.0

78.5

61.0

-

-

6000

67

176.7

 

14.29

169.2

151.7

 

134.2

116.7

99.3

81.8

64.3

166.0

 

15.72

164.8

147.3

 

129.8

112.3

94.8

77.3

59.8

62

160.9

 

14.09

160.9

160.9

 

159.9

142.4

124.9

107.4

89.9

151.6

 

15.54

151.6

151.6

 

151.6

134.1

116.6

99.1

81.6

 

 

 

 

 

 

57

163.5

 

14.13

163.5

163.5

 

163.5

146.0

128.5

111.0

93.5

155.0

 

15.56

155.0

155.0

 

155.0

137.5

120.0

102.6

85.1

 

72

199.3

 

14.65

145.7

126.3

 

106.8

87.3

67.8

-

-

187.1

 

16.07

141.1

121.6

 

102.1

82.6

63.1

-

-

6600

67

180.9

 

14.38

177.2

162.1

 

142.6

123.1

103.7

84.2

64.7

169.9

 

15.82

169.3

157.5

 

138.1

118.6

99.1

79.6

60.1

62

164.8

 

14.18

164.8

164.8

 

164.3

144.8

125.3

105.8

86.3

155.2

 

15.64

155.2

155.2

 

155.2

135.7

116.2

96.8

77.3

 

 

 

 

 

 

57

167.4

 

14.21

167.4

167.4

 

167.4

148.0

128.5

109.0

89.5

158.7

 

15.66

158.7

158.7

 

158.7

139.2

119.7

100.3

80.8

 

72

203.9

 

14.74

156.0

134.5

 

113.1

91.6

70.1

-

-

191.5

 

16.18

151.2

129.7

 

108.2

86.8

65.3

-

-

7200

67

185.2

 

14.47

185.2

172.5

 

151.0

129.5

108.1

86.6

65.2

173.8

 

15.93

173.8

167.8

 

146.3

124.9

103.4

81.9

60.5

62

168.6

 

14.27

168.6

168.6

 

168.6

147.2

125.7

104.2

82.8

158.8

 

15.74

158.8

158.8

 

158.8

137.3

115.9

94.4

72.9

 

 

 

 

 

 

57

171.4

 

14.30

171.4

171.4

 

171.4

149.9

128.4

107.0

85.5

162.4

 

15.77

162.4

162.4

 

162.4

140.9

119.4

98.0

76.5

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

162.5

 

17.41

102.4

89.5

 

76.7

63.9

51.0

-

-

 

 

 

 

 

 

 

 

 

 

 

4500

67

147.5

 

17.18

130.8

118.0

 

105.1

92.3

79.5

66.6

53.8

 

 

 

 

 

 

 

 

 

 

 

62

135.2

 

17.00

135.2

133.0

 

120.2

107.4

94.5

81.7

68.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

139.2

 

17.02

139.2

135.7

 

122.9

110.1

97.2

84.4

71.6

 

 

 

 

 

 

 

 

 

 

 

 

72

166.8

 

17.40

114.4

99.2

 

84.1

68.9

53.7

-

-

 

 

 

 

 

 

 

 

 

 

 

5250

67

151.3

 

17.17

145.5

130.4

 

115.2

100.1

84.9

69.7

54.6

 

 

 

 

 

 

 

 

 

 

 

62

138.8

 

16.99

138.8

137.7

 

131.8

116.6

101.5

86.3

71.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

142.9

 

17.01

142.9

141.1

 

134.7

119.6

104.4

89.2

74.1

 

 

 

 

 

 

 

 

 

 

 

 

72

171.0

 

17.38

126.4

108.9

 

91.4

73.9

56.5

-

-

 

 

 

 

 

 

 

 

 

 

 

6000

67

155.2

 

17.16

155.2

142.8

 

125.3

107.8

90.3

72.8

55.3

 

 

 

 

 

 

 

 

 

 

 

62

142.3

 

16.98

142.3

142.3

 

142.3

125.9

108.4

90.9

73.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

146.6

 

17.00

146.6

146.6

 

146.6

129.1

111.6

94.1

76.6

 

 

 

 

 

 

 

 

 

 

 

 

72

175.0

 

17.50

136.4

116.9

 

97.4

77.9

58.5

-

-

 

 

 

 

 

 

 

 

 

 

 

6600

67

158.8

 

17.27

158.8

153.0

 

133.5

114.0

94.5

75.0

55.6

 

 

 

 

 

 

 

 

 

 

 

62

145.6

 

17.10

145.6

145.6

 

145.6

126.7

107.2

87.7

68.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

150.0

 

17.12

150.0

150.0

 

150.0

130.5

111.0

91.5

72.0

 

 

 

 

 

 

 

 

 

 

 

 

72

179.0

 

17.62

146.3

124.9

 

103.4

81.9

60.5

-

-

 

 

 

 

 

 

 

 

 

 

 

7200

67

162.4

 

17.38

162.4

162.4

 

141.7

120.2

98.7

77.3

55.8

 

 

 

 

 

 

 

 

 

 

 

62

148.9

 

17.21

148.9

148.9

 

148.9

127.5

106.0

84.5

63.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

153.4

 

17.23

153.4

153.4

 

153.4

131.9

110.4

89.0

67.5

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

10

Johnson Controls Unitary Products

349687-JTG-A-1007

TABLE 5: COOLING CAPACITIES FOR J18DJ

Air on Evaporator Coil

 

 

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

Total2

 

 

95°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

 

Total2

 

Sensible Capacity (MBH)*

 

Total

 

 

Sensible Capacity (MBH)*

 

 

 

 

 

 

 

 

CFM

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

 

(°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

 

 

 

 

 

 

 

72

238.9

 

14.24

142.6

125.5

 

108.4

91.3

74.2

-

-

222.9

 

15.81

136.5

119.4

 

102.3

85.2

68.1

-

-

6000

67

221.2

 

13.83

178.6

161.5

 

144.4

127.3

110.2

93.1

76.0

207.1

 

15.38

172.8

155.7

 

138.6

121.5

104.4

87.2

70.1

62

207.4

 

13.57

207.4

192.8

 

175.7

158.5

141.4

124.3

107.2

197.6

 

15.09

197.6

181.0

 

163.8

146.7

129.6

112.5

95.4

 

 

 

 

 

 

57

197.6

 

13.52

197.6

195.7

 

178.6

161.4

144.3

127.2

110.1

186.0

 

15.06

186.0

181.8

 

164.7

147.6

130.5

113.4

96.3

 

72

246.1

 

14.36

154.5

135.8

 

117.0

98.3

79.5

-

-

231.8

 

15.91

149.7

130.9

 

112.2

93.4

74.6

-

-

6500

67

227.9

 

13.95

193.5

174.7

 

156.0

137.2

118.4

99.7

80.9

215.4

 

15.48

189.4

170.7

 

151.9

133.2

114.4

95.6

76.9

62

213.7

 

13.69

213.7

206.4

 

189.7

170.9

152.2

133.4

114.6

205.5

 

15.19

205.5

197.1

 

179.6

160.9

142.1

123.4

104.6

 

 

 

 

 

 

57

203.6

 

13.64

203.6

202.6

 

192.8

174.1

155.3

136.5

117.8

193.5

 

15.15

193.5

191.3

 

180.6

161.8

143.1

124.3

105.5

 

72

253.4

 

14.48

166.5

146.1

 

125.7

105.3

84.9

-

-

240.7

 

16.00

162.8

142.4

 

122.0

101.6

81.2

-

-

7000

67

234.6

 

14.06

208.3

187.9

 

167.5

147.1

126.7

106.3

85.9

223.6

 

15.57

206.1

185.7

 

165.3

144.8

124.4

104.0

83.6

62

220.0

 

13.80

220.0

220.0

 

203.7

183.3

162.9

142.5

122.1

213.3

 

15.28

213.3

213.3

 

195.4

175.0

154.6

134.2

113.8

 

 

 

 

 

 

57

209.6

 

13.75

209.6

209.6

 

207.1

186.7

166.2

145.8

125.4

200.9

 

15.24

200.9

200.9

 

196.4

176.0

155.6

135.2

114.8

 

72

258.4

 

14.56

180.9

157.6

 

134.4

111.2

87.9

-

-

243.3

 

16.09

176.8

153.6

 

130.3

107.1

83.8

-

-

7875

67

239.3

 

14.14

225.6

202.4

 

179.1

155.9

132.6

109.4

86.1

226.0

 

15.65

217.3

199.8

 

176.5

153.3

130.0

106.8

83.5

62

224.4

 

13.88

224.4

224.4

 

216.2

193.0

169.7

146.5

123.2

215.6

 

15.36

215.6

215.6

 

206.7

183.4

160.2

136.9

113.7

 

 

 

 

 

 

57

213.8

 

13.82

213.8

213.8

 

212.5

189.2

166.0

142.8

119.5

203.0

 

15.32

203.0

203.0

 

200.8

177.6

154.3

131.1

107.8

 

72

263.5

 

14.63

195.3

169.2

 

143.1

117.0

91.0

-

-

245.9

 

16.17

190.8

164.7

 

138.7

112.6

86.5

-

-

8750

67

243.9

 

14.21

242.9

216.8

 

190.7

164.7

138.6

112.5

86.4

228.4

 

15.73

228.4

213.9

 

187.8

161.7

135.6

109.5

83.5

62

228.7

 

13.95

228.7

228.7

 

228.7

202.6

176.6

150.5

124.4

217.9

 

15.43

217.9

217.9

 

217.9

191.8

165.8

139.7

113.6

 

 

 

 

 

 

57

217.9

 

13.90

217.9

217.9

 

217.9

191.8

165.8

139.7

113.6

205.2

 

15.40

205.2

205.2

 

205.2

179.1

153.0

126.9

100.9

 

 

 

 

 

 

 

105°F

 

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

72

210.2

 

17.65

131.0

113.9

 

96.8

79.7

62.6

-

-

197.6

 

19.49

125.5

108.3

 

91.2

74.1

57.0

-

-

6000

67

195.1

 

17.21

167.5

150.4

 

133.3

116.2

99.1

82.0

64.9

183.1

 

19.04

162.2

145.1

 

128.0

110.9

93.8

76.7

59.6

62

186.9

 

17.01

186.9

170.6

 

153.5

136.4

119.3

102.2

85.1

176.3

 

18.92

176.3

160.2

 

143.1

126.0

108.9

91.8

74.7

 

 

 

 

 

 

57

174.4

 

16.80

174.4

172.3

 

155.2

138.1

121.0

103.9

86.8

162.8

 

18.55

162.8

162.8

 

145.7

128.6

111.5

94.4

77.3

 

72

218.3

 

17.77

143.8

125.0

 

106.3

87.5

68.7

-

-

204.8

 

19.63

137.9

119.1

 

100.3

81.6

62.8

-

-

6500

67

202.6

 

17.33

183.9

165.1

 

146.4

127.6

108.8

90.1

71.3

189.9

 

19.18

178.3

159.5

 

140.8

122.0

103.3

84.5

65.8

62

194.1

 

17.12

194.1

186.0

 

168.5

149.8

131.0

112.2

93.5

182.8

 

19.06

182.8

174.8

 

157.4

138.6

119.9

101.1

82.4

 

 

 

 

 

 

57

181.1

 

16.92

181.1

180.1

 

170.4

151.7

132.9

114.1

95.4

168.8

 

18.69

168.8

168.8

 

160.3

141.5

122.8

104.0

85.2

 

72

226.4

 

17.89

156.6

136.2

 

115.7

95.3

74.9

-

-

212.1

 

19.77

150.3

129.9

 

109.5

89.0

68.6

-

-

7000

67

210.1

 

17.45

200.2

179.8

 

159.4

139.0

118.6

98.2

77.8

196.6

 

19.32

194.4

174.0

 

153.6

133.2

112.7

92.3

71.9

62

201.3

 

17.24

201.3

201.3

 

183.6

163.1

142.7

122.3

101.9

189.3

 

19.20

189.3

189.3

 

171.7

151.3

130.9

110.5

90.0

 

 

 

 

 

 

57

187.8

 

17.03

187.8

187.8

 

185.6

165.2

144.8

124.4

104.0

174.8

 

18.82

174.8

174.8

 

174.8

154.4

134.0

113.6

93.2

 

72

228.5

 

17.97

171.3

148.0

 

124.8

101.5

78.3

-

-

213.7

 

19.85

165.7

142.5

 

119.2

96.0

72.7

-

-

7875

67

212.1

 

17.53

207.1

193.3

 

171.9

148.6

125.4

102.2

78.9

198.1

 

19.40

197.0

186.8

 

167.3

144.0

120.8

97.5

74.3

62

203.2

 

17.32

203.2

203.2

 

194.3

171.0

147.8

124.5

101.3

190.7

 

19.28

190.7

190.7

 

181.9

158.6

135.4

112.1

88.9

 

 

 

 

 

 

57

189.6

 

17.11

189.6

189.6

 

188.5

165.2

142.0

118.7

95.5

176.1

 

18.90

176.1

176.1

 

176.1

152.9

129.6

106.4

83.1

 

72

230.6

 

18.05

186.0

159.9

 

133.8

107.7

81.7

-

-

215.2

 

19.94

181.1

155.1

 

129.0

102.9

76.8

-

-

8750

67

214.0

 

17.61

214.0

206.7

 

184.4

158.3

132.2

106.1

80.0

199.5

 

19.48

199.5

199.5

 

181.0

154.9

128.8

102.7

76.6

62

205.0

 

17.40

205.0

205.0

 

205.0

178.9

152.8

126.8

100.7

192.1

 

19.36

192.1

192.1

 

192.1

166.0

139.9

113.8

87.8

 

 

 

 

 

 

57

191.3

 

17.19

191.3

191.3

 

191.3

165.2

139.1

113.0

87.0

177.4

 

18.98

177.4

177.4

 

177.4

151.3

125.2

99.1

73.1

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

184.9

 

21.33

119.9

102.8

 

85.7

68.6

51.5

-

-

 

 

 

 

 

 

 

 

 

 

 

6000

67

171.1

 

20.87

156.9

139.8

 

122.7

105.6

88.5

71.4

54.3

 

 

 

 

 

 

 

 

 

 

 

62

165.7

 

20.84

165.7

149.9

 

132.7

115.6

98.5

81.4

64.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

151.2

 

20.30

151.2

151.2

 

136.2

119.1

102.0

84.9

67.8

 

 

 

 

 

 

 

 

 

 

 

 

72

191.4

 

21.49

132.0

113.2

 

94.4

75.7

56.9

-

-

 

 

 

 

 

 

 

 

 

 

 

6500

67

177.1

 

21.03

172.7

154.0

 

135.2

116.5

97.7

79.0

60.2

 

 

 

 

 

 

 

 

 

 

 

62

171.5

 

21.00

171.5

163.6

 

146.3

127.5

108.8

90.0

71.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

156.5

 

20.46

156.5

156.5

 

150.1

131.4

112.6

93.8

75.1

 

 

 

 

 

 

 

 

 

 

 

 

72

197.8

 

21.65

144.0

123.6

 

103.2

82.8

62.3

-

-

 

 

 

 

 

 

 

 

 

 

 

7000

67

183.1

 

21.19

183.1

168.1

 

147.7

127.3

106.9

86.5

66.1

 

 

 

 

 

 

 

 

 

 

 

62

177.3

 

21.16

177.3

177.3

 

159.8

139.4

119.0

98.6

78.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

161.8

 

20.61

161.8

161.8

 

161.8

143.6

123.2

102.8

82.4

 

 

 

 

 

 

 

 

 

 

 

 

72

198.9

 

21.74

160.2

136.9

 

113.7

90.4

67.2

-

-

 

 

 

 

 

 

 

 

 

 

 

7875

67

184.1

 

21.27

184.1

180.2

 

162.6

139.4

116.2

92.9

69.7

 

 

 

 

 

 

 

 

 

 

 

62

178.2

 

21.24

178.2

178.2

 

169.5

146.3

123.0

99.8

76.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

162.6

 

20.69

162.6

162.6

 

162.6

140.5

117.3

94.0

70.8

 

 

 

 

 

 

 

 

 

 

 

 

72

199.9

 

21.82

176.3

150.2

 

124.2

98.1

72.0

-

-

 

 

 

 

 

 

 

 

 

 

 

8750

67

185.1

 

21.35

185.1

185.1

 

177.6

151.5

125.4

99.3

73.2

 

 

 

 

 

 

 

 

 

 

 

62

179.2

 

21.32

179.2

179.2

 

179.2

153.1

127.0

100.9

74.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

163.5

 

20.77

163.5

163.5

 

163.5

137.4

111.3

85.2

59.2

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

Johnson Controls Unitary Products

11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

349687-JTG-A-1007

TABLE 6: COOLING CAPACITIES FOR J20DJ

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Air on Evaporator Coil

 

 

 

 

 

 

 

 

Temperature of Air on Condenser Coil

 

 

 

 

 

 

 

 

 

 

 

 

85°F

 

 

 

 

 

 

Total2

 

 

95°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WB

Total

 

Total2

 

Sensible Capacity (MBH)*

 

Total

 

 

Sensible Capacity (MBH)*

 

 

 

 

 

 

 

 

CFM

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

Cap.1

 

Input

 

Return Dry Bulb (°F)

 

 

(°F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

(MBH)

 

(kW)

86

83

 

80

77

74

71

68

 

 

 

 

 

 

 

72

273.1

 

16.90

149.8

132.7

 

115.6

98.5

81.4

-

-

257.3

 

18.45

150.2

133.1

 

116.0

98.9

81.8

-

-

6000

67

248.6

 

16.43

197.6

180.5

 

163.4

146.3

129.1

112.0

94.9

237.3

 

17.83

192.3

175.1

 

158.0

140.9

123.8

106.7

89.6

62

231.2

 

16.44

227.9

210.8

 

193.7

176.6

159.5

142.4

125.3

215.2

 

17.64

215.2

200.8

 

183.7

166.6

149.5

132.4

115.3

 

 

 

 

 

 

57

216.6

 

15.98

216.6

210.2

 

193.1

176.0

158.9

141.8

124.7

221.2

 

17.98

221.2

213.2

 

196.1

179.0

161.8

144.7

127.6

 

72

278.7

 

16.96

165.8

145.6

 

125.4

105.1

84.9

-

-

264.7

 

18.51

167.2

146.9

 

126.7

106.5

86.3

-

-

7000

67

253.8

 

16.49

217.5

197.3

 

177.1

156.9

136.7

116.5

96.2

244.2

 

17.89

213.1

192.9

 

172.7

152.4

132.2

112.0

91.8

62

236.0

 

16.50

234.4

225.8

 

210.0

189.8

169.6

149.4

129.2

221.5

 

17.70

221.5

214.3

 

200.7

180.5

160.3

140.0

119.8

 

 

 

 

 

 

57

221.1

 

16.04

221.1

217.9

 

209.3

189.1

168.9

148.7

128.5

227.6

 

18.04

227.6

223.6

 

214.2

194.0

173.8

153.5

133.3

 

72

284.4

 

17.02

181.8

158.4

 

135.1

111.8

88.4

-

-

272.2

 

18.58

184.1

160.8

 

137.4

114.1

90.8

-

-

8000

67

259.0

 

16.55

237.5

214.2

 

190.9

167.5

144.2

120.9

97.6

251.0

 

17.95

233.9

210.6

 

187.3

164.0

140.6

117.3

94.0

62

240.8

 

16.56

240.8

240.8

 

226.3

203.0

179.7

156.4

133.0

227.7

 

17.76

227.7

227.7

 

217.7

194.4

171.0

147.7

124.4

 

 

 

 

 

 

57

225.6

 

16.10

225.6

225.6

 

225.6

202.3

178.9

155.6

132.3

234.0

 

18.10

234.0

234.0

 

232.3

209.0

185.7

162.4

139.0

 

72

291.0

 

17.43

193.1

167.5

 

141.8

116.1

90.4

-

-

277.5

 

18.98

195.6

169.9

 

144.2

118.5

92.9

-

-

8700

67

265.0

 

16.95

251.7

226.0

 

200.3

174.7

149.0

123.3

97.6

256.0

 

18.33

247.4

222.2

 

196.5

170.8

145.2

119.5

93.8

62

246.4

 

16.96

246.4

246.4

 

237.6

211.9

186.2

160.5

134.9

232.2

 

18.14

232.2

232.2

 

227.2

201.5

175.8

150.1

124.5

 

 

 

 

 

 

57

230.8

 

16.49

230.8

230.8

 

230.8

205.2

179.5

153.8

128.1

238.6

 

18.50

238.6

238.6

 

237.7

212.1

186.4

160.7

135.0

 

72

297.7

 

17.84

204.5

176.5

 

148.5

120.5

92.4

-

-

282.9

 

19.38

207.0

179.0

 

151.0

123.0

94.9

-

-

9400

67

271.0

 

17.35

265.8

237.8

 

209.8

181.8

153.7

125.7

97.7

260.9

 

18.72

260.9

233.7

 

205.7

177.7

149.7

121.7

93.6

62

252.0

 

17.36

252.0

252.0

 

248.8

220.7

192.7

164.7

136.7

236.6

 

18.53

236.6

236.6

 

236.6

208.6

180.6

152.6

124.6

 

 

 

 

 

 

57

236.1

 

16.88

236.1

236.1

 

236.1

208.1

180.1

152.0

124.0

243.2

 

18.89

243.2

243.2

 

243.2

215.1

187.1

159.1

131.1

 

 

 

 

 

 

 

105°F

 

 

 

 

 

 

 

 

 

115°F

 

 

 

 

 

72

244.1

 

20.09

146.5

129.4

 

112.3

95.2

78.1

-

-

230.8

 

21.72

142.8

125.7

 

108.6

91.5

74.4

-

-

6000

67

225.3

 

19.63

186.7

169.6

 

152.5

135.4

118.3

101.2

84.1

213.4

 

21.43

181.2

164.1

 

147.0

129.9

112.8

95.7

78.6

62

202.7

 

19.37

202.7

194.9

 

177.7

160.6

143.5

126.4

109.3

190.2

 

21.09

190.2

188.9

 

171.8

154.7

137.6

120.5

103.4

 

 

 

 

 

 

57

211.7

 

19.63

211.7

205.7

 

188.6

171.5

154.4

137.3

120.2

202.2

 

21.28

202.2

198.2

 

181.1

164.0

146.9

129.8

112.7

 

72

250.6

 

20.15

162.5

142.2

 

122.0

101.8

81.6

-

-

236.4

 

21.79

157.8

137.5

 

117.3

97.1

76.9

-

-

7000

67

231.3

 

19.69

206.2

185.9

 

165.7

145.5

125.3

105.1

84.9

218.5

 

21.50

199.2

179.0

 

158.8

138.6

118.4

98.1

77.9

62

208.1

 

19.43

208.1

204.2

 

193.1

172.9

152.7

132.5

112.3

194.8

 

21.16

194.8

194.1

 

185.6

165.4

145.1

124.9

104.7

 

 

 

 

 

 

57

217.3

 

19.70

217.3

214.3

 

204.9

184.7

164.5

144.3

124.1

207.0

 

21.35

207.0

205.1

 

195.7

175.4

155.2

135.0

114.8

 

72

257.0

 

20.22

178.4

155.1

 

131.7

108.4

85.1

-

-

241.9

 

21.87

172.7

149.4

 

126.0

102.7

79.4

-

-

8000

67

237.3

 

19.76

225.6

202.3

 

178.9

155.6

132.3

109.0

85.6

223.6

 

21.58

217.3

193.9

 

170.6

147.3

123.9

100.6

77.3

62

213.5

 

19.50

213.5

213.5

 

208.5

185.2

161.9

138.5

115.2

199.4

 

21.24

199.4

199.4

 

199.4

176.0

152.7

129.4

106.1

 

 

 

 

 

 

57

222.9

 

19.77

222.9

222.9

 

221.3

197.9

174.6

151.3

128.0

211.9

 

21.43

211.9

211.9

 

210.2

186.9

163.5

140.2

116.9

 

72

264.1

 

20.56

191.3

165.6

 

139.9

114.3

88.6

-

-

250.6

 

22.15

187.0

161.3

 

135.6

110.0

84.3

-

-

8700

67

243.8

 

20.09

238.0

215.7

 

190.0

164.4

138.7

113.0

87.3

231.7

 

21.85

228.5

209.3

 

183.6

157.9

132.2

106.6

80.9

62

219.4

 

19.83

219.4

219.4

 

216.9

191.2

165.5

139.8

114.2

206.6

 

21.51

206.6

206.6

 

206.6

180.9

155.2

129.5

103.9

 

 

 

 

 

 

57

229.0

 

20.10

229.0

229.0

 

228.2

202.5

176.9

151.2

125.5

219.5

 

21.70

219.5

219.5

 

218.7

193.0

167.3

141.7

116.0

 

72

271.1

 

20.91

204.1

176.1

 

148.1

120.1

92.1

-

-

259.4

 

22.43

201.3

173.3

 

145.2

117.2

89.2

-

-

9400

67

250.3

 

20.43

250.3

229.2

 

201.1

173.1

145.1

117.1

89.1

239.7

 

22.13

239.7

224.6

 

196.6

168.6

140.5

112.5

84.5

62

225.2

 

20.16

225.2

225.2

 

225.2

197.2

169.2

141.1

113.1

213.8

 

21.78

213.8

213.8

 

213.8

185.7

157.7

129.7

101.7

 

 

 

 

 

 

57

235.2

 

20.43

235.2

235.2

 

235.2

207.1

179.1

151.1

123.1

227.2

 

21.98

227.2

227.2

 

227.2

199.2

171.1

143.1

115.1

 

 

 

 

 

 

 

125°F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

217.6

 

23.35

139.1

122.0

 

104.9

87.8

70.7

-

-

 

 

 

 

 

 

 

 

 

 

 

6000

67

201.4

 

23.23

175.7

158.6

 

141.5

124.4

107.3

90.2

73.1

 

 

 

 

 

 

 

 

 

 

 

62

177.7

 

22.82

177.7

177.7

 

165.8

148.7

131.6

114.5

97.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

192.7

 

22.93

192.7

190.8

 

173.7

156.5

139.4

122.3

105.2

 

 

 

 

 

 

 

 

 

 

 

 

72

222.2

 

23.43

153.1

132.8

 

112.6

92.4

72.2

-

-

 

 

 

 

 

 

 

 

 

 

 

7000

67

205.6

 

23.31

192.3

172.1

 

151.9

131.7

111.4

91.2

71.0

 

 

 

 

 

 

 

 

 

 

 

62

181.5

 

22.90

181.5

181.5

 

178.0

157.8

137.6

117.4

97.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

196.8

 

23.01

196.8

195.8

 

186.4

166.2

146.0

125.7

105.5

 

 

 

 

 

 

 

 

 

 

 

 

72

226.8

 

23.51

167.0

143.7

 

120.3

97.0

73.7

-

-

 

 

 

 

 

 

 

 

 

 

 

8000

67

209.9

 

23.39

208.9

185.6

 

162.3

138.9

115.6

92.3

68.9

 

 

 

 

 

 

 

 

 

 

 

62

185.2

 

22.98

185.2

185.2

 

185.2

166.9

143.5

120.2

96.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

200.8

 

23.09

200.8

200.8

 

199.1

175.8

152.5

129.1

105.8

 

 

 

 

 

 

 

 

 

 

 

 

72

237.2

 

23.74

182.7

157.0

 

131.3

105.7

80.0

-

-

 

 

 

 

 

 

 

 

 

 

 

8700

67

219.5

 

23.61

219.0

202.8

 

177.1

151.5

125.8

100.1

74.4

 

 

 

 

 

 

 

 

 

 

 

62

193.7

 

23.19

193.7

193.7

 

193.7

170.6

144.9

119.2

93.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

210.0

 

23.30

210.0

210.0

 

209.2

183.5

157.8

132.1

106.5

 

 

 

 

 

 

 

 

 

 

 

 

72

247.6

 

23.96

198.4

170.4

 

142.4

114.3

86.3

-

-

 

 

 

 

 

 

 

 

 

 

 

9400

67

229.1

 

23.84

229.1

220.0

 

192.0

164.0

136.0

107.9

79.9

 

 

 

 

 

 

 

 

 

 

 

62

202.3

 

23.41

202.3

202.3

 

202.3

174.3

146.3

118.2

90.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

219.2

 

23.52

219.2

219.2

 

219.2

191.2

163.2

135.1

107.1

 

 

 

 

 

 

 

 

 

 

 

1.The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower Performance table for the kW of the supply air blower motor.

2.These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.

12

Johnson Controls Unitary Products

Loading...
+ 28 hidden pages