Honeywell MS-9200UDLSE, MS-9200UDLS User Manual

PN: 52750:E1 ECN 09-062
Addressable Fire Alarm Control Panel
MS-9200UDLS
MS-9200UDLSE
IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52750
E1
01/27/09 Revision:
PN: 52750:E1 ECN 09-062
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise follow­ing the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These docu­ments can be found at http:/www.systemsensor.com/html/ applicat.html. A study by the Federal Emergency Manage­ment Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sens­ing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flam­ing fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.). Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life. IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently con­sumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or com­prehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmis­sion systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the require­ments of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and asso­ciated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F 93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room tempera­ture of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. This Class A digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. Cet appareil numerique de la Classe A est conforme a la norme NMB-003 du Canada.
Notes
4 MS-9200UDLS PN 52750:E1 01/27/09
Table of Contents
Product Description .................................................... ............................................................................................14
Features and Options .........................................................................................................................................14
Specifications ....................................................................................................................................................16
Current Availability .................................................................................................................................... 17
Controls and Indicators .....................................................................................................................................18
Circuits ..............................................................................................................................................................19
Digital Alarm Communicator/Transmitter ........................................................................................................19
Components .......................................................................................................................................................20
Intelligent Addressable Detectors: Newer Series ..................................... ..................................................20
Intelligent Addressable Modules: Newer Series ........................................................................................20
300 Series Intelligent Addressable Devices ...............................................................................................21
Addressable Device Accessories ................................................................................................................21
Optional Modules ..............................................................................................................................................21
Accessories ........................................................................................................................................................22
PS-Tools Programming Utility ................................................... ................................................................22
DP-9692 Dress Panel ............................................................................ .....................................................22
Trim Ring ...................................................................................................................................................22
Battery Box ................................................................................................................................................22
Battery Charger ..........................................................................................................................................23
CHG-75 Battery Charger ................................ ...................................................... .............................. 23
CHG-120F Battery Charger ................................................................................................................23
IPDACT- Internet Protocol DACT .............................................................................................................23
ANN-BUS Annunciators/Modules ............................................................................................................24
ANN-BUS Wiring ...............................................................................................................................24
Calculating Wiring Distance for ANN-BUS Modules .......................................................................24
Wiring Configuration .......................................................................................................................... 26
Powering ANN-BUS Devices from Auxiliary Power Supply ............................................................ 27
ANN-BUS Device Addressing ...........................................................................................................27
ANN-80 Remote Fire Annunciator ............................ ...................................................... ...................28
Specifications ......................................................................................................................................28
Installation ...........................................................................................................................................28
Mounting .............................................................................................................................................28
Opening/Closing Annunciator ............................................................................................................28
Wiring ANN-80 to FACP ...................................................................................................................29
ANN-S/PG Serial/Parallel Interface Installation ...............................................................................
Specifications ......................................................................................................................................31
PRN-6F Printer Installation ................................................................................................................31
ANN-I/O LED Driver Module ............................................................................................................33
ANN-I/O Board Layout ......................................................................................................................33
Specifications ......................................................................................................................................33
ANN-I/O Connection to FACP ...........................................................................................................34
ANN-I/O Module LED Wiring ...........................................................................................................34
ANN-LED Annunciator Module ........................................................................................................35
ANN-LED Board Layout ....................................................................................................................36
Specifications ......................................................................................................................................36
Mounting/Installation ..........................................................................................................................36
ANN-LED Connection to FACP ........................................................................................................37
ANN-RLY Annunciator Module ........................................................................................................38
ANN-RLY Board Layout ....................................................................................................................38
Specifications ......................................................................................................................................38
Mounting/Installation ..........................................................................................................................38
ANN-RLY Connection to FACP ........................................................................................................39
ANN-BUS Audio Panel Control .........................................................................................................39
Legacy ACS Series LED Zone Type Annunciators ...................................................................................41
Getting Started ......................................................... ..........................................................................................41
.31
MS-9200UDLS P/N: 52750:E1 01/27/09 5
Telephone Requirements and Warnings ............................................................................................................42
Telephone Circuitry ....................................................................................................................................42
Digital Communicator ................................................................................................................................42
Telephone Company Rights and Warnings ................................................................................................43
For Canadian Applications .........................................................................................................................44
Installation ...............................................................................................................................................................45
Mounting Backbox ................................ ...................................................... ......................................................45
Mounting Optional Transformer/Remounting Chassis .....................................................................................46
Power .................................................................................................................................................................49
AC Power and Earth Ground Connection ..................................................................................................49
Battery Power .............................................................................................................................................49
Special Application DC Power Output Connection ...................................................................................49
Relays ................................................................................................................................................................50
Notification Appliance Circuits ............................................................. ............................................................50
Configuring NACs .....................................................................................................................................51
Style Y (Class B) NAC Wiring ..................................................................................................................51
Style Z (Class A) NAC Wiring ..................................................................................................................52
Remote Synchronization Output .......................................................................................................................52
UL Power-limited Wiring Requirements ...........................................................................................................53
Digital Communicator .......................................................................................................................................54
Optional Module Installation .............................................................................................................................55
4XTMF Transmitter Module Installation ................................................................................. ..................56
Printer .........................................................................................................................................................57
Programming .........................................................................................................................................................59
Programming Data Entry ...................................................................................................................................59
User Programming .............................................................................................................................................60
Initial Power-up ............................................................................. ....................................................................61
Programming Screens Description ...................... ...................................................... ........................................61
Programming and Passwords ............................................................................................. ................................62
Master Programming Level ...............................................................................................................................63
Autoprogram ..............................................................................................................................................64
Point Program .............................................................................................................................................65
Detector Programming ........................................................................................................................65
Add Detector .......................................................................................................................................65
Delete Detector ....................................................................................................................................66
Edit Detector .......................................................................................................................................66
Module Programming .........................................................................................................................75
Add Module ........................................................................................................................................75
Delete Module .....................................................................................................................................76
Edit Module Screen for Monitor Module ............................................................................................76
Edit Module Screen for Control Modules ...........................................................................................85
Zone Setup ..................................................................................................................................................92
Enable ..................................................................................................................................................92
Disable .................................................................................................................................................93
Zone 97, 98 and 99 ..............................................................................................................................93
Zones Installed ......................................... ...................................................... ................
.....................94
Zones Enabled .....................................................................................................................................94
Zones Disabled ....................................................................................................................................94
Zone Type ...........................................................................................................................................95
Zones Available ............................... ..................................................... ..............................................96
Zone Message ......................................................................................................................................96
Loop Setup .................................................................................................................................................96
Style ..................................................................................................................................................... 96
Loop Protocol ......................................................................................................................................97
System Setup ..............................................................................................................................................97
6 MS-9200UDLS P/N: 52750:E1 01/27/09
Table of Contents
Trouble Reminder ...............................................................................................................................98
Banner .................................................................................................................................................98
Time-Date ...........................................................................................................................................100
Time ....................................................................................................................................................100
Date .....................................................................................................................................................101
Clock Format .......................................................................................................................................101
Daylight Savings Time ........................................................................................................................101
Timers .................................................................................................................................................102
PAS (Positive Alarm Sequence) Delay ...............................................................................................102
Pre-signal Delay ................................... ...............................................................................................103
Waterflow Delay .................................................................................................................................103
AC Loss Delay ....................................................................................................................................104
NAC (Notification Appliance Circuit) ................................................................................................104
Enabled ................................................................................................................................................105
Type ....................................................................................................................................................106
Silenceable ..........................................................................................................................................106
Auto Silence ........................................................................................................................................107
Coding (only for NACs not programmed as Sync Strobe Type) ........................................................107
Zone ....................................................................................................................................................109
Silence Inhibited .................................................................................................................................109
Sync Type ...........................................................................................................................................109
Relays ..................................................................................................................................................110
Canadian Option .................................................................................................................................111
Waterflow Silenceable ........................................................................................................................111
Verify Loop ................................................................................................................................................111
History ........................................................................................................................................................112
View Events ........................................................................................................................................112
Erase History .......................................................................................................................................112
Walktest ......................................................................................................................................................113
Option Modules .........................................................................................................................................115
Annunciators .......................................................................................................................................115
Term Options ......................................................................................................................................115
ACS Options .......................................................................................................................................116
ANN-BUS Options .............................................................................................................................118
Onboard DACT ...................................................................................................................................131
Onboard DACT Enable .......................................................................................................................131
Primary Phone .....................................................................................................................................131
Secondary Phone ...............................................................................................................
..................132
Service Terminal ................................................... ..................................................... .........................132
Central Station .....................................................................................................................................133
Trouble Call Limit (Dialer Runaway Prevention) ..............................................................................134
Supervised Phone Line ........................................................................................................................141
Printer/PC ............................................................................................................................................142
Password Change ........................................... ..................................................... .......................................143
Clear Program ........................................................... .................................................................................144
Program Check ................................... ...................................................... ..................................................145
Maintenance Programming Level .....................................................................................................................147
Disable Point ..............................................................................................................................................148
History ........................................................................................................................................................149
Program Check ................................... ...................................................... ..................................................150
Walktest ......................................................................................................................................................151
System ........................................................................................................................................................153
Zone Setup ..................................................................................................................................................154
Operating Instructions ...........................................................................................................................................156
Panel Control Buttons .......................................................................................................................................156
MS-9200UDLS P/N: 52750:E1 01/27/09 7
Acknowledge/Step ......................................................................................................................................156
Alarm Silence .............................................................................................................................................156
Drill/Hold 2 Sec ............................................................................................ ..............................................156
Reset ...........................................................................................................................................................156
LED Indicators ..................................................................................................................................................157
Normal Operation ...................................................... ..................................................... ...................................158
Trouble Operation ..............................................................................................................................................158
Alarm Operation ................................................................................................................................................160
Supervisory Operation ...................................... ...................................................... ...........................................161
Process Monitor Operation ........................................... ..................................................... ................................162
Hazard/Tornado Condition Operation ...............................................................................................................162
Medical Alert Condition Operation ...................................................................................................................162
NAC Operation ..................................................................................................................................................162
Programmed Zone Operation ............................................................................................................................163
Disable/Enable Operation ..................................................................................................................................163
Waterflow Circuits Operation ......................................................................................... ...................................163
Detector Functions .............................................................................................................................................163
Time Functions: Real-Time Clock ............................................................................................. .......................163
Synchronized NAC Operation ............................. ...................................................... ........................................164
Coded Operation ............................ ..................................................... ............................................................... 164
Presignal ............................................................................................................................................................164
Positive Alarm Sequence ...................................................................................................................................165
Special System Timers ......................................................................................................................................166
Silence Inhibit Timer ..................................................................................................................................166
Autosilence Timer ......................................................................................................................................166
Trouble Reminder .......................................................................................................................................166
Waterflow Retard Timer ............................................. ...................................................... ..........................166
Alarm Verification (None or One Minute) .................................................................................................166
Walktest .............................................................................................................................................................167
Read Status ........................................................................................................................................................168
System Point ...............................................................................................................................................169
Zones ..........................................................................................................................................................170
Power ..........................................................................................................................................................171
Trouble Reminder .......................................................................................................................................172
Timers .........................................................................................................................................................172
NAC ............................................................................................................................................................173
Relays .........................................................................................................................................................173
Program Check ...........................................................................................................................................174
History ........................................................................................................................................................174
Annunciators ..............................................................................................................................................174
Phone Line ..................................................................................................................................................176
Central Station ............................................................................................................................................176
Service Terminal .........................................................................................................................................177
Printer/PC ................................................................................................................................................... 177
Print ............................................................................................................................................................178
Time-Date .....................................................................................................................
..............................180
Central Station Communications ..........................................................................................................................181
Transmittal Priorities .........................................................................................................................................182
Remote Site Upload/Download ..............................................................................................................................184
Remote Download ......................... .................................................................................................................... 184
Transferring a Program ......................................................................................................................................185
Security Features ........................................................................................................................................186
Power Supply Calculations ....................................................................................................................................187
Overview ...........................................................................................................................................................187
Calculating the AC Branch Circuit ....................................................................................................................187
8 MS-9200UDLS P/N: 52750:E1 01/27/09
Table of Contents
Calculating the System Current Draw ...............................................................................................................188
Overview ....................................................................................................................................................188
How to Use Table 7.3 on page 189 to Calculate System Current Draw ....................................................188
Calculating the Battery Size ..............................................................................................................................190
NFPA Battery Requirements ......................................................................................................................190
Selecting and Locating Batteries ................................................................................................................190
Software Zones ........................................................................................................................................................191
Correlations .......................................................................................................................................................191
Default Programming .............................................................................................................................................197
NFPA Standard-Specific Requirements ...............................................................................................................198
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts ...........................................202
MBT-1 Municipal Box Trip - Silenceable ........................................................................................................203
FACP with Keltron .................................................................................................................................................204
Wire Requirements ............................................................................................... ..................................................205
NAC Wiring ............................................ ..........................................................................................................207
HVAC Control ........................................................................................................................................................208
Control Module Operation ................................................................................................................................208
HVAC SHUTDN .......................................................................................................................................208
Monitor Module Operation ...............................................................................................................................208
HVAC RESTART ......................................................................................................................................208
HVAC OVRRIDE ......................................................................................................................................209
Ademco Contact ID Format Event Code Descriptions .......................................................................................210
Transmission Format Between DACT and Receiver ........................................................................................210
Ademco Contact ID Typical Printout ................................................................................................................210
Central Station Points ............................................................................................................................................215
MS-9200UDLS P/N: 52750:E1 01/27/09 9
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions abou t so ftware and the appropriate version for a specific application.
10 MS-9200UDLS PN 52750:E1 01/27/09
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1610 Central Station Burglar Alarm Units UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard EIA-485 Serial Interface Standard NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire-Lite Documents:
Fire-Lite Device Compatibility Document #15384 SLC Wiring Manual Document #51309 ACS Series Annunciators Document #51480 CHG-120F Battery Charger Document #50888 CHG-75 Battery Charger Document #51315 LDM Series Lamp Driver Modules Document #50055 LCD-80F Remote Fire Annunciator Document #51338 ACM-8RF Relay Control Module Document #50362 IPDACT Communicator/Transmitter Document #53109 ANN-80 Product Installation Document Document #52749 ANN-(R)LED Product Installation Doc. Document #53032 ANN-I/O Product Installation Document Document #151416 ANN-RLY Product Installation Document Document #53033 ANN-S/PG Product Installation Document Document #151417 ACC-25/50(ZS/T) Manual Document #52750
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9200UDLS PN 52750:E1 01/27/09 11
TB8
GND DTR RCV
T
X
TB8 (option to DB-25)
5 4 3 2 1
9 8 7 613 12 11 10
25 24 23 22 21 20 19 18 17 16 15 1 4
TB8
GND DTR
RCV T
X
White
Green
Black
Red
9 8 7 6
DB9F
5 4 3 2 1
EIA-232
(nonsupervised)
to printer or
Upload/Download Utility.
For EDP-listed equipment or
personal computer
personal computer with FACP
50 foot maximum within same room.
OR
BA
SHIELDSLCSLC
shield
A A
-
B
-
SLCSLC
(supervised)
SLC Loop
Manual for detailed
information on wiring
Refer to the SLC Wiring
(EIA-485)
supervised)
(power-limited,
to Annu nc i ato rs
ACS/ANN-B US
OR
TERM
(EIA-485)
to LCD annunc.
+
B+ A+ B- A- A B
B
+
for Style 4, 6 and 7.
addressa ble devices
-
+
-
T
O
U
T
+
U
O
IN-
IN+ IN- OUT+ OUT-
I
+
N
Cut this jumper to enable
(Supervised, Power Limited)
NAC #1 & #2
Notification Appliance Circuits
Style Z (Class A)
Supervisory relay w hen
4XTMF module is installed
+
NAC #2
+
using NACKEY card.
NAC #1
2.5 amps max. per circuit.
JP6 config ure d for Cl ass A
4XTMF
JP3
4XTMF
CUT TO
MONITOR
J6
J5
KISSOFF
+
+
USB Port J12 for local
J7
Cut this jumper to supervise
the 4XTMF m odu le whe n
install ed (see J5 & J6)
B
-
A
-
A
+
+
B
+
92udLSlayo.cdr
TB4
B
-
A
-
A
+
+
B
+
TB3
programming using a
personal computer and
programming utility.
J12
SEC. A CTIVE
SEC. PHONE LINE
PH15 PH16
PRI. ACTIVE
(Nonpower-Limited)
PRI. PHONE LINE
JP2
NC NO C
1 Fixed Trouble Relay
Nonsupervised relay contacts
Contact Ra tin g s:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts show n be lo w in nor m al
condition (AC power with no alarm,
ELRs 4.7K, ½W
2 Programmable Relays &
++
NAC #4 NAC #2
++
for Class B using NACKEY card.
Notification Appliance Circuits
NAC #1 NAC #3
(See Style Z illustrated near right edge of board).
(Special Ap pl i cati on ) 2.5 amps max. per circuit. JP6 conf igur e d
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
++
+
+
2
1
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
++
+
+
4
3
Trouble
Alarm*
NO position during
trouble co nd it ions an d
under loss of all power.
Supervisory*
(* )Factory default relay programming
2
1
RELAY 2
TB6 TB8 TB9 TB10
RELAY 1
NO NC C NC NO C
NO NC C NC NO CNO NC C
TB5
Flash Memory Load Enable Switch.
UP is normal position for switch.
DOWN position allows loading of
factory software upgrades.
RELA Y 3
NO NC C
NAC
Number
B
-
-
B B
+
B
+
B
-
B
-
B
+
B
+
2244
1
33 1
-
-
+
- -
+ +
NAC 2 CLAS S A
NAC 2 & 4 CLASS B
TB4 TB7
B+ A+ A- B- B+ A+ A- B-
1B + 3B + 3B - 1B - 2B + 4B + 4B - 2B -
NAC 1 & 3 CLASS B
Configur e NA Cs for Cl as s A or
Class B wiring using NACKEY
TB3
+ -
SUPPLY SYNC NAC 1 CLASS A
REMOT E PW R
TB2
RST
+ 24V -
POWER
+ 24V -
POWER
NON-RST
TB1
321
JP4
card. Factory default is Class B.
JP6
SW1
JP7
REMOVE TO
DISABLE GND. FLT.
Remove this jumper
to disable the FACP
battery charger when
To disable ground fault detection,
remove jumper/shunt from JP7
using exte rnal charger.
JP5
J11
CAUTION!
HIGH VOLTAGE
TRANSFORMER 2
I/F
KEYPAD
J4
LCD DISPLA Y
J1
TB11
TRANSFORMER 1
J3
PS2 Keyboard Interface DACT Phone Line Jacks
MINI DIN
KEYBOARD CONN.
- +
J9
BATTERY
Battery
nonpower-limited
24 VDC, supervised,
18 Amp Ho ur ma x imu m
HOT NEUT EARTH
120 VAC, 60 HZ, 3.0 amps
220/240 VAC, 50 Hz, 1.5 amps
J10
only
Transformer 2 Connector
Removing Ground
Basic System Connections
Remote Synchronization Output
Special Application Power
24 VDC filtered, supervised and power-limited.
0.040 amps maximum, follows NAC1 control circuit.
Requires 4.7kohm End-of-Line resistor.
Special Application DC Power Outputs (24 VDC)
Nonsupe r v ised, power-limited circuits
Supervise with a power supervision relay A77-716B
Nonresettable or Resettable Power
Jumper s electable by JP4, 24 VDC filtered,
power-limited (0.3 00 amps maximum)
Supervi s io n r equired. Nonrese ttable
Power suitable for powering annunciat ors,
Resettable Power suitable for powering
Resettable Power - 24 VDC filtered, power-l imite d
(0.300 am p s max imu m ) to sm oke de te ct or s (ID C) .
Supervision required.
smoke detectors..
UL/NFPA Style/Class
Fault Disable Jumper JP7
identifications for circuits.
Remove jumper JP7
with the approval of the AHJ
Important!
voids
(Authority Havi ng Juri sdi ct io n)
Transformer 1 Connector
CAUTION! HIGH VOLTAGE
12 MS-9200UDLS PN 52750:E1 01/27/09
Peripheral Devices and Their Documents:
ANN Audio Control for ACC-25/50(ZS/T) Doc. #51889
ANN-BUS - TB9
ANN-80
LCD Text Annunciator
Doc. #52749
PH15 & PH16 Telephone Connections
J5 & J6
SLC Loop - TB10
ANN-RLY
10 Form-C Relay Card
Doc. #53033
Reverse Polarity Module
ANN-(R)LED
LED Display
Doc. #53032
ANN-I/O
LED Driver
Doc. #151416
IPDACT
Internet Communicator
Doc. #53109
4XTMF
Addressable Devices and SLC Wiring
Doc. #51309
ANN-S/PG
Printer Driver
Doc. #151417
CHG-120F Charger Doc. #50888
Battery Connector - J9
9200udLSannperi.cdr
CHG-75 Charger Doc. # 51315
MS-9200UDLS PN 52750:E1 01/27/09 13
Product Description
SECTION 1 Product Description
The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective, intelligent addressable control panel has an extensive list of powerful features.The combination of Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection technology. The power supply and all electronics are contained on a single circuit board housed in a metal cabinet, providing a complete fire control system for most applications. Optional modules, which plug into the main circuit board, are available for special functions. Available accessories include LED, graphic and LCD annunciators, reverse polarity/city box transmitter, local and remote upload/download software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via the public switched telephone network. It also allows remote programming or interrogation of the control panel using the PS-Tools Upload/Download utility via the public switched telephone network. Local programming and interrogation is also possible using the PS-Tools and the USB port (J12) on the FACP. Any personal computer with Windows baud or faster and PS-Tools software may serve as a Service Terminal. This allows download of the entire program or upload of the entire program, history file, walktest data, current status and system voltages.
XP or greater, and compatible modem with a speed of 2400
MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS (120 VAC version) and the MS-9200UDLSE (240 VAC version) FACPs.
Inventory
When MS-9200UDLS shipment is received, check that all parts have been included in shipment. The MS-9200UDLS shipment consists of one of each of the following:
main circuit board with displaybackbox with doorplastic bag containing screws, cables, key, etc.manual
1.1 Features and Options
New LiteSpeed™ polling protocol for faster SLC response time
SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire (refer to "Wire Requirements" on page 205)
Built-in DACT (Digital Alarm Communicator/Transmitter)
Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)
99 software zones
Onboard NACs (Notification Appliance Circuits) which can be configured as four Style Y (Class B) or two Style Z (Class A) circuits - special application
3.0 amps total power for NACs and 24 VDC special application auxiliary power outputs expandable to 6.0 amps
3.6 amps total system power (includes battery charger) expandable to 6.6 amps
T wo programmable relay outputs and one fixed trouble relay
Synchronization output for remote power supply applications (special application)
Built-in Programmer
Telephone Line Active LEDs
14 MS-9200UDLS PN 52750:E1 01/27/09
Product Description
Communication Confirmation (Kissoff) LED
Touchtone/Rotary di aling
Programmable Make/Break Ratio
EIA-232 Printer/PC interface (variable baud rate)
80-character LCD display (backlit)
Real-time clock/calendar with daylight savings time control
History file with 1,000 event capacity
Advanced fire technology features:
Automatic drift compensationMaintenance alertDetector sensit ivity test capability (NFPA 72 compliant)Autom a tic devi ce type-code veri ficationPoint trouble identification
Waterflow selection per modul e point
Alarm verification selection per detector point
Walktest, silent or audible
PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA 72 compliant)
Silence inhibit timer option per NAC
Autosilence timer option per NAC
Continuous, March Time, Temporal or California code for main circuit board NACs with two-stage capability
Selectable strobe synchronization per NAC
Remote Acknowledge, Alarm Silence, Reset and Drill via addressable modules, ACS annunciators or ANN-80 Remote annunciator
Auto-program (learn mode) reduces installation time. Reports two devices set to the same address
Password and key-protected nonvolatile memory
User programmable password
Fully programmable from local keypad or optional keyboard
Optional PK-CD (contains PS-Tools utility) for local or remote Upload/ Download of program and data
Compatible with Fire-Lite’s newer series devices in LiteSpeed and CLIP mode (refer to SLC Wiring Manual for a list of compatible addressable devices)
Compatible with legacy Fire-Lite 300 Series devices in CLIP mode only (refer to the SLC Wiring Manual for a list of compatible addressable devices)
Optional 4XTMF module (conventional reverse polarity/city box transmitter)
ANN-BUS for connection to following optional modules (cannot be used if ACS annunciators are used):
ANN-80 Remote AnnunciatorANN-I/O LED DriverANN-S/PG Printer ModuleANN-RLY Form-C Relay ModuleANN-LED Annunciator Module annunciates alarm, trouble and supervisoryANN-RLED Annunciator Module annunciates alarms only
Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center
Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are used):
ACS Series-LED Zone AnnunciatorsLDM Graphic Annunciator SeriesLCD-80F Liquid Crystal Display point annunciatorACM-8RF Relay Module
MS-9200UDLS PN 52750:E1 01/27/09 15
Product Description
1.2 Specifications
Refer to Illustration on page 10 for terminal locations and connections.
AC Power - TB11
MS-9200UDLS: 120 VAC, 60 Hz, 3.0 amps MS-9200UDLSE: 240 VAC, 50 Hz, 1.5 amps Wire size: minimum 14 AWG (2.00 mm
2
) with 600 V insulation
Battery (Lead Acid Only) - J9
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp Hour batteries. For greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box). Minimum Battery Size: 7 Amp Hour Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum Maximum length - refer to "Wire Requirements" on page 205) Maximum loop current is 400 mA (short circuit) or 100 mA (normal) Maximum loop resistance is 40 ohms Supervised and power-limited circuit Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z (Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs Style is configured using NACKEY card plugged into JP6 on main board Special Application full-wave rectified power Power-limited circuitry NAC wiring requirements refer to "NAC Wiring" on page 207 Nominal operating voltage: 24 VDC Current-limit: fuseless, electronic, power-limited circuitry Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 17) End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive) Form-C relays Refer to Figure 2.6 on page 50 for information on power-limited relay circuit wiring
Nonresettable or Resettable Special Application Power (24 VDC Nominal) ­TB1, Terminals 1 (+) & 2 (-)
Jumper selectable (JP4) for conversion to resettable power output Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 0.300 amps (see Figure 1.1) Power-limited circuit
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC nominal) - TB1, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 0.300 amps is available for powering 4-wire smoke detectors (see Figure 1.1) Power-limited circuit Refer to the Device Compatibility Document for listed compatible devices
16 MS-9200UDLS PN 52750:E1 01/27/09
Product Description
Remote Sync Output - TB2
Remote power supply synchronization output 24 VDC nominal special application power Maximum current is 40 mA End-of-Line Resistor: 4.7KΩ Output linked to NAC 1 control Supervised and power-limited circuit
EIA-485 (TERM) or EIA-232 Serial - TB8
EIA-485 Terminal Mode annunciator connections: Terminal 1 (In +), 2 (In -), 3 (Out +), 4 (Out -) EIA-232 PC/Printer applications connections: Terminal 1 (Transmit), 2 (Receive), 3 (DTR) 4 (Ground)
EIA-485 ACS or ANN-BUS - TB9
ACS/ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
1.2.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel circuit and the total current available from the FACP with optional second transformer.
Note: If NACs are configured as two Style Z (Class A) circuits, each circuit can handle 2.5 amps maximum.
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
6.0 amps with optional second XRM-24B(E) transformer.
3.0 amps max. with only standard transformer installed.
powerdist9200ud.cdr
MS-9200UDLS PN 52750:E1 01/27/09 17
Product Description
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character (4 lines X 20 characters) high viewing angle LCD display. The display includes a long life LED backlight that remains illuminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
AC Power (green)
Fire Alarm (red)
Supervisory (yellow)
Trouble (yellow)
Maintenance/presignal (yellow)
Alarm Silenced signals (yellow)
Disabled (yellow)
Battery fault (yellow)
Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD display and LED indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a telephone keypad.
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 012102
Function keys:
Acknowledge/Step
Alarm Silence
Drill
Reset (lamp test)
Service/program keys:
Keys labeled 1 to 9
* key
# key
0 (recall) key
2
1
4
GHI
78 9
PRS
*
QZ
ABC
5
JKL
TUV WXY
0
RECALL
3
DEF
6
MNO
#
-/.
1
CLR
ESC
MODE
st
EVENT
AC POWER FIRE ALARM
SUPERVISORY
TROUBLE
ENTER
MAINTENANCE
ALARM SILENCED
DISABLED BATTERY
ACK/STEP
ALARM SILENCE
DRILL
HOLD 2 SEC
RESET
GROUND
•1st Event key
Clear key
Figure 1.2 Membrane/Display Panel
Escape key
Mode key
Four cursor keys (up, down, left and right)
Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory conditions.
9600kypd.cdr
18 MS-9200UDLS PN 52750:E1 01/27/09
1.4 Circuits
Reference
Manual
Product Description
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop, configurable for NFPA Style 4, 6 or 7, provides communication to addressab le detectors, monitor (initiating device) and control (output device) modules. Refer to the SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
Special Application Power
24 VDC R eset table (sm oke detector power) output - 0.300 amps maximum24 VDC Nonresettable or Resettable power output - 0.300 amps maximum
24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The fixed fail-safe relay monitors system trouble and the two programmable relays are factory default programmed for system alarm and system supervisory. Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The programmable relays can be programmed for the following operations:
fire alarm
trouble
supervisory
supervisory auto-resettable
DACT communication failure
process monitor
process monitor auto-resettable
hazard alert
medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs are provided as well as a green Kissoff LED. The integral digital communicator provides the following functions:
Line Seizure: takes control of the phone lines disconnecting any premises phones
Off/On Hook: performs on and off-hook status to the phone lines
Listen for dial tone: 440 Hz tone typical in most networks
Dialing the Central Station(s) number: default is Touch-Tone rotary
For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly.
Communicate in the following formats:
Ademco Contact IDSIA DCS 8SIA DCS 20
®
, programmable to
MS-9200UDLS PN 52750:E1 01/27/09 19
Product Description
1.6 Components
See Page
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main circuit board.
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour). Ample knockouts are provided for system wiring. Also available is an optional dress panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for Canadian installations).
Transformer Assembly
Optional XRM-24B(E)
One 100VA transformer is provided standard with the panel (3.6 amps maximum). An optional 100 VA transformer XRM-24B
Standard XRM-24B(E)
(XRM-24BE for the MS-9200UDLSE) is available to provide maximum system and accessory power (6.6 amp total). Note that the
XRM-24B and XRM-24BE are only suitable for
9200xfor.cdr
use with MS-9200UDLS(E) with main circuit
board number 03611. This circuit board can also be identified by using the software revision of #9200UDV4.0 (meaning version 4.0) or later.
Batteries
Battery Cable P/N 75287
The MS-9200UDLS cabinet provides space for two batteries (up to 18 Amp Hou r). Batteries larger than 18 Amp Hour require an external charger such as the CHG-75 or
-
+
+
-
CHG-120F and a UL listed battery box such as the BB-55F. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the control panel to continually process the information to determine the status (alarm, trouble, maintenance or normal) of each detector. Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches. The maximum address cannot exceed address 99. Note that a blinking LED on an intelligent detector indicates communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 Series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operat e in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable detectors.
9200batt.cdr
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface between the control panel and conventional notification and initiating devices. Each module can be set to respond to an address with built-in rotary switches. The maximum
Reference
Manual
20 MS-9200UDLS PN 52750:E1 01/27/09
address cannot exceed address 99. Note that a blinking LED on an addressable module indicates communication between the module and the control panel.
Product Description
These devices (i.e., MMF-300, MMF-301, MMF-302, CMF-300, CRF-300) can operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible with older 300 series devices. If a mix of old and new series devices are installed on the same loop, the FACP must be programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of compatible addressable modules. Refer to the Device Compatibility Document for a list of approved conventional notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4­wire smoke detectors and notification appliances.
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision of a monitor and control module circuit.
1.7 Optional Modules
The MS-9200UDLS main circuit board includes option module connectors for the following module:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the module is used to select an option which allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which are located near the right edge the main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main circuit board, must be cut to allow supervision of the module.
MS-9200UDLS PN 52750:E1 01/27/09 21
Product Description
1.8 Accessories
1.8.1 PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the F ACP dir ectly from most IBM compatible computers (PC), running Windows™ XP (or newer). FACP program files can also be created and stored on the PC and then downloaded later to the control panel. The PK-CD Kit includes the Windows-based Programming Utility software on CD-ROM with on-line help file. A standard USB cable with male-A to male-B connectors, which must be purchased separately, is required for local connection of the PC to the USB port J12 on the FACP main circuit board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be enabled for remote download (refer to "Remote Site Upload/Download" on page 184). Remote interrogation of panel programming, history logs, detector status, etc., is possible without enabling the remote download option.
1.8.2 DP-9692 Dress Panel
An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC for Canadian installations). The dress panel restricts access to the system wiring while allowing access to the key panel. A ground strap must be connected between the stud on the inside of the dress panel and the ground stud in the backbox. An optional DP­9692-LED dress panel is available for use with the ANN-LED annunciator module.
1.8.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim Ring provides a finished appearance for a semi-flush mounted panel.
1.8.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the CHG-75 Battery Charger. The battery box, which is red and is provided with knockouts, was designed specifically to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two 26 AH or one 60 AH battery may also be housed in the battery box.
22 MS-9200UDLS PN 52750:E1 01/27/09
dp9200udls.cdr
Reference
Manual
Product Description
1.8.5 Battery Charger
1.8.5.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS­9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be housed in the BB-26 battery box. Larger batteries and the charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Refer to the CHG-75 Manual for additional information.
1.8.5.2 CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing jumper JP5, when using the CHG-120F . The batteries and charger can be housed in the BB-55F battery box which can be mounted up to 20 feet away from the control panel. Note that when using the BB-55F for housing the charger and batteries greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual for additional information.
1.8.6 IPDACT- Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter designed to allow FACP status communication to a Central Station via the internet. No telephone lines are required when using the IPDACT. Using Contact ID protocol from the FACP, the IPDACT converts the standard DACT phone communication to a protocol that can be transmitted and received via the internet. It also checks connectivity between the FACP and Central Station. Refer to the IPDACT Product Installation Document P/N 53109 for additional information.
MS-9200UDLS PN 52750:E1 01/27/09 23
Product Description
1.8.7 ANN-BUS Annunciators/Modules
WARNING! Disconnect all sources of power (AC and DC) before installing or removing any modules or wiring.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are being used due to incompatible serial communication protocols.
A variety of optional devices can be connected to the F ACP ANN-BUS communication circuit. ANN Series devices can be connected to the ACS (EIA-485) terminals on TB-9. Compatible devices include the following:
ANN-80 LCD Annunciator
ANN-S/PG Serial/Parallel Printer Interface Module
ANN-I/O LED Driver Module
ANN-LED Annunciator Module (alarm, trouble, supervisory LEDs)
ANN-RLED Annunciator Module (red alarm LEDs only)
ANN-RLY Relay Module
1.8.7.1 ANN-BUS Wiring
This section contains information on calculating ANN-BUS wire distances and the types of wiring configurations (Class B).
1.8.7.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire and the maximum wiring distance that can be used with FACP ANN-BUS accessory modules.
T o calculate the wire gauge that mus t be us ed to connect ANN-BUS modules to the FACP, it is necessary to calculate the total worst case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the following table:
Model Number Worst Case Current Draw
ANN-80 LCD Annunciator 0.040 amps ANN-S/PG Serial/Parallel Printer Interface Module 0.040 amps ANN-I/O LED Driver Module 0.200 amps ANN-(R)LED Annunciator Module 0.068 amps ANN-RLY Relay Module 0.075 amps
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp. If current draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices from Auxiliary Power Supply" on page 27.
24 MS-9200UDLS PN 52750:E1 01/27/09
Total Worst Case
Current Draw (amps)
0.100 1,852 ft. 4,688 ft. * 6,000 ft. *6,000 ft.
0.200 926 ft. 2,344 ft. 3,731 ft. 5,906 ft.
0.300 617 ft. 1,563 ft. 2,488 ft. 3,937 ft.
0.400 463 ft. 1,172 ft. 1,866 ft. 2,953 ft.
0.500 370 ft. 938 ft. 1,493 ft. 2,362 ft.
Product Description
After calculating the total worst case current draw, Table 1.1 specifies the maximum distance the modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges, capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
22 Gauge 18 Gauge 16 Gauge 14 Gauge
Table 1.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms) = 6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet) Maximum Resistance (Ohms) *500
(6,000 feet maximum) Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire Gauge Ohms per 1,000 feet (Rpu)
22 16.2 18 6.4 16 4.02 14 2.54
Exception: When using the ANN-RLY module, the installer must ensure that the maximum 24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:
Wire Gauge Maximum Wire Length
18 312 feet 16 497 feet 14 787 feet 12 1,250 feet
MS-9200UDLS PN 52750:E1 01/27/09 25
Product Description
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
3 ANN-80 Remote Fire Annunciators
1 ANN-S/PG Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
ANN-80 Current Draw = 3 X 0.040 amps = 0.120 amps ANN-S/PG Current Draw = 1 X.0.040 amps = 0.040 amps Total Worst Case Current Draw = 0.160 amps
Using this value and referring to the Wiring Distance Table 1.1 on page 25, it can be found that the available options are:
926 feet maxim um using 22 Gauge wire2,344 feet maximum using 18 Gauge wire3,731 feet maximum using 16 Gauge wire5,906 feet maximum using 14 Gauge wire
1.8.7.1.2 Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are supervised and power-limited
24 VDC nonresettable
ANN-BUS Device
MS-9200UDLS
ANN-BUS/ACS BUS
Figure 1.3 FACP wiring to ANN-BUS Device
92udlstoann80.cdr
26 MS-9200UDLS PN 52750:E1 01/27/09
Product Description
1.8.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 1.4 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as the FCPS-24FS6/8, when the total ANN-BUS power requirements exceed the panel’s DC Power Output capability.
Cut Ground Fault Detection jumper JP1 (FACP monitors for ground faults)
ANN-BUS and power wiring are supervised and power-limited
ANN-BUS
-24 VDC
ANN-80
+24 VDC nonresettable
ANN-BUS/ACS BUS
FCPS-24FS6/8
MS-9200UDLS
Figure 1.4 Powering ANN-BUS Devices from FCPS-24FS6/8
1.8.7.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the F ACP. A 5-position DIP switch on each device is used to set this address. The address set for these devices must also be programmed at the FACP for the specific device (refer to the programming section titled "ANN-BUS Options" on page 118).
A maximum of 8 devices can be connected to the F ACP ANN-BUS communication circuit. Device addresses do not need to be sequential and can be set to any number between 01 and 08. Note that 00 is not a valid address. The following table shows the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5 switch positions. Unless otherwise specified in the documentation supplied with each device, switch positions 6 and above must be set to OFF.
Address Switch 5 Switch 4 Switch 3 Switch 2 Switch 1
not valid OFF OFF OFF OFF OFF 01 OFF OFF OFF OFF ON 02 OFF OFF OFF ON OFF 03 OFF OFF OFF ON ON 04 OFF OFF ON OFF OFF 05 OFF OFF ON OFF ON 06 OFF OFF ON ON OFF 07 OFF OFF ON ON ON 08 OFF ON OFF OFF OFF
92udlstofcptoann.cdr
Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
MS-9200UDLS PN 52750:E1 01/27/09 27
Product Description
1.8.7.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire annunciator. It mimics the display on the control panel and will annunciate device type, point alarm, trouble or supervisory condition, zone assignment plus any custom alpha labels programmed into the FACP. The annunciator also provides system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm Silenced conditions. Additionally, the annunciator is capable of remotely performing critical system functions such as Acknowledge, Silence, Reset and Drill. Communication between the ANN-80 and FACP is accomplished over a two wire RS-485 serial interface employing the ANN-BUS communication format. The devices are powered, via two additional wires, from either the host FACP or remote UL-listed, filtered, power supply.
The function buttons, keyswitch and piezo sounder may be individually enabled and disabled through the FACP software. Refer to "ANN-80 Options" on page 130 for a description of this feature and programm in g information.
Note that if the keyswitch is enabled and remains in the unlocked position for more than two minutes without any buttons being pressed on the annunciator, a trouble indication will be annunciated.
1.8.7.3.1 Specifications
Operating Voltage Range: 18 VDC to 28 VDC
Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no act ivi ty): 37.0 mATrouble: 39.0 mAAlarm: 40.0 mAAC Fail ( not backlit): 15.0 mA
For use indoors in a dry location
1.8.7.3.2 Installation
Ensure that all power (AC and DC) has been removed from the FACP before installing the annunciator.
1.8.7.3.3 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square electrical box. Select and remove the appropriate knockout(s), pull the necessary wires through the knockouts and mount the annunciator in or on the wall depending on the type of installation desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting the annunciator to the electrical box/wall. The cover cannot be reattached or removed after the annunciator has been mounted.
1.8.7.3.4 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to access the terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counter­clockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover open
3. T o close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and remove the key
28 MS-9200UDLS PN 52750:E1 01/27/09
Product Description
Annunciator cover with LCD display
Press in latch and pull annunciator cover open
Key switch shown in ON position
Annunciator backplate
1.8.7.3.5 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all power has been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal block TB1
TB1
wiring channel
wires
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B). Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals 1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by dressing it neatly through wire channel, with any excess wire pushed back through hole into electrical box
MS-9200UDLS PN 52750:E1 01/27/09 29
Product Description
ANN-80
ANN-BUS and power wiring are supervised and power-limited
ANN-BUS
24 VDC nonresettable
ANN-BUS/ACS BUS
FACP
Figure 1.5 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-9200UDLS
MS-9200UDLS ANN-80 (TB1)
Terminal GND (-) on TB1 Terminal 1 (-) Terminal PWR (+)TB1 Terminal 2 (+) Terminal ACS on TB9 Terminal 3 (A) Terminal ACS on TB9 Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the F ACP, the annunciator must added to the system via FACP programming. Refer to the programming section titled "ANN-BUS Options" on page 118 in this manual for detailed programming information. Select the LCD option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN­80 will indicate a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus Trouble and the piezo will sound approximately once every 10 seconds. Note that the FACP will provide no indication of an ANN­80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program th e address corresponding to the address set on the ANN-80 at the FACP.
92udlstoann80.cdr
30 MS-9200UDLS PN 52750:E1 01/27/09
Loading...
+ 198 hidden pages