IMPORTANT! The SLC Manual Document #51309 must be referenced in addition to this
manual when installing or servicing the Fire Alarm Control Panel.
Document #52750
E1
01/27/09 Revision:
PN: 52750:E1 ECN 09-062
D
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of
smoke detectors, heat detectors, manual pull stations,
audible warning devices, and a fire alarm control panel with
remote notification capability–can provide early warning of a
developing fire. Such a system, however, does not assure
protection against property damage or loss of life resulting
from a fire.
The Manufacturer recommends that smoke and/or heat
detectors be located throughout a protected premise following the recommendations of the current edition of the
National Fire Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes,
and the recommendations contained in the Guides for
Proper Use of System Smoke Detectors, which are made
available at no charge to all installing dealers. These documents can be found at http:/www.systemsensor.com/html/applicat.html. A study by the Federal Emergency Management Agency (an agency of the United States government)
indicated that smoke detectors may not go off in as many as
35% of all fires. While fire alarm
systems are designed to provide early warning against fire,
they do not guarantee warning or protection against fire. A
fire alarm system may not provide timely or adequate
warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls,
on roofs, or on the other side of closed doors. Smoke
detectors also may not sense a fire on another level or floor
of a building. A second-floor detector, for example, may not
sense a first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors
because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not
reach the ceiling or upper walls where detectors are
located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm
at various levels of smoke density. If such density levels are
not created by a developing fire at the location of detectors,
the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have
ionizing-type sensing chambers tend to detect fast-flaming
fires better than smoldering fires. Because fires develop in
different ways and are often unpredictable in their growth,
neither type of detector is necessarily best and a given type
of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and
violent explosions (caused by escaping gas, improper stor-
age of flammable materials, etc.).
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a
predetermined rate or reaches a predetermined level.
Rate-of-rise heat detectors may be subject to reduced
sensitivity over time. For this reason, the rate-of-rise
feature of each detector should be tested at least once
per year by a qualified fire protection specialist. Heat
detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by
the system for the connection of alarm transmission
wiring, communications, signaling, and/or power. If
detectors are not so located, a developing fire may
damage the alarm system, crippling its ability to report
a fire.
Audible warning devices such as bells may not alert
people if these devices are located on the other side of
closed or partly open doors or are located on another
floor of a building. Any warning device may fail to alert
people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause
seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when
they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property
owner's responsibility to conduct fire drills and other
training exercise to make people aware of fire alarm
signals and instruct them on the proper reaction to
alarm signals.
• In rare instances, the sounding of a warning device
can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any
electrical power. If AC power fails, the system will
operate from standby batteries only for a specified time
and only if the batteries have been properly maintained
and replaced regularly.
Equipment used in the system may not be technically
compatible with the control. It is essential to use only
equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from
a premise to a central monitoring station may be out of
service or temporarily disabled. For added protection
against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is
inadequate maintenance. To keep the entire fire alarm
system in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations,
and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with
large amounts of dust, dirt or high air velocity require
more frequent maintenance. A maintenance agreement
should be arranged through the local manufacturer's
representative. Maintenance should be scheduled
monthly or as required by National and/or local fire codes
and should be performed by authorized professional fire
alarm installers only. Adequate written records of all
inspections should be kept.
PrecauLarge.PMD 02/26/2007
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be
connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or
inserting cards, modules, or interconnecting cables while
the unit is energized. Do not attempt to install, service, or
operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any
programming operation or change in site-specific software.
Reacceptance testing is required after any change,
addition or deletion of system components, or after any
modification, repair or adjustment to system hardware or
wiring.
All components, circuits, system operations, or software
functions known to be affected by a change must be 100%
tested. In addition, to ensure that other operations are not
inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of
50 devices, must also be tested and proper system
operation verified.
This system meets NFPA requirements for indoor dry
operation at 0-49° C/32-120° F
93 ±2% RH (non-condensing) at 32 ±2° C/90 ±3° F.
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore, it
is recommended that this system and all peripherals be
installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Refer to manual Specifications
section for maximum allowable I.R. drop from the specified
device voltage.
and at a relative humidity of
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to
lightning-induced transients. Although no system is
completely immune from lightning transients and
interferences, proper grounding will reduce susceptibility.
Overhead or outside aerial wiring is not recommended, due
to an increased susceptibility to nearby lightning strikes.
Consult with the Technical Services Department if any
problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or
inserting circuit boards. Failure to do so can damage
circuits.
Remove all electronic assemblies prior to any drilling,
filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear.
Before making modifications, verify that they will not
interfere with battery, transformer, and printed circuit board
location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
This system contains static-sensitive components.
Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed
from the body. Use static-suppressive packaging to
protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be
followed to avoid damage to the control panel and
associated equipment. FACP operation and reliability
depend upon proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment
in a residential area is likely to cause interference, in
which case the user will be required to correct the
interference at their own expense.
PrecauLarge.PMD 02/26/2007
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations of the
Canadian Department of Communications. This Class A
digital apparatus complies with Canadian ICES-003.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par
le ministere des Communications du Canada. Cet
appareil numerique de la Classe A est conforme a la
norme NMB-003 du Canada.
Features and Options .........................................................................................................................................14
Current Availability .................................................................................................................................... 17
Controls and Indicators .....................................................................................................................................18
Trim Ring ...................................................................................................................................................22
ANN-RLY Connection to FACP ........................................................................................................39
ANN-BUS Audio Panel Control .........................................................................................................39
Legacy ACS Series LED Zone Type Annunciators ...................................................................................41
Getting Started ......................................................... ..........................................................................................41
.31
MS-9200UDLS P/N: 52750:E1 01/27/095
Telephone Requirements and Warnings ............................................................................................................42
Digital Communicator ................................................................................................................................42
Telephone Company Rights and Warnings ................................................................................................43
For Canadian Applications .........................................................................................................................44
Power .................................................................................................................................................................49
AC Power and Earth Ground Connection ..................................................................................................49
Battery Power .............................................................................................................................................49
Special Application DC Power Output Connection ...................................................................................49
UL Power-limited Wiring Requirements ...........................................................................................................53
Digital Communicator .......................................................................................................................................54
Programming Data Entry ...................................................................................................................................59
User Programming .............................................................................................................................................60
Programming and Passwords ............................................................................................. ................................62
Point Program .............................................................................................................................................65
Edit Module Screen for Monitor Module ............................................................................................76
Edit Module Screen for Control Modules ...........................................................................................85
Zone Setup ..................................................................................................................................................92
Zone 97, 98 and 99 ..............................................................................................................................93
Zones Installed ......................................... ...................................................... ................
.....................94
Zones Enabled .....................................................................................................................................94
Zones Disabled ....................................................................................................................................94
Zone Type ...........................................................................................................................................95
Zones Available ............................... ..................................................... ..............................................96
Zone Message ......................................................................................................................................96
System Setup ..............................................................................................................................................97
Time ....................................................................................................................................................100
Date .....................................................................................................................................................101
Clock Format .......................................................................................................................................101
Daylight Savings Time ........................................................................................................................101
Type ....................................................................................................................................................106
Auto Silence ........................................................................................................................................107
Coding (only for NACs not programmed as Sync Strobe Type) ........................................................107
Zone ....................................................................................................................................................109
Sync Type ...........................................................................................................................................109
History ........................................................................................................................................................112
Erase History .......................................................................................................................................112
Service Terminal ................................................... ..................................................... .........................132
Central Station .....................................................................................................................................133
Clear Program ........................................................... .................................................................................144
Program Check ................................... ...................................................... ..................................................145
Disable Point ..............................................................................................................................................148
History ........................................................................................................................................................149
Program Check ................................... ...................................................... ..................................................150
System ........................................................................................................................................................153
Zone Setup ..................................................................................................................................................154
Panel Control Buttons .......................................................................................................................................156
LED Indicators ..................................................................................................................................................157
Normal Operation ...................................................... ..................................................... ...................................158
Medical Alert Condition Operation ...................................................................................................................162
Programmed Zone Operation ............................................................................................................................163
Special System Timers ......................................................................................................................................166
Read Status ........................................................................................................................................................168
System Point ...............................................................................................................................................169
Zones ..........................................................................................................................................................170
Power ..........................................................................................................................................................171
Program Check ...........................................................................................................................................174
History ........................................................................................................................................................174
Phone Line ..................................................................................................................................................176
Central Station ............................................................................................................................................176
Service Terminal .........................................................................................................................................177
Central Station Communications ..........................................................................................................................181
Remote Site Upload/Download ..............................................................................................................................184
Transferring a Program ......................................................................................................................................185
Security Features ........................................................................................................................................186
Power Supply Calculations ....................................................................................................................................187
Calculating the AC Branch Circuit ....................................................................................................................187
8MS-9200UDLS P/N: 52750:E1 01/27/09
Table of Contents
Calculating the System Current Draw ...............................................................................................................188
How to Use Table 7.3 on page 189 to Calculate System Current Draw ....................................................188
Calculating the Battery Size ..............................................................................................................................190
Selecting and Locating Batteries ................................................................................................................190
Software Zones ........................................................................................................................................................191
Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts ...........................................202
MBT-1 Municipal Box Trip - Silenceable ........................................................................................................203
FACP with Keltron .................................................................................................................................................204
HVAC Control ........................................................................................................................................................208
Control Module Operation ................................................................................................................................208
Ademco Contact ID Format Event Code Descriptions .......................................................................................210
Transmission Format Between DACT and Receiver ........................................................................................210
Ademco Contact ID Typical Printout ................................................................................................................210
Central Station Points ............................................................................................................................................215
MS-9200UDLS P/N: 52750:E1 01/27/099
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our
customers, we make frequent upgrades to the embedded software in our products. To ensure that
you are installing and programming the latest features, we strongly recommend that you download
the most current version of software for each product prior to commissioning any system. Contact
Technical Support with any questions abou t so ftware and the appropriate version for a specific
application.
10MS-9200UDLS PN 52750:E1 01/27/09
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction
(AHJ) and be familiar with the standards set forth by the following regulatory agencies:
•Underwriters Laboratories Standards
•NFPA 72 National Fire Alarm Code
•CAN/ULC - S527-99 Standard for Control Units for Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
NFPA 72 National Fire Alarm Code
NFPA 70 National Electrical Code
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1610 Central Station Burglar Alarm Units
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
UL 2017 General-Purpose Signaling Devices and Systems
CAN/ULC - S524-01 Standard for Installation of Fire Alarm Systems
Other:
EIA-232E Serial Interface Standard
EIA-485 Serial Interface Standard
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
MS-9200UDLS PN 52750:E1 01/27/0911
TB8
GND
DTR
RCV
T
X
TB8 (option to DB-25)
5 4 3 2 1
9 8 7 613 12 11 10
25 24 23 22 21 20 19 18 17 16 15 1 4
TB8
GND
DTR
RCV
T
X
White
Green
Black
Red
9 8 7 6
DB9F
5 4 3 2 1
EIA-232
(nonsupervised)
to printer or
Upload/Download Utility.
For EDP-listed equipment or
personal computer
personal computer with FACP
50 foot maximum within same room.
OR
BA
SHIELDSLCSLC
shield
A
A
-
B
-
SLCSLC
(supervised)
SLC Loop
Manual for detailed
information on wiring
Refer to the SLC Wiring
(EIA-485)
supervised)
(power-limited,
to Annu nc i ato rs
ACS/ANN-B US
OR
TERM
(EIA-485)
to LCD annunc.
+
B+ A+ B- A- A B
B
+
for Style 4, 6 and 7.
addressa ble devices
-
+
-
T
O
U
T
+
U
O
IN-
IN+ IN- OUT+ OUT-
I
+
N
Cut this jumper to enable
(Supervised, Power Limited)
NAC #1 & #2
Notification Appliance Circuits
Style Z (Class A)
Supervisory relay w hen
4XTMF module is installed
+
NAC #2
+
using NACKEY card.
NAC #1
2.5 amps max. per circuit.
JP6 config ure d for Cl ass A
4XTMF
JP3
4XTMF
CUT TO
MONITOR
J6
J5
KISSOFF
+
+
USB Port J12 for local
J7
Cut this jumper to supervise
the 4XTMF m odu le whe n
install ed (see J5 & J6)
B
-
A
-
A
+
+
B
+
92udLSlayo.cdr
TB4
B
-
A
-
A
+
+
B
+
TB3
programming using a
personal computer and
programming utility.
J12
SEC. A CTIVE
SEC. PHONE LINE
PH15PH16
PRI. ACTIVE
(Nonpower-Limited)
PRI. PHONE LINE
JP2
NC NO C
1 Fixed Trouble Relay
Nonsupervised relay contacts
Contact Ra tin g s:
2.0 amps @ 30 VDC (resistive)
0.5 amps @ 30 VAC (resistive)
Contacts show n be lo w in nor m al
condition (AC power with no alarm,
ELRs 4.7K, ½W
2 Programmable Relays &
++
NAC #4 NAC #2
++
for Class B using NACKEY card.
Notification Appliance Circuits
NAC #1 NAC #3
(See Style Z illustrated near right edge of board).
(Special Ap pl i cati on ) 2.5 amps max. per circuit. JP6 conf igur e d
NAC #1, #2, #3 & #4, Style Y (Class B) (Supervised, Power Limited)
++
+
+
2
1
trouble or supervisory activity).
A Fail Safe Trouble
relay switches to the
++
+
+
4
3
Trouble
Alarm*
NO position during
trouble co nd it ions an d
under loss of all power.
Supervisory*
(*)Factory default relay programming
2
1
RELAY 2
TB6TB8TB9TB10
RELAY 1
NO NC C NC NO C
NO NC C NC NO CNO NC C
TB5
Flash Memory Load Enable Switch.
UP is normal position for switch.
DOWN position allows loading of
factory software upgrades.
RELAY 3
NO NC C
NAC
Number
B
-
-
B
B
+
B
+
B
-
B
-
B
+
B
+
2244
1
33
1
-
-
+
- -
+ +
NAC 2 CLAS S A
NAC 2 & 4 CLASS B
TB4TB7
B+ A+ A- B-B+ A+ A- B-
1B + 3B + 3B - 1B - 2B + 4B + 4B - 2B -
NAC 1 & 3 CLASS B
Configur e NA Cs for Cl as s A or
Class B wiring using NACKEY
TB3
+ -
SUPPLY SYNCNAC 1 CLASS A
REMOT E PW R
TB2
RST
+ 24V -
POWER
+ 24V -
POWER
NON-RST
TB1
321
JP4
card. Factory default is Class B.
JP6
SW1
JP7
REMOVE TO
DISABLE GND. FLT.
Remove this jumper
to disable the FACP
battery charger when
To disable ground fault detection,
remove jumper/shunt from JP7
using exte rnal charger.
JP5
J11
CAUTION!
HIGH VOLTAGE
TRANSFORMER 2
I/F
KEYPAD
J4
LCD DISPLA Y
J1
TB11
TRANSFORMER 1
J3
PS2 Keyboard InterfaceDACT Phone Line Jacks
MINI DIN
KEYBOARDCONN.
- +
J9
BATTERY
Battery
nonpower-limited
24 VDC, supervised,
18 Amp Ho ur ma x imu m
HOT NEUT EARTH
120 VAC, 60 HZ, 3.0 amps
220/240 VAC, 50 Hz, 1.5 amps
J10
only
Transformer 2 Connector
Removing Ground
Basic System Connections
Remote Synchronization Output
Special Application Power
24 VDC filtered, supervised and power-limited.
0.040 amps maximum, follows NAC1 control circuit.
Requires 4.7kohm End-of-Line resistor.
Special Application DC Power Outputs (24 VDC)
Nonsupe r v ised, power-limited circuits
Supervise with a power supervision relay A77-716B
Nonresettable or Resettable Power
Jumper s electable by JP4, 24 VDC filtered,
power-limited (0.3 00 amps maximum)
Supervi s io n r equired. Nonrese ttable
Power suitable for powering annunciat ors,
Resettable Power suitable for powering
Resettable Power - 24 VDC filtered, power-l imite d
(0.300 am p s max imu m ) to sm oke de te ct or s (ID C) .
Supervision required.
smoke detectors..
UL/NFPA Style/Class
Fault Disable Jumper JP7
identifications for circuits.
Remove jumper JP7
with the approval of the AHJ
Important!
voids
(Authority Havi ng Juri sdi ct io n)
Transformer 1 Connector
CAUTION! HIGH VOLTAGE
12MS-9200UDLS PN 52750:E1 01/27/09
Peripheral Devices and Their Documents:
ANN Audio Control for ACC-25/50(ZS/T) Doc. #51889
ANN-BUS - TB9
ANN-80
LCD Text Annunciator
Doc. #52749
PH15 & PH16 Telephone Connections
J5 & J6
SLC Loop - TB10
ANN-RLY
10 Form-C Relay Card
Doc. #53033
Reverse Polarity Module
ANN-(R)LED
LED Display
Doc. #53032
ANN-I/O
LED Driver
Doc. #151416
IPDACT
Internet Communicator
Doc. #53109
4XTMF
Addressable Devices and SLC Wiring
Doc. #51309
ANN-S/PG
Printer Driver
Doc. #151417
CHG-120F Charger
Doc. #50888
Battery Connector - J9
9200udLSannperi.cdr
CHG-75 Charger
Doc. # 51315
MS-9200UDLS PN 52750:E1 01/27/0913
Product Description
SECTION 1Product Description
The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and
DACT (Digital Alarm Communicator/Transmitter) all on one circuit board. This
compact, cost effective, intelligent addressable control panel has an extensive list of
powerful features.The combination of Fire-Lite’s newer series devices and legacy 300
Series devices, along with the MS-9200UDLS FACP, offer the latest in fire protection
technology. The power supply and all electronics are contained on a single circuit
board housed in a metal cabinet, providing a complete fire control system for most
applications. Optional modules, which plug into the main circuit board, are available
for special functions. Available accessories include LED, graphic and LCD
annunciators, reverse polarity/city box transmitter, local and remote upload/download
software and remote power expansion.
The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central
Station via the public switched telephone network. It also allows remote programming
or interrogation of the control panel using the PS-Tools Upload/Download utility via
the public switched telephone network. Local programming and interrogation is also
possible using the PS-Tools and the USB port (J12) on the FACP. Any personal
computer with Windows
baud or faster and PS-Tools software may serve as a Service Terminal. This allows
download of the entire program or upload of the entire program, history file, walktest
data, current status and system voltages.
™
XP or greater, and compatible modem with a speed of 2400
MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS (120 VAC
version) and the MS-9200UDLSE (240 VAC version) FACPs.
Inventory
When MS-9200UDLS shipment is received, check that all parts have been included in
shipment. The MS-9200UDLS shipment consists of one of each of the following:
main circuit board with display
backbox with door
plastic bag containing screws, cables, key, etc.
manual
1.1 Features and Options
•New LiteSpeed™ polling protocol for faster SLC response time
•SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted,
unshielded wire (refer to "Wire Requirements" on page 205)
•Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements
•198 addressable device capacity (99 detectors and 99 control/relay/monitor
modules)
•99 software zones
•Onboard NACs (Notification Appliance Circuits) which can be configured as
four Style Y (Class B) or two Style Z (Class A) circuits - special application
•3.0 amps total power for NACs and 24 VDC special application auxiliary power
outputs expandable to 6.0 amps
•3.6 amps total system power (includes battery charger) expandable to 6.6 amps
•T wo programmable relay outputs and one fixed trouble relay
•Synchronization output for remote power supply applications (special
application)
Maximum Charging Circuit: Normal Flat Charge - 27.6 VDC @ 0.80 amp
Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of
two 18 Amp Hour batteries. For greater than 26 Amp Hour up to 120 Amp Hour
batteries, use the CHG-75 or CHG-120F Battery Charger and BB-55F Battery Box).
Minimum Battery Size: 7 Amp Hour
Note: Jumper JP5, on the FACP main circuit board, must be removed to disable the
FACP battery charger when using an external battery charger.
Communication Loop - TB10
24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to "Wire Requirements" on page 205)
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit
Refer to SLC Loop manual for wiring information
Notification Appliance Circuits - TB3 & TB4
Each Terminal Block provides connections for two Style Y (Class B) or one Style Z
(Class A) for a total of Four Style Y (Class B) or two Style Z (Class A) NACs
Style is configured using NACKEY card plugged into JP6 on main board
Special Application full-wave rectified power
Power-limited circuitry
NAC wiring requirements refer to "NAC Wiring" on page 207
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 17)
End-of-Line Resistor: 4.7 kΩ, ½ watt (P/N 71252 UL listed) for Style Y (Class B) NAC
Refer to the Device Compatibility Document for listed compatible devices
Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7
Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.6 on page 50 for information on power-limited relay circuit wiring
Nonresettable or Resettable Special Application Power (24 VDC Nominal) TB1, Terminals 1 (+) & 2 (-)
Jumper selectable (JP4) for conversion to resettable power output
Maximum ripple voltage: 10mV
RMS
Total DC current available from each output is up to 0.300 amps (see Figure 1.1)
Power-limited circuit
Four-Wire Resettable Special Application Smoke Detector Power (24 VDC
nominal) - TB1, Terminals 3 (+) & 4 (-)
Maximum ripple voltage: 10 mV
RMS
Up to 0.300 amps is available for powering 4-wire smoke detectors (see Figure 1.1)
Power-limited circuit
Refer to the Device Compatibility Document for listed compatible devices
16MS-9200UDLS PN 52750:E1 01/27/09
Product Description
Remote Sync Output - TB2
Remote power supply synchronization output
24 VDC nominal special application power
Maximum current is 40 mA
End-of-Line Resistor: 4.7KΩ
Output linked to NAC 1 control
Supervised and power-limited circuit
ACS/ANN-BUS annunciator connector, Terminal 1 (+/A) and Terminal 2 (-/B)
1.2.1 Current Availability
The following figure illustrates the maximum current that is possible for each panel
circuit and the total current available from the FACP with optional second transformer.
Note: If NACs are
configured as two Style Z
(Class A) circuits, each
circuit can handle 2.5
amps maximum.
Refer to the battery calculations section for additional information.
Figure 1.1 Current Availability
6.0 amps with optional second
XRM-24B(E) transformer.
3.0 amps max. with only
standard transformer installed.
powerdist9200ud.cdr
MS-9200UDLS PN 52750:E1 01/27/0917
Product Description
1.3 Controls and Indicators
LCD Display
The FACP uses an 80-character
(4 lines X 20 characters) high
viewing angle LCD display. The
display includes a long life LED
backlight that remains illuminated. If
AC power is lost and the system is
not in alarm, the LED backlight will turn off to conserve batteries.
LED Indicators
LED indicators are provided to annunciate the following conditions:
•AC Power (green)
•Fire Alarm (red)
•Supervisory (yellow)
•Trouble (yellow)
•Maintenance/presignal (yellow)
•Alarm Silenced signals (yellow)
•Disabled (yellow)
•Battery fault (yellow)
•Ground fault (yellow)
Key Panel
Mounted on the main circuit board, the key panel includes a window for the LCD
display and LED indicators as listed above. The key panel, which is visible with the
cabinet door closed, has 25 keys, including a 16 key alpha-numeric pad similar to a
telephone keypad.
HONEYWELL
LIFE SAFETY
SYSTEM ALL NORMAL
10:00A 012102
Function keys:
•Acknowledge/Step
•Alarm Silence
•Drill
•Reset (lamp test)
Service/program keys:
•Keys labeled 1 to 9
•* key
•# key
•0 (recall) key
2
1
4
GHI
78 9
PRS
*
QZ
ABC
5
JKL
TUVWXY
0
RECALL
3
DEF
6
MNO
#
-/.
1
CLR
ESC
MODE
st
EVENT
AC POWER
FIRE ALARM
SUPERVISORY
TROUBLE
ENTER
MAINTENANCE
ALARM
SILENCED
DISABLED
BATTERY
ACK/STEP
ALARM
SILENCE
DRILL
HOLD 2 SEC
RESET
GROUND
•1st Event key
•Clear key
Figure 1.2 Membrane/Display Panel
•Escape key
•Mode key
•Four cursor keys (up, down, left and right)
•Enter key
Local Piezo Sounder
A piezo sounder provides separate and distinct pulse rates for alarm, trouble and
supervisory conditions.
9600kypd.cdr
18MS-9200UDLS PN 52750:E1 01/27/09
1.4 Circuits
Reference
Manual
Product Description
SLC Communication Loop
One SLC loop is provided standard on the FACP main circuit board. The SLC loop,
configurable for NFPA Style 4, 6 or 7, provides communication to addressab le
detectors, monitor (initiating device) and control (output device) modules. Refer to the
SLC Wiring manual for information on wiring devices.
Output Circuits
The following output circuits are available on the FACP:
•Special Application Power
24 VDC R eset table (sm oke detector power) output - 0.300 amps maximum
24 VDC Nonresettable or Resettable power output - 0.300 amps maximum
•24 VDC Battery Charger (up to 18 AH batteries)
NAC (Notification Appliance Circuits)
NACs configurable for four Style Y (Class B) or two Style Z (Class A) using NACKEY
card in JP6, are provided with various programmable features.
Relays
One fixed and two fully programmable Form-C dry contact relays are provided. The
fixed fail-safe relay monitors system trouble and the two programmable relays are
factory default programmed for system alarm and system supervisory. Contacts are
rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30 VAC (resistive). The
programmable relays can be programmed for the following operations:
•fire alarm
•trouble
•supervisory
•supervisory auto-resettable
•DACT communication failure
•process monitor
•process monitor auto-resettable
•hazard alert
•medical alert
•AC loss
1.5 Digital Alarm Communicator/Transmitter
T wo modular phone jacks allow easy connecti on to telephone lines. Modular jacks are
labeled PH1 for Primary Phone Line and PH2 for Secondary Phone Line. Two
telephone line active red LEDs are provided as well as a green Kissoff LED. The
integral digital communicator provides the following functions:
•Line Seizure: takes control of the phone lines disconnecting any premises phones
•Off/On Hook: performs on and off-hook status to the phone lines
•Listen for dial tone: 440 Hz tone typical in most networks
•Dialing the Central Station(s) number: default is Touch-Tone
rotary
•For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s).
The frequency and time duration of the tone(s) varies with the transmission
format. The control panel will adjust accordingly.
•Communicate in the following formats:
Ademco Contact ID
SIA DCS 8
SIA DCS 20
®
, programmable to
MS-9200UDLS PN 52750:E1 01/27/0919
Product Description
1.6 Components
See Page
Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary
components and wiring interface connectors. The 4XTMF option module plugs in and
is mounted to the main circuit board.
Cabinet
The MS-9200UDLS backbox provides space for two batteries (up to 18 Amp Hour).
Ample knockouts are provided for system wiring. Also available is an optional dress
panel (DP-9692), which mounts to the inside of the cabinet (required by ULC for
Canadian installations).
Transformer Assembly
Optional
XRM-24B(E)
One 100VA transformer is provided standard
with the panel (3.6 amps maximum). An
optional 100 VA transformer XRM-24B
Standard
XRM-24B(E)
(XRM-24BE for the MS-9200UDLSE) is
available to provide maximum system and
accessory power (6.6 amp total). Note that the
XRM-24B and XRM-24BE are only suitable for
9200xfor.cdr
use with MS-9200UDLS(E) with main circuit
board number 03611. This circuit board can also be identified by using the software
revision of #9200UDV4.0 (meaning version 4.0) or later.
Batteries
Battery Cable P/N 75287
The MS-9200UDLS cabinet provides space
for two batteries (up to 18 Amp Hou r).
Batteries larger than 18 Amp Hour require an
external charger such as the CHG-75 or
-
+
+
-
CHG-120F and a UL listed battery box such
as the BB-55F. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal)
of each detector. Each detector responds to an SLC address that is set in the detector
head using built-in rotary decimal switches. The maximum address cannot exceed
address 99. Note that a blinking LED on an intelligent detector indicates
communication between the detector and the control panel.
These devices (350 Series or newer) can operate in CLIP mode (Classic Loop Interface
Protocol) or LiteSpeed mode to provide a quicker response. They are also compatible
with older 300 Series devices. If a mix of old and new series devices are installed on
the same loop, the FACP must be programmed to operat e in CLIP mode. Refer to the
SLC Wiring Manual for a list of compatible addressable detectors.
9200batt.cdr
1.6.2 Intelligent Addressable Modules: Newer Series
The newer series of Control Modules and Monitor Modules provide an interface
between the control panel and conventional notification and initiating devices. Each
module can be set to respond to an address with built-in rotary switches. The maximum
Reference
Manual
20MS-9200UDLS PN 52750:E1 01/27/09
address cannot exceed address 99. Note that a blinking LED on an addressable module
indicates communication between the module and the control panel.
Product Description
These devices (i.e., MMF-300, MMF-301, MMF-302, CMF-300, CRF-300) can
operate in CLIP mode (Classic Loop Interface Protocol) or LiteSpeed mode to provide
a quicker response. They are also compatible with older 300 series devices. If a mix of
old and new series devices are installed on the same loop, the FACP must be
programmed to operate in CLIP mode. Refer to the SLC Wiring Manual for a list of
compatible addressable modules. Refer to the Device Compatibility Document for a
list of approved conventional notification and initiating devices.
1.6.3 300 Series Intelligent Addressable Devices
Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the
MS-9200UDLS FACP. The address of 300 Series devices cannot be set above 99.
Refer to the SLC Wiring Manual for a list of compatible addressable devices.
1.6.4 Addressable Device Accessories
End-of-Line Resistor Assembly
The End-of-Line resistors are included with each module. Refer to the specific module
documentation for specific information.
Power Supervision Relay
The UL listed End-of-Line power supervision relay is used to supervise the power to 4wire smoke detectors and notification appliances.
EOL-C(R/W) Mounting Plate
The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which
are required for use in Canada. An ELR, which is supplied with each module and fire
alarm control panel, is mounted to the EOL-C(R/W) plate. Resistors mounted to the
plate can be used for the supervision of a monitor and control module circuit.
1.7 Optional Modules
The MS-9200UDLS main circuit board includes option module connectors for the
following module:
4XTMF Transmitter Module
The 4XTMF provides a supervised output for local energy municipal box transmitter,
alarm and trouble reverse polarity. It includes a disable switch and disable trouble
LED. A jumper on the module is used to select an option which allows the reverse
polarity circuit to open with a system trouble condition if no alarm condition exists.
The module plugs into connectors J5 and J6 which are located near the right edge the
main circuit board. When the 4XTMF module is installed, Jumper JP3, on the main
circuit board, must be cut to allow supervision of the module.
MS-9200UDLS PN 52750:E1 01/27/0921
Product Description
1.8 Accessories
1.8.1 PS-Tools Programming Utility
The PS-Tools Programming Utility can be used to locally or remotely program the
F ACP dir ectly from most IBM compatible computers (PC), running Windows™ XP (or
newer). FACP program files can also be created and stored on the PC and then
downloaded later to the control panel. The PK-CD Kit includes the Windows-based
Programming Utility software on CD-ROM with on-line help file. A standard USB
cable with male-A to male-B connectors, which must be purchased separately, is
required for local connection of the PC to the USB port J12 on the FACP main circuit
board. Remote programming requires that the PC have a 2400 baud (or faster) modem.
Important: Remote modification of FACP programming requires that the panel be
enabled for remote download (refer to "Remote Site Upload/Download" on page 184).
Remote interrogation of panel programming, history logs, detector status, etc., is
possible without enabling the remote download option.
1.8.2 DP-9692 Dress Panel
An optional dress panel DP-9692 is available for the MS-9200UDLS (required by ULC
for Canadian installations). The dress panel restricts access to the system wiring while
allowing access to the key panel. A ground strap must be connected between the stud
on the inside of the dress panel and the ground stud in the backbox. An optional DP9692-LED dress panel is available for use with the ANN-LED annunciator module.
1.8.3 Trim Ring
An optional Trim Ring (P/N TR-CE) is available for the FACP backbox. The Trim
Ring provides a finished appearance for a semi-flush mounted panel.
1.8.4 Battery Box
BB-26
The BB-26 battery box may be used to house up to two 26 AH batteries and the
CHG-75 Battery Charger. The battery box, which is red and is provided with
knockouts, was designed specifically to compliment mounting below the FACP.
BB-55F
The BB-55F battery box may be used to house two 26 AH batteries, two 60 AH
batteries or one 100 AH battery. When the CHG-120F is mounted in the BB-55F, two
26 AH or one 60 AH battery may also be housed in the battery box.
22MS-9200UDLS PN 52750:E1 01/27/09
dp9200udls.cdr
Reference
Manual
Product Description
1.8.5 Battery Charger
1.8.5.1 CHG-75 Battery Charger
The CHG-75 is capable of charging up to 75 AH lead-acid batteries with the MS9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-75. The charger and up to 26 AH batteries can be
housed in the BB-26 battery box. Larger batteries and the charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Refer to the CHG-75 Manual for additional information.
1.8.5.2 CHG-120F Battery Charger
The CHG-120F is capable of charging up to 120 AH lead-acid batteries with the
MS-9200UDLS FACP. The FACP battery charger must be disabled, by removing
jumper JP5, when using the CHG-120F . The batteries and charger can be housed in
the BB-55F battery box which can be mounted up to 20 feet away from the control
panel. Note that when using the BB-55F for housing the charger and batteries
greater than 26AH, multiple BB-55Fs are required. Refer to the CHG-120F Manual
for additional information.
1.8.6 IPDACT- Internet Protocol DACT
The IPDACT is a compact, Internet Protocol Digital Alarm Communicator/Transmitter
designed to allow FACP status communication to a Central Station via the internet. No
telephone lines are required when using the IPDACT. Using Contact ID protocol from
the FACP, the IPDACT converts the standard DACT phone communication to a
protocol that can be transmitted and received via the internet. It also checks
connectivity between the FACP and Central Station. Refer to the IPDACT Product
Installation Document P/N 53109 for additional information.
MS-9200UDLS PN 52750:E1 01/27/0923
Product Description
1.8.7 ANN-BUS Annunciators/Modules
WARNING! Disconnect all sources of power (AC and DC) before installing or
removing any modules or wiring.
The legacy ACS annunciators may not be used if new ANN-BUS annunciators are
being used due to incompatible serial communication protocols.
A variety of optional devices can be connected to the F ACP ANN-BUS communication
circuit. ANN Series devices can be connected to the ACS (EIA-485) terminals on
TB-9. Compatible devices include the following:
This section contains information on calculating ANN-BUS wire distances and the
types of wiring configurations (Class B).
1.8.7.1.1 Calculating Wiring Distance for ANN-BUS Modules
The following instructions will guide the installer in determining the type of wire
and the maximum wiring distance that can be used with FACP ANN-BUS
accessory modules.
T o calculate the wire gauge that mus t be us ed to connect ANN-BUS modules to the
FACP, it is necessary to calculate the total worst case current draw for all modules
on a single 4-conductor bus. The total worst case current draw is calculated by
adding the individual worst case currents for each module. The individual worst
case values are shown in the following table:
Note: Total worst case current draw on a single ANN-BUS cannot exceed 0.5 amp.
If current draw exceeds 0.5 amps, refer to "Powering ANN-BUS Devices from
Auxiliary Power Supply" on page 27.
24MS-9200UDLS PN 52750:E1 01/27/09
Total Worst Case
Current Draw (amps)
0.1001,852 ft.4,688 ft.* 6,000 ft.*6,000 ft.
0.200926 ft.2,344 ft.3,731 ft.5,906 ft.
0.300617 ft.1,563 ft.2,488 ft.3,937 ft.
0.400463 ft.1,172 ft.1,866 ft.2,953 ft.
0.500370 ft.938 ft.1,493 ft.2,362 ft.
Product Description
After calculating the total worst case current draw, Table 1.1 specifies the
maximum distance the modules can be located from the FACP on a single wire run.
The table ensures 6.0 volts of line drop maximum. In general, the wire length is
limited by resistance, but for heavier wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can
never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula
used to generate this chart is shown in the note below.
Wiring Distance: ANN-BUS Modules to FACP
22 Gauge18 Gauge16 Gauge14 Gauge
Table 1.1 Wiring Distances
Note: The following formulas were used to generate the wire distance chart:
Maximum Resistance (Ohms)=6.0 Volts
Total Worst Case Current Draw (amps)
Maximum Wire Length (feet)Maximum Resistance (Ohms)*500
(6,000 feet maximum)Rpu
where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)
Wire GaugeOhms per 1,000 feet (Rpu)
2216.2
186.4
164.02
142.54
Exception: When using the ANN-RLY module, the installer must ensure that the
maximum 24VDC power line drop does not exceed 0.3 volts. This results in the
following wiring limitations:
Wire GaugeMaximum Wire Length
18312 feet
16497 feet
14787 feet
121,250 feet
MS-9200UDLS PN 52750:E1 01/27/0925
Product Description
Wiring Distance Calculation Example:
Suppose a system is configured with the following ANN-BUS modules:
The total worst case current is calculated as follows:
ANN-80 Current Draw= 3 X 0.040 amps= 0.120 amps
ANN-S/PG Current Draw= 1 X.0.040 amps= 0.040 amps
Total Worst Case Current Draw= 0.160 amps
Using this value and referring to the Wiring Distance Table 1.1 on page 25, it can be
found that the available options are:
926 feet maxim um using 22 Gauge wire
2,344 feet maximum using 18 Gauge wire
3,731 feet maximum using 16 Gauge wire
5,906 feet maximum using 14 Gauge wire
1.8.7.1.2 Wiring Configuration
Figure 1.3 illustrates the wiring between the FACP and ANN-BUS devices.
ANN-BUS and power wiring are
supervised and power-limited
24 VDC
nonresettable
ANN-BUS Device
MS-9200UDLS
ANN-BUS/ACS BUS
Figure 1.3 FACP wiring to ANN-BUS Device
92udlstoann80.cdr
26MS-9200UDLS PN 52750:E1 01/27/09
Product Description
1.8.7.1.3 Powering ANN-BUS Devices from Auxiliary Power Supply
Figure 1.4 illustrates the powering of ANN-BUS devices from an auxiliary power
supply such as the FCPS-24FS6/8, when the total ANN-BUS power requirements
exceed the panel’s DC Power Output capability.
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
-24 VDC
ANN-80
+24 VDC
nonresettable
ANN-BUS/ACS BUS
FCPS-24FS6/8
MS-9200UDLS
Figure 1.4 Powering ANN-BUS Devices from FCPS-24FS6/8
1.8.7.2 ANN-BUS Device Addressing
Each ANN-BUS device requires a unique address (ID Number) in order to
communicate with the F ACP. A 5-position DIP switch on each device is used to set
this address. The address set for these devices must also be programmed at the
FACP for the specific device (refer to the programming section titled "ANN-BUS
Options" on page 118).
A maximum of 8 devices can be connected to the F ACP ANN-BUS communication
circuit. Device addresses do not need to be sequential and can be set to any number
between 01 and 08. Note that 00 is not a valid address. The following table shows
the DIP switch setting for each address.
Note: address (ID Number) DIP switches on some devices may have more than 5
switch positions. Unless otherwise specified in the documentation supplied with
each device, switch positions 6 and above must be set to OFF.
AddressSwitch 5Switch 4Switch 3Switch 2Switch 1
not validOFFOFFOFFOFFOFF
01OFFOFFOFFOFFON
02OFFOFFOFFONOFF
03OFFOFFOFFONON
04OFFOFFONOFFOFF
05OFFOFFONOFFON
06OFFOFFONONOFF
07OFFOFFONONON
08OFFONOFFOFFOFF
92udlstofcptoann.cdr
Note: Switch 5 must be set to OFF for ANN-BUS devices to be recognized.
MS-9200UDLS PN 52750:E1 01/27/0927
Product Description
1.8.7.3 ANN-80 Remote Fire Annunciator
The ANN-80 Annunciator is a compact, 80 character, backlit LCD remote fire
annunciator. It mimics the display on the control panel and will annunciate device
type, point alarm, trouble or supervisory condition, zone assignment plus any
custom alpha labels programmed into the FACP. The annunciator also provides
system status LEDs to display AC Power, Alarm, Trouble, Supervisory and Alarm
Silenced conditions. Additionally, the annunciator is capable of remotely
performing critical system functions such as Acknowledge, Silence, Reset and Drill.
Communication between the ANN-80 and FACP is accomplished over a two wire
RS-485 serial interface employing the ANN-BUS communication format. The
devices are powered, via two additional wires, from either the host FACP or remote
UL-listed, filtered, power supply.
The function buttons, keyswitch and piezo sounder may be individually enabled and
disabled through the FACP software. Refer to "ANN-80 Options" on page 130 for
a description of this feature and programm in g information.
Note that if the keyswitch is enabled and remains in the unlocked position for more
than two minutes without any buttons being pressed on the annunciator, a trouble
indication will be annunciated.
1.8.7.3.1 Specifications
•Operating Voltage Range: 18 VDC to 28 VDC
•Current Consumption @ 24 VDC nominal (filtered and nonresettable):
Normal/Standby (no act ivi ty): 37.0 mA
Trouble: 39.0 mA
Alarm: 40.0 mA
AC Fail ( not backlit): 15.0 mA
•For use indoors in a dry location
1.8.7.3.2 Installation
Ensure that all power (AC and DC) has been removed from the FACP before
installing the annunciator.
1.8.7.3.3 Mounting
The ANN-80 can be surface or semi-flush mounted to a single, double or 4” square
electrical box. Select and remove the appropriate knockout(s), pull the necessary
wires through the knockouts and mount the annunciator in or on the wall depending
on the type of installation desired.
The ANN-80 cover must be attached to the annunciator backplate before mounting
the annunciator to the electrical box/wall. The cover cannot be reattached or
removed after the annunciator has been mounted.
1.8.7.3.4 Opening/Closing Annunciator
The following procedure details the steps used to open the annunciator in order to
access the terminal block and DIP switches (refer to figure below):
1. Turn the key switch to the ON (Unlocked) position by turning the key counterclockwise
2. Push in the snap latch located on the right side of the unit while pulling the cover
open
3. T o close the cover, make certain the key switch is in the ON (Unlocked) position.
Swing the cover closed, snapping it shut
4. Turn the key switch to the OFF (Locked) position by turning clockwise and
remove the key
28MS-9200UDLS PN 52750:E1 01/27/09
Product Description
Annunciator cover with LCD display
Press in latch and pull
annunciator cover open
Key switch shown in ON position
Annunciator backplate
1.8.7.3.5 Wiring ANN-80 to FACP
The following steps can be used as a guide to wire the annunciator. Make certain all
power has been removed from the FACP prior to annunciator installation.
1. Route wires from hole in backplate, through wiring channel and then to ANN-80
terminal block TB1
TB1
wiring channel
wires
2. Remove appropriate amount of wire insulation
3. Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3
(A) & 4 (B). Make certain to connect A to A and B to B
4. If appropriate, connect the wiring going to the next device on the ANN-BUS to
TB1 terminals 3 & 4. Make certain to connect A to A and B to B
5. Connect the wiring from the 24 VDC power source to annunciator TB1 terminals
1 (-) & 2 (+). Make certain to observe proper polarity
6. If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity
7. After all connections are made, remove extra wire from inside of annunciator by
dressing it neatly through wire channel, with any excess wire pushed back
through hole into electrical box
MS-9200UDLS PN 52750:E1 01/27/0929
Product Description
ANN-80
ANN-BUS and power wiring are
supervised and power-limited
ANN-BUS
24 VDC
nonresettable
ANN-BUS/ACS BUS
FACP
Figure 1.5 ANN-80 Wiring to FACP
The following table shows the ANN-80 connections to the MS-9200UDLS
MS-9200UDLS ANN-80 (TB1)
Terminal GND (-) on TB1Terminal 1 (-)
Terminal PWR (+)TB1Terminal 2 (+)
Terminal ACS on TB9Terminal 3 (A)
Terminal ACS on TB9Terminal 4 (B)
Programming
Following installation and wiring of the ANN-80 LCD annunciator to the F ACP, the
annunciator must added to the system via FACP programming. Refer to the
programming section titled "ANN-BUS Options" on page 118 in this manual for
detailed programming information. Select the LCD option for programming.
Trouble Response
If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN80 will indicate a trouble condition by NOT turning on its AC Power indicator. The
LCD will also display Key Bus Trouble and the piezo will sound approximately
once every 10 seconds. Note that the FACP will provide no indication of an ANN80 trouble.
To clear the ANN-80 trouble condition, enable the ANN-BUS and program th e
address corresponding to the address set on the ANN-80 at the FACP.
92udlstoann80.cdr
30MS-9200UDLS PN 52750:E1 01/27/09
Loading...
+ 198 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.