Harman Stove Company PF 100 User Manual

Installation & Operating Manual
The Harman PF 100 Pellet Pro Furnace
“Ce manuel est disponible en Français sur demande”
R7
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES
IF THIS HARMAN PELLET FURNACE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW INSTALLATION DIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.
CETTE GUIDE D'UTILISATION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE COMPANY.
SAVE THESE INSTRUCTIONS.
R4
Vent Pipe
PF100 Parts
Fan Control
Hopper Lid Latches
Combustion Blower cover
Combustion Blower
3 Speed Switch
Hopper
Heat Exchanger Shaker Handle
Control Cover
Outer Door Latches
Outer Door
2
Viewing Glass
Filter Box
PF100
Table of Contents
Assembly 4
Venting 10
Installation 15
Operation 21
Maintenance 29
Troubleshooting 34
Feeder Parts 3 5
Specifications 36
Wiring Diagram 37
Parts List & Options 38
Warranty 39
Testing Label 40
Quick Reference Start-Up 41
Please read this entire manual before you install and use your new
furnace. Failure to follow instructions may result in
property damage, bodily injury, or even death.
DO NOT INSTALL IN A MOBILE HOME.
SAVE THESE INSTRUCTIONS
Harman Stove Company
352 Mountain House Road
Halifax, PA 17032
3PF100
Fig. 1
Fig. 2
Assembly
Design
The first thing that needs to be done is deciding
where and how the furnace will be installed.
Things that need to be taken into consideration are VENTING, SUPPLY& RETURN DUCTING, ELEC­TRICAL, and Condensation drainage (if A/C is in-
stalled). Don’t forget access to the furnace for service.
When the return air inlet position is known the filter box and distribution blower can be installed. See pages 5, 6, 7, 8.
When the furnace is set into place venting can be done.
Venting
Use 4” pellet vent pipe to vent your PF 100.
A combustion blower is used to extract the com­bustion gases from the firebox. This creates a negative pressure in the firebox and a positive pressure in the venting system as shown in fig. 2. The longer the vent pipe and more elbows used in the system, the greater the flow resistance. Because of these facts we recom­mend using as few elbows as possible and 30 feet or less of vent pipe. The maximum horizontal run should not exceed 18 feet.
Be sure to use wall and ceiling pass through fittings (which are approved for pellet vent pipe ) when going through combustible materials. Be sure
to use a starting collar to attach the venting system to the stove. The starting collar must be sealed to the
stove flue collar with high temp silicone caulking or aluminum tape, and screwed into the stove flue collar at least three (3) places.
Clearances and Venting
See NOTES: on page 12
4
PF100
The shaded areas are the clear­ances for the PL vent pipe that must be maintained at 3”. After the vent­ing leaves the shaded area it may be installed at 2” to com bu stible s. (Only UL listed wall pass-throughs and fire stops must be used.)
Vent Pipe
4” pellet venting pipe ( also known as PL vent ) is
constructed of two layers with air space between the layers. This air space acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of only 2 inches. This 2 inch clearance is also approved by the pipe manufacturers. See images on left. See page 14 (Fig. 24 and 26) for larger images.
The sections of pipe lock together to form an air tight seal in most cases; however, in some cases a per­fect seal is not achieved. For this reason and the fact that the PF100 operates with a positive vent pressure,
we specify that all joints within the structure should also be sealed with clear silicone.
NOTE:Use only 4” diameter type “L” or “PL”
venting system. Be sure to inspect and clean exhaust venting system frequently.
Blower access Panel Cover
Assembly
Filter Box
(Cold Air Return)
Top (same as bottom)
Solid Side Panel
Switch
Blower access Panel
Filter Frame Panel
NOTE:Read and follow all of the vent pipe
manufacturers’ instructions on the proper
installation and support of the vent pipe. Adhere to all clearances.
Tek screw from outside
Solid Side Panel
Bottom
Bottom (same as top)
Fig. 3
Assembling Filter Box
The cold air return filter box can be assembled with the filter frame on either side or the back, pro­vided there is access to the combustion blower and flue area.
It is not recomended that the filter frame be installed on the same side as the ash door due to the need to access the combustion blower, filter, and flue pipe for service.
This Edge Toward Furnace
Knockouts
Fig. 4
1. Place the bottom on the floor. The edge closest to the knockouts will be the edge towards the furnace. See Fig. 4.
2. Place the desired vertical panel inside the bot­tom tray and hold into place with one Tek screw in the bottom middle hole. (solid panel shown) See Fig 4.
5PF100
Assembly
Filter opening must be up
Filter Frame Panel
Fig. 5
Assembling Filter Box, Cont’d
3. Place the filter frame panel inside the bottom and inside the solid panel corner. See Fig. 6 for corner detail. Make sure that the filter opening is up.See Fig. 5 Hold the filter panel to the solid panel with a Tek screw in the middle hole of the solid panel, and one in the bot­tom middle hole under the filter opening.
NOTE: Do not put any screws into any of the top
holes at this time.
Open Side Panel
6
PF100
Fig. 6
4. Place the remaining panel, (in this case the blower access panel) in the bottom panel and into the corner of the solid panel. See Fig. 7. Make sure that the panel is in the upright position. There are no cover mount­ing holes in the bottom edge of this panel. Hold the panel into place with one Tek screw in the middle hole of the solid panel and one in the bottom middle hole of the blower access panel.
Fig. 7
Top
Assembly
Assembling Filter Box, Cont’d
5. Place the top on the filter box as shown in figure 8. At this time all Tek screws can be inserted around the filter box.
Note: Except for the (6) screws that attach the blower access panel in place. There should not be any screws protruding from the box on the side toward the furnace. Also DO NOT put a screw into the top center of the filter panel as a screw in this location will interfere with the filter access cover.
6. Pry out the two knockouts in the top of the box
and install the flex connector and the switch. See Fig. 9.
3 Speed Switch
Access Panel Cover opening
Yellow on 2000 CFM motor
Flex connector
Fig. 8
Fig. 9
Note: Don’t forget the HI-MED-LO switch label
on the switch before the locknut.Make sure that the set­screw on the flex connector is not pointing toward the furnace end of the box when the locknut is fully tightened.The filter box is now ready to install onto the furnace.
Follow the Blower mounting instructions on page 8 before continuing to step #7.
Note: The blower should be mounted on the fur­nace before the filter box for ease of distribution blower installation.
Note: It is best to wait until the blower , filter box, and cold air return duct work is installed before install­ing the filter and side panel.
7. After the Filter Box is installed on the furnace the electrical wiring to the three speed switch needs to be completed. WHITE to WHITE, VIOLET to the center terminal of the switch, and the BLACK, RED, BLUE to the terminals shown.
Note: The optional 1500 CFM blower is a single speed blower, therefore the three speed switch will not be used. The optional 2000CFM blower is a 4 speed, only hook up the three colors shown and tape off the orange wire. See Fig. 10.
Violet 120VAC
Fig. 10
8. Install the access panel cover by hooking the lip at the bottom of the cover over the edge in the filter box. Use 6 Tek screws to secure the access panel.
9. To install the filter, insert the filter into the filter slot and slide completely into the frame. Take note to the air flow arrow on the filter when installing.Slide the filter access cover over the opening with the upright angle toward the filter box. If a Tek was put into the middle hole by mistake, remove the screw to allow the access cover to fit properly.
7PF100
Mounting Screws
Assembly
Blower Assembly
Install the blower mounting brackets on the blower
as shown in Fig. 11.
1. Install ( 4) Tek screws on each side where shown in Fig. 11. Start with the two center screws.
NOTE: There are two small holes in the discharge end of the blower that match the two center holes on the small angle of the blower bracket. The two (2) outer holes are drilled by theTek screws.
Fig. 11
2. Mount blower with brackets installed on the furnace as shown in Fig. 12. Each side will require 6 Tek screws.
NOTE: The furnace blower opening is made large enough for the use of a 1500 or 2000 CFM blower. The blower mounting brackets will fit either blower. The inner hole pattern is for the 1000 CFM blower and the outer pattern is for the 1500 or 2000 CFM blower.
8
PF100
Fig. 12
Fig. 13
Fig. 14
NOTE: These Blower Motors are not designed to be operated without any positive static back pressure. OPERATION WITHOUT SUPPLY DUCTWORK OR IN FREE AIR WILL CAUSE MOTOR OVERLOAD AND PREMATURE FAILURE.
CAUTION: Regardless of the supply air duct size
installed, the Distribution Blower Motor MUST be checked for running Amperage. Check the motor name plate for the full load AMPS. If the amperage is running higher than that listed, a supply air restricting damper may be required to increase the supply plenum positive static pressure.
3. Mount the filter box on the furnace with ( 8 ) 10 x 3/4 Tek screws, 3 on each side. Visually locate these holes so you are familiar with their location on the filter box and the furnace. Access to the mounting holes can be gained through the blower access panel cover and the filter opening. See Fig. 14.
Note: Two pieces of 2x4 stacked laying flat on the floor 12 inches from the blower opening will support the filter box during installation.
Assembly
Firebrick
Fig. 15
Firebrick installation-required
The firebrick is shipped in the ashpan. It will need to be placed on the brick shelf as shown in Fig. 15. It can be installed with either face to the fire. Hold the brick longways and slide it down into the slot on the shelf. There is a stop at the rear of the shelf to stop the rearward travel.The brick just sits on the shelf in the upright position.
Baffle installation
The upper heat exchanger baffle comes shipped along side the ashpan. Remove the ashpan and the baffle. This upper baffle needs to be installed before operating the furnace.
Fig. 16
Baffle support bracket
Upper heat
exchanger baffle
45o bend
The baffle has a long 45 degree bend on the bot­tom of the firebox side. See Fig. 17.
The top has a 90 degree bend on the same side to use as a handle.
On the opposite side there are four hooks that will support the baffle.
On the front and rear of the firebox walls there are brackets that these hooks fit into. See Fig. 16
Slide the upper baffle down on to the brackets, while you hold the baffle against the heat exchanger. You will notice that the upper baffle will hold the lower baffle plate into position. See Fig.17.
Note how the upper and lower baffles are held into position because they will need to be removed during heat exchanger cleaning.
Fig. 17
9PF100
Venting
Venting
NOTE: Use only 4” diameter type “L” or “PL”
venting system. Be sure to inspect and clean exhaust venting system frequently.
4” Type “L” or “PL” Vent pipe
Fig. 18
This is the minimum venting configuration.
NOT E : T his would only b e a llowed with non- combustible walls.
The minimum vent configuration is a 90o or Tee on
a starter collar and a 24” length horizontal through an
exterior wall. A cap or other bird screen on the end should direct the flue gasses down and away from the structure. See Fig. 18.
The maximum horizontal length is 18 feet. The mini-
mum termination height above the exterior grade is 18”.
The maximum total length of any configuration is 30 feet*. * ( see venting graph on page 13 for exceptions )
NOTE: Cleanout Tee’s should always be used on
the transitions to horizontal pipe to allow easy access for cleaning.
The venting gragh allows for (one) 90 deg. or Tee
fitting in any configuration.
If more 90’s, T’s, or 45’s are needed the total length
must be adjusted to allow for the added restriction.
Up to four (4) additional 90’s, Tee’s, or equivalent
45’s can be added as long as the overall length is ad-
justed in accordance with the values listed below.
( See the venting graph on page 12.) Each Vertical ---- 90 deg. or T subtract 2.5 feet Each Vertical ---- 45 deg. subtract 1.5 feet Each Horizontal - 90 deg. or T subtract 5.0 feet Each Horizontal - 45 deg. subtract 2.5 feet
Any exterior venting (vent pipe exposed to out­side ambiant temperatures) should be kept to a minimum, due to potential condensation problems.
This is especially important in high humidity cold weather climates, such as maritime areas, lake shores, and low river valleys.
INSTALLATION IS TO BE PERFORMED BY A QUALIFIED INSTALLER.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONN ECT THIS UNIT TO A CHIM NEY FLUE S ERVING ANOTHER APPLIANCE.
INSTALL VENT WALL PASS-THROUGHS AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER
NOTE: All installation clearnaces and restrictions must be adhered to.
NOTE: Read and follow all of the vent pipe
manufacturers’ instructions on the proper
installation and support of the vent pipe. Adhere to all clearances.
WARNING
Keep combustible materials such as grass, leaves, etc. at least 3 feet away from the point directly under the vent termination. (between the vent and the ground)
WARNING
DO NOT INSTALL IN SLEEPING ROOM
CAUTION
KEEP COMBUSTIBLES AWAY
FROM FLUE OUTLET.
10
PF100
Venting
Fig. 19
Venting Configuration Graph
11PF100
Venting
Requirements for Terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding.
NOTE: Only PL vent pipe wall pass-throughs and fire stops should be used when venting through com­bustible materials.
NOTE: Always take into consideration the effect the prevailing wind direction or other wind currents will cause with flyash and /or smoke when placing the termi­nation.
In addition, the following must be observed:
A. The clearance above grade must be a minimum of 18".
1
B. The clearance to a window or door that may be opened must be a minimum of 48" to the side, 48" below the window/door, and 12" above the window/
1
door.
( with outside air installed, 18” )
C. A 12" clearance to a permanently closed win­dow is recommended to prevent condensation on the window.
D. The vertical clearance to a ventilated soffit lo­cated above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the terminal must be a minimum of 18".
E. The clearance to an unventilated soffit must be a minimum of 12".
F. The clearance to an outside corner is 11" from center of pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm) above a gas meter/regulator assembly when mea­sured from the horizontal center-line of the regulator.
1
I. The clearance to service regulator vent outlet must be a minimum of 6 feet.
1
J. The clearance to a non-mechanical air supply inlet to the building or the combustion air inlet to any
other appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply inlet must be a minimum of 10 feet.
1
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved driveway located on public property must be a minimum of 7 feet.
M. The clearance under a veranda, porch, deck
or balcony must be a minimum of 12 inches.
1,2
1,3
NOTE: The clearance to vegetation and other
exterior combustibles such as mulch is 36” as measured from the center of the outlet or cap. This 36” radius
continues to grade or a minimum of 7 feet below the outlet.
1
Certain Canadian and or Local codes or regula-
tions may require different clearances.
2
A vent shall not terminate directly above a side­walk or paved driveway which is located between two single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or bal­cony is fully open on a minimum of 2 sides beneath the floor.
NOTE: Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365. (if in Canada)
12
V
PF100
= Vent terminal
Fixed
Closed
Openable
A
Openable
= Air supply inlet
Fixed
Closed
Inside
Corner
Detail
= Area where terminal is not permitted
Fig. 20
Venting and Clearances
Floor Protector
PF100
Skidplate
Footprint
52” long
18”
48” wide

Fig.21
Clearances to combustibles
If installing the furnace in a room separated from the
remaining living spaces, the minimum size of the room must
be no smaller than 8’ x 8’. See Fig. 21. The reason for this
is heat build-up and required space for service and normal operation.
This is the minimum size of the room even if it is built
of non-combustible material.
High and low air vents MUST be installed between the room and the remaining living space. Each vent should be at least 72 square inches in area. ( The vent size will need to be increased if there is no return air ducting sys­tem.)
The striped areas are the minimum clearances to com-
bustibles which is 36” from stove body, not hopper or
blower.
The shaded area indicates the required floor protec-
tion area. The PF100 requires 48” x 52” of floor protec-
tion centered around the skidplate footprint. Flooring should be a minimum of 26 gauge sheet metal covering the instal-
lation clearance area and 18” in front of, and 8” to either
side of the ash pan door.
The 18” clearance on the hopper end is a manufactur-
ers recommendation for adding pellets and or servicing the feeder mechanism.
The minimum clearance to the top of the plenum is 4”.
Note the minimum height to the bottom of the supply duct if it crosses the hopper.
The minimum duct configuration to a living space above
the furnace is as shown in below. An offset of at least 24”
MUST be installed between the plenum and the floor regis­ter. The register size MUST have an area of at least 240 square inches.
The minimum ceiling height is 6’6”. This is set by the clearance to combustibles ( 28” ) from the top of the
of the furnace. See Fig. 22.
NOTE: Install vent at clearances specified by the vent manufacturer.
Fig. 22
CAUTION: When installing a floor
register, the temperature of the discharge air MUST be taken into consideration (The discharge air temperature may be high enough to cause burns if not properly operated and maintained.)
CAUTION: The Blower Motor full load AMPS MUST be checked.A plenum damper may be required to adjust the motor full load AMPS to the motor nameplate rating.
13PF100
Loading...
+ 28 hidden pages