“Ce manuel est disponible en Français sur demande”
R3
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO
FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES
IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW
INSTALLATION DIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION
REQUIREMENTS IN YOUR AREA.
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE
PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.
CETTE GUIDE D'UTILISATION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN STOVE
COMPANY.
R1
SAVE THESE INSTRUCTIONS.
2PC 45 Corn/Pellet Stove
Introduction
The PC 45 Corn Stove makes burning corn more convenient than ever. It’s special Sidewinder Burn Pot
allows corn to be burned from three days up to a week without cleaning, depending on the corn’s moisture
level and burn rate.
Automatic Ignition allows you to fill the hopper, set your desired room temperature and walk away. The PC
45 will adjust it’s feed rate based on the temperatures received by the room sensor, and keep your home
at the set temperature.
The PC 45’s automatic temperature control system eliminates the warm/cold cycle associated with ther-
mostatically controlled heating systems and even turns the PC 45 on and off as needed.
Our exclusive Accordion Heat Exchanger and Air Cooled Combustion Blower allows the PC 45 to produce
maximum heat without creating high exhaust temperatures. The Outside Air option can increase heat
efficiency even more.
The PC 45 can burn corn with moisture levels up to 16%, with 14.5% or less being ideal. It can also burn
pellets regardless of ash content. This allows you to buy lower cost fuel and still achieve the same results.
Please copy your
serial number from the
label on your stove to
the box below.
SERIAL NUMBER
SAFETY NOTICE: IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLED. A HOUSE FIRE MAY RESULT. FOR
YOUR SAFETY, FOLLOW THE INSTALLATION DIRECTIONS CONTACT LOCAL BUILDING OR FIRE OFFICIALS
ABOUT RESTRICTIONS AND INSTALLATION INSPECTION
REQUIREMENTS IN YOUR AREA.
Options24
Wiring Diagram26
Parts List27
Warranty28
3PC 45 Corn/Pellet Stove
Assembly and Installation
The PC 45 is bolted to the skid to prevent move-
ment during shipping.
To free the stove from the skid you must remove the hold-down bolts in the rear of the pedestal
base.
Installing rear cover panels
The rear cover panels are removed from the
stove to make it easier to get at the hold-down bolts.
The rear cover panels are packed inside the
hopper and should be installed on the stove as
shown. It is recommended that the rear covers are
installed after the unit is in place and the vent pipe is
installed.
Unpacking
Rear
Cover Panels
Shipping Bolts: These holes are
also used for Mobile Home
Installation
Fig. 1
Firebrick
Install the firebrick vertically on the angle above
the burnpot.
4PC 45 Corn/Pellet Stove
Fig. 2
Door Assembly/Installation Tips
Bottom Glass Retainer Clip Instructions
(2) Glass Retainer Clips
supplied with the door kit
(4) 10-24 x 3/8" button head allen
screws supplied in the door kit
Gasket goes
toward the stove
Fig. 3
HINGE
PINS
GLASS
4 GLASS
RETAINER
CLIPS4 GLASS RETAINER
Fig. 4
SET
SCREW
(1) left hand
(2) glass retainer clips
(1) right hand
DOOR
GLASS
GASKET
BOLTS
BRASS
HANDLE
Gasket
goes
toward
the stove
PAW
BOLT
Follow the instructions in the door kit except for the
bottom glass retainers. Install the special glass
retainer clips to the bottom of the door.
There is a left and right retainer clip with a radius to
match the door bottom. The fiber glass rope on the
clip must be facing the stove body when installed,
NOT FACING THE GLASS!!
These clips are designed to direct the air wash air
more evenly.
Assembling the door
Referring to the diagram, note how the various
•
components of the door system fit together.
Lay the load door face down on a soft surface.
•
Clean the glass and gold door using a nonabrasive
•
cleaner. Install the glass gasket around the outer edge
of the front face of the door glass carefully to insure
proper sealing. Set the glass pane gently onto the
door. Install the hold-down clips and tighten with bolts
as shown.
•
Install door on stove with hinge pins.
Install door handle as shown on the diagram.
•
NOTE: With the flat surface of the paw bolt to the
inside of the door.
•
Turn the paw bolt "in" for approx. (17) turns.
Turn the brass elbow onto the paw bolt approx. (5)
•
turns.
•
Align the set screw with the flat spot on the paw
and tighten.
•
After attaching the door handle, close and latch
the door by turning the handle to the six o'clock
position. Does the door rope compress? If not,
loosen the set screw, turn the paw bolt one more
turn into the door. Repeat as required to achieve a
tight door fit.
WOOD
HANDLE
Fig. 5
HANDLE
BOLT
NOTE: Remember to thoroughly clean the glass and
the gold door frame before lighting the stove for the
first time.
5PC 45 Corn/Pellet Stove
Installing
Installation
Place the stove on a noncombustible floor protector that extends 6 inches to the front, 6 inches to the
sides and 1 inch to the rear of the stove. The minimum
floor protector material is 24 gauge sheet metal.
Place the stove away from combustible walls at least
as far as shown in figures 6,7 & 8. Please note the difference in side wall clearance with and without side shields.
Note that the clearances shown are minimum for
safety but do not leave much room for access when cleaning or servicing. Please take this into account when placing the stove.
Connect the power cord to a 120 V.A.C. 60Hz
grounded receptacle. (A surge protector is recommened
to protect the circuit board).
Prior to installing the flue pipe, connect a draft meter
to the stove as shown in fig. 9. (The draft meter must
have a minimum range of 0"- 0.5"). Turn stove to "TEST"
Mode and record the draft reading ______. After the flue
pipe is connected, check the draft reading again making
sure all doors and windows in the home are closed. If
this reading is more than.05" higher than the unconnected
reading, check for possible restrictions or the need for
outside air. (See page 8).
Mobile Home Installation
When installing this unit in a mobile home several
requirements must be followed:
1. The unit must be bolted to the floor. This can be done
with 1/4" lag screws through the 2 holes in the base plate.
2. The unit must also be connected for the outside
air. See page 8.
3. Floor protection and clearances must be followed
as shown.
4. Unit must be grounded to the metal frame of the
mobile home.
CAUTION: This appliance must be vented to the outside.
Due to high temperatures, the stove should be placed out of traffic
and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away
to avoid burn to skin and/or clothing.
Young children should be carefully supervised when
they are in the same room as the stove.
Clothing and other flammable materials should not
be placed on or near this unit.
Installation and repair of this Harman Stove should
be done by a qualified service person. The appliance
should be inspected before use and at least annually by a
qualified service person. More frequent cleaning will be
required. It is imperative that control compartments, burners, and circulating air passageways of the stove be kept
clean.
Mobile home installation should be don e in accordance
with the Manufactured Home and Safety Standard (HUD),
CFR 3280, Part 24.
6PC 45 Corn/Pellet Stove
9"-13"
FLOOR PROTEC TOR
9" With Side Shields
13" Without Side Shields
Fig. 6
1"
6"
FLOOR PROTECTOR
Fig. 7
FLOOR PROTECTOR
Fig. 8
Fig. 9: Refer to page 18 for
detailed draft settings and
adjustment procedures.
2"
9"-13"
6"
10"
With Side Shields
6"
18"
Without Side Shields
Venting
Requirements for Terminating the Venting
WARNING: Venting terminals must not be re-
cessed into a wall or siding.
NOTE: Only PL vent pipe wall pass-throughs
and fire stops should be used when venting through
combustible materials.
NOTE: Always take into consideration the effect the prevailing wind direction or other wind currents will cause with flyash and /or smoke when placing the termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum of 18".
B. The clearance to a window or door that may
be opened must be a minimum of 48" to the side,
48" below the window/door, and 12" above the window/door.
( with outside air installed, 18” )
C. A 12" clearance to a permanently closed
window is recommended to prevent condensation
on the window.
D. The vertical clearance to a ventilated soffit
located above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the
terminal must be a minimum of 18".
E. The clearance to an unventilated soffit must
be a minimum of 12".
F. The clearance to an outside corner is 11"
from center of pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90
cm) above a gas meter/regulator assembly when
measured from the horizontal center-line of the regu-
1
lator.
1
1
I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
1
J. The clearance to a non-mechanical air sup-
ply inlet to the building or the combustion air inlet to
any other appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply
inlet must be a minimum of 10 feet.
1
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be
a minimum of 7 feet.
M. The clearance under a veranda, porch, deck
or balcony must be a minimum of 12 inches.
1,2
1,3
NOTE: The clearance to vegetation and other
exterior combustibles such as mulch is 36” as measured from the center of the outlet or cap. This 36”
radius continues to grade or a minimum of 7 feet
below the outlet.
1
Certain Canadian and or Local codes or regu-
lations may require different clearances.
2
A vent shall not terminate directly above a sidewalk or paved driveway which is located between
two single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or balcony is fully open on a minimum of 2 sides beneath
the floor.
NOTE: Where passage through a wall, or
partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365.
(if in Canada)
V
= Vent terminal
Fixed
Closed
Openable
A
Openable
= Air supply inlet
Inside Corner
Detail
Fixed
Closed
= Area where terminal is not permitted
7PC 45 Corn/Pellet Stove
Venting
IMPORTANT NOTICE
Pellet Vent Pipe or PL Vent Pipe Must be used.
+ = Positive static pressure
Fig. 10
= Negative static pressure
A combustion blower is used to extract the combustion gases from the firebox. This causes a negative pressure in the firebox and a positive pressure
in the venting system as shown in fig. 10. The longer
the vent pipe and more elbows used in the system,
the greater the flow resistance. Because of these
facts we recommend using as few elbows as possible and 15 feet or less of vent pipe. The maximum
horizontal run should not exceed 48". If more than
15 feet of pipe is needed, the diameter should be
increased from 3" to 4" because a larger pipe causes
less flow resistance. Be sure to use approved
pellet vent pipe wall and ceiling pass through
fittings to go through combustible walls and
ceilings. Be sure to use a starting collar to attachthe venting system to the stove. The starting collar must be sealed to the stove with high temp
silicone caulking.
Vent Pipe
Pellet venting pipe ( also known as PL vent ) is
constructed of two layers with air space between
the layers. This air space acts as an insulator and
reduces the outside surface temperature to allow a
clearance to combustibles of only 3 inches. The
sections of pipe lock together to form an air tight
seal in most cases; however, in some cases a perfect seal is not achieved. For this reason and the
fact that the PC45 operates with a positive vent pressure we specify that the joints also be sealed
with clear silicone.
Inlet Cover part#
1-10-08542
Fig. 11
8PC 45 Corn/Pellet Stove
Outside air flex pipe
goes here
Flex pipe part#
2-00-08543
Outside Air
Outside air is optional except in mobile homes
and where building codes require. The benefit of
outside air is mainly noticed in small very tight
houses.
To install outside air use 2 3/8" I.D. flex pipe
part number 2-00-08543. There is a break-away hole
on the rear panel which must be removed before
connecting the flex pipe. The pipe should be run outside and terminate 3 feet or more to the side or below the vent pipe outlet. Never terminate the outside
air above the vent pipe outlet. The maximum length
run of this pipe is 15 feet. If a longer run is needed
the size must be increased to 3". Inlet cover part
number 1-10-08542 should be used to keep birds,
rodents etc.out of pipe.
HRV
When installing in a house with a Heat Reclaiming Ventilation System (HRV) be sure the system is
balanced and is not creating a negative pressure in
the house.
Venting
mal operation and allows the stove to be installed
closest to the wall. Two inches from the wall is safe;
however, four inches allows better access to remove
the rear panel. The vertical portion of the vent should
be three to five feet high. This vertical section will
provide natural draft in the event of a power failure.
#1 Preferred method
This method provides excellent venting for nor-
Fig. 12
3 ft.
to
combustibles
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to five feet high and at least three
inches from a combustible wall. This vertical section will provide natural draft in the event of a power
failure.
If the stove is installed below grade the vent
termination should be at least 1 foot above grade.
CAUTION
Keep combustible materials (such as grass, leaves,
etc.) at least 3 feet away from the flue outlet on the
outside of the building.
Fig. 13
3 ft.
to
combustibles
9PC 45 Corn/Pellet Stove
Loading...
+ 19 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.