Harman Stove Company P61 User Manual

Installation & Operating Manual
P61 Pellet Stove Owners Manual
“Ce manuel est disponible en Français sur demande”
SAFETY NOTICE
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES
IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLATION DIRECTIONS.
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.
CETTE GUIDE D'UTILISATION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN HOME HEATING.
R10
SAVE THESE INSTRUCTIONS.
INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW
Item# 3-90-05810
NOTICE: This Label Copy Is For Reference Only. Consult The
Actual Unit Label For Clearances And Other Specic Information.
Fig. 1
Table of Contents
Testing Label 2
Assembly & Installation 4
Venting 7
Operation 12
ESP Control 14
Maintenance 15
Trouble Shooting 18
Feeder Parts 19
Specications 20
Wiring Diagram 21
Options 22
Parts List 24
Warranty 25
Please read this entire manual before you install and use your new
room heater. Failure to follow instructions may result in
property damage, bodily injury, or even death.
SUITABLE FOR MOBILE HOME INSTALLATIONS.
SAVE THESE INSTRUCTIONS
Harman Home Heating
352 Mountain House Road
Halifax, PA 17032
3
Assembly and Installation
Unpacking
The P61 is bolted to the skid to prevent movement
during shipping.
To free the stove from the skid you must remove the
hold-down bolts in the rear of the pedestal base.
Removing or Installing rear cover panels
To remove the rear cover panels, loosen the screws slightly and slide the covers outward as shown in the illustration. To reinstall, simply slide back into place and retighten the screws.
Firebrick
Install the rebrick vertically on the angle above the
burnpot.
Flame Guide
Install the cast iron ame guide on top of the burnpot
and make sure it is fully seated against the auger
opening. The bottom of the ame guide is marked 38+.
Draft Test Procedure
Fig. 2
Rear Cover Panels
Shipping Bolts: These holes are also used for Mobile Home Installation
Before attaching any vent pipe to the stove, perform
a draft test, for later comparison.
Remove the plug bolt on the underside of the rebox
as shown. Using the hole from the bolt, attach a draft meter that is capable of reading at least .5 inches of water column (W.C.). You are going to want the meter reading negative pressure.
Turn the feed adjuster to "Test". For the rst minute,
everything will run. Record the high draft reading
_______ . After the rst minute, the distribution blower
will go to a low speed. Then, after the second minute, two minutes after turning to test, the distribution blower will come back up to high, and the combustion blower will drop to low. During this time, record the low draft________. Perform the test again after the venting is complete. Compare your readings. If there is more than a .05 difference, you have too much restriction in the venting. There is no adjustment for the draft other
than improving the venting conguration. Leaving the
stove in "test" will continue to cycle the blowers each
minute. Record your nal draft redings here. _________ High, and ________ Low.
4
Installation
Installing
Place the stove on a non-combustible oor or a oor
protector providing a minimum .84k value. Floor protection
must extend 6 inches to the front, 6 inches to the sides and 1 inch to the rear of the stove.
Place the stove away from combustible walls at least
as far as shown in gures 3,4 and 5. Please note the
difference in side wall clearance with and without side shields.
Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing. Please take this into account when placing the stove.
Connect the power cord to a 120 V.A.C. 60Hz grounded receptacle.
After connecting the ue system, perform the second draft
test. However, prior to taking the draft reading be sure all doors and windows in the home are closed. Record the draft reading_______. If this reading is more than .05" lower than the unconnected reading, check for possible restrictions or the need for outside air (see page 7).
Mobile Home Installation
When installing this unit in a mobile home, several requirements must be followed:
1. The unit must be bolted to the oor. This can be done with
1/4" lag screws through the 2 holes in the base plate.
2. The unit must also be connected for the outside air.
See page 7.
3. Floor protection and clearances must be followed as
shown.
4. Unit must be grounded to the metal frame of the mobile
home.
5. The stove may not be installed in a room designated
for sleeping.
CAUTION: This appliance must be vented to the outside.
Due to high temperatures, the stove should be placed out
of trafc and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burn to skin and/or clothing.
Young children should be carefully supervised when they are in the same room as the stove.
Clothing and other ammable materials should not be
placed on or near this unit.
Installation and repair of this Harman Stove should be
done by a qualied service person. The appliance should be inspected before use and at least annually by a qualied
service person. More frequent cleaning will be required. It is imperative that control compartments, burners, and circulating air passageways of the stove be kept clean.
9"-13"
9" With Side Shields 13" Without Side Shields
9"-13"
Fig. 3
Fig. 4
18"
Mobile home installation should be done in accordance with the Manufactured Home and Safety Standard (HUD), CFR 3280, Part 24.
Fig. 5
5
Venting
Requirements for Terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding. NOTE: Only pellet vent pipe wall pass-throughs
and re stops should be used when venting through
combustible materials. NOTE: Always take into consideration the effect the prevailing wind direction or other wind currents will
cause with yash and /or smoke when placing the
termination.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
B. The clearance to a window or door that may be
opened must be a minimum of 48".
(with outside air installed, 18”)
C. A 12" clearance to a permanently closed window
is recommended to prevent condensation on the window.
D. The vertical clearance to a ventilated soft located
above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the terminal
must be a minimum of 18".
E. The clearance to an unventilated soft must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center
of pipe. G. The clearance to an inside corner is 12". H. A vent must not be installed within 3 feet (90 cm)
above a meter/regulator assembly when measured
from the horizontal center-line of the regulator. I. The clearance to service regulator vent outlet must
be a minimum of 6 feet.
1
1
1
1
J. The clearance to a non-mechanical air supply inlet to
the building or the combustion air inlet to any other
appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply inlet must
be a minimum of 10 feet.
1
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum of 7 feet.
1,2
M. The clearance under a veranda, porch, deck or
balcony must be a minimum of 12 inches.
1,3
(see B.)
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is 36” as measured from the center of the outlet or cap. This 36” radius continues
to grade or a minimum of 7 feet below the outlet.
1
Certain Canadian and or Local codes or regulations
may require different clearances.
2
A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or balcony is
fully open on a minimum of 2 sides beneath the oor.
NOTE: Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365. (if in Canada)
V
= Vent terminal
6
Venting
IMPORTANT NOTICE
Pellet Vent "L" or "PL" Vent Pipe Must be used.
+
Fig. 6
+
= Positive static pressure
-
= Negative static pressure
+
A combustion blower is used to extract the combustion
gases from the rebox. This causes a negative pressure in the rebox and a positive pressure in the venting system as shown in g. 6. The longer the vent pipe
and more elbows used in the system, the greater the
ow resistance. Because of these facts we recommend
using as few elbows as possible and 15 feet or less of vent pipe. The maximum horizontal run should not
exceed 48". If more than 15 feet of pipe is needed, the
diameter should be increased from 3" to 4" because
a larger pipe causes less ow resistance. Be sure to use approved pellet vent pipe wall and ceiling
pass through ttings to go through combustible
walls and ceilings. Be sure to use a starting collar to attach the venting system to the stove. The starting
collar must be sealed to the stove with high temp silicone caulking.
Vent Pipe
Pellet vent pipe (known as type "L" or "PL" vent) is
constructed of two layers with air space between the layers. This air space acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of only 3 inches. The sections of pipe lock together to form an air tight seal in most cases; however, in some cases a perfect seal is not achieved. For this reason and the fact that the P61 operates with a positive vent pressure we specify that the joints
also be sealed with high temp silicone.
Fig. 7
Outside air ex
pipe goes here
Flex pipe part # 1-00-08543 (25 ft.)
Inlet Cover part# 1-10-08542
The Harman Direct Vent Wall Passthrough allows the proper protection of the wall and brings outside air to the stove with one component. Part # 1-00-677077 is all you need.
(ts only 3" pellet pipe)
Outside Air
Outside air is optional except in mobile homes and
where building codes require. The benet of outside air
is mainly noticed in small very tight houses.
To install outside air use 2 3/8" I.D. ex pipe part
number 1-00-08543 (25 ft.). There is a break-away
hole on the rear panel which must be removed before connecting the ex pipe. The pipe should be run outside and terminate to the side or below the vent pipe outlet
so the ue outlet is more than 12" from the inlet cover.
The maximum length run of this pipe is 15 feet. If a longer run is needed the size must be increased to 3".
Inlet cover part number 1-10-08542 should be used to
keep birds, rodents etc. out of the pipe.
HRV
When installing in a house with a Heat Reclaiming Ventilation System (HRV) be sure the system is balanced and is not creating a negative pressure in the house.
7
Venting
#1 Preferred method
This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall. Two inches from the wall is safe; however, four inches allows better access to remove the rear panel. The vertical portion of the
vent should be three to ve feet high. This vertical
section will provide natural draft in the event of a power failure.
Fig. 8
3 ft.
to combustibles
#2 Preferred method
This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall. The vertical portion
of the vent should be three to ve feet high and at
least three inches from a combustible wall. This vertical section will provide natural draft in the event of a power failure.
Fig. 9
3 ft.
to combustibles
8
Loading...
+ 16 hidden pages