Harman Stove Company P43 User Manual

Installation & Operating Manual
P43 Pellet Stove Owners Manual
“Ce manuel est disponible en Français sur demande”
PLEASE READ THIS ENTIRE MANUAL BEFORE YOU INSTALL AND USE YOUR NEW ROOM HEATER. FAILURE TO FOLLOW INSTRUCTIONS MAY RESULT IN PROPERTY DAMAGE, BODILY INJURY, OR EVEN DEATH.
FOR USE IN THE U.S. AND CANADA. SUITABLE FOR INSTALLATION IN MOBILE HOMES.
IF THIS HARMAN STOVE IS NOT PROPERLY INSTALLATION DIRECTIONS.
CONTACT LOCAL BUILDING OR FIRE OFFICIALS ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIREMENTS IN YOUR AREA.
CONTACT YOUR LOCAL AUTHORITY (SUCH AS MUNICIPAL BUILDING DEPARTMENT, FIRE DEPARTMENT, FIRE PREVENTION BUREAU, ETC.) TO DETERMINE THE NEED FOR A PERMIT.
CETTE GUIDE D'UTILISATION EST DISPONIBLE EN FRANCAIS. CHEZ VOTRE CONCESSIONNAIRE DE HARMAN HOME HEATING.
INSTALLED, A HOUSE FIRE MAY RESULT. FOR YOUR SAFETY, FOLLOW
R1
SAVE THESE INSTRUCTIONS.
1
P43 Pellet Stove
3-90-04301R18_03/13
Floor protector
Rev C
US ENVIRONMENTAL PROTECTION AGENCY
This model is exempt from EPA certifi cation under 40 CFR 60.531
"PREVENTION DES INCENDIES"
Respecter scrupuleusement les instructions du constructeur pour l'installation et les consignes
de fonctionnement. Respecter les règles de sécuritè en vigueur dans votre région.
AVERTISSEMENT POUR MOBILE HOMES: Ne pas installer dans une chambre. ll est imperatif
de prévoir une prise d'alr extérieur. L'intégrité structurale du plancher, du plafond et des murs doit étre
strictement préservée. Se reporter aux instructions du fabricant et aux réglementations spécifi ques
locales concernant les précautions requises lors de la traversée d'un mur ou d'un plafond.
Contróler et nettoyer fréquemment tout le systeme d'evacuation des fumées conformément aux
recommandations du constructeur. Utiliser des tuyaux <<Spécial granulés>> de Ø76 mm ou
102 mm. Ne pas raccorder ce poéle à un conduit de cheminée déjà utilisé pour un autre appareil.
FONCTIONNE EXCLUSIVEMENT AVEC DES GRANULES DE BOIS.
Appareil de chauffage à granulé type. Consommation maximum: 2.5 kg/h.
US coupure: 115 VAC, 60 Hz, 4.2 amps Démarrer, Exécuter 2.8 AMPS
fonctionnement normal 1.1A. Tenir le cordon d'alimentation à l'écart du poèle.
DANGER: Risque d'électrocution. Débrancher l'appareil avant toute intervention.
Ne remplacer la vitre qu'avec une vitre céramique 5mm de méme qualité disponible
auprès de votre revendeur.
Pour une information plus compléte, se reporter à la notice d'utilisation. Tenir la porte
hermétiquement close durant fonctionnement.
Ne faites pas obstacle l’espace sous le réchauffeur. Toujours fournir un approvisionnement suffi sant en air frais
jusqu’au lieu d’installation Appliance
76mm min
3" min
2"(51mm)
10" (254mm) with side shields
16" (406mm) w/out side shields
Made in U.S.A. of US and imported parts. / Fabriqué
aux États-Unis-d’Amérique par des pièces d’origine
américaine et pièces importées.
WITH
SIDE SHIELDS
WITHOUT
SIDE SHIELDS
Latéraux
Avec Écrans
Latéraux
Sans Écrans
76mm min
9"(228mm)
3" min
9"(228mm)
BARCODE LABEL
USA Canada
by defi nition [Wood Heater (A) "Air-to-Fuel Ratio"]
Agence Américaine pour la Protection de l’Environnement
PROTECTION DE SOL
FLOOR PROTECTION
Date of Manufacture / Date de fabrication:
par dèfi nition [Appareil á bois (A) << Ratio air/combustible>>]
Ce modéle est dispensé par EPA certifi cation d’aprés 40 CFR 60.531
Fabriqué par: Harman Stove Company 352 Mountain House Road, Halifax PA 17032
2012 2013 2014 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
B
AA
C
USA CANADA
P.N. 3-90-04300
MINIMUM CLEARANCES TO COMBUSTIBLES/
DISTANCES DE SECURITE PAR RAPPORT AUX
MATERIAUX COMBUSTIBLES:
Back Wall / Entre Mur Arrière 2”/ 51mm 2”/ 51mm
Side Wall / Entre Paroi Latér 16”/ 406mm 10”/ 254mm
Homes in accordance with OAR 814-23-900 through 814-23-909
MODEL / MODÈLE: "PP38+ / P43"
Room Heater Pellet Fuel Burning Type. Also for use in Mobile Homes.
Appareil de chauffage à granulés de bois Utilisable dans des mobile homes.
This pellet burning appliance has been tested and listed for use in Manufactured
The label shown here is for referrence only. For specic
008
information on clearances and testing, consult the actual
label on the rear of the P43 fuel hopper.
de série:
o
Serial No.
N
"PREVENT HOUSE FIRES"
Install and Use Only in Accordance With Manufacturer's Installation and Operation Instructions.
Contact Local Building or Fire Offi cials About Restrictions and Installation Inspection in Your Area.
WARNING : THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL,
AND CEILING/ROOF MUST BE MAINTAINED. DO NOT INSTALL IN SLEEPING ROOM.
An outside combustion air inlet must be provided. Refer to Manufacturer’s instructions and local
Report #/ Raport # 135-S-21-6.2 (PP38+)
Report #/ Raport # 135-S-23b-6.2 (P43)
Tested to / Testé à:
ASTM E1509-04, ULC/ORD-C1482-
M1990, ULC-S627-00
codes regarding the requirements for passing the exhaust venting system through a combustible
Arrière (B) 6” 200mm
Côtés (A) 6” 200mm
Avant (C) 6” 450mm
Back**/
Sides*/
Front*/
**Measured from pedestal base in the US ONLY
**Mesuré à partir de la base du socle aux États-Unis uniquement
CORNER INSTALLATION / EN ANGLE
Walls to Appliance 9”/228mm 9”/228mm
Entre Murs et appareil
Flue Connector/Raccord à la cheminée 3” /76mm
FLOOR PROTECTION / Protection Du Plancher
wall or ceiling.
Inspect and Clean Exhaust Venting System Frequently.
Use a 3" or 4" diameter type "L" or "PL" venting system.
Do Not Connect This Unit to a Chimney Flue Serving Another Appliance.
FOR USE WITH WOOD PELLET FUEL OR UP TO 50% CORN / PELLET MIXTURE ONLY.
The Use of Other Fuels May Create an Unsafe Condition.
*Measured from Glass Opening
Input Rating Max: 5.5 lb. fuel/hr.
U.S. Electrical Rating: 115 VAC, 60 Hz, Start 4.2 AMPS, Run 2.8 AMPS
Route Power Cord Away From Unit.
*Mesurer à partir de la surface de la porte en verre
Floor Protection Must Be a Non-Combustible Material.
Must Also be Place Under Any Horizontal Flue Connector,
Extending 2” or 51mm Beyond the Pipe Measurement.
Pour protéger le plancher, il faut sous le pêole un matériau. Qui
doit aussi être placé sous les parties horizontales du tuyau de
raccord à la cheminée et s’étendre à 51mm o 2 po. au-delà de
la mesure du tuyau.
DANGER: Risk of Electrical Shock. Disconnect Power Before Servicing Unit.
For Further Instruction, Refer To Owner's Manual.
Replace glass only with 5mm ceramic available from your dealer.
Keep Viewing and Ash Removal Doors Tightly Closed During Operation.
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
3P43 Pellet Stove3-90-04301R18_03/13
Introduction
Harman PP38+/P43 Pellet Stove Label measures: 4-3/8" high X 10-3/4"wide Black Background with bare metal for print-adhesive backed, metal plate.
Floor protector
The P43 Pellet Stove has huge features in a small package, giving you 0 to 43,000 BTU when you need it,
automatically. You basically need to set your desired room temperature and ll the hopper. With the P43 you will
notice even heat throughout your zone and a level of convenience you never thought possible. The P43 epitomizes the capability of Harman Pellet Stoves, taking advantage of Harman’s 20+ years of pellet stove design, technology and manufacturing. This 43,000 BTU stove has the smartest controls coupled with minimal maintenance. The P43's output is managed by a microprocessor that senses the room temperature and
the re temperature with tiny thermistor probes and then determines the best feed rate for your heating demand.
This improved and smarter control also has a diagnostic port which allows a service representative to attach an external display showing live working data for ease in troubleshooting. The platinum combination is Harman’s Patented Feeder & Burn Pot, and ESP Control which have been developed to their highest state. These features work together to allow amazing heat output with little regard for fuel quality.
Table of Contents
Safety Information 5
Installation 6
This label is located on the back of the unit. Please copy the Serial Number for future reference.
Serial #:
MODEL / MODÈLE: "PP38+ / P43"
Room Heater Pellet Fuel Burning Type. Also for use in Mobile Homes.
Appareil de chauffage à granulés de bois Utilisable dans des mobile homes.
This pellet burning appliance has been tested and listed for use in Manufactured
Report #/ Raport # 135-S-21-6.2 (PP38+) Report #/ Raport # 135-S-23b-6.2 (P43) Tested to / Testé à: ASTM E1509-04, ULC/ORD-C1482­M1990, ULC-S627-00
"PREVENT HOUSE FIRES" Install and Use Only in Accordance With Manufacturer's Installation and Operation Instructions.
Contact Local Building or Fire Offi cials About Restrictions and Installation Inspection in Your Area.
WARNING : THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND CEILING/ROOF MUST BE MAINTAINED. DO NOT INSTALL IN SLEEPING ROOM.
An outside combustion air inlet must be provided. Refer to Manufacturer’s instructions and local codes regarding the requirements for passing the exhaust venting system through a combustible
wall or ceiling.
Inspect and Clean Exhaust Venting System Frequently.
Use a 3" or 4" diameter type "L" or "PL" venting system.
Do Not Connect This Unit to a Chimney Flue Serving Another Appliance. FOR USE WITH WOOD PELLET FUEL OR UP TO 50% CORN / PELLET MIXTURE ONLY.
The Use of Other Fuels May Create an Unsafe Condition.
Input Rating Max: 5.5 lb. fuel/hr.
U.S. Electrical Rating: 115 VAC, 60 Hz, Start 4.2 AMPS, Run 2.8 AMPS
Route Power Cord Away From Unit.
DANGER: Risk of Electrical Shock. Disconnect Power Before Servicing Unit.
For Further Instruction, Refer To Owner's Manual.
Replace glass only with 5mm ceramic available from your dealer.
Keep Viewing and Ash Removal Doors Tightly Closed During Operation.
DO NOT REMOVE THIS LABEL / NE PAS ENLEVER CETTE ÉTIQUETTE
Serial No.
No de série:
008
Homes in accordance with OAR 814-23-900 through 814-23-909
BARCODE LABEL
MINIMUM CLEARANCES TO COMBUSTIBLES/ DISTANCES DE SECURITE PAR RAPPORT AUX MATERIAUX COMBUSTIBLES:
Back Wall / Entre Mur Arrière 2”/ 51mm 2”/ 51mm Side Wall / Entre Paroi Latér 16”/ 406mm 10”/ 254mm CORNER INSTALLATION / EN ANGLE Walls to Appliance 9”/228mm 9”/228mm
Entre Murs et appareil
Flue Connector/Raccord à la cheminée 3” /76mm
FLOOR PROTECTION / Protection Du Plancher
USA Canada
Côtés (A) 6” 200mm
Sides*/
Arrière (B) 6” 200mm
Back**/
Avant (C) 6” 450mm
Front*/ **Measured from pedestal base in the US ONLY **Mesuré à partir de la base du socle aux États-Unis uniquement
*Measured from Glass Opening
*Mesurer à partir de la surface de la porte en verre
Floor Protection Must Be a Non-Combustible Material. Must Also be Place Under Any Horizontal Flue Connector, Extending 2” or 51mm Beyond the Pipe Measurement. Pour protéger le plancher, il faut sous le pêole un matériau. Qui doit aussi être placé sous les parties horizontales du tuyau de raccord à la cheminée et s’étendre à 51mm o 2 po. au-delà de
la mesure du tuyau.
WITHOUT
SIDE SHIELDS
Sans Écrans
Latéraux
Safety Listing: Omni-Test Laboratories, Inc. Tested to: ASTM E1509-04, ULC S627-00, and
ULC/ORD-C1482-M1990. Report #135-S-23b-6.2
This appliance is also approved for installation into a shop.
Made in U.S.A. of US and imported parts. / Fabriqué aux États-Unis-d’Amérique par des pièces d’origine américaine et pièces importées.
WITH
SIDE SHIELDS
Avec Écrans
Latéraux
"PREVENTION DES INCENDIES"
Respecter scrupuleusement les instructions du constructeur pour l'installation et les consignes
de fonctionnement. Respecter les règles de sécuritè en vigueur dans votre région. AVERTISSEMENT POUR MOBILE HOMES: Ne pas installer dans une chambre. ll est imperatif de prévoir une prise d'alr extérieur. L'intégrité structurale du plancher, du plafond et des murs doit étre strictement préservée. Se reporter aux instructions du fabricant et aux réglementations spécifi ques locales concernant les précautions requises lors de la traversée d'un mur ou d'un plafond.
2"(51mm)
Contróler et nettoyer fréquemment tout le systeme d'evacuation des fumées conformément aux recommandations du constructeur. Utiliser des tuyaux <<Spécial granulés>> de Ø76 mm ou 102 mm. Ne pas raccorder ce poéle à un conduit de cheminée déjà utilisé pour un autre appareil. FONCTIONNE EXCLUSIVEMENT AVEC DES GRANULES DE BOIS. Appareil de chauffage à granulé type. Consommation maximum: 2.5 kg/h. US coupure: 115 VAC, 60 Hz, 4.2 amps Démarrer, Exécuter 2.8 AMPS fonctionnement normal 1.1A. Tenir le cordon d'alimentation à l'écart du poèle.
10" (254mm) with side shields 16" (406mm) w/out side shields
9"(228mm)
DANGER: Risque d'électrocution. Débrancher l'appareil avant toute intervention. Ne remplacer la vitre qu'avec une vitre céramique 5mm de méme qualité disponible auprès de votre revendeur. Pour une information plus compléte, se reporter à la notice d'utilisation. Tenir la porte
76mm min
hermétiquement close durant fonctionnement.
3" min
76mm min
Ne faites pas obstacle l’espace sous le réchauffeur. Toujours fournir un approvisionnement suffi sant en air frais
3" min
jusqu’au lieu d’installation Appliance
PROTECTION DE SOL FLOOR PROTECTION
C
USA CANADA
9"(228mm)
B
AA
This model is exempt from EPA certifi cation under 40 CFR 60.531
Agence Américaine pour la Protection de l’Environnement
Ce modéle est dispensé par EPA certifi cation d’aprés 40 CFR 60.531
par dèfi nition [Appareil á bois (A) << Ratio air/combustible>>]
2012 2013 2014 JAN FEB MAR APR MAY JUN JUL AUG SEP OCT NOV DEC
Fabriqué par: Harman Stove Company 352 Mountain House Road, Halifax PA 17032
P.N. 3-90-04300
US ENVIRONMENTAL PROTECTION AGENCY
by defi nition [Wood Heater (A) "Air-to-Fuel Ratio"]
Date of Manufacture / Date de fabrication:
Venting 8
ESP Control 15
Automatic Operation 16
Manual Operation 19
Low Draft Voltage Adjustment 21
Maintenance 22
Troubleshooting 27
Specications / Wiring Diagram 28
Rev C
Options 29
Fuel Specication Details 30
Power Failure / Back-up 32
Warranty 33
Service Parts 35
Division of Hearth & Home Technologies, Inc
= Contains updated information
352 Mountain House Road
Halifax, PA 17032
4 P43 Pellet Stove 3-90-04301R18_03/13
IMPORTANT NOTES
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
SPECIAL NOTE:
DUE TO FLY ASH BUILDUP, IT IS STRONGLY RECOMMENDED THAT YOU HAVE YOUR STOVE PROFESSIONALLY CLEANED AND SERVICED ANNUALLY. THIS INCLUDES ALL PARTS OF THE STOVE, AND THE ENTIRE
VENTING SYSTEM.
CAUTION
ALWAYS BE SURE THERE IS NO UNBURNED FUEL IN THE ASH PAN PRIOR TO LIGHTING A FIRE. THIS WILL CAUSE SMOKE AND SOOT AND OTHER UNWANTED RESULTS.
WARNING
MOBILE/MANUFACTURED HOME STANDARDS DO NOT ALLOW INSTALLATION IN ROOMS DESIGNATED FOR SLEEPING.
CAUTION
THE STRUCTURAL INTEGRITY OF THE MOBILE HOME FLOOR, WALL, AND CEILING/ ROOF MUST BE MAINTAINED.
MOBILE HOME INSTALLATION SHOULD BE DONE IN ACCORDANCE WITH THE MANUFACTURED HOME AND SAFETY STANDARD (HUD), CFR 3280, PART 24.
CAUTION
KEEP COMBUSTIBLE MATERIALS (SUCH AS GRASS, LEAVES, ETC.) AT LEAST 3 FEET AWAY FROM THE FLUE OUTLET ON THE OUTSIDE OF THE BUILDING.
CAUTION
DO NOT USE MAKESHIFT COMPONENTS OR OTHER COMPROMISES WHEN
INSTALLING THIS APPLIANCE.
INSTALLATION AND REPAIR OF THIS HARMAN STOVE SHOULD BE DONE BY A QUALIFIED SERVICE PERSON. WE RECOMMEND THAT THE STOVE BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE PERSON. PERIODIC CLEANING IS REQUIRED THROUGHOUT THE HEATING SEASON AND AT THE END OF EACH WINTER FOR THE STOVE TO WORK EFFICIENTLY. SEE CLEANING INSTRUCTIONS ON PG 23.
CAUTION
A CHIMNEY CONNECTOR SHALL NOT PASS THROUGH AN ATTIC OR ROOF SPACE, CLOSET OR OTHER CONCEALED SPACE, A FLOOR, OR A CEILING.
CAUTION
DO NOT CONNECT TO OR USE IN
CONJUNCTION WITH ANY AIR
DISTRIBUTION DUCT WORK UNLESS
SPECIFICALLY APPROVED FOR SUCH
INSTALLATION.
5P43 Pellet Stove3-90-04301R18_03/13
Assembly and Installation
Shipping Bolts Note: These same holes are used for securing the
Fig. 1
Room Sensor Installation
The room sensor is a small temperature sensor on the end of a 60" wire. This sensor is installed much like a standard wall thermostat. There is a remote room sensor port on the rear of the unit for easy external connection. Use standard 18-2 thermostat wire to extend the distance to the desired location (50' maximum). The room sensor should be installed in the location where you want to control the temperature. NOTE: Distances of more than 25 feet from the unit or in another room are not recommended. The room sensor is
essential for the P43's excellent efciency.
NOTE: It is recommended that the room sensor be installed, even if only installed on the rear of the unit as a
return air sensor.
stove in mobile home installation.
Rear Cover
Panels
Unpacking
The P43 is bolted (1/4 x 1" hex head bolts) to the skid to prevent movement during shipping.
To free the stove from the skid you must remove the hold-down bolts in the rear of the pedestal base.
Removing rear cover panels
The rear cover panels are secured to the stove with three bolts each. Two of the bolts need only be loosened, not removed, to remove the panels. It is recommended that the rear covers are installed after the unit is in place and the vent pipe is installed, to prevent contact with hot or moving parts.
Firebrick
Install the single rebrick horizontally on the angle
bracket above the burnpot.
Flame Guide
Install the cast iron ame guide on top of the burn pot. Make sure that the ame guide is fully seated on the
vertical sides of the burn pot and that the back of the guide rests against the body of the stove.
INSTALL EXHAUST VENT AT CLEARANCES SPECIFIED BY THE MANUFACTURER. Most pellet vent pipe requires a minimum of 3" of clearance to combustible materials although some can be installed at 1" clearance.
Follow these instructions along with all local codes regarding installation of this appliance.
Do NOT use makeshift compromises when installing this appliance, serious consequences may result.
With any hearth appliance, installation of smoke
detectors is recommended on every level of the home.
Possible causes of smoke detector activation:
Paint curing process - Open a window near the
appliance for the rst few hours of burning.
Exhaust being drawn back inside the dwelling - Outside air connection to the appliance is necessary.
6 P43 Pellet Stove
Vent leakage - All interior seams and joints should be sealed with silicone where appliacable. Follow vent manufacturers instructions for proper sealing.
3-90-04301R18_03/13
Installation
Installing
Place the stove on a noncombustible type oor or oor protector
that extends a minimum of 6 inches (152mm) to the front of the load door opening, 6 inches (152mm) to the sides of the door opening, and 6 inches to the rear. Floor protection must also
extend 2 inches (51mm) beyond each side of any horizontal ue pipe. The minimum oor protector material is 20 gauge sheet metal. Other oor protector materials are ceramic tile, stone,
brick, etc. NOTE for Canadian installation only: Per ULC-S627-00, If installed on a combustible floor, the need to provide a noncombustible oor protector covering the area beneath the
space heater and extending at least 17.72" (450mm) on the ring
side and at least 7.87" (200mm) on the other sides.
In Canada, you may follow smaller U.S. oor protection
requirements ONLY if the user agrees to completely shut-
down the appliance, and allow it to cool to where all re is
extinguished and the combustion blower and its indicator
light shuts off, prior to opening the rebox door or ash door.
Place the stove away from combustible walls at least as far as shown in Figures 3 and 4. Please note the difference in side wall clearance with and without side shields.
Note that the clearances shown are minimum for safety but do not leave much room for access when cleaning or servicing. Please take this into account when placing the stove.
Connect the power cord to a 120 V.A.C. 60Hz grounded receptacle. (A surge protector is recommended to protect the circuit board.) Also be sure that the polarity of the outlet that the stove is plugged into is correct.
Prior to installing the ue pipe, connect a draft meter. (The
draft meter must have a minimum range of 0 - .5") Record the
rst reading. Connect ue pipe to stove and be sure all doors
and windows in the home are closed. Record the second draft reading_______. If the second reading is more than .05" lower
than the rst reading, check for possible restrictions or the need
for outside air (see page 10). For more information on the draft test procedure, refer to Page 21.
Mobile Home Installation
When installing this unit in a mobile home, several requirements
must be followed:
1. The unit must be bolted to the oor. This can be done with 1/4"
lag screws through the 2 holes in the base plate.
2. The unit must also be connected to outside air. See page 10.
3. Floor protection and clearances must be followed as shown.
4. Unit must be grounded to the metal frame of the mobile home.
CAUTION: This appliance must be vented to the outside.
Due to high temperatures, the stove should be placed out of
trafc and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperatures and should stay away to avoid burns to skin and/or clothing.
Young children should be carefully supervised when they are in the same room as the stove.
Clothing and other ammable materials should not be placed
on or near this unit.
WARNING
THE STRUCTURAL INTEGRITY OF THE
MANUFACTURED HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
DO NOT INSTALL IN SLEEPING ROOM.
Alternate floor protector
dimension may be used as long as they satisfy the measurement requirements shown below.
Minumum size oor protection
for a corner installation hearth pad is 36" x 36". Clearance shown as 9" with optional side shields installed.
9"(228mm)With or W/Out Side Shields
9"(228mm)
9"(228mm)
Fig. 3
2"(51mm)
10" (254mm) with
side shields
16" (406mm)
without side shields
Fig. 4
36"(914mm)
Minimum Size oor protection (USA) is 32
10" (254mm) 16" (406mm)
1/2
" wide By
33" deep (825mm X 838mm). * Floor protection dimensions for the front and sides
are measured from the appliance door opening in The United States. In Canada, the side dimension is measured from the widest part of the appliance.
Floor Protection Requirements
Sides
J
Front
K
Rear
L
US
Canada
6" 200mm
6" 450mm
6" 200mm
NOTE: Measurement "L" is measured from the pedestal base in the US ONLY
L
NOTE:
Measurement "K" is measured from the glass in the US ONLY
CANADA
J
USA
K
Floor protector
J
7P43 Pellet Stove3-90-04301R18_03/13
Venting
Requirements for Terminating the Venting
WARNING: Venting terminals must not be recessed
into a wall or siding. NOTE: Only approved pellet vent pipe, wall pass-
throughs, and re stops should be used when venting
through combustible materials. NOTE: Always take into consideration the effects of the prevailing wind direction or other wind currents
that may cause yash and/or smoke when placing the
termination of the vent.
In addition, the following must be observed:
A. The clearance above grade must be a minimum
of 18".
1
B. The clearance to a window or door that may be
opened must be a minimum of 48" to the side, 48" below the window/door, and 12" above the window/
1
door.
(with outside air installed, 18” to the side or
below)
C. A 12" clearance to a permanently closed window
is recommended to prevent condensation on the window.
D. The vertical clearance to a ventilated soft located
above the terminal within a horizontal distance of 2 feet (60 cm) from the center-line of the terminal must be a minimum of 18".
E. The clearance to an unventilated soft must be a
minimum of 12".
F. The clearance to an outside corner is 11" from center
of pipe.
G. The clearance to an inside corner is 12".
H. A vent must not be installed within 3 feet (90 cm)
above a gas meter/regulator assembly when measured from the horizontal center-line of the regulator.
1
I. The clearance to service regulator vent outlet must
be a minimum of 6 feet.
1
J. The clearance to a non-mechanical air supply inlet to
the building or the combustion air inlet to any other appliance must be a minimum of 48”.
1
K. The clearance to a mechanical air supply inlet must
be a minimum of 10 feet.
1
(with outside air installed, 6 feet ) L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum of 7 feet.
M. The clearance under a veranda, porch, deck or
balcony must be a minimum of 12 inches.
1,2
1,3
(B. also applies) NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is 36” as measured from the center of the outlet or cap. This 36” radius continues to grade or a minimum of 7 feet below the outlet.
1
Certain Canadian and/or Local codes or regulations
may require different clearances.
2
A vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings.
3
Only permitted if veranda, porch, deck, or balcony is
fully open on a minimum of 2 sides beneath the oor.
NOTE: Where passage through a wall, or partition of combustible construction is desired, the installation shall conform to CAN/CSA-B365. (if in Canada)
Inside Corner
Detail
Door
Sidewalk
=Vent Terminal
V
8 P43 Pellet Stove 3-90-04301R18_03/13
Fixed
Closed
Openable
Openable
=Air Supply Inlet
A
Fixed
Closed
Porch or
Deck
Openable
or Fixed
=Area where termination is mot permitted
Venting
IMPORTANT NOTICE
Approved 3" or 4" Pellet Vent Pipe Such As,
Type "PL", Must Be Used.
Fig. 7
= Positive Static Pressure
+
= Negative Static Pressure
-
+
-
Vent Pipe
Pellet venting pipe (known as PL vent) is constructed of two layers with air space between the layers. This air space acts as an insulator and reduces the outside surface temperature to allow a clearance to combustibles of 1 to 3 inches. The sections of pipe lock together to form an air tight seal in most cases. However, in some cases a perfect seal is not achieved. For this reason and the fact that the unit operates with a positive vent pressure we specify that the joints also be sealed with high temp (RTV) silicone. Aluminum tape can also be used for any joint that is 1ft. or more from the outlet of the stove.
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENT MANUFACTURER
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
A CHIMNEY CONNECTOR MAY NOT PASS THROUGH AN ATTIC OR ROOF SPACE, CLOSET OR SIMILAR CONCEALED SPACE, FLOOR , OR CEILING. REFERENCE LOCAL BUILDING CODES FOR DETAILS.
+
Venting
A combustion blower is used to extract the combustion
gases from the rebox. This causes a negative pressure in the rebox and a positive pressure in the venting system as
shown in Fig. 7. The longer the vent pipe and more elbows
used in the system, the greater the ow resistance. Because
of these facts we recommend using as few elbows as possible and 15 feet or less of vent pipe. The maximum horizontal run should not exceed 48". If more than 15 feet of pipe is needed, the interior diameter should be increased from 3" to
4" because a larger pipe causes less ow resistance. Be sure to use approved pellet vent pipe wall and ceiling pass-
through ttings to go through combustible walls and
ceilings. All joints for connector pipe must be fastened with a minimum of three screws and a termination cap must be installed. Follow pellet vent manufacturer instructions for properly securing each pellet vent joint. The pellet starting collar must be secured to the unit's
ue collar.
NOTE: Simpson DuraVent PelletVent Pro Harman Adapter Part #3PVP-ADHB and PelletVent Pro Harman Adapter Increaser Part #3PVP-X4ADHB are highly recommended to be installed on the starter collar to insure a proper pipe connection to the unit.
CAUTION
DO NOT USE MAKESHIFT COMPROMISES
WHEN INSTALLING THIS APPLIANCE.
DAMAGE AND/OR INJURY MAY RESULT.
Avoiding Smoke and Odors
Negative Pressure, Shut-down, and Power Failure: To reduce the probability of back-drafting or burn-back in the pellet burning appliance during power failure or shut­down conditions, the stove must be able to draft naturally
without exhaust blower operation. Negative pressure in the house will resist this natural draft if not accounted for in the pellet appliance installation.
Heat rises in the house and leaks out at upper levels. This
air must be replaced with cold air from outdoors, which ows
into lower levels of the house. Vents and chimneys into basements and lower levels of the house can become the conduit for air supply, and reverse under these conditions.
Outside Air: Hearth & Home Technologies strongly recommends attaching outside air in all installations, especially lower
level and main oor locations.
9P43 Pellet Stove3-90-04301R18_03/13
Inlet Cover part# 1-10-08542
Outside air ex pipe
goes here.
Flex pipe part#
1-00-08543 (25')
Venting
Per national building codes, consideration must be given to combustion air supply to all combustion appliances. Failure to supply adequate combustion air for all appliance demands, may lead to back-drafting of those and other appliances.
When the appliance is side-wall vented: The air intake
is best located on the same exterior wall as the exhaust vent outlet and located lower on the wall than the exhaust vent outlet.
When the appliance is roof vented: The air intake is
best located on the exterior wall oriented towards the prevailing wind direction during the heating season.
The outside air connection will supply the demands of the pellet appliance, but consideration must be given to the total house demand. House demand may consume some air needed for the stove, especially during a power failure. It may be necessary to add additional ventilation to the space in which the pellet appliance is located. Consult with your local HVAC professional to determine the ventilation demands for your house.
To install outside air use 2 3/8" I.D. non-combustible
ex pipe. There is a break-away hole on the rear
Direct Vent Wall Passthrough Kit
(part #1-00-677077)
panel of the P43 stove which must be removed before connecting the ex pipe. The pipe should be run outside and terminate to the side or below the vent pipe outlet
so the ue outlet is more than 12" from the inlet cover.
The maximum length run of this pipe is 15 feet. If a longer run is needed the size must be increased to 3". Inlet cover, part number 1-10-08542 should be used to keep birds, rodents, etc.out of the pipe.
You may choose to use the optional Direct Vent Wall
Passthrough Kit (part #1-00-677077) which incorporates the venting passthrough and outside air inlet into one component.
Vent Congurations:
To reduce probability of reverse drafting during shut-down conditions, Hearth & Home Technologies strongly recommends:
• Installing the pellet vent with a minimum vertical run of ve feet, preferably terminating above the roof line.
• Installing the outside air intake at least four feet below the vent termination.
To prevent soot damage to exterior walls of the house and to prevent re-entry of soot or ash into the house:
• Maintain specied clearances to windows, doors, and air inlets, including air conditioners.
• Vents should not be placed below ventilated softs. Run the vent above the roof.
• Avoid venting into alcove locations.
• Vents should not terminate under overhangs, decks or onto covered porches.
• Maintain minimum clearance of 12 inches from the vent termination to the exterior wall. If you see deposits
developing on the wall, you may need to extend this distance to accommodate your installation conditions.
Hearth & Home Technologies assumes no responsibility for, nor does the warranty extend to, smoke damage caused by reverse drafting of pellet appliances under shut-down or power failure conditions.
10 P43 Pellet Stove 3-90-04301R18_03/13
Venting
3 Ft.
to
Combustibles
#1 Preferred method
This method provides excellent venting for normal operation and allows the stove to be installed closest to the wall. Two inches from the wall is safe; however, four inches allows better access to remove the rear panel. The vertical portion of the vent should be three
to ve feet high. This vertical section will help provide
natural draft in the event of a power failure.
Note: Do not place joints within wall pass-throughs.
Fig. 8
3 Ft.
to Combustibles
3 Ft.
to
Combustibles
#2 Preferred method
This method also provides excellent venting for normal operation but requires the stove to be installed farther from the wall. The vertical portion of the vent should
be three to ve feet high and at least three inches from
a combustible wall. This vertical section will provide natural draft in the event of a power failure.
If the stove is installed below grade be sure the vent termination is at least 18" above grade. The outlet must
also be 1 foot from the house/building.
Note: Do not place joints within wall pass-throughs.
CAUTION
Keep combustible materials (such as grass,
leaves, etc.) at least 3 feet away from the ue
outlet on the outside of the building.
Fig. 9
3 Ft.
to Combustibles
12" min. wall to outlet
36" min clearance to any combustible material
Shaded area represents the minimum clearance to combustible materials such as shrubbery, mulch or tall grasses.
11P43 Pellet Stove3-90-04301R18_03/13
Venting
#4 Installing into an existing chimney
This method provides excellent venting for normal operation. This method also provides natural draft in the event of a power failure. If the chimney condition is questionable* you may want to install a liner as in method #7.
In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney.
*The chimney should be inspected and cleaned before installing your stove. If you discover that the chimney
does not have a clay tile liner or has cracks or aking of
the tile liner you will need to install a stainless steel liner within the chimney. In most cases the inside diameter
of this liner should be 4". Either exible or rigid liner
may be used for this purpose. Refer to Method 6 & 7.
Be sure to design the venting so that it can be easily cleaned.
Fig. 10
#5 Installing into an existing replace
chimney
This method provides excellent venting for normal operation. This method also provides natural draft in the event of a power failure. If the chimney condition is questionable* you may want to install a liner as in method #6.
In some places in the US and Canada it is required that the vent pipe extend all the way to the top of the chimney.
*The chimney should be inspected and cleaned before installing your stove. If you discover that the chimney
does not have a clay tile liner or has cracks or aking of
the tile liner you will need to install a stainless steel liner within the chimney. In most cases the inside diameter
of this liner should be 4". Either exible or rigid liner
may be used for this purpose. Refer to Method 6 & 7.
The chimney should be sealed at the damper using a steel plate. Kaowool, mineral wool or an equivalent non­combustible insulation is recommended to be installed on top of the sealing plate to reduce the possibility of condensation. The connector pipe should extend through the smoke chamber to the base or into the
rst ue tile.
Be sure to design the venting so that it can be easily cleaned.
Fig. 11
12 P43 Pellet Stove 3-90-04301R18_03/13
Loading...
+ 28 hidden pages