Goodman MBVC2000AA-1 User Manual

0 (0)
Goodman MBVC2000AA-1 User Manual

MBVC

Multi-Position,Variable-Speed

ECM-Based,ModularBlower

ComfortNet™ Compatible

Contents

 

Air Handler Nomenclature....................

2

Heater Kit Nomenclature.......................

2

Product Specifications...........................

3

Airflow Data............................................

3

Heat Kit Data..........................................

4

Dimensions.............................................

5

Wiring Diagram......................................

6

Product Features

Variable-speed ECM blower motor

ComfortNet™ Communicating System compatible

Advanced configuration of the airflow and tonnage in communicating mode

Provides constant CFM over a wide range of static pressure conditions independent of duct system

CFM indicator

Fault recall of six most recent faults

Provides adjustable low CFM for efficient fan-only operation

Improved humidity and comfort control

Built-in compatibility with multi-stage heat pump and cooling applications

3 kW – 21 kW electric heat kits

Blower section usable as electric heater

Horizontal or vertical configuration capabilities

21" depth for easier attic access

Foil-faced insulation covers the internal casing to reduce cabinet condensation

Galvanized, leather grain-embossed finish

Cabinet air leakage less than 2% at 1.0 inch

H 0 when tested in accordance with

ASHRE standard 193

Cabinet air leakage less than 1.4% at 0.5 inch

H 0 when tested in accordance with

ASHRE standard 193

AHRI certified; ETL listed

* Complete warranty details available from your local dealer or at www.daikincomfort.com. To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.

SS-DMBVC

www.daikincomfort.com

11/15

 

 

Supersedes 9/15

Nomenclature

 

 

 

 

MB

VC

12

00

 

A

 

A

1

 

 

 

 

 

 

1,2

 

3,4

 

5,6

 

7,8

 

9

 

10

 

11

 

 

 

 

Design Series

 

 

 

 

 

 

 

 

 

 

 

 

 

Electrical

 

 

MB

Modular Blower

 

 

 

 

 

 

 

 

 

 

 

 

 

1 208-­230/60/1

 

 

Motor Speed

 

 

 

 

 

 

 

 

 

 

 

 

Revisions

 

 

V

Variable Speed

 

 

 

 

 

 

 

 

 

 

 

 

A First Series

 

 

C

ComfortNet™ Compatible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit Breaker

 

 

Airflow Delivered

 

 

 

 

 

 

 

 

 

 

 

 

A No Circuit Breaker

 

 

08

800 CFM

 

 

 

 

 

 

 

 

 

 

 

 

B Circuit Breaker

 

 

12

1200 CFM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

1600 CFM

 

 

 

 

 

 

 

 

 

Factory-­installed Electric Heat

 

 

20

2000 CFM

 

 

 

 

 

 

 

 

 

 

 

 

00 No Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HKR

*

 

-­05

*

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

4,5

 

11

 

 

 

 

 

Unit Type

 

 

 

 

 

 

 

 

 

 

 

 

Revisions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HKR

Air Handlers & Packaged Units

 

 

 

 

 

 

 

 

Engineering Revisions

 

 

HKA

Air Handlers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HKP

Packaged Units

 

 

 

 

 

 

 

 

 

 

 

 

Circuit Breaker

 

 

 

 

 

 

 

 

 

 

 

 

 

None

 

Single-­ or 3-­Phase Kit;

 

 

 

Phase

 

 

 

 

 

 

 

 

 

 

 

 

No Circuit Breaker

 

 

None Single-­Phase

 

 

 

 

 

 

 

 

 

C

 

Single-­Phase Kit w/

 

 

3

Three-­Phase

 

 

 

 

 

 

 

 

 

 

 

Circuit Breaker

 

 

Heating Capacity @ 240 Volts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

4.75 kW

15

14.25 to 15.00 kW

 

 

 

 

 

 

 

 

 

 

8

7.00 kW

20

19.00 to 19.60 kW

 

 

 

 

 

 

 

 

 

 

10

9.50 kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

www.daikincomfort.com

SS-DMBVC

Product Specifications

Model

MBVC1200AA-1

MBVC1600AA-1

MBVC2000AA-1

 

 

 

 

Blower

 

 

 

Diameter

10"

10"

11"

Width

8"

8"

10"

 

 

 

 

ElectricalData

 

 

 

Voltage

208 / 230

208 / 230

208 / 230

Min Circuit Ampacity

4.3

6.3

5.8

Max. Overcurrent Device (Amps)

15

15

15

 

 

 

 

BlowerMotor

 

 

 

Horsepower (HP)

½

¾

¾

 

 

 

 

ShipWeight(Lbs.)

67

80

86

 

 

 

 

Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed. Refer to unit nameplate for these specifications with approved accessory heaters installed.

SS-DMBVC

www.daikincomfort.com

3